Generac Portable Generator 004373 1 004626 0 User Manual

®
P O W E R S YS TE M S , IN C .  
Owner’s Manual  
Liquid-cooled, Prepackaged  
Standby Generators  
Models:  
004373-1 (40 kW/Single-phase  
* T h is M a n u a l S h o u ld  
w/ 200 Amp  
Transfer Switch)  
R e m a in W it h T h e U n it *  
004626-0 (40 kW/Single-phase  
w/ 200 Amp  
Transfer Switch  
California Emissions)  
®
P O W E R S YS TE M S , IN C .  
®
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS  
SHOULD ATTEMPT INSTALLATION!!  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Guardian Liquid-cooled 40 kW Generator  
2.8.7 Electrical System ............................11  
2.8.8 Rodent Protection ............................11  
Introduction ......................Inside Front Cover  
Read This Manual Thoroughly ......................IFC  
Contents ........................................................IFC  
Operation and Maintenance............................IFC  
How to Obtain Service ....................................IFC  
Authorized Dealer Locator Number ..................IFC  
Section 3 – Operation ..................................12  
3.1 Control Console Com ponents ......................12  
3.1.1 AC Voltm eter ..................................12  
3.1.2 AC Am m eter ..................................12  
3.1.3 AC Frequency Meter ......................12  
3.1.4 DC Voltm eter ..................................12  
3.1.5 Hourm eter ......................................12  
3.1.6 Auto/Off/Manual Switch ..................12  
3.1.7 Fault Indicator Lam p ......................12  
3.1.8 15-am p Fuse ..................................12  
3.1.9 7.5 Am p Inline Fuse ......................12  
3.1.10 Voltage-phase Selector Switch ........12  
3.1.11 Set Exercise Tim e Switch ..............12  
Safety Rules ......................................................2  
Section 1 – General Information..................4  
1.1 Unpacking/Inspection ..................................4  
1.1.1 Lifting the Generator ........................4  
1.2 The Generator ..............................................4  
1.3 Generator AC Connection System s ..............4  
1.4 Autom atic System Operation ........................4  
1.5 Main Circuit Breaker ..................................5  
1.6 Engine Protective Devices ............................5  
1.6.1 Low Oil Pressure Switch ..................5  
1.6.2 High Coolant  
3.2 Using the Auto/Off/Manual Switch ..............12  
3.2.1 Auto” Position ................................12  
3.2.2 Off” Position ..................................13  
3.2.3 Manual” Position ..........................13  
3.3 Autom atic Transfer Operation ....................13  
3.4 Sequence of Autom atic Operation ..............13  
3.5 Engine Heater ..............................................13  
3.6 Weekly Exercise Cycle ................................14  
Tem perature Switch ........................5  
1.6.3 Low Coolant Level Switch ................5  
1.6.4 Overspeed Shutdown ......................5  
1.6.5 Overcrank Shutdown ......................5  
1.6.6 DC Fuse............................................5  
1.7 Specifications ..............................................5  
1.7.1 Generator ........................................5  
1.7.1.1 Generator Load  
and Com patibility ....................6  
1.7.2 Engine ..............................................6  
1.8 Fuel Requirem ents  
and Recom m endations ............................6  
1.8.1 Conversion to LP Gas Vapor ............6  
1.9 Engine Oil Recom m endations ......................7  
1.10 Coolant ........................................................7  
1.11 Em ission Control System ............................7  
Section 4 – Maintenance ............................14  
4.1 Checking the Engine Oil Level....................14  
4.2 Changing the Engine Oil and Filter ............15  
4.2.1 Engine Oil Recom m endations ........15  
4.2.2 Oil and Filter Change Procedure ......15  
4.3 Changing the Engine Air Cleaner................15  
4.4 Spark Plugs................................................16  
4.5 Battery Maintenance ..................................16  
4.6 Cooling System ..........................................17  
4.7 Overload Protection for  
Engine DC Electrical System ......................17  
4.8 DC Fuse ....................................................17  
4.9 Engine Coolant ..........................................17  
4.10 Miscellaneous Maintenance ........................17  
4.10.1 Cleaning the Generator ..................17  
4.10.2 Rodent Protection ..........................18  
4.11 Out of Service Procedure ............................18  
4.11.1 Rem oval From Service....................18  
4.11.2 Return to Service............................18  
4.12 Service Schedule ........................................19  
Section 2 – Installation ..................................8  
2.1 Basic Standby Electric System ....................8  
2.2 Em ergency Circuit Isolation Method ............9  
2.3 Total Circuit Isolation Method ......................9  
2.4 Grounding the Generator ............................9  
2.5 Generator AC Neutral Connections ..............9  
2.6 Transfer Switch Start Signal Connections ....9  
2.6.1 GTS” Type Switch ............................9  
2.6.2 Pre-Packaged Type Switch..................9  
2.7 Battery Installation ....................................10  
2.7.1 Vented Batteries ..............................10  
2.8 Preparation Before Start-up ......................10  
2.8.1 Prior to Initial Start-up ....................11  
2.8.2 Transfer Switch ..............................11  
2.8.3 Fuel System ....................................11  
2.8.4 Generator Set Lubrication ..............11  
2.8.5 Engine Coolant ................................11  
2.8.6 Belt Tension ....................................11  
Section 5 – Troubleshooting ......................20  
Section 6 – Electrical Data ....................21-29  
Section 7 – Exploded Views and  
Parts Lists ............................30-54  
Section 8 – Notes ..........................................55  
Section 9 – Installation Drawings........56-57  
Section 10 – Warranty ..................Back Cover  
®
G e n e r a c P o w e r S y s t e m s , In c .  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Instructions  
Guardian Liquid-cooled 40 kW Generator  
SAVE THESE INSTRUCTIONS – Th e m a n u fa ct u r er su ggest s t h a t t h ese r u les for sa fe  
op er a t ion be cop ied a n d p ost ed in p ot en t ia l h a za r d a r ea s. Sa fet y sh ou ld be st r essed t o a ll  
op er a t or s a n d p ot en t ia l op er a t or s of t h is equ ip m en t .  
!
!
!
!
SAVE THESE INSTRUCTIONS – Th is m a n u a l con t a in s im p or t a n t in st r u ct ion s t h a t sh ou ld be  
followed d u r in g in st a lla t ion a n d m a in t en a n ce of t h e gen er a t or a n d ba t t er ies.  
!
!
!
!
GENERAL HAZARDS  
WARNING:  
The engine exhaust from this product  
contains chemicals known to the state  
of California to cause cancer, birth  
defects or other reproductive harm.  
• For  
safety  
r easons,  
Gener ac  
r ecom m end s  
that the installation, initial start-up and m aintenance  
of this equipm ent is car r ied out by  
Generac/Guardian Authorized Dealer.  
a
• Installation, operation, servicing and repair of this  
(and related) equipm ent m ust always com ply with  
applicable codes, standards, laws and regulations.  
Adhere strictly to local, state and national electrical  
and building codes. Com ply with regulations the  
Occupational Safety and Health Ad m inistr ation  
(OSHA) has established. Also, ensure that the gener-  
ator is installed, operated and serviced in accordance  
with the m anufacturers instructions and recom m en-  
dations. Following installation, do not do anything  
that m ight render the unit unsafe or in noncom pli-  
ance with the aforem entioned codes, standards, laws  
and regulations.  
!
!
WARNING:  
This product contains or emits chemicals  
known to the state of California to cause  
cancer, birth defects or other reproductive harm.  
Study these SAFETY RULES carefully before installing,  
operating or servicing this equipm ent. Becom e fam iliar  
with this Ow ners Ma nua l and with the unit. The gen-  
erator can operate safely, efficiently and reliably only if  
it is properly installed, operated and m aintained. Many  
accidents are caused by failing to follow sim ple and fun-  
dam ental rules or precautions.  
Generac cannot possibly anticipate every possible  
circum stance that m ight involve a hazard. The warn-  
ings in this m anual, and on tags and d ecals  
affixed to the unit are, therefore, not all-inclusive. If you  
use a procedure, work m ethod or operating technique  
Generac does not specifically recom m end, you m ust  
satisfy yourself that it is safe for you and others. You  
also m ust m ake sure the procedure, work m ethod or  
operating technique that is chosen does not render the  
generator unsafe.  
• The engine exhaust fum es contain carbon m onoxide,  
which can be DEADLY. This dangerous gas, if  
breathed in sufficient concentrations, can cause  
unconsciousness or even death. For that reason, ade-  
quate ventilation m ust be provided. Exhaust gases  
m ust be piped safely away from any building or  
enclosure that houses the generator to an area where  
people, anim als, etc., will not be harm ed. This  
exhaust system m ust be installed properly, in strict  
com pliance with applicable codes and standards.  
• Keep hands, feet, clothing, etc., away from drive belts,  
fans, and other m oving or hot parts. Never rem ove  
any drive belt or fan guard while the unit is operating.  
• Adequate, unobstructed flow of cooling and ventilating  
air is critical in any room or building housing the gen-  
erator to prevent buildup of explosive gases and to  
ensure correct generator operation. Do not alter the  
installation or perm it even partial blockage of ventila-  
tion provisions, as this can seriously affect safe oper-  
ation of the generator.  
Despite the safe design of this generator,  
!
operating this equipment imprudently, neglecting its  
maintenance or being careless can cause  
possible injury or death. Permit only responsible and  
capable persons to operate or maintain this equip-  
ment.  
Potentially lethal voltages are generated by these  
machines. Ensure all steps are taken to render the  
machine safe before attempting to w ork on the  
generator.  
• Keep the area around the generator clean and unclut-  
tered. Rem ove any m aterials that could becom e haz-  
ardous.  
• When working on this equipm ent, rem ain alert at all  
tim es. Never work on the equipm ent when you are  
physically or m entally fatigued.  
Parts of the generator are rotating and/or hot  
during operation. Exercise care near running gen-  
erators.  
!
®
2
G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Instructions  
Guardian Liquid-cooled 40 kW Generator  
• Inspect the generator regularly, and prom ptly repair • Generators installed with an autom atically transfer  
or replace all worn, dam aged or defective parts using  
only factory-approved parts.  
• Before perform ing any m aintenance on the generator,  
disconnect its battery cables to prevent accidental  
start-up. Disconnect the cable from the battery post  
ind icated by a NEGATIVE, NEG or (–) fir st.  
Reconnect that cable last.  
• Never use the generator or any of its parts as a step.  
Stepping on the unit can stress and break parts, and  
m ay result in dangerous operating conditions from  
leaking exhaust gases, fuel leakage, oil leakage, etc.  
switch will crank and start autom atically when nor-  
m al (utility) source voltage is rem oved or is below an  
acceptable preset level. To prevent such autom atic  
start-up and possible injury to personnel, disable the  
generators autom atic start circuit (battery cables,  
etc.) before working on or around the unit. Then,  
place a Do Not Operate” tag on the generator control  
panel and on the transfer switch.  
• In case of accident caused by electric shock, im m edi-  
ately shut down the source of electrical power. If this  
is not possible, attem pt to free the victim from the  
live conductor. AVOID DIRECT CONTACT WITH  
THE VICTIM. Use a nonconducting im plem ent, such  
as a rope or board, to free the victim from the live  
conductor. If the victim is unconscious, apply first aid  
and get im m ediate m edical help.  
• Never wear jewelry when working on this equipm ent.  
J ewelry can conduct electricity resulting in electric  
shock, or m ay get caught in m oving com ponents  
causing injury.  
ELECTRICAL HAZARDS  
• All generators covered by this m anual produce dan-  
gerous electrical voltages and can cause fatal electri-  
cal shock. Utility power delivers extrem ely high and  
dangerous voltages to the transfer switch as does the  
standby generator when it is in operation. Avoid con-  
tact with bare wires, term inals, connections, etc.,  
while the unit is running. Ensure all appropriate cov-  
ers, guards and barriers are in place before operating  
the generator. If work m ust be done around an oper-  
ating unit, stand on an insulated, dry surface to  
reduce shock hazard.  
FIRE HAZARDS  
• Keep a fire extinguisher near the generator at all  
tim es. DO NOT use any carbon tetra-chloride type  
extinguisher. Its fum es are toxic, and the liquid can  
deteriorate wiring insulation. Keep the extinguisher  
properly charged and be fam iliar with its use. If there  
are any questions pertaining to fire extinguishers,  
consult the local fire departm ent.  
• Do not handle any kind of electrical device while  
standing in water, while barefoot, or while hands or  
feet are wet. DANGEROUS ELECTRICAL SHOCK  
MAY RESULT.  
• If people m ust stand on m etal or concrete while  
installing, operating, servicing, adjusting or repairing  
this equipm ent, place insulative m ats over a dry  
wooden platform . Work on the equipm ent only while  
standing on such insulative m ats.  
• The National Electrical Code (NEC) requires the  
fram e and external electrically conductive parts of the  
generator to be connected to an approved earth  
ground and/or grounding rods. This grounding will  
help prevent dangerous electrical shock that m ight be  
caused by a ground fault condition in the generator  
set or by static electricity. Never disconnect the  
ground wire.  
• Wire gauge sizes of electrical wiring, cables and cord  
sets m ust be adequate to handle the m axim um elec-  
trical current (am pacity) to which they will be sub-  
jected to.  
• Before installing or servicing this (and related) equip-  
m ent, m ake sure that all power voltage supplies are  
positively turned off at their source. Failure to do so  
will result in hazardous and possibly fatal electrical  
shock.  
• Connecting this unit to an electrical system norm ally  
supplied by an electric utility shall be by m eans of a  
transfer switch so as to isolate the genrator electric  
system from the utility electric system while in oper-  
ation. Failure to isolate the two electric system power  
sources from each other by such m eans will result in  
dam age to the generator and m ay also result in injury  
or death to utility power workers due to backfeed of  
electrical energy.  
EXPLOSION HAZARDS  
• Properly ventilate any room or building housing the  
generator to prevent build-up of explosive gas.  
• Do not sm oke around the generator. Wipe up any fuel  
or oil spills im m ediately. Ensure that no com bustible  
m aterials are left in the generator com partm ent, or  
on or near the generator, as FIRE or EXPLOSION  
m ay result. Keep the area surrounding the generator  
clean and free from debris.  
• Generac generator sets m ay operate using one of sev-  
eral types of fuels. All fuel types are potentially  
FLAMMABLE and/or EXPLOSIVE and should be  
handled with care. Com ply with all laws regulating  
the storage and handling of fuels. Inspect the units  
fuel system frequently and correct any leaks im m e-  
diately. Fuel supply lines m ust be properly installed,  
purged and leak tested according to applicable fuel-  
gas codes before placing this equipm ent into service.  
• Diesel fuels are highly FLAMMABLE. Gaseous fluids  
such as natural gas and liquid propane (LP) gas are  
extrem ely EXPLOSIVE. Natural gas is lighter than  
air, and LP gas is heavier than air; install leak detec-  
tors accordingly.  
®
G e n e r a c P o w e r S y s t e m s , In c .  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 General Information  
Guardian Liquid-cooled 40 kW Generator  
1.1 UNPACKING/ INSPECTION  
1.2 THE GENERATOR  
After unpack ing, car efully inspect the contents This liquid-cooled, Guardian generator set is designed  
for dam age.  
to supply electrical power to operate critical electrical  
loads during utility power failure. Use this generator as  
a source of electrical power for the operation of 120  
and/or 240-volt, single-phase loads.  
• This standby generator set has been factory installed  
in an all-weather, m etal enclosure that is intended  
exclusively for outdoor installation.  
1.3 GENERATOR AC  
CONNECTION SYSTEMS  
If this generator is used to pow er electrical load  
circuits normally pow ered by a utility pow er  
source, code requires to install a transfer sw itch.  
The transfer sw itch must effectively isolate the  
electrical system from the utility distribution sys-  
tem w hen the generator is operating (NEC 701).  
Failure to isolate an electrical system by such  
means w ill result in damage to the generator and  
also may result in injury or death to utility pow er  
w orkers due to backfeed of electrical energy.  
Figure 1.1 represents a single-phase, four-wire genera-  
tor AC connection system . The stator assem bly in this  
system consists of a pair of stationary windings with  
two leads brought out of each winding. Each single  
winding can supply a 120-volt, 60-Hertz AC output.  
When the two windings are connected in series, a 240-  
volt, 60-Hertz AC output results. Typically, the two hot”  
leads in the circuit are Wires 11 and 44. The neutral  
leads are the junction of Wires 22 and 33.  
If any loss or dam age is noted at tim e of delivery, have  
the person(s) m aking the delivery note all dam age on  
the freight bill or affix his or her signature under the  
consignor's m em o of loss or dam age.  
Figure 1.1 – Single-phase  
Generator AC Connection System  
If there is loss or dam age after delivery, separate the  
dam aged m aterials and contact the carrier for claim  
procedures.  
“Concealed dam age” is understood to m ean dam age to  
the contents of a package that is not in evidence at the  
tim e of delivery, but is discovered later.  
