Generac Portable Generator 005030 0 (15kW) User Manual

Owner’s Manual  
Liquid-cooled, Prepackaged  
Standby Generators  
Model Number 005030-0 (15kW)  
005028-0 (20kW)  
005031-0 (25kW)  
This manual should remain with the unit.  
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS  
SHOULD ATTEMPT INSTALLATION!!  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Liquid-cooled 15, 20 and 25 kW Generators  
INTRODUCTION................................................IFC  
Read this Manual Thoroughly......................................IFC  
Operation and Maintenance ........................................IFC  
How to Obtain Service ................................................IFC  
Authorized Service Dealer Location ............................IFC  
SAFETY RULES....................................................2  
Standards Index..............................................................3  
Section 1 — GENERAL INFORMATION ............4  
1.1 Generator..............................................................4  
1.2 Transfer Switch ....................................................4  
1.3 ATS Mode (Automatic Operation)..........................4  
Section 3 OPERATION ................................15  
3.1 Control Console Components..............................15  
3.2 Manual Transfer and Startup..............................15  
3.3 Engine Governor Gain Adjustments....................16  
3.4 Manual Retransfer and Shutdown ......................17  
3.5 Automatic Operation ..........................................17  
3.6 Weekly Exercise Cycle..........................................17  
3.7 Control Board DIP Switch Settings ....................18  
3.8 Voltage Regulator Adjustment..............................18  
Section 4 — MAINTENANCE ..........................19  
4.1 Maintenance Performed by Authorized  
Service Facilities..................................................19  
1.4 Engineered Transfer Switch (2-wire Start  
GTS Mode)............................................................4  
4.2 Exhaust Manifold Procedure ..............................19  
4.3 Intake Manifold Procedure ..................................19  
4.4 Cylinder Head Procedure ....................................20  
4.5 Cooling System....................................................20  
1.5 Generator AC Connection Systems........................4  
1.6 Main Circuit Breaker ............................................5  
1.7 Generator Fuel System..........................................5  
1.8 Engine Protective Devices......................................5  
1.9 Unpacking ............................................................6  
1.10 Lifting the Generator ............................................6  
1.11 Specifications ........................................................7  
1.12 Fuel Consumption ................................................7  
1.13 Reconfiguring the Fuel System for LP Vapor..........7  
1.14 Engine Oil Recommendations ..............................8  
1.15 Coolant Recommendations....................................8  
1.16 Before Installation ................................................8  
Section 2 — INSTALLATION ............................9  
2.1 Standby Generator Installation ............................9  
2.2 Generator Location................................................9  
2.3 Generator Mounting and Support ........................9  
2.4 Basic Standby Electric System............................10  
2.5 Emergency Circuit Isolation Method....................10  
2.6 Total Circuit Isolation Method ............................10  
2.7 Grounding the Generator ....................................10  
2.8 Generator AC Neutral Connections......................11  
2.9 Automatic Transfer Switch (ATS Mode) ..............11  
4.6 Overload Protection for Engine DC  
Electrical System ................................................20  
4.7 Checking Fluid Levels ........................................20  
4.8 Maintenance Owner/Operator  
Can Perform........................................................21  
4.9 Miscellaneous Maintenance ................................22  
4.10 Scheduled Maintenance ......................................24  
Section 5 — TROUBLESHOOTING ..................27  
Section 6 — NOTES ........................................28  
Section 7 — ELECTRICAL DATA ....................30  
Section 8 — EXPLODED VIEWS AND  
PARTS LISTS ..............................38  
Section 9 — INSTALLATION DIAGRAM ..........55  
Section 10 — WARRANTY...............................56  
2.10 Engineered Transfer Switch (2-wire Start  
GTS Mode)..........................................................12  
2.11 Battery Installation..............................................13  
2.12 Preparation Before Start-Up................................14  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Instructions  
Liquid-cooled 15, 20 and 25 kW Generators  
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe  
operation be copied and posted in potential hazard areas. Safety should be stressed to all  
operators, potential operators, and service and repair technicians for this equipment.  
!
!
!
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be  
followed during installation and maintenance of the generator and batteries.  
!
!
!
GENERAL HAZARDS  
!
!
WARNING:  
For safety reasons, the manufacturer recommends that this  
equipment be installed, serviced and repaired by an  
Authorized Service Dealer or other competent, qualified  
electrician or installation technician who is familiar with  
applicable codes, standards and regulations. The operator  
also must comply with all such codes, standards and regu-  
lations.  
• Installation, operation, servicing and repair of this (and  
related) equipment must always comply with applicable  
codes, standards, laws and regulations. Adhere strictly to  
local, state and national electrical and building codes.  
Comply with regulations the Occupational Safety and  
Health Administration (OSHA) has established. Also,  
ensure that the generator is installed, operated and serv-  
iced in accordance with the manufacturer’s instructions  
and recommendations. Following installation, do nothing  
that might render the unit unsafe or in noncompliance with  
the aforementioned codes, standards, laws and regula-  
tions.  
The engine exhaust from this product  
contains chemicals known to the state  
of California to cause cancer, birth  
defects or other reproductive harm.  
!
!
WARNING:  
This product contains or emits chemicals  
known to the state of California to cause  
cancer, birth defects or other reproductive harm.  
Study these SAFETY RULES carefully before installing,  
operating or servicing this equipment. Become familiar  
with this Owner’s Manual and with the unit. The gen-  
erator can operate safely, efficiently and reliably only if  
it is properly installed, operated and maintained. Many  
accidents are caused by failing to follow simple and fun-  
damental rules or precautions.  
The manufacturer cannot anticipate every possible cir-  
cumstance that might involve a hazard. The warnings in  
this manual, and on tags and decals affixed to the unit  
are, therefore, not all-inclusive. If using a procedure,  
work method or operating technique that the manufac-  
turer does not specifically recommend, ensure that it is  
safe for others. Also make sure the procedure, work  
method or operating technique chosen does not render  
the generator unsafe.  
• The engine exhaust fumes contain carbon monoxide gas,  
which can be DEADLY. This dangerous gas, if breathed in  
sufficient concentrations, can cause unconsciousness or  
even death. For that reason, adequate ventilation must be  
provided.  
• Keep hands, feet, clothing, etc., away from drive belts, fans,  
and other moving or hot parts. Never remove any drive belt  
or fan guard while the unit is operating.  
• Adequate, unobstructed flow of cooling and ventilating air  
is critical to prevent buildup of explosive gases and to  
ensure correct generator operation. Do not alter the instal-  
lation or permit even partial blockage of ventilation provi-  
sions, as this can seriously affect safe operation of the gen-  
erator.  
• Keep the area around the generator clean and uncluttered.  
Remove any materials that could become hazardous.  
• When working on this equipment, remain alert at all times.  
Never work on the equipment when physically or mentally  
fatigued.  
• Inspect the generator regularly, and promptly repair or  
replace all worn, damaged or defective parts using only fac-  
tory-approved parts.  
DANGER  
Despite the safe design of this generator,  
operating this equipment imprudently, neglecting  
!
its maintenance or being careless can cause  
possible injury or death. Permit only responsible  
and capable persons to install, operate or main-  
tain this equipment.  
Potentially lethal voltages are generated by these  
machines. Ensure all steps are taken to render the  
machine safe before attempting to work on the  
generator.  
• Before performing any maintenance on the generator, dis-  
connect its battery cables to prevent accidental start-up.  
Disconnect the cable from the battery post indicated by a  
NEGATIVE, NEG or (–) first. Reconnect that cable last.  
Parts of the generator are rotating and/or hot  
during operation. Exercise care near running gen-  
erators.  
!
• Never use the generator or any of its parts as a step.  
Stepping on the unit can stress and break parts, and may  
result in dangerous operating conditions from leaking  
exhaust gases, fuel leakage, oil leakage, etc.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Instructions  
Liquid-cooled 15, 20 and 25 kW Generators  
ELECTRICAL HAZARDS  
FIRE HAZARDS  
• All generators covered by this manual produce dangerous  
electrical voltages and can cause fatal electrical shock.  
Utility power delivers extremely high and dangerous volt-  
ages to the transfer switch as well as the standby generator.  
Avoid contact with bare wires, terminals, connections, etc.,  
on the generator as well as the transfer switch, if applicable.  
Ensure all appropriate covers, guards and barriers are in  
place before operating the generator. If work must be done  
around an operating unit, stand on an insulated, dry surface  
to reduce shock hazard.  
• Do not handle any kind of electrical device while standing  
in water, while barefoot, or while hands or feet are wet.  
DANGEROUS ELECTRICAL SHOCK MAY RESULT.  
• If personnel must stand on metal or concrete while  
installing, operating, servicing, adjusting or repairing this  
equipment, place insulative mats over a dry wooden plat-  
form. Work on the equipment only while standing on such  
insulative mats.  
• The National Electrical Code (NEC), Article 250 requires  
the frame and external electrically conductive parts of the  
generator to be connected to an approved earth ground  
and/or grounding rods. This grounding will help prevent  
dangerous electrical shock that might be caused by a  
ground fault condition in the generator set or by static elec-  
tricity. Never disconnect the ground wire.  
• Wire gauge sizes of electrical wiring, cables and cord sets  
must be adequate to handle the maximum electrical current  
(ampacity) to which they will be subjected.  
• Keep a fire extinguisher near the generator at all times. Do  
NOT use any carbon tetra-chloride type extinguisher. Its  
fumes are toxic, and the liquid can deteriorate wiring insu-  
lation. Keep the extinguisher properly charged and be  
familiar with its use. If there are any questions pertaining  
to fire extinguishers, consult the local fire department.  
EXPLOSION HAZARDS  
• Do not smoke around the generator. Wipe up any fuel or oil  
spills immediately. Ensure that no combustible materials  
are left in the generator compartment, or on or near the  
generator, as FIRE or EXPLOSION may result. Keep the  
area surrounding the generator clean and free from debris.  
• These generator sets may operate using one of several types  
of fuels. All fuel types are potentially FLAMMABLE and/or  
EXPLOSIVE and should be handled with care. Comply with  
all laws regulating the storage and handling of fuels. Inspect  
the unit’s fuel system frequently and correct any leaks  
immediately. Fuel supply lines must be properly installed,  
purged and leak tested according to applicable fuel-gas  
codes before placing this equipment into service.  
• Gaseous fluids such as natural gas and liquid propane (LP)  
gas are extremely EXPLOSIVE. Natural gas is lighter than  
air, and LP gas is heavier than air; install leak detectors  
accordingly.  