Neutral Block  
1.1.1 LIFTING THE GENERATOR  
1.4 AUTOMATIC SYSTEM OPERATION  
When this generator, along with its transfer switch, has  
been installed and interconnected, a circuit board in the  
generator panel continuously monitors utility power  
source voltage. Should that voltage drop below a preset  
value, and remain at such a low state for a preset amount  
of time, the generator cranks and starts. After the gener-  
ator starts, the transfer switch transfers load circuits so  
the generator can power them.  
When lifting or hoisting equipment is used, be  
careful not to touch overhead pow er lines.  
The generators w eight of more than 2,000  
pounds requires proper tools and equipment, and  
qualified personnel to be used in all phases of  
handling and unpacking.  
!
When utility source voltage has been restored, the  
switch transfers back to the utility source voltage, and  
the generator then shuts down after a brief cool-down  
tim e.  
®
4
G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 General Information  
Guardian Liquid-cooled 40 kW Generator  
1.6.3 LOW COOLANT LEVEL SWITCH  
1.5 MAIN CIRCUIT BREAKER  
The generators main circuit breaker is included with the  
unit as shipped from the factory. The breaker for each  
unit is described as follows:  
Should the engine coolant level drop below the level of the  
high coolant temperature switch, it is possible for the  
engine to overheat without automatic shut down. To pre-  
vent such overheating without automatic shut down, the  
engine has a low coolant level sensor. If the engine coolant  
drops too low, the engine automatically shuts down  
(Figure 1.2).  
Model Number  
004373-1  
Circuit Breaker Rating  
200-amp breaker  
200-amp breaker  
004626-0  
1.6 ENGINE PROTECTIVE DEVICES  
The engine has several safety switches that cause  
it to automatically shut down under the following condi-  
tions: low oil pressure, high coolant temperature, low  
coolant level, engine overspeed and overcrank.  
1.6.4 OVERSPEED SHUTDOWN  
The control m odule assem bly (CMA) circuit board on  
liquid-cooled units receives AC frequency (rpm ) signals  
directly from the stator AC power windings. Should AC  
frequency exceed approxim ately 72 Hertz, circuit board  
action will autom atically shut down the engine.  
1.6.1 LOW OIL PRESSURE SWITCH  
This switch is normally closed (N.C.) but is held open by  
engine oil pressure during engine running. Should oper-  
ating oil pressure drop below approximately 10 psi (68  
kPa), the switch contacts close, and the engine shuts down  
automatically (Figure 1.2).  
1.6.5 OVERCRANK SHUTDOWN  
After 90 seconds of crank-rest cycles (about seven sec-  
onds cranking/seven seconds at rest), this function ends  
cranking if the engine fails to start in that 90-second  
span.  
Figure 1.2 – Engine Protective Devices  
1.6.6 DC FUSE  
This fuse is located on the front panel of the control sys-  
tem . It protects the panel wiring and com ponents from  
dam aging overload. Always rem ove this fuse before  
com m encing work on the generator. The unit will not  
start or crank if the fuse is blown. Replace the fuse with  
one of the sam e size, type, and rating. Generac uses an  
AGC fuse rated at 15 am ps.  
1.7 SPECIFICATIONS  
1.7.1 GENERATOR  
Models  
0 0 4 3 7 3 -1 & 0 0 4 6 2 6 -0  
Rated Maxim um Continuous  
AC Power Output (kW)*  
40  
Rated Voltage (volts)  
120/240  
Rated Maxim um Continuous  
Current at 240 Volts,  
167  
Single-phase (amps)  
Num ber of Rotor Poles  
Driven Speed of Rotor (rpm )  
Type of Stator  
4
1,800  
Four-wire  
Rotor Excitation System  
Direct Excited  
1.6.2 HIGH COOLANT TEMPERATURE SWITCH  
Brush-type System  
Rotor and Stator Insulation  
Class H”  
This norm ally open (N.O.) therm ostatic switch has a  
sensing tip that is im m ersed in captive coolant. Should  
the coolant tem perature exceed approxim ately 121° C  
(250° F), the switch contacts close, which causes the  
engine to shut down automatically (Figure 1.2).  
*Rated power of generator is subject to and limited by such factors as ambient tempera-  
ture, altitude, engine condition and other factors. Engine power will decrease about 3.5  
percent for each 1,000 feet above sea level; and also will decrease an additional 1 percent  
for each 6° C (10° F) above 15.5° C (60° F) ambient. Maximum output power of the gener-  
ator is limited by maximum engine power.  
®
G e n e r a c P o w e r S y s t e m s , In c .  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 General Information  
Guardian Liquid-cooled 40 kW Generator  
1.7.1.1 Generator and Load Compatibility  
1.8 FUEL REQUIREMENTS  
The generator m ust be fully com patible with the rated  
voltage, num ber of phases and frequency of the con-  
nected electrical loads. The generator, connected elec- This type of system uses the vapors form ed above the  
trical devices, or both, can be dam aged if voltage, num -  
ber of phases and frequency are not com patible.  
AND RECOMMENDATIONS  
With LP gas, use only the vapor withdrawal system .  
liquid fuel in the storage tank.  
Recom m ended fuels should have a Btu content of at  
least 1,000 Btus per cubic foot for natural gas; or at  
least 2,520 Btus per cubic foot for LP gas. Ask your fuel  
supplier for the Btu content of your fuel.  
Not e:  
Th is m an u al assu m es t h at t h e st an dby gen erat or  
h as been properly select ed, in st alled an d in t ercon -  
n ect ed by a com pet en t , qu alified elect rician or  
in st allat ion con t ract or. On ce t h e in st allat ion is  
com plet e, do n ot h in g t h at m ay resu lt in n on com -  
pat ibilit y bet ween t h e gen erat or an d con n ect ed  
elect rical loads.  
Fuel pressure for both natural gas and liquid propane  
setups should be 11 inches to 14 inches of water colum n  
(0.6 psi) at all load ranges.  
Gaseous fuels such as natural gas and liquid  
propane (LP) gas are highly explosive. Even the  
slightest spark can ignite such fuels and cause an  
explosion. No leakage of fuel is permitted. Natural  
gas, w hich is lighter than air, tends to collect in  
high areas; LP gas is heavier than air and tends to  
settle in low areas – install leak detectors accord-  
ingly.  
1.7.2 ENGINE  
Make........................................................General Motors  
Displacem ent ................................4.3 liters (262 cu. in.)  
Cylinder Arrangem ent ................................................V-6  
Valve Arrangem ent..................................Overhead Valves  
Firing Order ..................................................1-6-5-4-3-2  
Num ber of Main Bearings ..............................................4  
Com pression Ratio ..............................................9.4-to-1  
No. of Teeth on Flywheel............................................168  
Ignition System ................................................Electronic  
Ignition Tim ing at 1,800 rpm ..............40 degrees BTDC  
Rated Horsepower at 1,800 rpm ..................................67  
Spark Plug Gap ..............................0.045 inch (1.1 m m )  
Recom m ended Spark Plugs ......AC 41-932 or equivalent  
Oil Pressure ......................................................30-50 psi  
Crankcase Oil Capacity ..............4.5 U.S. quarts (4.25 L)  
Recom m ended Engine Oil ............................SAE 15W-40  
Type of Cooling System ......Pressurized, closed recovery  
Cooling Fan ..................................................Pusher Type  
Cooling System Capacity ..............4.5 U.S. gallons (17 L)  
Recom m ended Coolant ..................Use a 50-50 mixture of  
ethylene glycol and soft water.  
1.8.1 CONVERSION TO LP GAS VAPOR  
The generator is shipped from the factory configured for  
using natural gas as fuel. To convert the fuel system to LP  
gas, proceed as follows (Figure 1.5).  
1. Remove end cap from the pressure reducer valve.  
2. Turn the tension screw counterclockwise until all ten-  
sion is removed from the inner spring.  
3. Install and tighten the end cap.  
4. Invert the pressure reducer valve. In other words, turn  
it upside down (end cap facing downward).  
5. Purge and leak test the entire fuel system according to  
gaseous fuel codes. NO LEAKS can appear at any point  
in the system.  
Fu el Con su m pt ion  
Figure 1.5 – Conversion to LP Gas Vapor  
Natural Gas  
004373-1 & 004626-0 ........................................720 cfh  
LP Gas  
004373-1 & 004626-0 ..............................288 cfh/7.9gph  
®
6
G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 General Information  
Guardian Liquid-cooled 40 kW Generator  
carburetor, oxygen sensor, air-fuel ratio controller, sole-  
noid valve and gas regulator. These item s are not sub-  
ject to periodic m aintenance or adjustm ent.  
1.9 ENGINE OIL RECOMMENDATIONS  
The unit has been filled with 15W-40 engine oil at the  
factory. Use a high-quality detergent oil classified For  
Service CC, SD, SE or SF. Detergent oils keep the  
engine cleaner and reduce carbon deposits. Use oil hav-  
ing the following SAE viscosity rating, based on the  
am bient tem perature range anticipated before the next  
oil change:  
This m odel is of a size (greater than 50 brakehorse-  
power) that m ay require a review by air perm itting  
authorities prior to installation and operation. Consult  
the local air m anagem ent district for details and specif-  
ic requirem ents.  
Tem perature  
Oil Grade(Recom m en ded)  
Figure 1.3 - Emissions Control System  
Above 80º F (27º C)  
32º to 80º F (-1º C to 27º C) SAE 20W-20 or 15W-40  
Below 32º F (0º C) SAE 10W or 15W-40  
SAE 30W or 15W-40  
Any attempt to crank or start the engine before it  
has been properly serviced w ith the recommended  
oil may result in an engine failure.  
!
1.10 COOLANT  
Use a m ixture of half low silicate, ethylene glycol base  
antifreeze and half soft water. Use only soft water and  
only low silicate antifreeze. If desired, add a high qual-  
ity rust inhibitor to the recom m ended coolant m ixture.  
When adding coolant, always add the recom m ended 50-  
50 m ixture.  
Do not remove the radiator pressure cap w hile the  
engine is hot or serious burns from boiling liquid or  
steam could result.  
AIR FUEL RATIO CONTROLLER  
The air fuel ratio controller is an advanced m icro-  
processor designed to work with a three-way catalyst  
and a feedback (rich bias) carburetor to provide close-  
loop fuel m anagem ent. Its digital adaptive control is  
able to com pensate for variations in fuel m ixtures and  
engine tunes. It is tim e based activated. (For exam ple, it  
will activate after 45 seconds from receiving the power  
signal.) The part num ber for the air fuel ratio controller  
is 0D4221.  
Ethylene glycol base antifreeze is poisonous. Do not  
use mouth to siphon coolant from the radiator, recov-  
ery bottle or any container. Wash hands thoroughly  
after handling. Never store used antifreeze in an  
open container because animals are atracted to the  
smell and taste of antifreeze even though it is poison-  
ous to them.  
Do not use any chromate base rust inhibitor w ith eth-  
ylene glycol base antifreeze, or chromium hydroxide  
(“green slime”) w ill form and cause overheating.  
Engines that have been operated w ith a chromate  
base rust inhibitor must be chemically cleaned before  
adding ethylene glycol base antifreeze. Using any  
high silicate antifreeze boosters or additives also w ill  
cause overheating. Generac also  
Principle of Operation: The oxygen sensor, installed on  
the exhaust pipe, between the engine and the catalytic  
m uffler (closer to the engine), continuously m onitors  
the exhaust gas com position. A feedback signal is sent  
from the oxygen sensor to the air fuel ratio controller,  
which controls the fuel system to m aintain the optim al,  
stoichiom etric air fuel ratio. The air fuel m ixture to the  
engine is controlled by biasing the diaphragm in the fuel  
regulator using vacuum (from the carburetor). This  
vacuum signal is directed to the fuel regulator via the  
control valve. The air fuel ratio controller determ ines  
the am ount of vacuum signal sent to the fuel regulator.  
The m ore vacuum sent to the regulator, the m ore  
restricted the fuel flow will be, therefore the leaner the  
air fuel m ixture.  
recommends that any soluble oil inhibitor NOT be  
used for this equipment.  
1.11 EMISSIONS CONTROL SYSTEM  
(Model 0 0 4 6 2 6 -0 )  
This m odel is equipped with an active exhaust em is-  
sions control system to com ply with certain California  
air district regulations for natural gas em ergency gener-  
ating sets, including the South Coast Air Quality  
Managem ent District. Do not tam per with or disable  
any part of this system , including the exhaust catalyst,  
®
G e n e r a c P o w e r S y s t e m s , In c .  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 Installation  
Guardian Liquid-cooled 40 kW Generator  
STANDBY GENERATOR INSTALLATION  
Connecting this generator to an electrical system normally supplied by an electric utility shall be by  
means of a transfer sw itch (such as the Generac “GTS” type transfer switch), so as to isolate the electric  
system from the utility distribution system w hen the generator is operating. Failure to isolate the  
electric system by these means w ill result in damage to the generator and may also result in injury  
or death to utility w orkers due to backfeed of electrical energy.  
OTHER PUBLISHED STANDARDS  
In addition to NFPA standards, the following inform a-  
tion pertaining to the installation and use of standby  
electric system s is available:  
If an open bottom is used, the engine-generator is  
to be installed over non-combustible materials  
and should be located such that combustible  
materials are not capable of accumulating under  
the generator set.  
• Article X, NATIONAL BUILDING CODE, available  
from the Am erican Insurance Association, 85 J ohn  
Street, New York, N.Y. 10038.  
• AGRICULTURAL WIRING HANDBOOK, obtainable  
from the Food and Energy Council, 909 University  
Avenue, Colum bia, MO, 65201.  
• ASAE EP-364.2, INSTALLATION AND MAINTE-  
NANCE OF FARM STANDBY ELECTRIC POWER,  
available from the Am erican Society of Agricultural  
Engineers, 2950 Niles Road, St. J oseph, MI 49085.  
• A52.1, AMERICAN NATIONAL STANDARD FOR  
CHIMNEYS, FIREPLACES AND VENTING SYS-  
TEMS, available fr om the Am er ican National  
Standard Institute, 1430 Broadway, New York, N.Y.  
10018.  
Only qualified, com petent installation contractors or  
electricians thoroughly fam iliar with applicable codes,  
standards and regulations should install this standby  
electric power system . The installation m ust com ply  
strictly with all codes, standards and regulations per-  
taining to the installation.  
After the system has been installed, you must not do  
anything that might render the installation in noncom-  
pliance w ith such codes, standards and regulations.  
NOTE:  
For m ore inform ation about the installation of a stand-  
by system , you can order Engine-Genera tor Sta ndby  
Electr ic Pow er S ys tem s In s ta ller s Gu id e a n d  
Reference Ma nua l (part # 046622) from a Generac  
Authorized Service Dealer.  
• NEC HANDBOOK available from the National Fire  
Pr otection Association,  
1
Batter ym ar ch Par k ,  
PO Box 9146, Quincy, MA 02269-9959.  
2.1 BASIC STANDBY ELECTRIC SYSTEM  
Figure 2.1 shows a schem atic diagram of a basic stand-  
by electric system . Both the UTILITY power supply and  
the STANDBY (generator) output are connected to an  
approved transfer switch. The transfer switch is  
required by electrical code and serves the following  
functions:  
NFPA STANDARDS  
The following published standards booklets pertaining  
to standby electric system s are available form the  
National Fir e  
Pr otection  
Association  
(NFPA),  
Batterym arch Park, Quincy, MA 02269:  
• Perm its the LOAD circuits to be connected to only one  
power supply at a tim e.  
• Pr events electr ical back feed between STANDBY  
power and the UTILITY power circuits.  
• NFPA No. 37, STATIONARY COMBUSTION ENGINES  
AND GAS TURBINES.  
• NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS  
FOR HEALTH CARE FACILITIES.  
Notice that both the STANDBY and the UTILITY power  
supplies to the transfer switch are protected against  
overload by a m ain line circuit breaker.  
• NFPA No. 220, STANDARD TYPES OF BUILDING  
CONSTRUCTION  
• NFPA No. 68, GUIDE FOR EXPLOSION VENTING  
• NFPA No. 70, NATIONAL ELECTRICAL CODE.  
• NFPA No. 30, FLAMMABLE AND COMBUSTIBLE  
LIQUIDS CODE.  
NOTE:  
Gen erac recom m en ds th e use of a Gen erac Power  
System s “pre-packaged” type tran sfer switch (Part  
No. 0 D4 4 0 6 ) in con jun ction with th is gen erator.  
• NFPA No. 10, INSTALLATION, MAINTENANCE AND  
USE OF PORTABLE FIRE EXTINGUISHERS.  
®
8
G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 Installation  
Guardian Liquid-cooled 40 kW Generator  
Figure 2.1 – Basic Standby Electric System  
Do not connect the ground w ire to any pipe that  
carries a flammable or explosive substance – FIRE  
or an EXPLOSION may result.  
Proper grounding helps protect personnel against electri-  
cal shock in the event of a ground fault condition in the  
generator or in connected electrical devices. In addition,  
grounding helps dissipate static electricity that often  
builds up in ungrounded devices.  