• Before installing or servicing this (and related) equipment,  
make sure that all power voltage supplies are positively  
turned off at their source. Failure to do so will result in haz-  
ardous and possibly fatal electrical shock.  
• Connecting this unit to an electrical system normally sup-  
plied by an electric utility shall be by means of a transfer  
switch so as to isolate the generator electric system from  
the electric utility distribution system when the generator is  
operating. Failure to isolate the two electric system power  
sources from each other by such means will result in dam-  
age to the generator and may also result in injury or death  
to utility power workers due to backfeed of electrical ener-  
gy.  
• Generators installed with an automatic transfer switch will  
crank and start automatically when NORMAL (UTILITY)  
source voltage is removed or is below an acceptable preset  
level. To prevent such automatic start-up and possible  
injury to personnel, disable the generator’s automatic start  
circuit (battery cables, etc.) before working on or around  
the unit. Then, place a “Do Not Operate” tag on the genera-  
tor control panel and on the transfer switch.  
• In case of accident caused by electric shock, immediately  
shut down the source of electrical power. If this is not pos-  
sible, attempt to free the victim from the live conductor.  
AVOID DIRECT CONTACT WITH THE VICTIM. Use a  
nonconducting implement, such as a dry rope or board, to  
free the victim from the live conductor. If the victim is  
unconscious, apply first aid and get immediate medical  
help.  
STANDARDS INDEX  
In the absence of pertinent standards, codes, regulations and  
laws, the published information listed below may be used as  
installation guide for this equipment.  
1. NFPA No. 37, STATIONARY COMBUSTION ENGINES  
AND GAS TURBINES, available from the National Fire  
Protection Association, 470 Atlantic Avenue, Boston, MA  
02210.  
2. NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR  
HEALTH CARE FACILITIES, available same as Item 1.  
3. NFPA No. 54, NATIONAL FUEL GAS CODE, available  
same as Item 1.  
4. NFPA No. 58, AMERICAN NATIONAL STANDARD FOR  
STORAGE AND HANDLING OF LIQUEFIED PETROLE-  
UM GAS, available same as Item 1.  
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELEC-  
TRIC CODE, available same as Item 1.  
6. Article X, NATIONAL BUILDING CODE, available from  
the American Insurance Association, 85 John Street, New  
York, N.Y. 10038.  
7. AGRICULTURAL WIRING HANDBOOK, available from the  
Food and Energy Council, 909 University Avenue,  
Columbia, MO 65201.  
8. ASAE EP-3634, INSTALLATION AND MAINTENANCE OF  
FARM STANDBY ELECTRICAL SYSTEMS, available from  
the American Society of Agricultural Engineers, 2950  
Niles Road, St. Joseph, MI 49085.  
• Never wear jewelry when working on this equipment.  
Jewelry can conduct electricity resulting in electric shock, 9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQ-  
or may get caught in moving components causing injury.  
UIDS CODE, available same as Item 1.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 - General Information  
Liquid-cooled 15, 20 and 25 kW Generators  
If a transfer switch is not included, one may be pur-  
chased separately from an Authorized Dealer.  
1.1 GENERATOR  
This equipment is a liquid-cooled, engine-driven gen-  
erator set. The generator is designed to supply elec-  
trical power that operates critical electrical loads  
during utility power failure. The unit has been facto-  
ry-installed in a weather resistant, all metal enclosure  
and is intended for outdoor installation only. Use this  
generator as a source of electrical power for the oper-  
ation of 120 and/or 240VAC, single-phase loads.  
1.3 AUTOMATIC TRANSFER SWITCH  
(ATS MODE)  
When this generator, along with an HS Type automat-  
ic transfer switch has been installed and connected,  
a circuit board in the generator control panel con-  
stantly monitors the utility voltage and controls the  
operation of the transfer switch.  
These models are available. They are rated as follows:  
In ATS Mode utility voltage sensing, weekly exercis-  
ing, and load transferring is under the control of the  
generator.  
Model 005031-0: Provides 25,000 watts (25 kW) of single-  
phase power.  
Model 005028-0: Provides 20,000 watts (20 kW) of single-  
phase power.  
Should the utility voltage drop below a preset value,  
and remain at this low voltage for a preset amount of  
time, the generator cranks and starts. After the gen-  
erator starts, the transfer switch transfers the load  
circuits to the generator so the generator can power  
them. When the utility source voltage has been  
restored, the transfer switch re-transfers the load cir-  
cuits back to the utility source voltage and the gener-  
ator shuts down.  
Model 005030-0: Provides 15,000 watts (15 kW) of single-  
phase power.  
If this generator is used to power electrical load  
!
circuits normally powered by a utility power  
source, it is required by code to install a trans-  
fer switch. The transfer switch must effectively  
isolate the electric system from the utility distri-  
bution system when the generator is operating  
(NEC 701). Failure to isolate an electrical system  
by such means results in damage to the genera-  
tor and may also result in injury or even death  
to utility power workers due to backfeed of  
electrical energy.  
1.4 ENGINEERED TRANSFER SWITCH  
(2-WIRE START GTS MODE)  
When required, the pre-packaged standby generator  
can be installed with an engineered W-type transfer  
switch which controls utility voltage sensing, weekly  
exercising and load transferring.  
UTILITY voltage sensing, weekly exercising and load  
transferring is then under the control of the  
Engineered W-type transfer switch (GTS Mode).  
1.2 TRANSFER SWITCH  
This generator system is intended to be used with a  
matched automatic transfer switch. It may be supplied  
in either a NEMA 1 enclosure or a NEMA 3R enclo-  
sure. The NEMA 1 enclosure is intended for indoor  
use only. The NEMA 3R enclosure is weather proof and  
can be used indoors or outdoors. Follow these rules:  
1.5 GENERATOR AC CONNECTION  
SYSTEMS  
The generator was shipped from the factory with its  
stator AC output leads connected in a single-phase,  
3-wire generator AC connection system (Figure 1.1).  
The stator assembly in this system consists of a pair  
of stationary windings, with two leads brought out of  
each winding. Each single winding can supply 120  
VAC, 60 Hertz. When the two windings are connected  
in series, a 240 VAC, 60 Hertz AC output results.  
Typically the two “hot” leads in the circuit are Wires  
No. 11 and 44. The “Neutral” leads are the junction  
of Wires 22 and 33.  
• Install the transfer switch on a firm, sturdy sup-  
porting structure.  
To prevent switch distortion, level the switch if nec-  
essary. This can be done by placing washers  
between the switch enclosure and the mounting  
surface.  
• Never install the switch where water or any corro-  
sive substance might drip onto the enclosure.  
• Protect the switch at all times against excessive  
moisture, dust, dirt, lint, construction grit and cor-  
rosive vapors.  
Figure 1.2 - Main Circuit Breaker  
Model  
005031-0  
005028-0  
005030-0  
Rating  
25,000 W  
20,000 W  
15,000 W  
Phase  
Actual Current  
C/B Rating*  
% over rating  
120%  
Circuit Breaker  
125A BQ2  
1
1
1
104.2 A  
125 A  
83.3 A  
62.5  
100 A  
70 A  
120%  
112%  
100A BQ2  
70A BQ2  
* Amp Rating of C/B structured under model.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 - General Information  
Liquid-cooled 15, 20 and 25 kW Generators  
Figure 1.1 - Generator AC Connection System  
Figure 1.3 - Engine Protective Devices  
(BLACK)  
0
(WHITE)  
(BLACK)  
NEUTRAL  
1.6 MAIN CIRCUIT BREAKER  
The generator’s main circuit breaker is included with  
the unit as shipped from the factory. The breaker for  
each unit is described in Figure 1.2.  
1.7 GENERATOR FUEL SYSTEM  
This unit has been factory tested and adjusted using  
a natural gas fuel system. If propane (LP) gas is pre-  
ferred, refer to Section 1.13, Reconfiguring the Fuel  
System for LP Vapor.  
Fuel pressure for a natural gas set up should be five  
inches to 14 inches of water column (0.18 to 0.5  
psi) at all load ranges.  
1.8.1 LOW OIL PRESSURE SWITCH  
This switch is normally-closed (N.C.) but is held open  
by engine oil pressure during engine running. Should  
operating oil pressure drop below about 8-10 psi  
(55-68 kPa), the switch contacts close and the engine  
shuts down automatically (Figure 1.4).  
Fuel pressure for an LP vapor set up should be 11  
inches to 14 inches of water column (0.4 to 0.5  
psi) at all load ranges.  
NOTE:  
Figure 1.4 - Low Oil Pressure Switch  
A seperate gas line and regulator may be needed  
to assure proper gas pressure to the generator.  
Improper gas pressure can cause hard starting and  
affect engine durability.  
Gaseous fuels such as natural and LP (propane)  
!
gas are highly explosive. Even the slightest  
spark can ignite such fuels and cause an explo-  
sion. No leakage of fuel is permitted. Natural  
gas, which is lighter than air, tends to collect in  
high areas. LP gas is heavier than air and tends  
to settle in low areas.  
1.8.2 HIGH COOLANT TEMPERATURE  
SWITCH  
Normally open (N.O.) thermostatic switch has sens-  
ing tip which is immersed in captive coolant. Should  
coolant temperature exceed about 230°F (110°C), the  
switch contacts close, which causes the engine to  
shut down automatically (Figure 1.5).  
1.8 ENGINE PROTECTIVE DEVICES  
The engine has several safety switches which cause  
the engine to automatically shut down under the fol-  
lowing conditions: low oil pressure, high coolant tem-  
perature, engine overspeed, low coolant level or over-  
crank (Figure 1.3).  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Liquid-cooled 15, 20 and 25 kW Generators  
Figure 1.5- High Coolant Temperature Switch  
1.8.6 LOW BATTERY  
The engine control board continually monitors the  
battery voltage and turns on the low battery LED if  
the battery voltage falls below 12 VDC for one minute.  
Low battery voltage is a non-latching alarm, which  
will automatically clear if the battery voltage rises  
above 12 VDC. If battery voltage goes below 6 VDC  
during cranking, the low battery voltage alarm is  
latched, cranking is terminated, and the low battery  
LED stays on.  
1.8.7 15A DC FUSE  
This fuse is located inside the control panel. It pro-  
tects the panel wiring and components from damag-  
ing overload. The unit will not start or crank if the  
fuse is blown. Replace the fuse with one of the same  
size, type, and rating.  
1.8.3 LOW COOLANT LEVEL SWITCH  
Should engine coolant level drop below the level of  
the high coolant temperature switch, it is possible for  
the engine to overheat without automatic shutdown.  
To prevent such overheating without automatic shut  
down, the engine has a low coolant level sensor. If the  
engine coolant drops too low, the engine automatical-  
ly shuts down (Figure 1.6).  
1.9 UNPACKING  
1.9.1 UNPACKING PRECAUTIONS  
Handle shipping cartons and crates with care. Use  
care to avoid damage from dropping, bumping, colli-  
sion, etc. Store and unpack cartons with the proper  
side up, as noted on the shipping carton.  
Figure 1.6 - Low Coolant Level Sensor  
1.9.2 INSPECTION  
Upon delivery, carefully inspect the generator for any  
damage that may have occurred during shipment. If  
loss or damage is noted at the time of delivery, have  
the person(s) making delivery note all damage on the  
freight bill or affix their signature under the consign-  
or’s memo of loss or damage.  
1.10 LIFTING THE GENERATOR  
1.8.4 OVERSPEED SHUTDOWN  
Should AC frequency exceed about 72 Hz, circuit  
board action will automatically shutdown the engine.  
When lifting or hoisting equipment is used, be  
!
careful not to touch overhead power lines. The  
generators weight of more than 900 pounds  
requires proper tools, equipment, and qualified  
personnel to be used in all phases of handling  
and unpacking.  
1.8.5 OVERCRANK SHUTDOWN  
The engine control board uses a cyclic cranking  
process when attempting to start the engine. The first  
crank cycle is a 15-second crank followed by a seven-  
second rest. This is followed by five more crank  
cycles each with a seven second crank followed by a  
seven-second rest.  
If the engine fails to start after all six attempts, the start  
attempt is stopped and the overcrank LED turns on.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Liquid-cooled 15, 20 and 25 kW Generators  
1.11 SPECIFICATIONS  
1.12 FUEL CONSUMPTION  
15 kW Models  
Using Natural Gas ........................................236 cu. ft. per hour  
Using LP Gas ..................................................92 cu. ft. per hour  
20 kW Models  
1.11.1 ENGINE  
Make ......................................................................................Ford  
Displacement ............................................153 inches3 (2.5 liters)  
Cylinder Arrangement......................................................4, in-line  
Valve Arrangement................................................Overhead Cam  
Firing Order........................................................................1-3-4-2  
Number of Main Bearings............................................................5  
Compression Ratio..........................................................9.37 to 1  
No. of Teeth on Crank ............................................................36-1  
Ignition Timing (Waste Spark System)  
Using Natural Gas ........................................307 cu. ft. per hour  
Using LP Gas ................................................122 cu. ft. per hour  
25 kW Models  
Using Natural Gas ........................................441 cu. ft. per hour  
Using LP Gas ................................................175 cu. ft. per hour  
NOTE:  
Fuel consumption is given at rated maximum con-  
tinuous power output when using natural gas  
rated at 1000 Btu per cubic foot; or LP gas rated  
2520 Btu per cubic foot. Actual fuel consumption  
obtained may vary depending on such variables as  
applied load, ambient temperature, engine condi-  
tions and other environmental factors.  
at 1800 rpm (NG) ..........................................36 degrees BTDC  
at 1800 rpm (LP vapor)................................28` degrees BTDC  
Spark Plug Gap ............................................................0.044 inch  
Recommended Spark Plugs  
Motorcraft ................................................................AWSF-52-C  
Oil Pressure....................................................................30-50 psi  
Crankcase Oil Capacity......................4.5 U.S. quarts (4.26 liters)  
Recommended Engine Oil........................................SAE 15W-40  
Type of Cooling System ..................Pressurized, closed recovery  
Cooling Fan ..............................................................Pusher Type  
Cooling System Capacity ......................2 U.S. gallons (7.6 liters)  
Fuel pressure for a natural gas set up should be five  
inches to 14 inches of water column (0.18 to 0.5  
psi) at all load ranges.  
Fuel pressure for an LP vapor set up should be 11  
inches to 14 inches of water column (0.4 to 0.5  
psi) at all load ranges.  
Recommended Coolant ............Use a 50-50 mixture of ethylene  
glycol base and deionized water.  
1.13 RECONFIGURING THE FUEL  
SYSTEM FOR LP VAPOR  
NOTE:  
Home standby control board assembly part  
number 0E9704 must be used on 1800 rpm gen-  
!
All models are configured for natural gas (NG)  
from the factory.  
erators.  
To reconfigure the fuel system from NG to LP vapor,  
follow these steps:  
1. Turn the main gas supply off.  
1.11.2 GENERATOR  
Single-phase  
Single-phase  
Single-phase  
Model  
005031-0  
25  
005028-0  
20  
005030-0  
15  
Rated Max. Cont.  
AC Power Output (kW)*  
Rated Voltage (volts)  
No. of Rotor Poles  
Driven Speed of Rotor (rpm)  
Rotor Excitation System  
Type of Stator  
120/240  
4
1800  
120/240  
4
1800  
120/240  
4
1800  
Direct excited brush type  
Direct excited brush type  
Direct excited brush type  
4 Wire  
4 Wire  
4 Wire  
Rotor Insulation  
Stator Insulation  
Class F  
Class H  
Class F  
Class H  
Class F  
Class H  
* Rated power of generator is subject to and limited by such factors as ambient temperature, altitude, engine condition, and other fac-  
tors. Engine power will decrease about 3.5% for each 1000 feet above sea level and will decrease an additional 1% for each 10°F  
above 60°F. Maximum output power of the generator is limited by maximum engine power.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Liquid-cooled 15, 20 and 25 kW Generators  
2. Remove the carburetor fuel hose from the outlet  
port (Port 1) of the demand regulator (Figure  
1.8).  
NOTE:  
Synthetic oil is highly recommended when the  
generator will be operating in ambient tempera-  
tures which regularly exceed 90° F and/or fall  
below 30° F.  
3. Remove the brass hose fitting from the outlet port  
(Port 1) of the demand regulator.  
4. Remove pipe plug from Port 2.  
5. Install brass hose fitting into Port 2.  
6. Install pipe plug into Port 1.  
7. Connect carburetor gas hose to brass fitting.  
8. Tighten all clamps and plugs.  
9. Make sure fuel supply is of the proper pressure  
and type for configuration (not to exceed 14 inch-  
es water column).  
10. Move DIP switch position 4 on the control board  
to the off position (LP vapor, see Figure 3.2 and  
Section 3.7).  
Any attempt to crank or start the engine before  
it has been properly serviced with the recom-  
mended oil may result in an engine failure.  
!
1.15 COOLANT RECOMMENDATIONS  
Use a mixture of half low silicate ethylene glycol base  
anti-freeze and half deionized water. Cooling system  
capacity is about 8 U.S. quarts (7.6 liters). Use only  
deionized water and only low silicate anti-freeze. If  
desired, add a high quality rust inhibitor to the rec-  
ommended coolant mixture. When adding coolant,  
always add the recommended 50-50 mixture.  
11. Reverse the procedure to convert back to natural  
gas.  
Figure 1.8 — Reconfigure the Fuel System  
Port 1  
Port 2  
FUEL HOSE  
FUEL HOSE  
BRASS HOSE  
FITTING  
BRASS HOSE  
FITTING  
Do not use any chromate base rust inhibitor  
with ethylene glycol base anti-freeze or chromi-  
PLUG  
PLUG  
!
OUT  
PORT 1  
OUT  
PORT 2  
umhydroxide (“green slime”) forms and will  
cause overheating. Engines that have been  
operated with a chromate base rust inhibitor  
must be chemically cleaned before adding eth-  
ylene glycol base anti-freeze. Using any high  
silicate anti-freeze boosters or additives will  
also cause overheating. DO NOT use any solu-  
ble oil inhibitor for this equipment.  
FUEL INLET  
NG FUEL SYSTEM  
LP FUEL SYSTEM  
NOTE:  
1.16 BEFORE INSTALLATION  
Before installing this equipment, check the ratings of  
both the generator and the transfer switch. Read  
“Emergency Isolation Method” and “Total Circuit  
Isolation Method” in the installation manual (Part No.  
079699).  
Port 1 is for NG only and Port 2 is for LP vapor  
only. No provision for dual fuel has been made.  
DANGER  
Serious injury or damage may occur if not con-  
figured properly. Please consult an Authorized  
Service Dealer with any questions.  
The generator’s rated wattage/amperage capacity  
must be adequate to handle all electrical loads that  
the unit will power. It may be necessary to group the  
critical (essential) loads together and wire them into  
a separate “emergency” distribution panel.  
!
1.14 ENGINE OIL RECOMMENDATIONS  
The unit has been filled with 15W-40 engine oil at the  
factory. Use a high-quality detergent oil classified “For  
Service CC, SD, SE, SF.” Detergent oils keep the  
engine cleaner and reduce carbon deposits. Use oil  
having the following SAE viscosity rating, based on  
the ambient temperature range anticipated before the  
next oil change:  
This generator can be installed in conjunction with  
an engineered transfer switch, if necessary (see  
Section 2.10).  
The standard prepackaged transfer switch (ATS  
mode) does not have sensing or controlling circuit  
boards. Instead, the generator control console hous-  
es a “Printed Circuit Board Assembly”, which con-  
trols all phases of operation, including engine start  
up and load transfer.  
Temperature  
Above 80° F (27° C)  
32° to 80° F (-1° to 27° C)  
Below 32° F (0° C)  
Oil Grade (Recommended)  
SAE 30W or 15W-40  
SAE 20W-20 or 15W-40  
SAE 10W or 15W-40  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Liquid-cooled 15, 20 and 25 kW Generators  
2.1.2 OTHER PUBLISHED STANDARDS  
In addition to NFPA standards, the following infor-  
mation pertaining to the installation and use of  
standby electric systems is available:  
2.1 STANDBY GENERATOR  
INSTALLATION  
DANGER  
• Article X, NATIONAL BUILDING CODE, available  
from the American Insurance Association, 85 John  
Street, New York, N.Y. 10038.  
• AGRICULTURAL WIRING HANDBOOK, obtainable  
from the Food and Energy Council, 909 University  
Avenue, Columbia, MO, 65201.  
• ASAE EP-364.2, INSTALLATION AND MAINTE-  
NANCE OF FARM STANDBY ELECTRIC POWER,  
available from the American Society of Agricultural  
Engineers, 2950 Niles Road, St. Joseph, MI 49085.  