Figure 2.2 – Generator Grounding Lug (typical)  
2.2 EMERGENCY CIRCUIT ISOLATION  
METHOD  
This prevents overloading the generator by keeping elec-  
trical loads below the wattage/am perage capacity of the  
generator. If the generator is powering only critical  
loads, within its wattage/am perage capacity, during util-  
ity power outages, consider using the em ergency circuit  
isolation m ethod.  
Critical electrical loads are grouped together and wired  
into a separate Em ergency Distribution Panel.” Load  
cir cuits power ed by that panel ar e within the  
wattage/am perage capacity of the generator set. When  
this m ethod is used, it is difficult to overload the gener-  
ator. The transfer switch m ust m eet the following  
requirem ents:  
2.5 GENERATOR AC NEUTRAL  
CONNECTIONS  
Generac uses an UNGROUNDED AC neutral. Grounding  
is recommended only at the main service entrance.  
• It m ust have an am pere rating equal to or greater  
than the total am perage rating of the em ergency dis-  
tribution panel circuit.  
• It must be installed between the buildings main distri-  
bution panel and the emergency distribution panel.  
2.6 TRANSFER SWITCH START SIGNAL  
CONNECTIONS  
2.6.1 GTSType Switch  
2.3 TOTAL CIRCUIT ISOLATION METHOD  
When a generator capable of powering all electrical  
loads in the circuit is to be installed, use the Total  
Circuit Isolation Method.” It is possible for the genera-  
tor to be overloaded when this isolation m ethod is  
em ployed. The following apply to the transfer switch in  
this type of system .  
Connect the two-wire start signal from the automatic  
transfer switch to the automatic start connection, which is  
located in the right hand corner inside the lower panel.  
Match wires 178 and 183 in the transfer switch to 178  
and 183 on the terminal strip in the control panel. The  
conductors for the two-wire start circuit must be in their  
own conduit.  
• Am pere rating of the transfer switch m ust be equal to  
or greater than the am pere rating of the norm al  
incom ing utility service.  
2.6.2 Pre-Packaged Type Switch  
• The transfer switch m ust be installed between the  
utility service entrance and the building distribution  
panel.  
Connect the six signal wires from the autom atic trans-  
fer switch to the engine generator control, which is  
located on the upper right side and inside the lower  
control panel. Match wires 23, 194, N1, N2, T1 and T2  
in the transfer switch to the corresponding wires on the  
term inal strip in the lower panel. The conductors for  
these wires m ust be in seperate conduit from the m ain  
AC output wires.  
2.4 GROUNDING THE GENERATOR  
The National Electrical Code requires the fram e and  
external electrically conductive parts of this equipm ent  
to be properly connected to an approved earth ground  
and/or grounding rods. For that purpose, a GROUND  
LUG (Figure 2.2) is provided on the generator m ounting  
base. Consult a qualified electrician for grounding  
requirem ents in your area. Grounding procedures m ust  
m eet local regulations.  
®
G e n e r a c P o w e r S y s t e m s , In c .  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 Installation  
Guardian Liquid-cooled 40 kW Generator  
• Where electrolyte contacts the eyes, flush thoroughly  
and immediately w ith w ater and seek medical atten-  
tion, and  
2.7 BATTERY INSTALLATION  
• Spilled electrolyte is to be w ashed dow n w ith an acid-  
neutralizing agent. A common practice is to use a  
solution of one pound (500 grams) bicarbonate of  
soda to one gallon (4 liters) of w ater. The bicarbonate  
of soda solution is to be added until the evidence of  
reaction (foaming) has ceased. The resulting liquid is  
to be flushed w ith w ater and the area dried.  
Standby generators installed w ith automatic trans-  
fer sw itches w ill crank and start automatically  
w hen normal (utility) source voltage is removed or  
is below an acceptable preset level. To prevent  
such automatic start-up and possible injury to per-  
sonnel, do not connect battery cables until the  
normal source voltage at the transfer sw itch is cor-  
rect and the system is ready to be placed into  
operation.  
!
Lead acid batteries present a risk of fire because  
they generate hydrogen gas. The follow ing proce-  
dures are to be follow ed:  
Storage batteries give off explosive hydrogen gas.  
This gas can form an explosive mixture around  
the battery for several hours after charging. The  
slightest spark can ignite the gas and cause an  
explosion. Such an explosion can shatter the bat-  
tery and cause blindness or other injury. Any area  
that houses a storage battery must be properly  
ventilated. Do not allow smoking, open flame,  
sparks or any spark producing tools or equipment  
near the battery.  
• DO NOT SMOKE w hen near batteries,  
• DO NOT cause flame or spark in battery area, and  
• Discharge static electricity from body before touching  
batteries by first touching a grounded metal surface.  
Servicing of batteries is to be perform ed or supervised  
by personnel knowledgeable of batteries and the  
required precautions. Keep unauthorized personnel  
away from batteries.  
For recom m ended batteries, see Battery Maintenance”  
page 16. All batteries m ust be at 100 percent state-of-  
charge before they are installed on the generator.  
Battery electrolyte fluid is an extremely caustic  
sulfuric acid solution that can cause severe burns.  
Do not permit fluid to contact eyes, skin, clothing,  
painted surfaces, etc. Wear protective goggles,  
protective clothing and gloves w hen handling a  
battery. If fluid is spilled, flush the affected area  
immediately w ith clear w ater.  
!
!
!
When using m aintenance-free batteries, it is not neces-  
sary to check the specific gravity or electrolyte level.  
Have these procedures perform ed at the intervals spec-  
ified in Section 4, “Maintenance.” A negative ground sys-  
tem is used. Battery connections are shown on the  
wiring diagram s. Make sure all batteries are correctly  
connected and term inals are tight. Observe battery  
polarity when connecting batteries to the generator set.  
Do not dispose of the battery in a fire. The  
battery is capable of exploding.  
Note:  
Dam age will result if th e battery con n ection s are  
reversed.  
Do not open or mutilate the battery. Released  
electrolyte can be toxic and harmful to the skin  
and eyes.  
The battery represents a risk of high short circuit  
current. When w orking on the battery, alw ays  
2.8 PREPARATION BEFORE START-UP  
The instructions in this section assume that the standby  
remove w atches, rings or other metal objects, and generator has been properly installed, serviced, tested,  
only use tools that have insulated handles.  
adjusted and otherwise prepared for use by a competent,  
qualified installation contractor. Be sure to read the  
Safety Rules” on Pages 2 and 3, as well as all other safe-  
ty information in this manual, before attempting to oper-  
ate this (and related) equipment.  
2.7.1 VENTED BATTERIES  
The electrolyte is a dilute sulfuric acid that is  
harmful to the skin and eyes. It is electrically con-  
ductive and corrosive. The follow ing procedures  
are to be observed:  
• Wear full eye protection and protective clothing,  
• Where electrolyte contacts the skin, w ash it off  
immediately w ith w ater,  
®
1 0 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 Installation  
Guardian Liquid-cooled 40 kW Generator  
2.8.1 PRIOR TO INITIAL START-UP  
2.8.6 Belt Tension  
Check the engine fan belt tension and condition prior to  
placing the unit into service and at recom m ended  
intervals. Belt tension is correct when a force of approx-  
im ately 22 pounds (10 kg), applied m idway between  
pulleys, deflects the belt about 3/8- to 5/8-inch (10 to 16  
m m ).  
Prior to initially starting the generator, it must be  
properly prepared for use. Any attempt to crank  
or start the engine before it has been properly  
serviced w ith the recommended types and quanti-  
ties of engine fluids (oil, coolant, fuel, etc.) may  
result in an engine failure.  
!
2.8.7 Electrical System  
Make sure the generator is properly connected to an  
approved earth ground and/or ground rod.  
Before starting the generator for the first tim e, the  
installer m ust com plete the following procedures. For  
follow-up m aintenance inform ation and/or service inter-  
vals, please refer to Section 4, Maintenance.”  
Make sure the generator battery is fully charged, proper-  
ly installed and interconnected, and ready for use.  
Check to ensure that there are no loose electrical con-  
nections. Restrain any loose wires to keep them clear of  
any m oving generator set com ponents.  
2.8.2 Transfer Switch  
If this generator is used to supply power to any electri-  
cal system norm ally powered by an electric utility, the  
National Electrical Code requires that a transfer switch  
be installed. The transfer switch prevents electrical  
backfeed between two different electrical system s. (For  
additional inform ation, see the applicable transfer  
switch m anual for this unit.) The transfer switch, as  
well as the generator and other standby com ponents,  
m ust be properly located and m ounted in strict com pli-  
ance with applicable codes, standards and regulations.  
2.8.8 Rodent Protection  
Make sure the four 3-inch diam eter cap plugs (part #  
0A8785) are properly installed in the tie-down holes in  
the side rails of the units base fram e (Figure 2.3). The  
cap plugs are shipped in a plastic bag located in the  
lower connection box. These plugs are needed to pre-  
vent rodents from accessing the interior of the genera-  
tor set. On acoustic units, cap plugs also are needed to  
stay within noise specification lim its.  
2.8.3 Fuel System  
Make sure the fuel supply system to the generator (a)  
delivers the correct fuel at the correct pressure and (b)  
is pr oper ly pur ged and leak tested accor d ing  
to cod e. No fuel leak age is per m itted . See  
Specifications” (Page 6) for m ore inform ation.  
Figure 2.3 - Base Frame Cap Plugs  
2.8.4 Generator Set Lubrication  
Check the engine crankcase oil level before operating  
and add oil to the proper level – the dipstick FULL”  
m ark. Never operate the engine with the oil level below  
the dipstick ADD” m ark. See Specifications” (Page 5)  
and Engine Oil Recom m endations” (Page 7).  
NOTE:  
Th is en gin e is sh ipped from t h e m an u fact u rer wit h  
SAE 1 5 W-4 0 oil. Th is oil sh ou ld be ch an ged aft er  
3 0 h ou rs of operat ion .  
2.8.5 Engine Coolant  
Have the engine cooling system properly filled with the  
recom m ended coolant m ixture. Check the system for  
leaks and other problem s. See Specifications” (Page 5)  
and Coolant” (Page 7).  
®
G e n e r a c P o w e r S y s t e m s , In c . 1 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 Operation  
Guardian Liquid-cooled 40 kW Generator  
3.1.6 AUTO/ OFF/ MANUAL SWITCH  
3.1 CONTROL CONSOLE COMPONENTS  
The com ponents of a liquid-cooled generator control  
console (Figure 3.1) are as follows:  
See Section 3.2.  
3.1.7 FAULT INDICATOR LAMP  
Figure 3.1 – Control Console  
This lamp goes ON when one or more of the following  
engine faults occurs and when engine shuts down.  
• Low oil pressure  
• Low coolant level  
• Overspeed  
High coolant tem perature  
Overcrank  
3.1.8 15-AMP FUSE  
This fuse protects the control consoles DC control cir-  
cuit against electrical overload. If the fuse has m elted  
open because of an overload, engine cranking and start-  
up cannot occur. Replace the fuse with an identical AGC  
15-am p replacem ent fuse.  
15  
3.1.9 7.5 AMP INLINE FUSE (NOT SHOWN)  
3.1.1 AC VOLTMETER  
This inline fuse is connected in the 15A line that runs  
between the Auto/Off/Manual switch and position 10 of  
the 76009A PCB. This fuse protects the start, fuel, field  
boost, and transfer outputs from the PCB and will open  
if there is excessive current draw on any one of these  
outputs.  
The voltm eter displays generator AC output voltage dur-  
ing operation. Voltage is regulated by a solid-state volt-  
age regulator and is proportional to AC frequency. Refer  
to the units DATA PLATE for rated AC voltage.  
3.1.2 AC AMMETER  
This indicates current draw of connected electrical  
loads during operation. DO NOT EXCEED THE UNITS  
RATED MAXIMUM CONTINUOUS CURRENT. Refer to  
the unit DATA PLATE.  
3.1.10 VOLTAGE-PHASE SELECTOR SWITCH  
This switch perm its selection between either line-to-line  
or line-to-neutral voltage and am perage readings on the  
console AC voltm eter and AC am m eter.  
3.1.3 AC FREQUENCY METER  
3.1.11 SET EXERCISE TIME SWITCH  
This indicates generator AC output frequency in Hertz  
(cycles per second). Frequency is proportional to engine  
speed. Units with a four-pole rotor, supply 60 Hertz at  
1,800 rpm . The frequency reading with no electrical  
loads connected (no-load condition) should be between  
60-62 Hertz.  
This switch allows to program the generator to start and  
exercise autom atically. (See Section 3.6, page 14)  
3.2 USING THE AUTO/ OFF/ MANUAL  
SWITCH  
3.1.4 DC VOLTMETER  
3.2.1 AUTOPOSITION  
The generator is equipped with a belt-driven DC alter-  
nator, which m aintains battery state of charge when the  
engine operates. The control m odule assem bly (CMA)  
also incorporates a trickle charge circuit that m aintains  
battery state of charge during nonoperating periods.  
Battery voltage should read approxim ately12.5 to 14.5  
volts DC. A low battery voltage indicates the battery is  
discharging.  
Selecting this switch position activates fully autom atic  
system operation. It also allows the unit to start and  
exercise the engine every seven days with the setting of  
the exercise tim er.  
3.1.5 HOURMETER  
This indicates the tim e the engine-generator has operat-  
ed, in hours and tenths of hours. Use the hourm eter  
along with the periodic m aintenance schedule for your  
generator set.  
®
1 2 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 Operation  
Guardian Liquid-cooled 40 kW Generator  
Upon restoration of utility source voltage above a preset  
level, generator circuit board action signals the transfer  
switch to transfer loads back to that power supply. After  
retransfer, the engine is signalled to shut down.  
3.2.2 OFFPOSITION  
This switch position shuts down the engine. This posi-  
tion also prevents operation.  
The actual sequence of operation is controlled by  
sensors and tim ers on a control logic circuit board, as  
follows:  
3.2.3 MANUALPOSITION  
Set the switch to Manual to crank and start the engine.  
Transfer to standby power will not autom atically occur  
unless there is a utility failure.  
A. Utility Voltage Dropout Sensor  
• This sensor m onitors utility source voltage.  
• If utility source voltage drops below about 60 per-  
cent of the nom inal supply voltage, the sensor ener-  
gizes a 15-second tim er.  
• Once the tim er has expired, the engine will crank  
and start.  
With the sw itch set to AUTO, the engine may  
!
crank and start at any time w ithout w arning.  
Such automatic starting normally occurs w hen  
utility pow er source voltage drops below a preset  
level or during the normal exercise cycle. To pre-  
vent possible injury that might be caused by such  
sudden starts, alw ays set the sw itch to OFF and  
remove the fuse before w orking on or around the  
generator or transfer sw itch. Then, place a “Do  
Not Operate” tag on the generator panel and on  
the transfer sw itch.  
B. Engine Warm -up Tim e Delay  
• This m echanism lets the engine warm up for about  
10 seconds before the load is transferred to a stand-  
by source.  
C. Standby Voltage Sensor  
• This sensor m onitors generator AC output voltage.  
When the voltage has reached 50 percent of the  
nom inal rated voltage, transfer to standby can  
occur.  
3.3 AUTOMATIC TRANSFER OPERATION  
D.Utility Voltage Pickup Sensor  
• This sensor m onitors utility power supply voltage.  
When that voltage is restored above 80 percent of  
the nom inal source voltage, a retransfer tim e delay  
starts tim ing.  
To select autom atic operation, do the following:  
1. Make sure the transfer switch m ain contacts are set  
to their Utility” position, i.e., loads connected to the  
utility power source.  
E.Retransfer Tim e Delay  
2. Be sure that normal utility power source voltage is  
available to transfer switch terminal lugs N1 and N2.  
3. Set the generators Auto/Off/Manual switch to AUTO.  
4. Set the generators m ain circuit breaker to its ON  
(or closed) position.  
• This tim er runs for about 15 seconds.  
• At end of a 15-second delay, circuit board action de-  
energizes transfer relay in the transfer switch.  
• Retransfer to utility power source then occurs.  
F. Engine Cool-down Tim er  
With the preceding steps com plete, the generator will  
start autom atically when utility source voltage drops  
below a preset level. After the unit starts, loads are  
transferred to the standby power source. Refer to  
Sequence of Autom atic Operation.”  
• When the load is transferred back to utility power  
source, the engine cool-down tim er starts tim ing.  
• The tim er will run for about one m inute, and the  
generator will then shut down.  
3.5 ENGINE HEATER  
3.4 SEQUENCE OF AUTOMATIC OPERATION  
This Generac standby generator com es equipped with a  
block heater (Figure 3.2, page 14) that is sim ilar to the  
block heaters used in autom otive applications.  
The generators control panel houses a control logic cir-  
cuit board. This board constantly m onitors utility  
power source voltage. Should that voltage drop below a  
preset level, circuit board action will signal the engine to  
crank and start. After the engine starts, the circuit  
board signals the transfer switch to activate and connect  
load circuits to the standby power supply (load term inal  
lugs T1/T2 connect to term inal lugs E1/E2).  