• A52.1, AMERICAN NATIONAL STANDARD FOR  
CHIMNEYS, FIREPLACES AND VENTING SYS-  
TEMS, available from the American National  
Standard Institute, 1430 Broadway, New York, N.Y.  
10018.  
Connecting this generator to an electrical sys-  
tem normally supplied by an electric utility  
shall be by means of a transfer switch, so as to  
isolate the electric system from the utility distri-  
bution system when the generator is operating.  
Failure to isolate the electric system by these  
means will result in damage to the generator  
and may also result in injury or death to utility  
workers due to backfeed of electrical energy.  
If an open bottom is used, the engine-genera-  
tor must be installed over non-combustible  
materials and should be located such that com-  
bustible materials are not capable of accumu-  
lating under the generator set.  
Only qualified, competent installation contractors or  
electricians thoroughly familiar with applicable  
codes, standards and regulations should install this  
standby electric power system. The installation must  
comply strictly with all codes, standards and regula-  
tions pertaining to the installation.  
2.2 GENERATOR LOCATION  
Install the generator set, in its protective enclosure  
outdoors, where adequate cooling and ventilating air  
always is available. Consider these factors:  
• Install the unit where air inlet and outlet openings  
will not become obstructed by leaves, grass, snow,  
etc. If prevailing winds will cause blowing or drift-  
ing, consider using a windbreak to protect the unit.  
• Install the generator on high ground where water  
levels will not rise and endanger it.  
• Allow sufficient room on all sides of the generator  
for maintenance and servicing. A required mini-  
mum allowance of space to any solid structure is  
three feet. Five feet allowance of space is recom-  
mended.  
• Where strong prevailing winds blow from one  
direction, face the generator air inlet openings into  
the prevailing winds.  
• Install the generator as close as possible to the  
transfer switch. This reduces the length of wiring  
and conduit.  
After the system has been installed, do nothing  
that might render the installation in noncompli-  
ance with such codes, standards and regula-  
tions.  
!
NOTE:  
For more information about the installation of a  
standby system contact an Authorized Service  
Dealer.  
2.1.1 NFPA STANDARDS  
The following published standards booklets pertain-  
ing to standby electric systems are available form the  
National Fire Protection Association (NFPA),  
Batterymarch Park, Quincy, MA 02269:  
• Install the generator as close as possible to the fuel  
supply, to reduce the length of piping. HOWEVER,  
REMEMBER THAT LAWS OR CODES MAY REG-  
ULATE THE DISTANCE.  
• NFPA No. 37, STATIONARY COMBUSTION  
ENGINES AND GAS TURBINES.  
• NFPA No. 76A, ESSENTIAL ELECTRICAL SYS-  
TEMS FOR HEALTH CARE FACILITIES.  
• NFPA No. 220, STANDARD TYPES OF BUILDING  
CONSTRUCTION  
• NFPA No. 68, GUIDE FOR EXPLOSION VENTING  
• NFPA No. 70, NATIONAL ELECTRICAL CODE.  
• NFPA No. 30, FLAMMABLE AND COMBUSTIBLE  
LIQUIDS CODE.  
2.3 GENERATOR MOUNTING AND  
SUPPORT  
Retain the generator compartment to a concrete slab  
with 1/4-inch masonry type anchor bolts. Be sure the  
bolts are long enough to retain the compartment. The  
slab should be at least six inches thick and should  
extend beyond the enclosure to a distance of at least  
three inches on all sides.  
• NFPA No. 10, INSTALLATION, MAINTENANCE AND  
USE OF PORTABLE FIRE EXTINGUISHERS.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Liquid-cooled 15, 20 and 25 kW Generators  
• It must have an ampere rating equal to the total  
amperage rating of the emergency distribution  
panel circuit.  
• It must be installed between the building’s main  
distribution panel and the emergency distribution  
panel.  
2.4 BASIC STANDBY ELECTRIC  
SYSTEM  
Figure 2.1 shows a schematic diagram of a basic  
standby electric system. Both the UTILITY power  
supply and the STANDBY GENERATOR output are  
connected to an approved transfer switch. The trans-  
fer switch is required by electrical code and serves  
the following functions:  
2.6 TOTAL CIRCUIT ISOLATION  
METHOD  
• Permits the LOAD circuits to be connected to only  
one power supply at a time.  
When a generator capable of powering all electrical  
loads in the circuit is to be installed, the “Total  
Circuit Isolation Method” may be used. The following  
apply to the transfer switch in this type of system.  
• Prevents electrical backfeed between the generator  
and the UTILITY power circuits.  
Notice that both the STANDBY and the UTILITY  
power supplies to the transfer switch are protected  
against overload by a main line circuit breaker.  
• Ampere rating of the transfer switch must equal  
the ampere rating of the normal incoming utility  
service.  
• The transfer switch is installed between the utility  
service entrance and the building distribution  
panel.  
Figure 2.1 – Basic Standby Electric System  
2.7 GROUNDING THE GENERATOR  
A GROUNDING LUG (Figure 2.2) is provided on the  
generator mounting base for the purpose of ground-  
ing the frame and the external electrically conductive  
parts of the equipment to an approved earth ground  
and/or grounding rods where required by the  
National Electrical Code. Consult a qualified electri-  
cian for grounding requirements in the area.  
Grounding procedures must meet local regulations.  
DANGER  
Do not connect the ground wire to any pipe  
that carries a flammable or explosive substance  
– FIRE or an EXPLOSION may result.  
NOTE:  
Proper grounding helps protect personnel against  
electrical shock in the event of a ground fault condi-  
tion in the generator or in connected electrical  
devices. In addition, grounding helps dissipate static  
electricity that often builds up in ungrounded  
devices.  
The manufacturer recommends the use of a  
Generac Power Systems transfer switch in con-  
junction with this generator.  
2.5 EMERGENCY CIRCUIT ISOLATION  
METHOD  
Figure 2.2 – Generator Grounding Lug (typical)  
This prevents overloading the generator by keeping  
electrical loads below the wattage/amperage capacity  
of the generator. If the generator is powering only crit-  
ical loads, within its wattage/amperage capacity, dur-  
ing utility power outages, consider using the emer-  
gency circuit isolation method.  
Critical electrical loads are grouped together and  
wired into a separate “Emergency Distribution  
Panel.” The generator only supplies electrical circuits  
connected to the emergency distribution panel during  
utility power outages. Load circuits powered by that  
panel must be within the wattage/amperage capacity  
of the generator set. The transfer switch must meet  
the following requirements:  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Liquid-cooled 15, 20 and 25 kW Generators  
The HS Type transfer switch is controlled by the gen-  
erator circuit board via control wires 23 and 194.  
Wire 23 connects the relay driver output (collector of  
an NPN transistor) on the generator circuit board to  
the "low side" (Terminal 23) of the transfer relay coil  
in the transfer switch. Wire 194 connects positive  
battery voltage from the generator circuit board to the  
"high side" (Terminal 194) of the transfer relay coil in  
the transfer switch.  
2.8 GENERATOR AC NEUTRAL  
CONNECTIONS  
The manufacturer uses an UNGROUNDED AC neu-  
tral. Grounding is recommended only at the main  
service entrance. If the neutral wire is grounded and  
one of the phase loads becomes grounded, the exces-  
sive current opens the load circuit breaker or col-  
lapses the generator field. The actual result depends  
on the electrical characteristics of the particular  
installed generator.  
If generator wires 23 and 194 are not wired to  
2.9 AUTOMATIC TRANSFER SWITCH  
!
the correct terminals in the transfer switch, the  
circuit board in the generator control panel will  
be damaged.  
(ATS MODE)  
When this generator, along with an HS Type automat-  
ic transfer switch has been installed and connected,  
a circuit board in the generator control panel con-  
stantly monitors the utility voltage and controls the  
operation of the transfer switch.  
In order for the generator utility voltage sensing and  
battery charging functions to work, it is necessary to  
provide a 5 amp fused 240Vac utility source connec-  
tion from the transfer switch main N1 and N2 termi-  
nals to the generator control panel N1 and N2 termi-  
nals (See Figure 2.3).  
To implement this mode of operation, Position 2 of  
the eight-position DIP switch, which is located on the  
generator circuit board (see Figure 3.2), must be in  
the OFF position. In ATS Mode utility voltage sensing,  
weekly exercising, and load transferring is under the  
control of the generator.  
Transfer Switch terminals N1 and N2 (also called  
Utility 1 and Utility 2) are the input utility AC power  
connections to the Transfer Switch. Transfer Switch  
terminals T1 and T2 (also called Load 1 and Load 2)  
are the transfer switch AC output power terminals  
that go to the load circuit distribution panel. Transfer  
Switch terminals E1 and E2 are the AC power termi-  
nals that come from the generator's main alternator.  
Should the utility voltage drop below a preset value,  
and remain at this low voltage for a preset amount of  
time, the generator cranks and starts. After the gen-  
erator starts, the transfer switch transfers the load  
circuits to the generator so the generator can power  
them. When the utility source voltage has been  
restored, the transfer switch re-transfers the load cir-  
cuits back to the utility source voltage and the gener-  
ator shuts down.  
Figure 2.3 - Connection Diagram (ATS Mode)  
FROM UTILITY  
TO LOAD  
FEEDER CIRCUITS  
MAIN LINE  
CIRCUIT  
BREAKER  
OR FUSE  
LOAD  
DISTRIBUTION  
PANEL  
N1 N2  
FUSE  
FUSE  
N1  
N2  
T1  
T2  
GENERATOR  
194  
23  
194  
23  
HS TYPE  
TRANSFER  
SWITCH  
178  
183  
N2 N1  
E1 E2  
E1 E2  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Liquid-cooled 15, 20 and 25 kW Generators  
Start terminals. Recommended wire gauge sizes for  
the 2-Wire Start wiring depend on the length of the  
wire (see wiring length chart).  
2.10 ENGINEERED TRANSFER SWITCH  
(2-WIRE START GTS MODE)  
When required, the pre-packaged standby generator  
can be installed with an engineered W Type transfer  
switch which controls utility voltage sensing, weekly  
exercising and load transferring.  
MAXIMUM WIRE LENGTH RECOMMENDED WIRE  
SIZE  
460 feet (140m)  
No. 18 AWG.  
No. 16 AWG.  
No. 14 AWG.  
No. 12 AWG.  
461 to 730 feet (223m)  
731 to 1,160 feet (354m)  
1,161 to 1,850 feet (565m)  
When Position 2 of the eight-position DIP switch,  
which is located on the generator circuit board (See  
Figure 3.2), is in the ON position then utility voltage  
sensing, weekly exercising and load transferring is  
under the control of the Engineered W Type transfer  
switch (GTS Mode).  
Route the 2-Wire Start control wires through suitable,  
approved conduit which is separate from the AC  
power leads. Connection of wire 178 to wire 183 by  
relay contact closure action (volt free switch contacts)  
in the transfer switch must result in generator engine  
cranking and startup (See Figure 2.4).  
Generator DIP Switch Position 2 ON = 2-Wire Start  
GTS Mode  
• The generator control board will NOT monitor the  
utility.  
• The generator control board will NOT perform a  
weekly exercise. (The five red LEDs will flash one  
at a time in GTS mode.)  
Do NOT connect battery voltage, utility voltage  
!
(N1/N2) or load voltage (T1/T2) to either the  
178 or the 183 2-Wire start terminals as this will  
damage the generator control board.  
• The generator control board will NOT activate the  
transfer output.  
The generator control board WILL monitor all engine  
conditions and shut down on all the faults listed in  
this document.  
In order for the generator battery charging function to  
work, it is necessary to provide a 5 amp fused 240Vac  
utility source connection from the transfer switch  
main N1 and N2 terminals to the generator control  
panel N1 and N2 terminals (See Figure 2.4).  
For the W Type transfer switch to control utility volt-  
age sensing, weekly exercising and load transferring,  
suitable wiring must also be connected from the  
transfer switch 178 and 183, 2-Wire Start terminals  
to the corresponding generator 178 and 183 2-Wire  
Figure 2.4 - Connection Diagram (GTS Mode)  
FROM UTILITY  
TO LOAD  
FEEDER CIRCUITS  
MAIN LINE  
CIRCUIT  
BREAKER  
OR FUSE  
LOAD  
DISTRIBUTION  
PANEL  
N1 N2  
FUSE  
FUSE  
N1  
N2  
T1  
T2  
GENERATOR  
W-TYPE  
TRANSFER  
SWITCH  
194  
23  
178  
183  
178  
183  
N2 N1  
E1 E2  
E1 E2  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Liquid-cooled 15, 20 and 25 kW Generators  
Transfer Switch terminals N1 and N2 (also called  
Utility 1 and Utility 2) are the input utility AC power  
connections to the Transfer Switch. Transfer Switch  
terminals T1 and T2 (also called Load 1 and Load 2)  
are the transfer switch AC output power terminals  
that go to the load circuit distribution panel. Transfer  
Switch terminals E1 and E2 are the AC power termi-  
nals that come from the generator's main alternator.  
Battery electrolyte fluid is an extremely corro-  
!
sive sulfuric acid solution that can cause severe  
burns. Do not permit fluid to contact eyes, skin,  
clothing, painted surfaces, etc. Wear protective  
goggles, protective clothing and gloves when  
handling a battery. If fluid is spilled, flush the  
affected area immediately with clear water.  
When in GTS mode, the control board will respond  
as follows based on the generator AUTO/OFF/MANU-  
AL switch position.  
Do not dispose of the battery in a fire. The bat-  
tery is capable of exploding.  
OFF — The generator will not start and run in this  
Do not open or mutilate the battery. Released  
electrolyte can be toxic and harmful to the skin  
and eyes.  
position  
!
MANUAL — The generator control board will start  
and run the generator whenever the switch is in the  
manual position.  
The battery represents a risk of high short cir-  
cuit current. When working on the battery,  
always remove watches, rings or other metal  
objects, and only use tools that have insulated  
handles.  
AUTO — The generator control board will monitor  
the 2-Wire start circuit (terminals 178 and 183 in the  
generator control panel). When a 2-Wire start signal  
is issued by the W type engineered transfer switch,  
via a relay contact closure that connects wire 178 to  
wire 183, the generator control board will immedi-  
ately start and run the generator. When the 2-Wire  
start signal is removed the control board will imme-  
diately stop the generator.  
2.11.1 VENTED BATTERIES  
The electrolyte is a dilute sulfuric acid that is  
harmful to the skin and eyes. It is electrically  
conductive and corrosive. The following proce-  
dures are to be observed:  
!
2.11 BATTERY INSTALLATION  
DANGER  
• Wear full eye protection and protective clothing,  
• Where electrolyte contacts the skin, wash it off  
immediately with water,  
• Where electrolyte contacts the eyes, flush thor-  
oughly and immediately with water and seek med-  
ical attention, and  
• Spilled electrolyte is to be washed down with an  
acid-neutralizing agent. A common practice is to  
use a solution of one pound (500 grams) bicarbon-  
ate of soda to one gallon (4 liters) of water. The  
bicarbonate of soda solution is to be added until  
the evidence of reaction (foaming) has ceased. The  
resulting liquid is to be flushed with water and the  
area dried.  
Standby generators installed with automatic  
transfer switches will crank and start automati-  
!
cally when NORMAL (UTILITY) source voltage is  
removed or is below an acceptable preset level.  
To prevent such automatic start-up and possible  
injury to personnel, do not connect battery  
cables until certain that normal source voltage at  
the transfer switch is correct; the generator main  
line circuit breaker is switched to OFF; the  
AUTO/OFF/MANUAL switch on the control con-  
sole is switched to OFF; the 15A and 5A fuses  
have been removed from the control console;  
utility fed supply to battery charger (terminals  
N1 and N2) is removed; and the system is ready  
to be placed into operation. Ensure that the 5A  
and 15A fuses in the control panel are removed  
when connecting or disconnecting battery cables.  
Lead acid batteries present a risk of fire  
because they generate hydrogen gas. The fol-  
lowing procedure are to be followed:  
• DO NOT SMOKE when near batteries,  
Storage batteries give off explosive hydrogen  
gas. This gas can form an explosive mixture  
around the battery for several hours after  
charging. The slightest spark can ignite the gas  
and cause an explosion. Such an explosion can  
shatter the battery and cause blindness or  
other injury. Any area that houses a storage  
battery must be properly ventilated. Do not  
allow smoking, open flame, sparks or any spark  
producing tools or equipment near the battery.  
• DO NOT cause flame or spark in battery area, and  
• Discharge static electricity from body before touch-  
ing batteries by first touching a grounded metal  
surface.  
Servicing of batteries is to be performed or super-  
vised by personnel knowledgeable of batteries and  
the required precautions. Keep unauthorized person-  
nel away from batteries.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Liquid-cooled 15, 20 and 25 kW Generators  
The recommended battery is Group 26, 12VDC, 550  
2.12.3 FUEL SYSTEM  
CCA/75 AH minimum. All batteries must be at 100  
percent state-of-charge before they are installed on  
the generator.  
Make sure the fuel supply system to the generator (a)  
delivers the correct fuel at the correct pressure and  
volume and, (b) is properly purged and leak tested  
according to code. No fuel leakage is permitted.  
When using maintenance-free batteries, it is not nec-  
essary to check the specific gravity or electrolyte level.  
Have these procedures performed at the intervals  
specified in Section 4, “Maintenance.” A negative  
ground system is used. Battery connections are  
shown on the wiring diagrams. Make sure all batter-  
ies are correctly connected and terminals are tight.  
Observe battery polarity when connecting batteries to  
the generator set.  
2.12.4 GENERATOR SET LUBRICATION  
Check the engine crankcase oil level before operating  
and add oil to the proper level – the dipstick “FULL”  
mark. Never operate the engine with the oil level  
below the dipstick ADD” mark. See “Specifications”  
and “Engine Oil Recommendations”.  
NOTE:  
NOTE:  
Damage will result if the battery connections are  
This engine is shipped from the manufacturer  
with 15W-40 oil. This oil should be changed after  
30 hours of operation.  
made in reverse.  
2.12 PREPARATION BEFORE START-UP  
The instructions in this section assume that the  
standby generator has been properly installed, serv-  
iced, tested, adjusted and otherwise prepared for use  
by a competent, qualified installation contractor. Be  
sure to read the “Safety Rules” on pages 2 and 3, as  
well as all other safety information in this manual,  
before attempting to operate this (and related) equip-  
ment.  
2.12.5 ENGINE COOLANT  
Have the engine cooling system properly filled with  
the recommended coolant mixture. Check the system  
for leaks and other problems. See “Specifications”  
and “Coolant”.  
2.12.6 BELT TENSION  
Check the engine fan belt tension and condition prior  
to placing the unit into service and at recommended  
intervals. Belt tension is correct when a force of  
approximately 22 pounds (10 kg), applied midway  
between pulleys, deflects the belt about 3/8- to 5/8-  
inches (10 to 16 mm).  
2.12.1 PRIOR TO INITIAL START-UP  
Prior to initially starting the generator, it must  
be properly prepared for use. Any attempt to  
crank or start the engine before it has been  
properly serviced with the recommended types  
and quantities of engine fluids (oil, coolant,  
fuel, etc.) may result in an engine failure.  
!
2.12.7 ELECTRICAL SYSTEM  
Make sure the generator is properly connected to an  
approved earth ground and/or ground rod.  
Before starting the generator for the first time, the  
installer must complete the following procedures. For  
follow-up maintenance information and/or service  
intervals, please refer to Section 4, “Maintenance.”  
Make sure the generator battery is fully charged,  
properly installed and interconnected, and ready for  
use.  
Check to ensure that there are no loose electrical con-  
nections. Restrain any loose wires to keep them clear  
of any moving generator set components.  
2.12.2 TRANSFER SWITCH  
If this generator is used to supply power to any elec-  
trical system normally powered by an electric utility,  
the National Electrical Code requires that a transfer  
switch be installed. The transfer switch prevents elec-  
trical backfeed between two different electrical sys-  
tems, (for additional information, see the applicable  
transfer switch manual for this unit). The transfer  
switch, as well as the generator and other standby  
components, must be properly located and mounted  
in strict compliance with applicable codes, standards  
and regulations.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 - Operation  
Liquid-cooled 15, 20 and 25 kW Generators  
See Section 1.7 for further explanation of engine pro-  
tection functions.  
3.1 CONTROL CONSOLE  
COMPONENTS  
The components of a home standby generator control  
console (Figure 3.1) are as follows:  
3.1.3 15 AMP FUSE  
This fuse protects the control console’s DC control  
circuit against electrical overload and is located  
inside the control panel. If the fuse has melted open  
because of an overload, engine cranking and startup  
cannot occur. If the fuse needs to be replaced, use  
only an identical 15-amp replacement fuse (type  
ATO).  