®
G e n e r a c P o w e r S y s t e m s , In c . 1 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 Maintenance  
Guardian Liquid-cooled 40 kW Generator  
the transfer switch that indicates the day and tim e  
the generator will be exercising.  
NOTE:  
Figure 3.2 – Engine Block Heater  
OUTLET  
If t h e bat t ery t erm in als are discon n ect ed or t h e  
con t rol pan el fu se is rem oved, t h e exercise t im er  
n eeds t o be reset for au t om at ic exercise operat ion .  
Figure 3.3 – “Set Exercise” Switch on Control Panel  
INLET  
Refer to applicable wiring diagram (s) and electrical  
schem atic(s) at the back of this m anual for wiring con-  
nections.  
3.6 WEEKLY EXERCISE CYCLE  
The generator will start and exercise once every seven  
days. During this weekly exercise, the unit runs for  
approxim ately 20 m inutes and shuts down. Transfer of  
loads to generator output does not occur during the  
exercise unless power is lost during the exercise period.  
4.1 CHECKING THE ENGINE OIL LEVEL  
For oil capacities, see Specifications,” Section 1.7.2,  
Page 6. For engine oil recom m endations, see Section  
4.2.1. To check the engine oil level, proceed as follows  
(Figure 4.1):  
To select the day of the week and tim e of day for exer-  
cising, proceed as follows:  
1. Rem ove the dipstick and wipe it dry with  
clean cloth.  
2. Install the dipstick cap; then, rem ove it again. The  
oil level should be at the dipstick Full” m ark. If nec-  
essary, add oil to the Full” m ark only. DO NOT FILL  
ABOVE THE FULLMARK.  
a
Set the Auto/Off/Manual switch to OFF.  
Set generators m ain circuit breaker to its OFF (or  
open) position.  
• Locate the rocker switch on the control panel identi-  
fied with the words Set Exercise Tim e” (Figure 3.3).  
• Push Set Exercise Tim e” switch to the ON position  
for 20 to 30 seconds and then release. The switch will  
spring back into its original position when released.  
Wait 30 second s befor e setting the Auto/Off/  
Manual switch to the AUTO position.  
3. Install the dipstick.  
Never operate the engine w ith the oil level below  
the “Add” mark on the dipstick. Doing this could  
!
NOTE:  
damage the engine.  
Th e u n it will exercise 2 0 m in u t es before it is set .  
Exam ple: Set – Noon ; Exercise – 1 1 :4 0 a.m .  
If you sw itch the Auto/Off/Manual sw itch is  
sw itched too soon, the engine may start. If  
!
engine does start, it w ill shut dow n automatically  
in about tw o (2) minutes.  
Set the generators m ain circuit breaker to its ON (or  
closed) position.  
• The generator is now program m ed to start and exer-  
cise every seven days thereafter, on the day and at the  
tim e of day the switch was activated.  
• Place a sign on the generators control panel and on  
®
1 4 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 Maintenance  
Guardian Liquid-cooled 40 kW Generator  
Figure 4.1 – Oil Dipstick and Fill  
Figure 4.2 – Oil Filter  
OIL DIPSTICK  
OIL FILL CAP  
OIL FILTER  
OIL DRAIN HOSE  
4.2 CHANGING THE ENGINE OIL AND FILTER  
TO BASE  
4.2.1 Engine Oil Recommendations  
Use oil of API Service Class SG, SH or SJ . The  
r ecom m end ed oil gr ad e for the engine is  
SAE 15W-40.  
5. Apply a light coating of engine oil to the seal of  
new oil filter. Install the filter and tighten by hand  
only. DO NOT OVERTIGHTEN.  
6. Remove the oil fill cap (Figure 4.1). Add the recom-  
mended oil (see Section 4.2.1). DO NOT FILL  
ABOVE THE DIPSTICK FULLMARK. Crankcase  
oil capacity is 4.5 U.S. quarts (4.25 L).  
NOTE:  
Th e u n it is su pplied wit h “break -in ” oil. See t h e  
“Service Sch edu le,” Sect ion 4 .1 2 (Page 1 9 ), for  
t h e first requ ired oil ch an ge.  
After refilling the crankcase w ith oil, alw ays  
check the oil level on the dipstick. Never  
!
Any attempt to crank or start the engine before  
it has been properly serviced w ith the recom-  
mended oil may result in an engine failure.  
operate the engine w ith the oil level below the  
“Add” mark on the dipstick. Doing this could  
damage the engine.  
!
4.2.2 Oil and Filter Change Procedure  
To change the oil and filter, proceed as follows:  
7. Start the engine and check for oil leaks.  
8. Check the oil level after checking for leaks to  
ensure that the oil is filled to the proper level.  
Refer to the Service Schedule,” (Section 4.12, Page 19)  
for engine oil and filter change frequencies.  
4.3 CHANGING THE ENGINE AIR CLEANER  
Drain the oil while the engine is still warm from run-  
ning. This means, warm up the engine, shut it down  
and drain it immediately as follows:  
To replace the engine air cleaner, (Generac part num -  
ber 0A4637, sim ply rem ove the air cleaner cover and  
replace the air filter m aking sure it is positioned  
properly before reattaching the cover. (See Figure  
4.3, page 16)  
1. Remove the oil drain hose from its retaining clip,  
located on the generator base frame.  
2. Loosen and remove the oil drain hose cap, located  
on the base frame end of the hose. Drain the oil  
completely into a suitable container.  
3. When all of the oil has drained, install and tighten  
the oil drain hose cap.  
4. Turn the oil filter (Generac part num ber  
0A37970001, Figure 4.2) counterclockwise and  
remove it. Properly dispose of the old filter.  
®
G e n e r a c P o w e r S y s t e m s , In c . 1 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 Maintenance  
Guardian Liquid-cooled 40 kW Generator  
3. Have the state of charge and condition checked.  
This should be done with an autom otive-type bat-  
tery hydrom eter or load test.  
Figure 4.3 – Engine Air Cleaner  
Air Cleaner  
Standby generators installed w ith automatic  
transfer sw itches w ill crank and start automatical-  
ly w hen normal (utility) source voltage is removed  
or is below an acceptable preset level. To prevent  
such automatic start-up and possible injury to per-  
sonnel, do not connect battery cables until the  
normal source voltage at the transfer sw itch is  
correct and the system is ready to be placed into  
operation.  
See the Service Schedule,” Section 4.12, Page 19, for rec-  
ommended air cleaner m aintenance.  
Storage batteries give off explosive hydrogen gas.  
This gas can form an explosive mixture around  
!
4.4 SPARK PLUGS  
the battery for several hours after charging. The  
slightest spark can ignite the gas and cause an  
explosion. Such an explosion can shatter the bat-  
tery and cause blindness or other injury. Any area  
that houses a storage battery must be properly  
ventilated. Do not allow smoking, open flame,  
sparks or any spark producing tools or equipment  
near the battery.  
Reset the spark plug gap or replace the spark plugs as  
necessary. See Section 4.12, Page 19.  
1. Clean the area around the base of the spark plugs to  
keep dirt and debris out of the engine. Clean the  
plugs by scraping using a wire brush. Do not blast”  
the spark plugs to clean.  
2. Remove the spark plugs and check the condition.  
Replace the spark plugs if worn or if reuse is ques-  
tionable. See the Service Schedule,” Section 4.12,  
Page 19, for recommended inspection.  
3. Check the spark plug gap using a feeler gauge.  
Adjust the gap to 0.045 inch (1.1 m m ) by carefully  
bending the ground electrode (Figure 4.4).  
Battery electrolyte fluid is an extremely caustic  
sulfuric acid solution that can cause severe burns.  
Do not permit fluid to contact eyes, skin, clothing,  
painted surfaces, etc. Wear protective goggles,  
protective clothing and gloves w hen handling a  
battery. If fluid is spilled, flush the affected area  
immediately w ith clear w ater.  
!
Figure 4.4 – Setting the Spark Plug Gap  
Do not dispose of the battery in a fire. The bat-  
tery is capable of exploding.  
Do not open or mutilate the battery. Released  
electrolyte can be toxic and harmful to the skin  
!
and eyes.  
The battery represents a risk of high short circuit  
current. When w orking on the battery, alw ays  
remove w atches, rings or other metal objects, and  
only use tools that have insulated handles.  
Battery replacement  
Generac uses a Group 27F vented type battery that has  
600 CCA @ 0º F. Generacs part num ber is 058665.  
4.5 BATTERY MAINTENANCE  
Not e:  
The battery should be inspected per the Service  
Schedule,” Section 4.12, Page 19. The following proce-  
dure should be followed for inspection:  
Th e BCI n u m ber sh ou ld be locat ed direct ly on t h e  
bat t ery.  
1. Inspect the battery posts and cables for tightness  
and corrosion. Tighten and clean as necessary.  
2. Check the battery fluid level of unsealed batteries  
and, if necessary, fill with DISTILLED WATER  
ONLY. DO NOT USE TAP WATER IN BATTERIES.  
®
1 6 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 Maintenance  
Guardian Liquid-cooled 40 kW Generator  
Figure 4.4 – Location of 15-amp Fuse  
4.6 COOLING SYSTEM  
Air intake and outlet openings in the generator compart-  
ment must be open and unobstructed for continued prop-  
er operation. This includes such obstructions as high  
grass, weeds, brush, leaves and snow.  
Without sufficient cooling and ventilating air flow, the  
engine/generator quickly overheats, which causes it to  
shut down.  
The exhaust system of this product gets extremely  
hot and remains hot after shutdow n. High grass,  
w eeds, brush, leaves, etc. must remain clear of the  
exhaust. Such materials may ignite and burn from  
the heat of the exhaust system.  
15  
4.7 OVERLOAD PROTECTION FOR ENGINE DC  
ELECTRICAL SYSTEM  
4.9 ENGINE COOLANT  
Engine cranking, start-up and running are controlled by  
a solid-state engine controller circuit board. Battery  
voltage is delivered to that circuit board via a 15-am p  
fuse. These overcurrent protection devices will open if  
the circuit is overloaded.  
Check the coolant level in the coolant recovery bottle.  
• Ad d the r ecom m end ed coolant m ixtur e as  
necessary. See Section 1.10 on Page 7.  
• Periodically remove the radiator pressure cap to make  
sure the coolant recovery system is functioning  
properly. Coolant should be at the bottom of the radia-  
tor filler neck. If the coolant level is low, inspect the  
gasket in the radiator pressure cap. Replace the cap, if  
necessary. To have the pressure cap tested, contact a  
Generac/Guardian Authorized Dealer. Inspect the cool-  
ing system and coolant recovery system for leaks.  
If a circuit breaker opens or a fuse element melts,  
you should find the cause of the overload before  
resetting the circuit breaker or replacing the fuse.  
4.8 DC FUSE  
4.10 MISCELLANEOUS MAINTENANCE  
The generator panels 15-am p AGC fuse (Figure 4.4) pro-  
tects the DC control circuit against overload. The fuse is  
wired in series with the battery output lead to the panel.  
If the fuse elem ent has m elted open, cranking or starting  
the engine cannot occur. Replace the fuse using only an  
identical 15-am p AGC replacem ent.  
4.10.1 Cleaning the Generator  
Keep the generator as clean and as dry as possible. Dirt  
and m oisture that accum ulate on internal generator  
windings have an adverse effect on insulation resist-  
ance.  
Periodically, clean the generators exterior surfaces.  
A
soft brush m ay be used to loosen caked on dirt. Use a  
vacuum system or dry, low pressure air to rem ove any  
accum ulations of dirt. The generator is housed inside  
an all-weather enclosure; clean the enclosure with a  
soft, dam p cloth or sponge and water.  
Once each year, have the generator cleaned and inspect-  
ed by a Generac/Guardian Authorized Dealer. Service  
technicians will use dry, low pressure air to clean inter-  
nal windings. Parts inside the control console should be  
cleaned and inspected at this tim e as well.  
Finally, have the insulation resistance of stator and rotor  
windings checked. If insulation resistances are excessive-  
ly low, the generator may require drying.  
®
G e n e r a c P o w e r S y s t e m s , In c . 1 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 Maintenance  
Guardian Liquid-cooled 40 kW Generator  
6. Attach a tag to the engine indicating the viscosity  
and classification of the oil in the crankcase.  
7. Rem ove the spark plug(s) and spray fogging agent  
into the spark plug(s) threaded openings. Reinstall  
and tighten the spark plug(s).  
8. Rem ove the battery and store it in a cool, dry room  
on a wooden board. Never store the battery on any  
concrete or earthen floor.  
4.10.2 Rodent Protection  
The intrusion of rodents into the generator set can  
cause a wide range of problem s, from failure of the unit  
to start, to personal injury and, in extrem e circum -  
stances, short circuit or fire. Although the unit was  
designed to lim it this problem , further precautions can  
be taken by the owner to help m inim ize both the chance  
of rodent entry and the extent of any dam age. The fol-  
lowing inspection should be perform ed.  
9. Clean and wipe the entire generator.  
1. The base frame of the unit contains an optional fuel  
inlet location and four lifting holes that are capped at  
the factory. These caps are sometimes removed for  
transportation during installation but always should  
be replaced afterwards. Check that they are secured in  
place. The same applies for any access ports in the  
roof of the enclosure. If any of these caps are missing,  
contact a Generac/Guardian Authorized Dealer.  
2. Inside the generator set, the chance of rodent entry  
into the control panel is greatly reduced by the inclu-  
sion of adjustable wire connectors. Check that the  
wire connector screws are tight, thus closing off any  
gap between the access holes and the wires.  
4.11.2 Return To Service  
To return the unit to service after storage, proceed  
as follows:  
1. Verify that utility power is turned off to the transfer  
switch and that the Auto/Off/Manual switch is set to  
OFF.  
2. Check the tag on the engine for oil viscosity and  
classification. Verify that the correct recom m ended  
oil is used in engine. See Section 4.2.1 (Page 14). If  
necessary, drain and refill with the proper oil.  
3. Check the battery. Fill all cells to the proper level  
with distilled water. DO NOT USE TAP WATER IN  
THE BATTERY. Rem ove the battery before charging.  
Recharge the battery to 100 percent state of charge,  
or, if defective, replace the battery with a 12-volt DC  
Group 27F battery rated for 90 am p hours (part #  
058665).  
4.11 OUT OF SERVICE PROCEDURE  
4.11.1 Removal From Service  
If the generator cannot exercise every seven days, and it  
is to be out of service longer than 90 days, prepare the  
generator for storage as follows:  
4. Clean and wipe the entire generator.  
5. Reconnect the battery. Observe battery polarity.  
Dam age m ay occur if the battery is connected incor-  
rectly.  
1. Start the engine and let it warm up.  
2. Close the fuel shutoff valve in the fuel supply line  
and allow the unit to shut down.  
6. Open the fuel shutoff valve.  
3. Once the unit has shut down, it will signal a fault on 7. Start the unit by m oving the Auto/Off/Manual switch  
the control panel.  
to MANUAL. Allow the unit to warm up thoroughly.  
4. Set the Auto/Off/Manual switch to OFF and turn off 8. Stop the unit and set the Auto/Off/Manual switch to  
the utility power to the transfer switch.  
AUTO.  
5. While the engine is still warm from running, drain 9. Turn on the utility power to the transfer switch.  
the oil com pletely. Refill the crankcase with SAE  
15W-40 oil having API Service Class SG, SH or SJ .  
10. The generator is now ready for service.  
®
1 8 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 Maintenance  
Guardian Liquid-cooled 40 kW Generator  
4.12 SERVICE SCHEDULE  
ATTENTION: It is recommended that all service w ork  
be performed by your nearest Generac/Guardian Authorized Dealer.  
SYSTEM/ COMPONENT  
PROCEDURE  
FREQUENCY  
X = Action  
Inspect  
Change  
Clean  
W = Weekly  
M = Monthly  
Y = Yearly  
R = Replace/Adjust as Needed  
* = Notify Dealer  
if Repair is Needed.  
H = Hours  
FUEL  
Fuel lines and connections*  
X
X
EVERY 3 M  
M
LUBRICATION  
Oil level  
Oil  
X
X
FIRST 9 H,  
EVERY 150 H / 6 M  
Oil filter  
FIRST 9 H,  
EVERY 150 H / 6 M  
Oil line leakage*  
COOLING  
Engine cooling system *  
Coolant  
X
X
X
100 H  
M
Y
X
Enclosure louvers  
EXHAUST  
Exhaust system  
Retorque Exhaust Manifold*  
X
X
W
X
X
EVERY 3 M  
FIRST 100 H AND  
EVERY 800 H  
BATTERY  
Charge and condition  
FAN BELT  
Tension and condition*  
ENGINE  
X
X
R
R
EVERY 3 M  
EVERY 3 M  
Retorque cylinder head*  
X
X
FIRST 100 H AND  
EVERY 800 H  
Retorque intake m anifold*  
FIRST 100 H AND  
EVERY 800 H  
Starter m otor*  
DC alternator*  
Air cleaner*  
X
X
X
X
X
X
X
X
X
R
R
R
EVERY 500 H  
EVERY 500 H AND Y  
EVERY 500 H  
EVERY 800 H  
EVERY 800 H  
Y
Com pression*  
Valve clearance*  
Governor*  
R
R
R
R
R
Safety devices*  
Spark plugs  
EVERY 6 M  
500 H AND Y  
EVERY 3 M  
Ignition system *  
GENERAL  
Overall condition  
Exercise system  
COMPLETE TUNE-UP*  
X
X
M
W
Y
TO BE COMPLETED BY A GENERAC/  
GUARDIAN AUTHORIZED DEALER  
®
G e n e r a c P o w e r S y s t e m s , In c . 1 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 Troubleshooting  
Guardian Liquid-cooled 40 kW Generator  
5.1 TROUBLESHOOTING GUIDE  
PROBLEM  
The engine will not crank.  
CAUSE  
1. Fuse blown  
CORRECTION  
1. Replace fuse.  
2. Loose, corroded or defective  
battery cables  
2. Tighten, clean or replace  
as necessary.  
3. Defective starter contactor  
4. Defective starter m otor  
5. Dead Battery  
3.  
4.  
*
*
5. Charge or replace battery.  
The engine cranks but  
will not start.  
1. Out of fuel  
1. Replenish fuel.  
2. Defective fuel solenoid (FS)  
3. Open # 14 wire from  
engine control board  
2.  
3.  
*
*
4. Defective spark plug(s)  
5. Dirty/Blocked air filter  
4. Clean, re-gap or replace plug(s).  
5. Clean or replace as required.  
The engine starts hard  
and runs rough.  
1. Air cleaner  
1. Check, clean or replace air cleaner.  
plugged or dam aged  
2. Defective spark plug(s)  
3. Dirty/Blocked air filter  
2. Clean, re-gap or replace plug(s).  
3. Clean or replace as required.  
The engine starts, but then  
shuts down.  
1. Engine oil level low  
2. Defective low oil  
pressure switch  
3. Defective high tem perature  
switch  
1. Check oil and add oil as needed.  
2.  
3.  
4.  
*
*
*
4. Defective control board  
5. Low coolant level  
5. Check coolant level, repair leaks  
and refill.  
The Auto/Off/Manual switch  
is set to OFF, but the engine  
continues to run.  
1. Defective switch  
2. Defective control board  
1.  
2.  
*
*
There is no AC output from  
the generator.  
1. Generator m ain line circuit  
breaker open  
1. Reset circuit breaker  
to ON (or closed).  
2. Generator internal failure  
2.  
*
There is no transfer to  
standby after utility  
source failure.  
1. Generator m ain line circuit  
breaker open  
2. Defective transfer switch coil  
3. Defective transfer relay  
4. Transfer relay circuit open  
5. Defective control logic board  
1. Reset circuit breaker  
to ON (or closed).  
2.  
3.  
4.  
5.  
*
*
*
*
*Con t act you r n earest Gen erac/ Gu ardian Au t h orized Dealer for assist an ce.  
®
2 0 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 Electrical Data  
(Model No. 004373-1) Guardian Liquid-cooled 40 kW Generator  
Electrical Schematic (Control Panel) Drawing No. 0D4993-A  
Y E L L O W  
O R A N G E  
Y E L L O W  
B R O W N  
B L A C K  
T O E N G I N E ( C O N N E C T O R E H )  
T O L O W E R P A N E L ( C O N N E C T O R C P )  
®
G e n e r a c P o w e r S y s t e m s , In c . 2 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 Electrical Data  
(Model No. 004373-1) Guardian Liquid-cooled 40 kW Generator  
Wiring Diagram (Control Panel) Drawing No. 0D4992-A  
1 7 8  
2 2 9  
4
8 5  
2 3  
1 9 4  
2 1 9  
2 1 8  
1 5 0  
8 6  
5 6  
1 4  
8 5  
6 9  
6 8  
1 7 8  
1 5 A  
2 3 9  
5 6  
2 2 9  
2 2 9  
2 2 9  
4
1 5  
1 5 A  
1 5 A  
1 4  
1 4  
1 3  
7 9  
0
1 5 C  
R E D  
2 2 5 A  
0
0
B L A C K  
6
5
4
3
2
1
DEUTSCH  
7
8
9
10  
11  
12  
A C T U A T O R  
T O G O V E R N O R  
®
2 2 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 Electrical Data  
(Model No. 004626-0) Guardian Liquid-cooled 40 kW Generator  
Schematic (Control Panel) Drawing No. 0D6975  
1 6 0  
1 6 1  
7 9  
0
0
Y E L L O W  
M P U S H I E L D  
M P U -  
0
0
M P U +  
7 9  
A C T -  
1 6 1  
A C T +  
1 6 0  
T O E N G I N E ( C O N N E C T O R E H )  
T O L O W E R P A N E L ( C O N N E C T O R C P )  
®
G e n e r a c P o w e r S y s t e m s , In c . 2 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 Electrical Data  
(Model No. 004626-0) Guardian Liquid-cooled 40 kW Generator  
Wiring Diagram (Control Panel) Drawing No. 0D6974  
®
2 4 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 Electrical Data  
(Model Nos. 004373-1 & 004262-0) Guardian Liquid-cooled 40 kW Generator  
Electrical Schematic Engine (4.3L) Drawing No. 0A4592-B  
®
G e n e r a c P o w e r S y s t e m s , In c . 2 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 Electrical Data  
(Model Nos. 004373-1 & 004262-0) Guardian Liquid-cooled 40 kW Generator  
Wiring Diagram Engine (4.3L) Drawing No. 0A4591-B  
®
2 6 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 Electrical Data  
(Model No. 004373-1) Guardian Liquid-cooled 40 kW Generator  
Electrical Schematic Stepper Motor Drawing No. 0A5858  
®
G e n e r a c P o w e r S y s t e m s , In c . 2 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
0
183  
4
1
RED  
4
BRUSH HOLDER  
MTG. SCREW.  
1
1
0
0
194  
183  
4
23  
194  
23  
1
T2  
A
2
TS3  
X
K
W
2
T1  
N2  
N1  
A R  
L
V
PREPACKAGE  
TRANSFER  
SWITCH  
T2  
T1  
N2  
N1  
J
B
6
H
6
S16  
S15  
M
U
C
A
E
G
BRUSH WITH RED(4) LEAD  
CLOSEST TO BEARING.  
CONNECTION  
183  
N
T
D
F
O
P
S
DIRECT  
R
Q
CP  
PIN  
00  
178  
S1  
2
6
183  
178  
2-WIRE START CONNECTION  
FROM STANDARD GENERAC GTS  
TS4  
58  
57 S3  
S15  
S1  
0
00  
58  
2
2
S16  
S15  
6
6
57  
S3  
S3  
58  
57  
NB  
22  
5
33  
00  
0
57  
58  
S15  
A S  
(390mm)  
0
S16  
E1  
E3  
11  
CB2  
CT1  
44  
CT2  
LEGEND  
AR = ALTERNATOR ROTOR  
AS = ALTERNATOR STATOR  
CB2 = CIRCUIT BREAKER - MAIN  
CP = CONTROL PANEL CONNECTOR LOWER PANEL  
E1 TO E3 240V.  
E1 TO 00  
CUSTOMER CONNECTION  
120/240V. 1-PHASE  
120V.  
CT1 & CT2 = CURRENT TRANSFORMER  
DPE = EXCITATION WINDING  
NB = NEUTRAL BLOCK  
E3 TO 00  
TP = THERMAL PROTECTER  
TS3 = TERMINAL STRIP, PRE-PACKAGED TRANSFER SWITCH CONNECTION  
TS4 = TERMINAL STRIP, 2-WIRE START CONNECTION  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 Electrical Data  
(Model Nos. 004373-1 & 004262-0) Guardian Liquid-cooled 40 kW Generators  
Electrical Schematic - Lower Panel - Drawing No. 0D5997  
1
D
1
AR  
RED  
4
C
4
BRUSH UNITS  
6
F
THERMAL PROTECTOR BYPASS  
5
5
6
2
E
DPE  
22  
TP  
S1  
K
AS  
Q
44  
33  
11  
00  
M
S3  
57  
N
O
CT1  
0
58  
CT2  
S16  
0
A
G
S15  
CB2  
H
194  
23  
X
W
V
U
T
T2  
NB  
E1  
E3  
TS3  
TS4  
CUSTOMER CONNECTION  
120/240-V. 1-PHASE  
T1  
N2  
N1  
183  
178  
S
B
J
®
G e n e r a c P o w e r S y s t e m s , In c . 2 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No. 004373-1) Guardian Liquid-cooled 40 kW Generators  
Control Panel - Drawing No. 0D4995-C  
+
-
0
0
0
P I N  
Q
R
P
S
O
E
A
F
D
T
N
G
C
U
M
H
B
J
V
L
W
K
X
®
3 0 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No. 004373-1) Guardian Liquid-cooled 40 kW Generators  
Control Panel - Drawing No. 0D4995-C  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
3
4
5
6
8
9
0D1523  
0D1521A  
0D1522  
067680  
0C8243  
0C8244  
048467  
057907  
064008  
055444  
030468  
049939  
070370  
022158  
023762  
023897  
076009A  
040213  
027744  
082573  
076020  
032300  
022676  
064009  
061945  
076037  
070081  
070043  
070045  
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
PANEL BTM & BACK CONTROL PANEL  
CONTROL PANEL, FRONT W/ SILK SCREEN  
PANEL,SIDE COVER CONTROL PANEL  
ASSY VOLTAGE REGULATOR 60HZ  
WASHER LOCK HDP DEUTSCH  
NUT, HDP DEUTSCH  
CIRCT BRK 7 X 1 ETA 46-500-P  
RES WW LUG 10R 10% 25W  
COVER CON PNL TOP (NOT SHOWN)  
HEATSINK  
WASHER STEP NYLON .20  
RECTIFIER MSC 12A 600V 1N1206R  
WASHER MICA .203  
NUT HEX #10-32 STEEL  
WASHER SHAKEPROOF EXT #10 STL  
32  
33  
34  
35  
36  
37  
39  
41  
42  
43  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62*  
63*  
070042  
081988  
0C1229  
098647  
0A3968  
048766  
083264  
057335  
076061  
029333  
040479  
022507  
022127  
022097  
033121  
022152  
036902  
022155  
022985  
036918  
022264  
038150  
022471  
022188  
036908  
0C2428  
0C2323  
0D5324  
0A9611  
1
1
1
1
1
FREQUENCY METER 240V 55-65HZ  
DECAL EXERCISE INFO  
DECAL CUST CONN BOX  
ASSY L.C. ELECT GOV  
CAPACITOR FILTER ASY  
REF BLOCK TERM 20A 2 X 6 X 1100V  
TFMR ASM,CMA 240/12V  
REF BLOCK TERM 20A 20 X 6 X 1100V  
1
10  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
1
6
4
4
4
4
DECAL, TERM. STRIP  
TIE WRAP 7.4" X .19" NATL UL  
VIB MNT 1.0 X 1.0 X 1/4-20  
SCREW HHC 1/4-20 X 1/2 G5  
NUT HEX 1/4-20 STEEL  
WASHER LOCK M6-1/4  
14 SCREW HHC #10-32 X 1/2  
14 WASHER LOCK #10  
15 WASHER FLAT #10 ZINC  
1
4
1
1
1
1
1
1
1
1
1
1
1
PP LOGIC ASM 50/60HZ  
PCB SUPPORT SNAP-IN 1/4"  
GROMMET 3/4 X 5/32 X 5/16  
SWITCH ROCKER DPST 125V SPD  
SWITCH TOG DPDT 15/10 SP  
HOLDER FUSE  
4
6
8
8
8
8
8
6
2
4
4
1
SCREW PPHM #6-32 X 1/2  
WASHER LOCK #6  
WASHER FLAT #6 ZINC  
SCREW PPHM #8-32 X 1/2  
WASHER LOCK #8-M4  
WASHER FLAT #8 ZINC  
NUT HEX #8-32 STEEL  
NUT HEX #6-32 STEEL  
SCREW PPHM #6-32 X 1-1/4  
SCREW PHTT #6-32 X 1/2 ZYC  
SCREW PHTT #6-32 X 5/8 ZYC  
FUSE & HOLDER LITTEL 7.5A  
FUSE 15A X AGC15  
LIGHT 12VDC .02A LED RED PILOT  
SWITCH SELECTOR 6A AMP/V  
VOLTMETER DC 8-18V  
HOURMETER  
VOLTMETER AC 0-300  
AMMETER AC 0-200  
REF. FUSE 7.5AXBK/AGC7.5NX  
* PART OF CONTROL PANEL WIRE HARNESS  
®
G e n e r a c P o w e r S y s t e m s , In c . 3 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No. 004626-0) Guardian Liquid-cooled 40 kW Generators  
Control Panel - Drawing No. 0D6978-A  
+
-
0
0
0
P I N  
Q
R
P
S
O
E
A
F
D
T
N
G
C
U
M
H
B
J
V
L
W
K
X
®
3 2 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No. 004626-0) Guardian Liquid-cooled 40 kW Generators  
Control Panel - Drawing No. 0D6978-A  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
0D7397  
0D1521A  
1
1
PNL BTM & BACK CNTL PNL 04626  
CONTROL PANEL FRONT W/ SILK  
SCREEN  
PANEL SIDE COVER CONTROL PANEL  
ASSY VOLTAGE REGULATOR 60HZ  
WASHER LOCK HDP DEUTSCH  
NUT, HDP DEUTSCH  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62*  
63*  
0C1229  
0D3440  
0A3968  
048766  
0A1441B  
083264  
0A1441C  
057335  
076061  
029333  
040479  
022507  
022127  
022097  
033121  
022152  
036902  
022155  
022985  
036918  
022264  
038150  
022471  
022188  
0C2428  
0C2323  
0A2284  
0C1127  
0D5324  
0A9611  
1
1
1
REF  
1
1
1
REF  
1
6
4
4
4
4
14  
14  
4
6
8
8
8
8
8
6
8
4
4
DECAL CUST CONN BOX  
CONTROLLER, B-C #DPG-2103  
CAPACITOR FILTER ASY  
BLOCK TERM 20A 2 X 6 X 1100V  
COVER PLATE AVR  
TFMR ASM,CMA 240/12V  
COVER PLATE EGOV  
BLOCK TERM 20A 20 X 6 X 1100V  
DECAL TERM. STRIP  
TIE WRAP 7.4" X .19" NATL UL  
VIB MNT 1.0 X 1.0 X 1/4-20  
SCREW HHC 1/4-20 X 1/2 G5  
NUT HEX 1/4-20 STEEL  
WASHER LOCK M6-1/4  
SCREW HHC #10-32 X 1/2  
WASHER LOCK #10  
SCREW PPHM #6-32 X 1/2  
WASHER LOCK #6  
3
4
5
6
7
0D1522  
067680  
0C8243  
0C8244  
0A6321  
048467  
057907  
064008  
0A6323  
055444  
030468  
049939  
070370  
022158  
023762  
023897  
076009A  
040213  
0A3394  
082573  
076020  
032300  
022676  
064009  
061945  
076037  
070081  
070043  
070045  
070042  
081988  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
15  
1
4
1
1
1
1
1
1
1
1
1
1
1
1
1
PANEL LEFT SIDE E  
8
9
CIRCT BRK 7 X 1 ETA 46-500-P  
RES WW LUG 10R 10% 25W  
COVER CON PNL TOP (NOT SHOWN)  
CHASSIS AVR & E-GOV  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
HEATSINK  
WASHER STEP NYLON .20  
RECTIFIER MSC 12A 600V 1N1206R  
WASHER MICA .203  
NUT HEX #10-32 STEEL  
WASHER SHAKEPROOF EXT #10 STL  
WASHER FLAT #10 ZINC  
PP LOGIC ASM 50/60HZ  
PCB SUPPORT SNAP-IN 1/4"  
DECAL, ELEC GOVERNOR  
SWITCH ROCKER DPST 125V SPD  
SWITCH TOG DPDT 15/10 SP  
HOLDER FUSE  
WASHER FLAT #6 ZINC  
SCREW PPHM #8-32 X 1/2  
WASHER LOCK #8-M4  
WASHER FLAT #8 ZINC  
NUT HEX #8-32 STEEL  
NUT HEX #6-32 STEEL  
SCREW PHTT #6-32 X 1/2 ZYC  
SCREW PHTT #6-32 X 5/8 ZYC  
SCREW SWAGE 8-32 X 1/2 Z/YC  
DECAL AVR COVER  
FUSE & HOLDER LITTEL 7.5A  
FUSE 7.5AXBK/AGC7.5NX  
FUSE 15A X AGC15  
LIGHT 12VDC .02A LED RED PILOT  
SWITCH SELECTOR 6A AMP/V  
VOLTMETER DC 8-18V  
HOURMETER  
VOLTMETER AC 0-300  
AMMETER AC 0-200  
FREQUENCY METER 240V 55-65HZ  
DECAL EXERCISE INFO  
1
4
1
* PART OF CONTROL PANEL WIRE HARNESS  
®
G e n e r a c P o w e r S y s t e m s , In c . 3 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No. 004373-1) Guardian Liquid-cooled 40 kW Generator  
Electronic Governor Drawing No. 0A2615-F  
ITEM (18) NEOPRENE  
COATING  
14  
13  
3
12  
17  
WIRE HARNESS  
1
"A"  
9
11  
SECURE WIRE HARNESS  
WITH TIE WRAP AS SHOWN.  