Figure 3.1 - Generator Control Console  
OVER CRANK  
CAUTION  
OVER SPEED  
LOW COOL. LEVEL  
HI COOL. TEMP.  
LOW OIL PRESS.  
RISK OF ELECTRICAL SHOCK. DO NOT REMOVE COVER. NO USER SERVICEABLE  
PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.  
LOW BATTERY  
SYSTEM READY  
LED INDICATORS:  
FLASHING GREEN LED  
CAUTION  
=
NO UTILITY SENSE  
5
FLASHING RED LED'S  
(IN AUTO MODE ONLY)  
SOLID GREEN LED SYSTEM READY, UTILITY POWER ON  
RED LED'S INDIVIDUAL FAULT  
=
EXERCISER NOT SET  
FOR STAND-BY SERVICE CONNECT OUTPUT OF GENERATOR TO SUITABLY RATED  
TRANSFER SWITCH IN ACCORDANCE WITH CANADIAN ELECTRICAL CODE, PART I.  
=
3.1.4 5 AMP FUSE  
=
(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)  
TENTION: POUR L'ALIMENTATION DE RESERVE, CONNECTER LA SORTIE DE  
ATRICE A UN COMMUTATEUR DE CALIBRE APPROPRIE, CONFORMENENT AU  
CANADIEN DE L'ECTRICITE, PREMIERE PARTIE.  
This fuse protects the battery charger against electri-  
cal overload and is located inside the control panel. If  
the fuse needs to be replaced, use only an identical 5-  
amp replacement fuse (type ATO).  
AUTO  
OFF  
OFF  
ON  
WARNING  
CAN AUTOMATICALLY START AT ANYTIME WITHOUT NOTICE.  
Y REMOVE FUSE ON CONTROL PANEL AND NEGATIVE BATTE  
SERVICING.  
SET  
EXERCISE  
TIME  
MANUAL  
WARNING  
TO SET EXERCISER TIME  
1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.  
NOTE:  
THIS EMERGENCY POWER SYSTEM IS DESIGNED EXCLUSIVELY FOR  
OUTDOOR INSTALLATION ONLY!  
2) HOLD "SET EXERCISE TIME" SWITCH IN "ON" POSITION FOR THREE SECONDS  
AND RELEASE. (SEE OWNER'S MANUAL FOR COMPLETE DETAILS)  
THE EXERCISER IS NOW SET. ALL FIVE RED LED'S WILL FLASH FOR 10 SECONDS  
THEN THE UNIT WILL START, RUN THROUGH THE EXERCISE CYCLE AND SHUTDOWN.  
This fuse will not remove the + battery input  
power from the PCB when it opens. This means  
the exercise timer will not be reset.  
USE OF SYNTHETIC OIL IS RECOMMENDED  
0F2629  
0E7193  
3.1.1 AUTO/OFF/MANUAL SWITCH  
Use this three-position switch as follows:  
3.1.5 SET EXERCISE TIME SWITCH  
This switch allows programming the generator to  
start and exercise automatically. See Weekly  
Exercise Cycle” (see Figure 3.3 and Section 3.6).  
• Set the switch to AUTO for fully automatic opera-  
tion. See Automatic Operation” (Section 3.6).  
• Set switch to MANUAL position to crank and start  
the generator engine.  
• Set switch to OFF position to shut down an oper-  
ating engine. With OFF selected, operation will not  
be possible.  
3.1.6 SYSTEM READY LED  
The System Ready LED (green) has two main pur-  
poses. First, the LED will be ON when the  
AUTO/OFF/MANUAL switch is in the AUTO position,  
utility is present, and there are no system alarms.  
This ON state indicates the system is fully ready for  
automatic operation.  
DANGER  
With switch set to AUTO, engine can crank and  
!
start suddenly without warning. Such automat-  
ic start up normally occurs when utility source  
voltage drops below a pre-set level. To prevent  
possible injury that might be caused by such  
sudden starts, set AUTO/OFF/ MANUAL switch  
to OFF before working on or around the unit.  
Then, place a “DO NOT OPERATE” tag on con-  
trol console.  
The system ready LED will be OFF when the switch  
is in the MANUAL or OFF positions.  
The system ready LED is also used to indicate the  
presence of utility sensing at the PCB when the switch  
is either in the AUTO or MANUAL modes. The LED  
will flash at the rate of 1/2 second on, 1/2 second off  
if the utility sensing level is below the transfer back  
threshold.  
3.1.2 FAULT INDICATOR LEDS  
This secondary function is only available with DIP  
switch two in the OFF position (ATS - automatic  
transfer switch application).  
(SEE CHART ON PAGE 16)  
These red LEDs turn ON when one or more of the fol-  
lowing engine faults occurs and the engine shuts  
down.  
3.2 MANUAL TRANSFER AND  
• Low Oil Pressure  
• Overcrank  
• Low Battery  
• Overspeed/Engine Speed Signal Fault  
• High Coolant Temperature/Low Coolant Level  
START-UP  
To transfer electrical loads to the Standby (EMER-  
GENCY) power source side and start the engine man-  
ually, refer to the Owner’s Manual of the particular  
transfer switch.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 - Operation  
Liquid-cooled 15, 20 and 25 kW Generators  
Condition  
System  
Ready (Green)  
Low  
Bat (Red)  
Low  
Oil (Red)  
High  
Temp (Red)  
Over  
Speed (Red)  
Over  
Crank (Red)  
Switch Position  
Manual  
Auto  
Off  
Generator Switch is  
in the OFF Mode.  
OFF  
ON  
OFF  
X
X
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
O
System Ready for  
Automatic Start  
X
X
O
Generator Switch is  
in the MANUAL Mode  
OFF  
OFF  
OFF  
OFF  
O
O
O
Weekly Exerciser  
is not set  
Flashing  
Flashing  
Flashing  
Flashing  
Flashing  
O
O
O
O
(-----------------------------------1 sec rate---------------------------------------)  
Battery Voltage <12.2V  
for >1 minute  
X
ON  
(Non-latching)  
Battery Voltage <6V  
OFF  
OFF  
ON  
X
O
O
O
O
Unit Shutdown due  
to Low Oil Pressure  
ON  
Unit Shutdown due to  
High Coolant Temperature  
or Low Coolant Level  
OFF  
OFF  
OFF  
X
X
X
X
ON  
O
O
O
O
O
O
O
O
Unit Shutdown due  
to Engine Overspeed  
ON  
Unit Failed to Start  
during it’s Crank Cycle  
ON  
Utility Voltage is  
<45% of Nominal  
Flashing  
1 sec rate  
Engine Speed Signal Fault  
OFF  
OFF  
X
X
Flashing  
O
O
O
O
Control Board is  
in GTS Mode  
The five RED LED’s will turn on one at a time  
O
X = indicates that the LED can be ON or OFF depending on the operating conditions.  
Figure 3.2 — Control Board Dip Switch Location  
3.3 ENGINE GOVERNOR GAIN  
ADJUSTMENTS  
Engine speed governing is also controlled by the  
engine control board. The engine governor has been  
set by the factory during final testing of the generator  
and should not be adjusted.  
If, however, adjustments are necessary, the following  
procedure should be followed (Figure 3.2 and Section  
3.7):  
1. Move DIP switch 8 to the TEST mode (OFF posi-  
tion).  
2. Set all three potentiometers (pots) fully counter-  
clockwise.  
3. Under no load condition, increase the GAIN pot  
as much as possible without causing instability.  
4. Apply 1/4, 1/2, 3/4 and full load to the unit.  
Decrease the GAIN pot if there is instability at any  
load point.  
5. Under full load condition, increase the stability  
pot until the unit returns to 60 Hertz (or 50 Hertz  
in 50 Hertz applications).  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 - Operation  
Liquid-cooled 15, 20 and 25 kW Generators  
6. Reduce load to 3/4, 1/2, 1/4 and no load.  
Decrease the stability pot if there is instability at  
any load point.  
7. Adjust differential pot to make the recovery to  
load changes even faster and minimize load  
change undershoot and overshoot. If it is set too  
high, it may introduce oscillations at some load.  
It can be set to zero (full CCW) if a small amount  
causes oscillations at some load.  
1. Place the AUTO/OFF/MANUAL switch in the  
AUTO position (Figure 3.3).  
2. Press and hold the “Set Exercise Time” switch for  
five seconds, then release.  
At this time all five red LEDs will flash for approxi-  
mately 10 seconds, then the engine will start and run  
for it’s 12 minute exercise period, then shut down.  
The generator will now start and run each week at the  
same time.  
8. Leave DIP switch 8 in TEST mode.  
Figure 3.3 - “Set Exercise Time” Switch  
3.4 MANUAL RETRANSFER AND  
RED LED'S = INDIVIDUAL FAULT  
SHUTDOWN  
(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)  
When utility power source voltage has been restored,  
electrical loads may be transferred back to that  
source and the generator can be shut down as fol-  
lows:  
AUTO  
OFF  
OFF  
ON  
Verify that utility power supply voltage to the trans-  
fer switch has been positively turned Off, using  
whatever means provided (such as utility main line  
circuit breaker).  
SET  
EXERCISE  
TIME  
MANUAL  
• Set the generator’s main circuit breaker to its Off  
or Open position.  
TO SET EXERCISER TIME  
• Let the generator engine run at no-load for a few  
minutes, to stabilize internal unit temperatures.  
• On the generator console, set the Auto/Off/ Manual  
switch to Off. Wait for engine to come to a complete  
stop.  
1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.  
2) HOLD "SET EXERCISE TIME" SWITCH IN "ON" POSITION FOR THREE SECONDS  
AND RELEASE. (SEE OWNER'S MANUAL FOR COMPLETE DETAILS)  
THE EXERCISER IS NOW SET. ALL FIVE RED LED'S WILL FLASH FOR 10 SECONDS  
THEN THE UNIT WILL START, RUN THROUGH THE EXERCISE CYCLE AND SHUTDOWN.  
0
For transfer to utility position, refer to the Owner’s  
Manual of the particular transfer switch.  
Turn on the utility power supply to the transfer  
switch, using whatever means provided (such as a  
utility main line circuit breaker). The utility power  
source now powers the loads.  