15  
16  
15  
4
9
23  
EXISTING  
ENGINE  
HARDWARE  
19  
20  
CARB. ARM  
(REF.)  
24  
5
22  
21  
2
15  
11  
14  
13  
"A"  
3
12  
ITEM PART NO.QTY.  
DESCRIPTION  
1
2
3
4
5
098290  
0A3439  
098958A  
021888  
082508  
036409  
043146  
098941A  
098942A  
098225  
022097  
064526  
029333A  
074031  
051716  
049226  
076040  
098647  
036409  
0C2184  
1
1
1
1
2
2
3
2
2
4
4
1
1
-
2
2
2
1
2
1
ASSEMBLY MOTOR STEPPER  
BRACKET GOVERNOR MOUNTING  
CONNECTOR INTERFACE ASSEMBLY  
LEVER STEPPER MOTOR  
BALL JOINT PLA .25-.28  
NUT HEX 1/4-28 STEEL  
SCREW HHC M6-1.0 X 10 G8.8  
HOUSING GOVERNOR CONNECT  
COVER CONN HOUSING  
SCREW FHM #2 X 5/8 SELF TAP  
WASHER LOCK M6-1/4  
SCREW TAP HWH #6-25 X 3/8 ZINC  
TIE WRAP 7.4" X .19" BLACK UL  
LIQUID NEOPRENE (NOT SHOWN)  
NUT HEX M5-0.8 G8 YEL CHR  
WASHER LOCK M5  
9
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
SCREW PPHM M5-0.8 X 16  
ASSEMBLY L.C. ELECTRONIC GOVERNOR  
NUT HEX 1/4-28 STEEL  
STUD THR 1/4-28 X 3-1/2 G2 ZINC  
®
3 4 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generator  
Mounting Base Drawing No. 0C4399-C  
*26  
*27  
6
12 19  
5
11  
10  
18  
18  
20  
15  
19  
12  
11  
*28  
5
6
1
10  
*27  
14  
15  
To Oil Drain  
On Oil Pan.  
21  
16  
17  
13  
23  
22  
*26  
*27  
*28  
24  
*26  
*27  
29  
3
*28  
33  
32  
*27  
12  
31  
30  
16  
17  
13  
*25  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
0C3250  
1
BASE, MOUNTING ASSEMBLY, 4.3L  
(DIRECT-COUPLED)  
LUG SLDLSS #2-#8 X 17/64 CU  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 YEL CHR  
SCREW HHC M8-1.25 X 25 G8.8  
WASHER FLAT 5/16 ZINC  
WASHER SHAKEPROOF EXT 5/16 STL  
SCREW HHC M12-1.75 X 85 G8.8  
DAMPENER VIBRATION 40 BLUE  
SPACER .49 X .62 X 1.87 PWDR/ZINC  
DAMPENER VIBRATION  
* 25  
* 26  
* 27  
* 28  
* 29  
30  
31  
32  
33  
0A8785  
0C4360  
071693  
0C2454  
0C4753  
022413  
022473  
022097  
022127  
4
8
16  
16  
1
1
1
PLUG BUTTON 3" DIA.  
PLATE VARMINT  
WASHER FLAT .281 ID X 1.0 OD  
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
PLUG 3/4 BUTTON  
SCREW HHC 1/4-20 X 1 G5  
WASHER FLAT 1/4 ZINC  
WASHER LOCK M6-1/4  
3
5
6
055414  
022129  
045771  
043107  
022145  
027482  
055597  
052251  
052257  
052252  
052259  
052860  
0536210098  
052251A  
044118  
057823  
057448  
024310  
1
2
2
2
2
3
4
2
4
4
4
4
1
2
1
2
11"  
1
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
1
1
NUT HEX 1/4-20 STEEL  
NOTES: 1) * ITEMS 25, 26, 27, 28 & 29 ARE INCLUDED FOR UNITS  
WITH ENCLOSURES ONLY. NOT INCLUDED WITH  
OPEN SETS.  
WASHER FLAT M12  
NUT LOCKING M12-1.75  
ASSEMBLY GROUNDWIRE 10"/3/8  
DAMPENER VIBRATION 50 WHITE  
BARBED STRAIGHT 1/2 NPT X 5/8  
CLAMP HOSE #10 .56 - 1.06  
HOSE 5/8 ID TYPE 3 SINGLE  
PLUG STD PIPE 1/2 STEEL SQ HD  
2) ITEM 25 (PLUG BUTTON 3" DIA.) IS USED AFTER  
SHIPPING. HOLES ARE TO REMAIN UNCOVERED  
FOR SHIPPING PURPOSES. PLUGS CAN BE FOUND  
IN THE MANUAL BAG LOCATED INSIDE THE LOWER  
CONNECTION BOX.  
®
G e n e r a c P o w e r S y s t e m s , In c . 3 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generator  
Engine Common Parts Drawing No. 0A4304-J  
®
3 6 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generator  
Engine Common Parts Drawing No. 0A4304-J  
ITEM PART NO.QTY. DESCRIPTION  
ITEM PART NO.QTY. DESCRIPTION  
1
3
4
5
0A9046  
0A4239  
0A4240  
0A5640  
0A5640A  
0A5639  
0D3293A  
1
1
1
1
1
1
1
ENGINE 4.3L GM  
PULLEY CRANKSHAFT  
PULLEY WATER PUMP  
SPACER FAN 50MM (35 kW UNITS ONLY)  
SPACER FAN 62MM (45KW UNITS ONLY)  
FAN 17" REVRS ROT (35KW UNITS ONLY)  
FAN COOLING 22" DIA REVRS ROT  
(45KW UNITS ONLY)  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
0C2885  
0A4100G  
022131  
077456  
044117  
057823  
057448  
022129  
022142  
048614  
022237  
029745  
042633  
033819  
022241  
0A5768  
046526  
049814  
0C3756  
045772  
0D2514  
052259  
055934D  
1
1
8
1
1
1
1
8
4
4
12  
4
3
1
4
1
5
2
1
2
8
1
1
PULLEY TENSIONER  
SPACER DC ALTERNATOR 32MM  
WASHER FLAT 3/8-M10 ZINC  
ADAPTOR M12-1.75 3/8 NPT  
BARBED STRAIGHT 3/8 NPT X 5/8  
CLAMP HOSE #10 .56 - 1.06  
HOSE 5/8 ID TYPE 3 SINGLE (12")  
WASHER LOCK M8-5/16  
SCREW HHC 5/16-18 X 3/4 G5 (45KW)  
SCREW HHC 5/16-24 X 3/4 G5  
WASHER LOCK 3/8  
SCREW HHC 3/8-16 X 1 G5  
SCREW HHC 3/8-24 X 1 G5  
SCREW HHC 3/8-16 X 4 G5  
NUT HEX 3/8-16 STEEL  
WASHER FLAT HEAVY DUTY  
WASHER LOCK M10  
SCREW HHC M10-1.5 X 25 G8.8  
BOLT TENSIONER PULLEY  
NUT HEX M10-1.5 G8 YEL CHR  
SPARK PLUG 5.7L GM  
WASHER FLAT M12  
CLAMP VINYL 1.06 X .406 Z  
FILTER OIL  
6
7
8
9
077996  
057823  
035579  
037065  
022302  
0A8584  
052644  
0A4278A  
0A4930A  
0A4085  
0A3927  
0C7947  
0A1232  
0A7801B  
021928  
0C6239  
0A4241  
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
CAP HOSE  
CLAMP HOSE #10 .56 - 1.06  
BUSHING REDUCER 1/4 TO 1/8  
SCREW HHC 7/16-20 X 2-1/4 G5  
WASHER LOCK 7/16  
SWITCH OIL PRESSURE  
SPACER .5 X 1.5 X .25 STL/ZINC  
BELT SERPENTNE 72.5"  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
HEAT SHIELD LEFT  
GASKET EXHAUST MANIFOLD  
MANIFOLD LEFT EXHAUST  
BOLT U 3/8-16 X 2.50  
DC ALTERNATOR ASSEMBLY  
PULLEY PLOY-V 82 OD.  
BRACKET ALT. SUPPORT  
ASSEMBLY BRACKET MOUNTING WELD  
PULLEY GROOVED IDLER  
0A37970001 1  
®
G e n e r a c P o w e r S y s t e m s , In c . 3 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generators  
Engine Parts Drawing No. 0D6980  
®
3 8 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generators  
Engine Parts Drawing No. 0D6980  
ITEM  
PART NO. QTY. DESCRIPTION  
ITEM  
PART NO. QTY. DESCRIPTION  
1
2
3
4
6
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
0A9046  
0A9118A  
070022  
0A6021  
059056A  
0A9050  
022237  
045772  
049226  
051716  
0A4244  
0A4215  
0A4231  
059057  
0A2440  
026568  
099729A  
061012  
069939  
035606  
0A4930B  
0A4084  
029745  
044101  
1
1
1
6
1
2
17  
1
1
1
1
1
1
10"  
2
2
1
1
1
ENGINE 4.3L GM  
FLYWHL 4.3L GM SAE  
WASHER STAR M12 EXT  
SCREW HHC 7/16-20 X 1 G8  
STARTER 5.7L/7.4L GM  
BOLT STARTER 4.3L  
WASHER LOCK 3/8  
NUT HEX M10-1.5 G8 YEL CHR  
WASHER LOCK M5  
NUT HEX M5-0.8 G8 YEL CHR  
CONNECTOR COIL TO DISTRIBUTOR  
DIP STICK 4.3L GM  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
023152  
022131  
058030  
0A4085  
0A3928  
0C7947  
057794  
0A4277  
022241  
057795  
048191  
032303  
0A3852  
098239  
057522  
0D2244M  
2
2
2
1
1
2
2
1
4
1
2
6
3
1
1
1
SCREW HHC 3/8-16 X 3/4 G5  
WASHER FLAT 3/8-M10 ZINC  
RETAINER PLUG WIRES  
GASKET EXHAUST MANIFOLD  
MANIFOLD RIGHT EXHAUST  
BOLT U 3/8-16 X 2.50  
RETAINER SPARK PLUG WIRES  
WIRES SPARK PLUG 4.3L  
NUT HEX 3/8-16 STEEL  
CONNECTOR C/C VENT  
PIN DOWEL M10 X 24  
SCREW HHC 3/8-16 X 3-1/2 G5  
PLATE FLEX GM  
TUBE DIP STICK 4.3L  
HOSE 3/4 ID SAE-30R2  
GASKET THERMOSTAT  
CASTING ADAPTOR  
SENSOR COOLANT LEVEL  
ASSY MAGPICKUP (3/8-24 MALE)  
(MODEL 004626 0NLY)  
SCREW HHC 3/8-16 X 2-3/4 G5  
HOUSING THERM IMPREX  
PLUG STD PIPE 1/8 SOCKET HEAD  
HOUSING THERMOSTAT/WATER INLET  
SENSOR HI COOLANT SHUTDOWN  
HEAT SHIELD RIGHT  
MOUNT ENGINE R & L  
SCREW HHC 3/8-16 X 1 G5  
SPARK PLUG WIRE SUPPORT BRACKET  
43  
075885  
1
THERMOSTAT 195 DEG  
1
1
1
3
*
*
0D6979  
0A4308  
1
1
40KW GUARDIAN WIRE HARNESS  
(NOT SHOWN FOR MOD. 004626-0)  
HARNESS 4.3L STD WIRE  
2
(NOT SHOWN FOR MOD. 004373-1)  
®
G e n e r a c P o w e r S y s t e m s , In c . 3 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE:  
TORQUE ITEM #6 TO 24 FT/LB AND USE  
THREAD LOCKING COMPOUND (T-13717).  
To Engine Flywheel  
1
2
3
4
9
10  
13  
5
11  
12  
Add item #42  
vinyl trim as  
shown.  
14  
6
41  
15  
7
40  
16  
17  
39  
To Engine  
18  
Flywheel Housing  
23  
24  
25  
26  
20  
21  
22  
19  
Note:  
Thread in Sensor (8) until contact  
is made with Ring Gear, then back off  
1/2 to 3/4 turn and tighten nut.  
Caution:  
27  
39  
28  
29  
38  
Do not rotate engine during this  
adjustment.  
30  
37  
36  
31  
33  
35  
32  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-0 & 004626-0) Guardian Liquid-cooled 40 kW Generators  
Generator Drawing No. 0D5333-A  
ITEM  
PART NO. QTY. DESCRIPTION  
ITEM  
PART NO. QTY. DESCRIPTION  
1
2
3
4
5
6
7
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
051768  
051769  
022237  
043097  
0A3852  
055173  
022129  
0A5526  
0A2601  
0A2602  
0A1138  
021941  
020808A  
052624  
070892  
065477  
0A1633  
020729A  
022131  
046526  
057642  
6
6
8
8
3
6
6
1
1
1
1
1
1
1
1
4
4
SCREW HHC M12-1.75 X 25 G8.8  
WASHER LOCK M12  
WASHER LOCK 3/8  
SCREW SHC 3/8-16 X 1 G8.8 NZ  
PLATE FLEX GM  
SCREW HHC M8-1.25 X 20 G10.9  
WASHER LOCK M8-5/16  
FAN ASSEMBLY 390 SAE DD  
SCREW HHC M16-2.0 X 45 G8.8  
WASHER FLAT .688 ID X 3.25 OD  
KEY SQ 3/8 X 2-1/2 STEEL  
COUPLER 390 SAE  
ROTOR 390 40 1P DIRECT  
BEARING BALL 6212 SEALED  
SLIP RING -MACHINED-  
SCREW HHC M14-2.0 X 150 G8.8  
WASHER 390 SAE ALT  
STATOR 390 40AD2 SAE  
WASHER FLAT 3/8-M10 ZINC  
WASHER LOCK M10  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
068113  
068115  
043123  
051779  
046852  
022250  
051769  
057821  
022145  
022129  
057821  
024044A  
023877D  
022155  
025105  
071639  
0A4089  
0A2437  
022473  
056326  
1
1
4
4
1
1
1
1
1
1
4
2
4
4
4
1
1
CARRIER REAR BEARING 15"  
LOWER PANEL 15  
WASHER LOCK M14  
NUT HEX M14-2.0 G8 YEL CHR  
SCREW HHTT #10-32 X 1/4 BP  
WASHER FLAT 7/16  
WASHER LOCK M12  
SCREW HHC M8-1.25 X 40 G8.8  
WASHER FLAT 5/16 ZINC  
WASHER LOCK M8-5/16  
SCREW HHC M8-1.25 X 40 G8.8  
ASSEMBLY BRUSH & SHUNT  
BRUSH HOLDER-UNIV  
WASHER LOCK #6  
SCREW RHM 6-32 X 1/4 SIMS  
HOLDER BRUSH SUPPORT  
ASSEMBLY SCROLL 390 SAE  
SCREW SWAGE 1/4-20 X 5/8 Z/YC  
WASHER FLAT 1/4 ZINC  
TRIM VINYL BLACK 1/8 GP  
1
2
2
8.4'  
12  
12  
12  
SCREW HHC M10-1.5 X 40 G8.8  
®
G e n e r a c P o w e r S y s t e m s , In c . 4 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generators  
Compartment Drawing No. 0C4401-F  
28  
26  
13  
29  
23  
32  
33  
34  
25  
31  
30  
44  
15  
43  
39  
22  
11  
9
29  
12  
24  
14  
8
11  
36  
7
11  
35  
1
42  
10  
4
3
12  
16  
5
21  
20  
1
5
4
19  
18  
3
6
17  
11  
5
10  
BASE  
FRAME  
32  
29  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
ASSEMBLY M6 HINGE  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
0C3594  
0A3359  
0A3360  
10  
40  
40  
5
1
1
1
1
2
4
2
1
1
1
1
1
5
20  
5
23  
24  
25  
26  
28  
29  
30  
31  
32  
33  
34  
35  
36  
39  
42  
43  
44  
0C4064 (A)  
0C4066 (A)  
0C4067 (A)  
0C4117 (A)  
0C2634A  
0C2454  
022129  
042907  
022473  
022097  
022127  
0A9881  
0C3393  
0C3400 (A)  
0C3397  
066760  
022145  
1
1
1
1
1
76  
2
2
15  
1
1
DUCT FRONT RH  
DUCT BOTTOM  
DUCT FRONT PANEL  
SCREW BHSC M6-1.0 X 16 SS  
SHAKEPROOF INT M6 SS  
DOOR SMALL STD. WELD  
CORNER POST LH REAR  
CORNER POST RH REAR  
CORNER POST LH FRONT  
CORNER POST RH FRONT  
REAR BRACE TOP & BOTTOM  
SIDE BRACE TOP & BOTTOM  
SIDE SUPPORT  
0C2522 (A)  
0C2527 (A)  
0C2528 (A)  
0C2535 (A)  
0C2536 (A)  
0C2547 (A)  
0C2550 (A)  
0C2555 (A)  
0C2560 (A)  
0C2642 (A)  
0C4567 (A)  
0C2641 (A)  
0C4566 (A)  
0C2633  
0C6749  
060069  
0C6748  
080490  
087233  
0C4065 (A)  
DUCT FRONT TOP RH  
ASSEMBLY COVER ACCESS  
SCREW TH-FRM M6-1X16 N WA Z/JS  
WASHER LOCK M8-5/16  
SCREW HHC M8-1.25 X 16 G8.8  
WASHER FLAT 1/4 ZINC  
WASHER LOCK M6-1/4  
NUT HEX 1/4-20 STEEL  
ROOF ONE-PIECE WLDMT  
49.1 FT. GASKET DOOR RUBBER  
FRONT BRACE BOTTOM (2.4L & 4.3L)  
FRONT BRACE BOTTOM (3.0L D ONLY)  
FRONT BRACE TOP (2.4L & 4.3L)  
FRONT BRACE TOP (3.0L D ONLY)  
PLATE STRIKER GEN 2000  
SCREW PPHM M4-0.7 X 12 SS  
PADDLE HANDLE LOCK  
NUT LOCK HEX M4-0.7 SS NYL INS  
WASHER FLAT #8 SS  
RIVET POP 3/16 X 1/4  
2
1
4
SCREW SHOULDER  
COVER EXHAUST HOLE  
FASTENER RATCHET  
15  
39-3/8" STRIP SEALANT 1/8 X 1  
WASHER FLAT 5/16 ZINC  
16  
17  
18  
19  
20  
21  
22  
2
20  
20  
5
OPTIONAL COMPARTMENT MATERIALS:  
ALL P/N'S WITH AN "A" SUFFIX INDICATE  
ALUMINUM MATERIAL OPTION.  
1
DUCT FRONT LH  
®
4 2 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generators  
Radiator Drawing No. 0D4991-A  
29  
30  
1
10  
27  
22  
23  
15  
"A"  
24  
16  
22  
6
27  
5
4
7
To "A"  
13  
12  
11  
20  
21  
19  
8
12  
18  
14  
10  
10  
17  
9
ITEM  
PART NO. QTY. DESCRIPTION  
1
4
5
6
7
068928  
024655  
022097  
022473  
097246A  
097246B  
0A5397  
0A4375  
035685  
047290  
040173  
049340  
036865  
029032  
052250  
058443  
029745  
022237  
022131  
0A4374  
076749  
080712  
090388  
048031C  
0C4341  
046627  
1
4
4
4
1
1
1
1
4
16"  
2
1
1
46"  
2
9
4
4
4
RADIATOR 14 FIN/INCH  
SCREW HHTT 1/4-20 X 1 CZ  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4 ZINC  
VENTURI 16" DIA 35KW  
VENTURI 18" DIA 45KW  
GUARD FAN 4.3L D.C.  
HOSE 4.3L STD LOWER  
CLAMP HOSE #28 1.32 - 2.25  
HOSE 3/8 ID SINGLE BRAID  
CLAMP HOSE #5.5 .62 - .62  
BARBED ELBOW 90 1/4 NPT X 3/8  
DRAINCOCK  
HOSE 9/32 ID  
TAPE FOAM 1 X 1  
SCREW CRIMPTITE 1/4-20 X 5/8  
SCREW HHC 3/8-16 X 1 G5  
WASHER LOCK 3/8  
WASHER FLAT 3/8-M10 ZINC  
HOSE 4.3L STD UPPER  
TANK COOLANT RECOVERY  
BRACKET COOLANT RECOVERY TANK  
SCREW HHTT M6-1.0 X 12 YC  
CLAMP HOSE BAND 1/4  
SUPPORT RADIATOR A GROUP  
CAP RADIATOR  
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
27  
29  
30  
1
1
1
1
1
2
1
®
G e n e r a c P o w e r S y s t e m s , In c . 4 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No. 004373-1) Guardian Liquid-cooled 40 kW Generators  
Carburetor Drawing No. 0A5764-E  
USE FASTENER LOCATED ON  
ALTERNATOR FAN SCROLL  
TO  
25  
REGULATOR  
19  
24  
12  
11  
23  
21  
20  
6
10  
9
7
17  
8
19  
18  
TO STEPPER  
MOTOR  
5
3
4
22  
16  
2
1
13  
FRONT OF  
ENGINE  
15  
14  
27  
28  
26  
TO ALTERNATOR  
FAN SCROLL  
ITEM  
PART NO. QTY. DESCRIPTION  
ITEM  
PART NO. QTY. DESCRIPTION  
1
2
3
4
5
6
064945  
0A4120  
033212  
022129  
052865  
0A7631  
1
1
4
4
1
1
GASKET CARBURETOR ADAPTOR  
ADAPTOR CARBURETOR W/INLET  
SCREW HHC 5/16-18 X 1-1/4 G5  
WASHER LOCK M8-5/16  
CARBURETOR GASKET  
CARB. REWORK 4.3L (NATURAL  
GAS + VAPOR)  
CARBURETOR, REWORK (LPG LIQUID)  
SCREW HHC 3/8-16 X 1 G5  
WASHER LOCK 3/8  
ELBOW 90 DEG STREET 3/4  
TOE NIPPLE 3/4 NPT x 2  
CLAMP HOSE #16 .87 - 1.50  
HOSE 1IN ID LP GAS (NATURAL  
GAS + VAPOR) (3.6)  
HOSE 1IN ID LP GAS (LPG LIQUID) (1)  
BARBED ELBOW 90 1/8 NPT X 3/8  
HOSE 3/8 ID SINGLE BRAID (.75)  
VALVE PCV  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29*  
082508  
055934Z  
022097  
036409  
0A4632B  
0A4637  
0A5763  
0A4632A  
062522  
037561  
061258  
057796  
057795  
0A5737B  
0A5737C  
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
BALL JOINT PLA .25-28  
CLAMP VINYL 1.13 X .406 Z  
WASHER LOCK M6-1/4  
NUT HEX 1/4-28 STEEL  
PLATE AIR CLEANR BOTTOM  
FILTER AIR 11.5"  
ARM THROTTLE - REWORK  
PLATE AIR CLEANER TOP  
STUD THR 1/4-20 X 3 G2 ZNC FULL  
NUT WING 1/4-20 NYLK  
GASKET AIR CLEANER  
GROMMET  
0C5716  
029745  
022237  
026307  
028641  
057824  
057422  
1
2
2
1
1
1
1
7
8
9
10  
11  
12  
CONNECTOR C/C VENT  
SPACER DC ALT. 30LG (LP GAS)  
SPACER DC ALT. (VAPOR & NATURAL  
GAS)  
057422  
0A6344  
047290  
0A4121  
1
1
1
1
13  
14  
15  
* NOT SHOWN  
®
4 4 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No. 004626-0) Guardian Liquid-cooled 40 kW Generators  
Carburetor Drawing No. 0D6977  
USE FASTENER LOCATED ON  
ALTERNATOR FAN SCROLL  
TO  
REGULATOR  
19  
24  
12  
11  
10  
6
9
25  
17  
18  
22  
23  
21  
20  
31  
32  
30  
16  
7
8
31  
33  
5
3
4
2
1
13  
FRONT OF  
ENGINE  
15  
27  
28  
26  
14  
TO ALTERNATOR  
FAN SCROLL  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
3
4
5
6
7
8
9
064945  
0A4120  
033212  
022129  
0C7059  
0C7650A  
029745  
022237  
026307  
028641  
1
1
4
4
1
1
2
2
1
1
GASKET CARBURETOR ADAPTOR  
ADAPTOR CARBURETOR W/INLET  
SCREW HHC 5/16-18 X 1-1/4 G5  
WASHER LOCK M8-5/16  
GASKET GOVERNOR THROTTLE BODY  
MIXER (ONLY) NATURAL GAS  
SCREW HHC 3/8-16 X 1 G5  
WASHER LOCK 3/8  
ELBOW 90 DEG STREET 3/4  
NIPPLE TOE (THREADED ONE END) 3/4  
NPT X 2  
CLAMP HOSE #16 .87-1.50  
HOSE 1 IN ID LP GAS  
BARBED ELBOW 90 1/8 NPT X 3/8  
HOSE 3/8 ID SINGLE BRAID  
VALVE PCV  
ACTUATOR THROTTLE 42MM  
CLAMP VINYL 1.13 X .406 Z  
GASKET CARB IMPCO 225  
19  
20  
21  
22  
036409  
0A4632B  
0A4637  
0C7820  
1
1
1
1
NUT HEX 1/4-28 STEEL  
PLATE AIR CLEANR BOTTOM  
FILTER AIR 11.5"  
MACHINING CARBURETOR  
ADAPTOR  
PLATE AIR CLEANER TOP  
STUD THR 1/4-20 X 3 G2 ZNC FULL  
NUT WING 1/4-20 NYLK  
GASKET AIR CLEANER  
GROMMET  
CONNECTOR C/C VENT  
SPACER DC ALTERNATOR  
GASKET CARBURETOR ADAPTOR  
WASHER LOCK #10  
23  
24  
25  
26  
27  
28  
29*  
30  
31  
32  
33  
0A4632A  
062522  
037561  
061258  
057796  
057795  
0A5737C  
0C7060  
022152  
064090  
0C7908  
1
1
1
1
1
1
1
1
8
4
4
10  
11  
12  
13  
14  
15  
16  
17  
18  
057824  
057422  
0A6344  
047290  
0A4121  
0D2803  
055934Z  
0A6613  
1
44"  
1
9"  
1
1
1
1
SCREW PHM SEMS #12-24 X 5/8 EX  
SCREW SHC #10-32 X 5/8 G8.8 NZ  
* NOT SHOWN  
®
G e n e r a c P o w e r S y s t e m s , In c . 4 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
Guardian Liquid-cooled 40 kW Generators  
Regulator Drawing No. 0C2776-C  
TO  
CARBURETOR  
18  
For LPG Vapor Withdrawal Turn  
Regulator (Item 7)  
Upside Down, Remove Items A & B  
19  
Then Replace End Cap.  
A
B
18  
17  
END CAP  
6
7
6
2
5
4
2
8
9
11  
12  
3
13  
25  
12  
26  
10  
MOUNTING  
BASE  
2
11  
23  
21  
1
20  
11  
12  
13  
11  
12  
13  
14  
24  
11  
12  
13  
15  
16  
ITEM  
PART NO. QTY. DESCRIPTION  
ITEM  
PART NO. QTY. DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
065907  
026307  
076691  
043768A  
026490  
026577  
055944  
067018  
0C2775  
061910  
022145  
022129  
030795  
025655  
022132  
051778  
1
3
1
1
1
2
1
1
1
4
6
6
4
1
2
2
SUPPORT SOLENOID NAT GAS  
ELBOW 90 DEG STREET 3/4  
NIPPLE PIPE 3/4NPTX4.5 BLK IRN  
SOLENOID GAS FUEL  
17  
18  
19  
20  
21  
22*  
23  
24  
25  
26  
028641  
057824  
057422  
043123  
051779  
055934P  
027482  
0C3168  
022259  
058359  
1
2
1
2
2
1
1
1
1
1
NIPPLE TOE 3/4 NPT X 2  
CLAMP HOSE #16 .87 - 1.50  
HOSE 1IN ID LP GAS  
WASHER LOCK M14  
NIPPLE PIPE 3/4 NPT X 2  
NUT HEX M14-2 G8 YEL CHR  
CLAMP VINYL 1.62 X .486 Z  
WASHER SHAKEPROOF EXT 5/16 STL  
WASHER LOCK SPECIAL 5/16  
NUT HEX 5/16-18 STEEL  
BUSHING REDUCER 1 TO 3/4  
REGULATOR NAT GAS LPG VAPOR  
SUPPORT REGULATOR  
BRACKET REGULATOR 4.3L  
SCREW HHTT #10-24 X 3/4 CZ  
WASHER FLAT 5/16 ZINC  
LUG RNGTNG INS 22-18 X 5/16 X .477  
WASHER LOCK M8-5/16  
* NOT SHOWN  
SCREW HHC 5/16-18 X 1 G5  
PLUG STD PIPE 3/4 STEEL SQ HD  
WASHER FLAT 9/16 ZINC  
NOTE: ITEM #22 ATTACHES TO ALTERNATOR SCROLL  
SCREW HHC M14-2.0 X 25 G8.8  
®
4 6 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No. 004626-0) Guardian Liquid-cooled 40 kW Generators  
Carburetor Drawing No. 0D4823-A  
TO  
CARBURETOR  
18  
19  
18  
17  
10  
6
7
6
2
5
4
8
2
27  
9
3
11  
12  
25  
12  
26  
11  
13  
11  
12  
25  
2
23  
MOUNTING  
BASE  
21  
1
20  
11  
12  
13  
11  
12  
13  
28  
14  
24  
11  
12  
15  
13  
16  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
065907  
026307  
076691  
043768A  
026490  
026577  
0D2758  
028237  
0C2775  
028238  
022145  
022129  
030795  
025655  
022132  
051778  
028641  
1
3
1
1
1
2
1
2
1
SUPPORT SOLENOID NAT GAS  
ELBOW 90 DEG STREET 3/4  
NIPPLE PIPE 3/4 NPT X 4.5 BLK IRN  
SOLENOID GAS FUEL  
NIPPLE PIPE 3/4 NPT X 2  
BUSHING REDUCER 1 TO 3/4  
REGULATOR N/G (R600S)  
SADDLE 1-3/8  
BRACKET REGULATOR 4.3L  
BOLT U 5/16-18 X 1.50  
18  
19  
20  
21  
22*  
23  
24  
25  
26  
057824  
057422  
043123  
051779  
055934P  
027482  
0C3168  
022259  
058359  
2
1
2
2
1
1
1
5
1
CLAMP HOSE #16 .87-1.50  
HOSE 1 IN ID LP GAS  
WASHER LOCK M14  
NUT HEX M14-2 G8 YEL CHR  
CLAMP VINYL 1.62 X .486 Z  
WASHER SHAKEPROOF EXT 5/16 STL  
WASHER LOCK SPECIAL 5/16  
NUT HEX 5/16-18 STEEL  
LUG RNGTNG INS  
2
22-18 X 5/16 X .477  
SUPPORT REGULATOR  
DECAL,INLET PRESSURE  
10  
10  
4
1
2
WASHER FLAT 5/16 ZINC  
WASHER LOCK M8-5/16  
27  
28  
0D2616  
0D1509  
1
1
SCREW HHC 5/16-18 X 1 G5  
PLUG STD PIPE 3/4 STEEL SQ HD  
WASHER FLAT 9/16 ZINC  
SCREW HHC M14-2.0 X 25 G8.8  
NIPPLE TOE 3/4 NPT X 2  
* NOT SHOWN  
2
1
NOTE: ITEM #22 ATTACHES TO ALTERNATOR SCROLL  
®
G e n e r a c P o w e r S y s t e m s , In c . 4 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generators  
Engine Coolant Heater Drawing No. 087434-D  
Lower Radiator  
Hose  
To Water  
Pump  
To Engine  
Block  
To Lower  
1
3
2
14  
Radiator  
7
3
6
5
13  
3
11  
3
4
11  
10  
10  
12  
9
8
ITEM PART NO. QTY. DESCRIPTION  
1
2
3
4
080723  
035685  
057822  
084918C  
*084918D  
050967  
0A6283  
053660  
084427  
047411  
022097  
022473  
049813  
042568  
**077043E  
1
2
4
1
1
1
1
1
1
2
4
4
2
2
36"  
HOSE CONNECTION TEE 1.75-.62  
CLAMP, HOSE #28 1.32-2.25  
CLAMP, HOSE #8 .53-1.00  
HEATER, ENGINE 1800W 120V.  
HEATER, ENGINE 2000W 240V.  
HOSE, 5/8" I.D. RIA 250F (36)  
HOSE, PREFORMED BLOCK HEATER  
BARBED ST. 1/4" NPT x 5/8 I.D.  