If DC power to the control board is lost, the weekly  
exercise setting will be lost. This is indicated by all  
five red LEDs continually flashing. In this state the  
generator will still start and run in MANUAL mode,  
or automatically start and run if utility is lost while in  
AUTO mode, but it will not perform a weekly exercise  
cycle.  
3.5 AUTOMATIC OPERATION  
To set the system for fully automatic operation, pro-  
ceed as follows:  
If a failure occurs while running in this mode, the five  
red LEDs will stop flashing, the individual fault LED  
will turn on and the engine will shut down. Once the  
AUTO/OFF/MANUAL switch has been switched to  
OFF, the individual fault LED will turn OFF and the  
five red LEDs will begin flashing to show exercise has  
still not been set.  
• Check that load circuits are connected to the  
utility power supply.  
• Set the AUTO/OFF/MANUAL switch to its AUTO  
position.  
• Set the generator main circuit breaker to its ON or  
CLOSED position.  
3.6 WEEKLY EXERCISE CYCLE  
The engine control board will start and run the gen-  
erator once every seven days for approximately 12  
minutes. If utility should fail during this exercise  
period, the engine control board will transfer the load  
to the generator output and continue to run until util-  
ity returns.  
On the day, and at the time of day chosen for the gen-  
erator to exercise, set the weekly exercise cycle as fol-  
lows:  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 - Operation  
Liquid-cooled 15, 20 and 25 kW Generators  
3.7 CONTROL BOARD DIP SWITCH  
3.8 VOLTAGE REGULATOR  
SETTINGS  
ADJUSTMENT  
Located on the control board is an eight position DIP  
switch (see Figure 3.2). The eight different switches,  
are used to configure the control board for the spe-  
cific engine and governor being used and are pre-set  
at the factory.  
Four adjustment potentiometers are provided on the  
voltage regulator installed in the control panel (Figure  
3.4). These are (a) voltage adjust, (b) gain, (c) stabili-  
ty and (d) underfrequency adjust. The voltage regula-  
tor potentiometers have been factory set and  
SHOULD NOT be adjusted. If however, adjustments  
are necessary, contact the local Dealer to implement  
the following procedure.  
If the DIP switch settings are not set correctly,  
the generator may not start or operate correct-  
!
ly.  
High voltage is present inside the control panel  
during this procedure.  
1. Disconnect all electrical loads from the generator  
(initial adjustments are done under no-load con-  
ditions).  
240 VAC can be present within the control  
panel.  
If it is necessary to select an alternate switch position,  
move the AUTO/OFF/MANUAL switch to the OFF  
position. Remove the 15 amp fuse in the generator  
control panel. Move the DIP switch position that  
needs to be changed to its new position. Wait five sec-  
onds, then re-install the 15 amp fuse.  
Figure 3.4 — Voltage Regulator  
The ON position is marked on the switch and is  
shown in Figure 3.2.  
Switch Position 1 — Selects the generator alternator  
output frequency and is factory pre-set for 60 Hz.  
Switch Position 2 — Selects the type of transfer  
switch and is factory pre-set for an automatic trans-  
fer switch (ATS).  
Switch Position 3 — Selects the type of governor  
control used, and is factory pre-set for stepper motor  
operation.  
Switch Position 4 — Selects the type of fuel being  
used and is factory pre-set for natural gas (NG).  
Switch Position 5 — Selects the engine displacement  
and is factory pre-set for a 2.5 liter (2.5L) engine.  
2. Connect an accurate AC voltmeter and AC fre-  
quency meter to the generator’s AC output leads.  
3. On the voltage regulator, set the potentiometers  
as follows:  
Switch Position 6 — Selects the number of engine  
cylinders and is factory pre-set for four cylinders.  
Switch Position 7 — Selects the direction of rotation  
of the governor stepper motor and is factory pre-set  
for CCW rotation (rotation is observed looking at the  
stepper shaft as it moves from closed throttle to open  
throttle).  
A. Turn the Voltage Adjust pot fully counterclock-  
wise (CCW).  
B. Set the GAIN pot to its centered (mid) position.  
C. Set the STABILITY pot to its centered (mid)  
position.  
Switch Position 8 — Selects whether the control is  
in the Normal Mode of operation or Test Mode. In the  
Normal Mode of operation, pre-determined governor  
gains are used and the gain trimpots on the control  
board (Gain, Stability, and Differential) are not active  
and have no effect on the gains. In Test Mode the gain  
trimpots are active and can be adjusted. See Section  
3.3.  
D. DO NOT adjust the UNDERFREQUENCY  
ADJUST pot.  
4. Start the engine. Let it stabilize and warm up at  
no-load.  
5. Verify that the three voltage regulator’s LED’s are  
ON.  
6. Check the reading on the AC frequency meter.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Liquid-cooled 15, 20 and 25 kW Generators  
7. Turn the voltage regulator’s VOLTAGE ADJUST  
pot to obtain a line-to-line voltage of:  
A. 240 VAC if the generator has been configured for  
60 Hertz operation.  
D. FIRST 100 OPERATING HOURS  
1. Change engine oil and oil filter. After initial  
change, service engine oil and filter at 150 oper-  
ating hours or six months, whichever comes first.  
2. Retorque cylinder head (see torque specs).  
3. Retorque intake and exhaust manifold (see  
torque specs).  
B. 200 VAC if the generator has been configured for  
50 Hertz operation.  
8. If the RED REGULATOR LED is flashing, adjust  
the STABILITY pot in either direction until the  
flashing stops.  
E. EVERY 500 OPERATING HOURS  
1. Service air cleaner.  
2. Check starter.  
9. Apply an electrical load and check the engine  
speed recovery.  
A. Adjust the UNDERFEQUENCY ADJUST pot  
CCW to reduce load during engine recovery.  
B. For flat regulation (no voltage decrease as fre-  
quency drops) set the UNDERFREQUENCY  
ADJUST pot fully CW.  
C. To obtain a constant voltage regulation as fre-  
quency decreases, set the UNDERFREQUENCY  
ADJUST pot fully CCW.  
10. With the electrical load still applied, check the  
REGULATOR LED for flashing. If the LED is  
flashing, adjust the STABILITY pot until the flash-  
ing stops.  
11. If better response is needed, adjust the GAIN pot  
clockwise (CW) as needed. Then (if needed) cor-  
rect for stability by adjusting the STABILITY pot.  
12. Turn OFF the electrical loads.  
3. Check engine DC alternator.  
F. EVERY 800 OPERATING HOURS  
1. Retorque cylinder head (see torque specs).  
2. Retorque intake and exhaust manifold (see  
torque specs).  
3. Check engine compression.  
4. Check valve clearance.  
4.2 EXHAUST MANIFOLD PROCEDURE  
1. If necessary, clean gasket surfaces on exhaust  
manifold and cylinder head.  
2. Install exhaust manifold and exhaust manifold  
gasket.  
3. Install fasteners.  
13. Verify that all the voltage regulator’s LED’s are  
NOTE:  
ON.  
Exhaust manifold fasteners must be tightened in  
two stages.  
14. Turn OFF the generator.  
4.1 MAINTENANCE PERFORMED BY  
AUTHORIZED SERVICE FACILITIES  
4. Tighten fasteners to 20-30 N-m (15-22 lb-ft) dur-  
ing the first stage.  
5. Retighten fasteners to 60-80 N-m (44-59 lb-ft)  
during the second stage.  
A. EVERY THREE MONTHS  
1. Check battery condition.  
2. Inspect and test fuel system.  
3. Check transfer switch.  
4. Inspect exhaust system.  
5. Check engine ignition system.  
6. Check fan belts.  
4.3 INTAKE MANIFOLD PROCEDURE  
1. Clean and inspect the mounting surfaces of the  
intake manifold and the cylinder head. Both sur-  
faces must be clean and flat (Figure 4.1).  
2. Clean and lightly oil the manifold bolt/stud  
threads.  
Figure 4.1 — Intake Manifold Installation  
B. ONCE EVERY SIX MONTHS  
1. Test Engine Safety Devices (low oil pressure, low  
coolant level, high coolant temperature).  
C. ONCE ANNUALLY  
1. Test engine governor; adjust or repair, if needed.  
2. Clean, inspect generator.  
3. Flush cooling system.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Liquid-cooled 15, 20 and 25 kW Generators  
3. Install a new lower intake manifold gasket.  
4. Position the lower intake manifold to the cylinder  
head.  
The exhaust system parts from this product get  
extremely hot and remains hot after shutdown.  
High grass, weeds, brush, leaves, etc. must  
remain clear of the exhaust. Such materials may  
ignite and burn from the heat of the exhaust  
system.  
5. Install retaining bolts/studs finger tight.  
6. Tighten all bolts/studs to specifications in the  
tightening sequence shown:  
• First pass = 7=10 N-m (5-7 lb-ft).  
• Final pass = 26-38 N-m (19-28 lb-ft).  
4.6 OVERLOAD PROTECTION FOR  
4.4 CYLINDER HEAD PROCEDURE  
1. Position head gasket on the block (Figure 4.2).  
2. Position cylinder head to cylinder block.  
3. Install 10 cylinder head bolts in numerical  
sequence. Tighten to 70 N-m (52 lb-ft) in  
sequence. Retighten to 70 N-m (52 lb-ft) in  
sequence. Then turn all head bolts an additional  
90 - 100 degrees in sequence.  
ENGINE DC ELECTRICAL SYSTEM  
Engine cranking, start up and running are controlled  
by a solid state Engine Controller circuit board.  
Battery voltage is delivered to that circuit board via a  
15 amp fuse. These overcurrent protection devices  
will open if the circuit is overloaded.  
Figure 4.2 — Cylinder Head Installation  
If a circuit breaker opens or a fuse element  
!
melts, find the cause of the overload before  
resetting the circuit breaker or replacing the  
fuse.  
4.7 CHECKING FLUID LEVELS  
4.7.1 CHECK ENGINE OIL  
Check engine crankcase oil level (Figure 4.3) at least  
every 20 hours of operation, or prior to use.  
• Remove oil dipstick and wipe dry with a clean,  
lint-free cloth.  
• Install oil dipstick, then remove again.  
• Oil should be between FULL and ADD marks.  
• If oil level is below the dipstick ADD mark, remove  
oil fill cap. Add the recommended oil to bring oil  
level up to the FULL mark. DO NOT FILL ABOVE  
THE “FULLMARK. See “Engine Oil Recommen-  
dations” for recommended oils.  