BRACKET, HEATER  
SCREW HHC M6-1.0 X 16 G8.8  
WASHER, LOCK-M6-1/4  
WASHER, FLAT 1/4 ZINC  
NUT, HEX-M6 X 1.00 G8 YEL CHR  
SCREW, HHC-M6-1.0 x 20MM G8.8  
FLEXIBLE CONDUIT 1" BLACK  
5
6
7
8
9
10  
11  
12  
13  
14  
*USED ON "R" VOLTAGE GENERATORS ONLY  
**ITEM #14 USED ONLY ON 4.3L UNITS  
®
4 8 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generators  
Battery Drawing No. A6708-F  
TO STARTER  
SOLENOID  
6
11  
12  
5
9
13  
RED  
3
14  
TO ENGINE BLOCK  
BLACK  
2
9
4
8
8
7
7
ITEM  
PART NO. QTY. DESCRIPTION  
2
3
4
5
6
058665  
061902  
059473  
038805H  
038804N  
038804T  
0A4010  
052858  
049820  
023152  
022131  
025507  
022237  
1
1
1
1
1
1
2
2
2
1
1
1
1
BATTERY 12VDC 90-AH 27F (OPTIONAL)  
HOLD DOWN BATTERY  
HOLD DOWN BATTERY  
CABLE BATTERY BLACK #1 X 23.00  
CABLE BATTERY RED #1 X 15.00  
CABLE BATTERY RED #1 X 31.00 (GEAR BOX-NON-GUARDIAN UNITS)  
SCREW HHC M8-1.25 X 60 FT G8.8  
NUT LOCK FLANGE M8-1.25  
NUT LOCK HEX M8-1.25 (NYLON INSERT)  
SCREW HHC 3/8-16 X 3/4 G5  
WASHER FLAT M10-3/8 ZINC  
WASHER SHAKEPROOF EXT 7/16 STL  
WASHER LOCK 3/8  
7
8
9
11  
12  
13  
14  
®
G e n e r a c P o w e r S y s t e m s , In c . 4 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generators  
Lower Panel Drawing No. 0D5334-B  
®
5 0 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generators  
Lower Panel Drawing No. 0D5334-B  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
35  
36  
37  
39  
40  
41  
43  
44  
45  
46  
53  
54  
022152  
023897  
069232  
022471  
022507  
022287  
022473  
022097  
022127  
022259  
069173  
057329  
062684  
057073  
039287  
045771  
022511  
022241  
022237  
0D3388  
14  
8
4
7
8
27  
19  
50  
12  
6
1
1
1
2
2
2
1
3
WASHER LOCK #10  
WASHER FLAT #10 ZINC  
1
2
3
4
6
068115  
0D5489  
040479  
023484N  
056739  
058710  
048766  
022985  
068116  
081418  
081419  
081523U  
042419  
0D5840  
022264  
0C2212  
022142  
022145  
022129  
022158  
1
1
4
1
1
2
1
2
1
1
1
1
4
1
13  
4
6
8
LOWER PANEL 15  
COVER LOWER CONNECTION BOX  
VIBRATION MOUNT 1.0 X 1.0 X 1/4-20  
BUSHING SNAP SB-2.5-31  
RELAY SOLENOID 12VDC PNL MNT  
TRANSFORMER 200A TO 5A 5VA  
BLOCK TERM 20A 2 X 6 X 1100V  
WASHER FLAT #6 ZINC  
COVER LOWER PANEL 15  
COVER-CB KAP36000 15"  
COVER-CB TERM KAP 15"  
CIRCT BRK 200 X 3 600V UL SQ D  
SCREW RHM 10-32 X 4  
DECAL CUSTOMER CONNECTN FOR TS  
WASHER LOCK M4  
SCREW PHTT M4-0.7 X 16 ZYC  
SCREW HHC 5/16-18 X 3/4 G5  
WASHER FLAT 5/16 ZINC  
SCREW RHM #10-32 X 3-3/4  
NUT HEX #8-32 STEEL  
SCREW HHC 1/4-20 X 1/2 G5  
SCREW HHC 1/4-20 X 3/4 G5  
WASHER FLAT 1/4 ZINC  
WASHER LOCK M6-1/4  
NUT HEX 1/4-20 STEEL  
NUT HEX 5/16-18 STEEL  
BUS BAR NEUTRAL STRP  
LUG SLDLSS 350-#6 X 13/32 AL/CU  
LUG SLDLSS 2/0-#12 X 11/32 CU  
JUNCTION BLOCK 3/8-16  
SCREW HHC M8-1.25 X 45 G8.8  
NUT HEX M8-1.25 G8 YEL CHR  
SCREW HHC 3/8-16 X 1-1/4 G5  
NUT HEX 3/8-16 STEEL  
10  
11  
12  
13  
14  
15  
16  
17  
18  
29  
30  
31  
32  
33  
34  
55  
57  
58  
59  
60  
61  
70  
3
1
WASHER LOCK 3/8  
DECAL REMOTE START CONNECTION  
12  
10  
WASHER LOCK M8-5/16  
NUT HEX #10-32 STEEL  
®
G e n e r a c P o w e r S y s t e m s , In c . 5 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No 004626-0) Guardian Liquid-cooled 40 kW Generators  
Exhaust Muffler Drawing No. 0D6976  
®
5 2 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No 004626-0) Guardian Liquid-cooled 40 kW Generators  
Exhaust Muffler Drawing No. 0D6976  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
18  
059902A  
0C9641  
0D4208  
0D5061  
0C4126  
0D5787  
0A5215B  
0D5792  
0D5793  
0C4170  
0C4305  
0C2454  
0C3433A  
022129  
022145  
045771  
042907  
1
1
1
4
2
1
2
1
1
2
1
2
4
CAP RAIN 2.50 / 2.69  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
080762  
022237  
022241  
0D5187  
0D5190  
077879  
0D4221  
0D4512  
043116  
022471  
022264  
038150  
036918  
049811  
022097  
049813  
8
BOLT U 3/8-16 X 2.62  
TUBE STRAIGHT 'A' GROUP  
MUFFLER CATALYST 4.3L  
MOUNTING BAND A-GRP CATALYST  
BRACKET MUFFLER MOUNTING  
TUBE ELBOW 90 DEG 2.5"  
PIPE FLEX 2.5"  
16 WASHER LOCK 3/8  
16 NUT HEX 3/8-16 STEEL  
1
1
1
1
1
2
5
5
8
5
2
2
2
SHIELD HEAT CROSSOVER 4.3L  
SHIELD HEAT EXHAUST 4.3L  
HOSE VACUUM 5/32 (3)  
KIT AIR/FUEL RATIO CONTROLLER  
BRACKET AIR/FUEL CONTROLLER  
SCREW HHC M6-1.0 X 12 G8.8  
NUT HEX #8-32 STEEL  
WASHER LOCK #8-M4  
WASHER FLAT #8 ZINC  
SCREW PPHM #8-32 X 1/2  
WASHER FLAT M6  
WASHER LOCK M6-1/4  
TUBE 2.5" SMALL TEE  
TUBE ELBOW 90 DEG 2.5" FLARED  
BRACKET EXHAUST SHIELD  
SHIELD A-GRP HEAT  
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
CLAMP BAND 2.5"  
16 WASHER LOCK M8-5/16  
20 WASHER FLAT 5/16 ZINC  
4
NUT HEX M8-1.25 G8 YEL CHR  
NUT HEX M6 X 1.0 G8 YEL CHR  
16 SCREW HHC M8-1.25 X 16 G8.8  
®
G e n e r a c P o w e r S y s t e m s , In c . 5 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 Exploded Views and Parts Lists  
(Model No. 004373-1) Guardian Liquid-cooled 40 kW Generators  
Generator Drawing No. 0D5786  
20  
19  
21  
1
21  
20  
2.5" Dia. Clamp Assembly  
21  
20  
2
22  
23  
19  
19  
6
19  
19  
3
13  
9
7
13  
19  
19  
13  
19  
18  
7
14  
8
18  
15  
14  
11  
4
16  
5
15  
To Engine  
10  
To  
Compartment  
Front  
19  
15  
To Engine  
12  
14  
4
18  
5
10  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
12  
13  
14  
15  
16  
18  
19  
20  
21  
22  
23  
0C2454  
0C3433A  
022129  
022145  
0C9748  
042907  
080762  
022237  
022241  
0D5187  
0D5190  
2
4
12  
12  
1
12  
8
16  
16  
1
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
CLAMP BAND 2.5"  
WASHER LOCK M8-5/16  
WASHER FLAT 5/16 ZINC  
PLUG M18-1.5  
SCREW HHC M8-1.25 X 16 G8.8  
BOLT U 3/8-16 X 2.62  
WASHER LOCK 3/8  
1
2
3
4
5
6
7
8
9
059902A  
0C9641  
0C9650  
0C4114A  
0C4126  
0D5787  
0A5215B  
0D5792  
0D5793  
0C4170  
0C4305  
1
1
1
2
2
1
2
1
1
2
1
CAP RAIN 2.50 / 2.69  
TUBE STRAIGHT 'A' GROUP  
MUFFLER 2-1/2" INLET/OUTLET  
CLAMP BAND MUFFLER 6.5"  
BRACKET MUFFLER MOUNTING  
TUBE ELBOW 90 DEG 2.5"  
PIPE FLEX 2.5"  
TUBE 2.5" SMALL TEE  
NUT HEX 3/8-16 STEEL  
SHIELD HEAT CROSSOVER 4.3L  
SHIELD HEAT EXHAUST 4.3L  
TUBE ELBOW 90 DEG 2.5" FLARED  
BRACKET EXHAUST SHIELD  
SHIELD A-GRP HEAT  
10  
11  
1
®
5 4 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 Notes  
Guardian Liquid-cooled 40 kW Generators  
®
G e n e r a c P o w e r S y s t e m s , In c . 5 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 Installation Drawings  
Guardian Liquid-cooled 40 kW Generators  
Installation Drawing Drawing No. 0D5335  
NOTE 7  
220 [8.65"] STUB-UP AREA  
R677 [R26.66"]  
TYP  
STUB-UP AREA  
SEE NOTE 8  
AND CHART  
ALT  
AIR  
OU  
247 [9.73"]  
204 [8.03"]  
794 [31.28"]  
STUB-UP  
AREA  
839 [33.01"]  
TYP  
A1  
C
140 [5.50"]  
TYP  
49 [1.92"]  
TYP  
MOUNTING HOLES  
Ø13.5 [Ø0.53"]  
8 HOLES ON BOTTOM  
ALT  
AIR  
OUT  
NOTE 1  
71 [2.79"]  
110 [4.33"] TYP.  
570 [22.44"] TYP.  
37 [1.44"]  
665 [26.19"]  
TOP OR PLAN VIEW  
2397 [94.37"]  
454 [17.87"]  
NOTE 3  
NOTE 5  
NOTE 9  
V
A
Hz  
NOTE 2  
NOTE 6  
1
1117 [43.98"]  
103 [4.06"]  
53 [2.09"]  
NATURAL GAS INLET  
3/4" NPT FEMALE  
835 [32.87"]  
936 [36.85"]  
OIL DRAIN  
1/2" N.P.T. FEMALE  
LEFT SIDE VIEW  
®
5 6 G e n e r a c P o w e r S y s t e m s , In c .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 Installation Drawings  
Guardian Liquid-cooled 40 kW Generators  
Installation Drawing Drawing No. 0D5335  
NOTES:  
RECOMMENDED FUEL/ELECTRICAL STUB-UPS  
(SEE TOP VIEW)  
1. STANDARD BLOCK HEATER REQUIRES 120V AC CONNECTION  
2. CONNECTION POINTS FOR AC LOAD LEADS, TRANSFER SWITCH, AND  
ENGINE AUTOMATIC START/STOP CONTROL WIRES PROVIDED IN  
AC CONNECTION PANEL.  
3. EXHAUST MUFFLER SUPPORT BRACKETS SUPPLIED WITH OPTIONAL COMPARTMENT.  
4. 12 VOLT NEGATIVE GROUND SYSTEM  
INSIDE  
BASE  
DESCRIPTION  
A1  
(LEFT)  
AC LOAD LEAD CONDUIT  
INSIDE STUB-UP FOR  
FUEL CONNECTIONS  
C
BATTERY TRAY INSIDE DIMENSIONS: 178 X 342.5 [7" X 13.5"]  
5. 2.5" I.D. FLEX EXHAUST  
6. MAIN LINE CIRCUIT BREAKER.  
7. DOORS MUST BE OPENED 90 DEG. TO BE REMOVED.  
8. A1 MAY BE USED  
NOTE:  
FUEL SYSTEM SET UP WITH OUTSIDE STUB UPS  
(SEE LEFT SIDE VIEW). SMALL FUEL SYSTEM  
MODIFICATIONS REQUIRED FOR  
FOR CIRCUIT BREAKER STUB-UP LOCATION.  
9. SEE DRAWING C3850 FOR DUCT REMOVAL. REMOVAL OF FRONT  
DUCT WILL PROVIDE ACCESS TO MUFFLER FOR SERVICING.  
INSIDE STUB-UPS.  
WEIGHT DATA  
ENGINE SERVICE CONNECTIONS  
UNIT: 729.7 kg [1609 lbs]  
STEEL COMPARTMENT: 208.6 kg [460 lbs]  
INLET NATURAL GAS = 3/4" NPT COUPLING  
OIL DRAIN = 1/2" NPT COUPLING  
EXHAUST OUTLET -  
2.5" OD MUFFLER OUTLET  
UNITS: mm [INCHES]  
965 [37.99"]  
(1) 12V BATTERY  
SEE NOTE 4  
LIFTING EYE  
(4 PLACES)  
1160 [45.67"]  
158 [6.22"]  
CENTER OF  
GRAVITY  
981 [38.62"]  
877 [34.51"]  
REAR VIEW  
1930 [75.98"]  
RIGHT SIDE VIEW  
®
G e n e r a c P o w e r S y s t e m s , In c . 5 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 Warranty  
Guardian Liquid-cooled 40 kW Generators  
GENERAC POWER SYSTEMS "TWO YEAR" STANDARD WARRANTY FOR GUARDIAN®  
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"  
For a period of two years or 2000 hours of operation from the date of original sale, whichever occurs first, Generac Power  
System s, Inc. (Generac) will, at its option, repair or replace any part which, upon exam ination, inspection and testing by  
Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under norm al use and service, in accor-  
dance with the warranty schedule set forth below. Any equipm ent that the purchaser/owner claim s to be defective m ust be  
returned to and exam ined by the nearest Generac Authorized Warranty Service Dealer. All transportation costs under the war-  
ranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty applies only to  
Generac Guardian prepackaged em ergency autom atic standby generators sold and rated for use in "Standby" applications.  
WARRANTY SCHEDULE  
YEARS ONE an d TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and  
m aintenance is required):  
Engine - All Com ponents  
Alternator - All Com ponents  
Transfer System - All Com ponents  
All warranty expense allowances are subject to the conditions defined in Generac's Warranty Policies, Procedures and Flat Rate  
Manual.  
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:  
Generac Guardian generators that utilize non-Generac replacem ent parts.  
Any Generac Guardian generators used as rental or trailer m ounted applications.  
Units used for prim e power in place of existing utility power where utility power is present or in place of utility power where  
utility power service does not norm ally exist.  
Costs of norm al m aintenance, adjustm ents, installation and start-up.  
Failures caused by any contam inated fuels, oils, coolants or lack of proper fluid am ounts.  
Failures due, but not lim ited, to norm al wear and tear, accident, m isuse, abuse, negligence or im proper installation. As with  
all m echanical devices, the Generac engines need periodic part(s) service and replacem ent to perform well. This warranty  
will not cover repair when norm al use has exhausted the life of a part(s) or engine.  
Failures caused by any external cause or act of God, such as collision, theft, vandalism , riot or wars, nuclear holocaust, fire,  
freezing, lightning, earthquake, windstorm , hail, volcanic eruption, water or flood, tornado or hurricane.  
Dam age related to rodent infestation.  
Products that are m odified or altered in a m anner not authorized by Generac in writing.  
Any incidental, consequential or indirect dam ages caused by defects in m aterials or workm anship, or any delay in repair or  
replacem ent of the defective part(s).  
Failure due to m isapplication.  
Telephone, cellular phone, facsim ile, internet access or other com m unication expenses.  
Living or travel expenses of person(s) perform ing service, except as specifically included within the term s of a specific unit  
warranty period.  
Expenses related to "custom er instruction" or troubleshooting where no m anufacturing defect is found.  
Rental equipm ent used while warranty repairs are being perform ed.  
Overnight freight costs for replacem ent part(s).  
Overtim e labor.  
Starting batteries, fuses, light bulbs and engine fluids.  
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES  
NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Som e states do not  
allow lim itations on how long an im plied warranty lasts, so the above lim itation m ay not apply to you.  
GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT  
SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A  
DIRECT RESULT OF GENERAC'S NEGLIGENCE. Som e states do not allow the exclusion or lim itation of incidental or conse-  
quential dam ages, so the above lim itation m ay not apply to you.  
This warranty gives you specific legal rights. You also have other rights from state to state.  
®
G E N E R A C P O W E R S Y S T E M S , IN C .  
P .O . B O X 2 9 7  
W H ITE W ATE R , W I 5 3 1 9 0  
P a r t N o . 0 D 4 9 6 3  
R e v is io n 1 (1 2 / 2 0 / 0 1 )  
P r in t e d in U .S .A .  