Figure 4.3 - Oil Dipstick and Oil Fill Cap  
Engine  
Air Cleaner  
Oil Fill Cap  
Oil Dipstick  
4.5 COOLING SYSTEM  
Air intake and outlet openings in the generator com-  
partment must be open and unobstructed for contin-  
ued proper operation. This includes such obstruc-  
tions as high grass, weeds, brush, leaves and snow.  
Oil  
Filter  
Without sufficient cooling and ventilating air flow, the  
engine/generator quickly overheats, which causes it  
to shut down. (See the installation diagram.)  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Liquid-cooled 15, 20 and 25 kW Generators  
4.7.2 BATTERY FLUID  
4.8.6 PERFORM VISUAL INSPECTION  
Check battery electrolyte fluid based on the  
Maintenance Schedule. Fluid should cover separa-  
tors in all battery cells. If fluid level is low, add dis-  
tilled water to cover tops of separators. DO NOT USE  
TAP WATER IN BATTERY.  
Complete a thorough visual inspection of the entire  
engine-generator monthly. Look for obvious damage,  
loose, missing or corroded nuts, bolts and other fas-  
teners. Look for fuel, oil or coolant leaks.  
4.8.7 INSPECT EXHAUST SYSTEM  
4.7.3 ENGINE COOLANT  
Check coolant level in coolant recovery bottle. See  
Specifications.  
Inspect the exhaust system at least once every three  
months. Check all exhaust system pipes, mufflers,  
clamps, etc. for condition, tightness, leaks, security,  
damage.  
• Add recommended coolant mixture as necessary.  
• Periodically remove radiator pressure cap (only  
when engine has cooled down) to make sure the  
coolant recovery system is functioning properly.  
Coolant should be at bottom of radiator filler neck.  
If coolant level is low, inspect gasket in radiator  
pressure cap. Replace cap, if necessary. To have  
pressure cap tested, contact an Authorized Service  
Dealer. Inspect cooling system and coolant recov-  
ery system for leaks.  
4.8.8 CHECK FAN BELT  
• Inspect fan belts every three months. Replace any  
damaged, deteriorated, worn or otherwise defec-  
tive belt.  
• Check fan belt tension. Thumb pressure, exerted  
midway between pulleys, should deflect about 3/8  
to 5/8 of an inch. Adjust belt tension as required.  
4.8.9 INSPECT ENGINE GOVERNOR  
Visually inspect electronic governor.  
4.8 MAINTENANCE OWNER/  
OPERATOR CAN PERFORM  
DANGER  
4.8.1 CHECK ENGINE OIL LEVEL  
Do not attempt to adjust the governor. Only  
qualified service facilities should adjust the  
Refer to “Checking Fluid Levels”.  
!
governor. Excessively high operating speeds are  
dangerous and increase the risk of personal  
injury. Low speeds impose a heavy load on the  
engine when adequate engine power is not  
available and may shorten engine life. Correct  
rated frequency and voltage are supplied only  
at the proper governed speed. Some connected  
electrical load devices may be damaged by  
incorrect frequency and/or voltage. Only quali-  
fied service technicians should adjust the gov-  
erned speed.  
4.8.2 CHECK BATTERY  
• See “Checking Fluid Levels”.  
• Check battery cables for condition, tightness, cor-  
rosion or damage. Clean, tighten or replace as  
necessary.  
4.8.3 EXERCISE SYSTEM  
Start the generator engine at least once every seven  
days and let it run at least 12 minutes. See “Weekly  
Exercise Cycle”.  
4.8.10 CHANGING ENGINE OIL  
Refer to maintenance performed by authorized service  
facilities for engine oil and filter change frequencies.  
4.8.4 INSPECT COOLING SYSTEM  
• Inspect engine cooling system. See “Maintenance  
Schedule”.  
Drain the oil while the engine is still warm from run-  
ning. This means warm up the engine, shut it down  
and drain immediately as follows:  
• Check hoses for damage, deterioration, leaks, etc.  
Correct any discrepancies found.  
• Check hose clamps for tightness.  
1. Remove OIL DRAIN HOSE from its retaining clip.  
2. Loosen and remove OIL DRAIN HOSE CAP. Drain  
oil completely into suitable container.  
3. When all oil has drained, install and tighten OIL  
DRAIN HOSE CAP, and re-install into its retaining  
clip.  
4.8.5 CHECK ENGINE COOLANT LEVEL  
See “Checking Fluid Levels”.  
4. Turn OIL FILTER (Figure 4.1) counterclockwise  
and remove. Properly dispose of old filter.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Liquid-cooled 15, 20 and 25 kW Generators  
5. Apply light coating of new engine oil to seal of new  
4.8.13 COOLANT CHANGE  
oil filter. Install FILTER and tighten by hand only.  
Every year, have an Authorized Service Facility drain,  
flush and refill the cooling system. See  
“Specifications” for cooling system recommenda-  
tions.  
DO NOT OVER TIGHTEN.  
6. Remove OIL FILL CAP. Add recommended oil (see  
SPECIFICATIONS). DO NOT FILL ABOVE THE  
DIPSTICK “FULLMARK. Crankcase oil capacity  
is 4.0 U.S. quarts (3.8 liters).  
4.9 MISCELLANEOUS MAINTENANCE  
4.9.1 CLEANING THE GENERATOR  
After refilling the crankcase with oil, always  
check oil level on dipstick. NEVER OPERATE  
ENGINE WITH OIL BELOW THE DIPSTICK “ADD”  
MARK.  
Keep the generator as clean and as dry as possible.  
Dirt and moisture that accumulates on internal gen-  
erator windings have an adverse effect on insulation  
resistance.  
!
7. Start engine and check for oil leaks.  
Periodically clean generator exterior surfaces. A soft  
brush may be used to loosen caked on dirt. Use a  
vacuum system or dry, low pressure air to remove  
any accumulations of dirt. The generator is housed  
inside an all-weather enclosure, clean the enclosure  
with a soft, damp cloth or sponge and water.  
4.8.11 CHANGING THE ENGINE AIR CLEANER  
To replace the engine air cleaner, (part number  
059402), simply remove the air cleaner cover and  
replace the air filter making sure it is positioned  
properly before reattaching the cover (Figure 4.1).  
Once each year have the generator cleaned and  
inspected by an Authorized Service Dealer. That deal-  
er will use dry, low pressure air to clean internal  
windings. Parts inside the control console should be  
cleaned and inspected at this time as well.  
See the “Service Schedule,” for air cleaner mainte-  
nance.  
4.8.12 SPARK PLUGS  
Reset the spark plug gap or replace the spark plugs  
as necessary (Figure 4.4). See Section 6.  
Finally, have the insulation resistance of stator and  
rotor windings checked. If insulation resistances are  
excessively low, the generator may require drying.  
1. Clean the area around the base of the spark plugs  
to keep dirt and debris out of the engine. Clean by  
scraping or washing using a wire brush and com-  
mercial solvent. Do not blast the spark plugs to  
clean.  
2. Remove the spark plugs and check the condition.  
Replace the spark plugs if worn or if reuse is  
questionable. See the “Service Schedule,” Section  
6, for recommended inspection.  
3. Check the spark plug gap using a wire feeler  
gauge. Adjust the gap to 1.07-1.17 mm (0.042-  
0.046 inch) by carefully bending the ground elec-  
trode (Figure 4.2).  
4.9.2 BATTERY  
All lead-acid storage batteries discharge when not in  
use. Refer to specific instructions and warnings that  
accompany the battery. If such information is not  
available, observe the following precautions when  
handling a battery:  
• DO NOT use jumper cables and a booster battery  
to crank or start the generator engine.  
• DO NOT recharge a weak battery while it is  
installed in the generator. Remove battery from  
generator and recharge in a well-ventilated area,  
away from fuel vapors, sparks, heat or flames.  
• Battery electrolyte fluid is an extremely caustic  
sulfuric solution that can cause severe burns. DO  
NOT permit fluid to contact eyes, skin, clothing,  
painted surfaces, wiring insulation, etc. If any bat-  
tery fluid is spilled, flush the affected area with  
clear water immediately.  
Figure 4.4 – Setting the Spark Plug Gap  
SET PLUG GAP AT 1.07 - 1.17 mm  
(0.042 - 0.046 inch)  
• Always wear safety glasses, rubber apron and  
gloves when handling a battery.  
• Batteries give off explosive hydrogen gas while  
charging. The gas can form an explosive mixture  
around the battery for several hours after charging.  
Any spark, heat or flames can ignite the gas and  
cause an explosion which can shatter the battery,  
causing blindness or other serious injury.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Liquid-cooled 15, 20 and 25 kW Generators  
4.9.3 BATTERY MAINTENANCE  
The battery should be inspected per Section 4.7,  
Scheduled Maintenance. The following procedure  
should be followed for inspection:  
Be sure the AUTO/OFF/MANUAL switch is set to  
!
the OFF position, before connecting the battery  
cables. If the switch is set to AUTO or MANUAL,  
the generator can crank and start as soon as  
the battery cables are connected.  
1. Inspect the battery posts and cables for tightness  
and corrosion. Tighten and clean as necessary.  
2. Check the battery fluid level of unsealed batteries  
and, if necessary, fill with DISTILLED WATER  
ONLY. Do not use tap water in batteries.  
3. Have the state of charge and condition checked.  
This should be done with an automotive-type bat-  
tery hydrometer.  
Be sure the utility power supply to the battery  
charger is turned off, or sparking may occur at  
the battery posts as the cables are attached  
and cause an explosion.  
4.9.4 BATTERY REPLACEMENT  
DANGER  
When replacing batteries, use the same number and  
the type of battery that follows:  
Storage batteries give off explosive hydrogen  
gas. This gas can form an explosive mixture  
around the battery for several hours after  
charging. The slightest spark can ignite the gas  
and cause an explosion. Such an explosion can  
shatter the battery and cause blindness or  
other injury. Any area that houses a storage  
battery must be properly ventilated. Do not  
allow smoking, open flame, sparks or any spark  
producing tools or equipment near the battery.  
BCI Group No.  
CCA  
525 @ 0 deg. F  
26-60R  
NOTE:  
The BCI number should be located directly  
on the battery.  
PERIODIC REPLACEMENT PARTS  
Battery electrolyte fluid is an extremely corro-  
sive sulfuric acid solution that can cause severe  
burns. Do not permit fluid to contact eyes, skin,  
clothing, painted surfaces, etc. Wear protective  
goggles, protective clothing and gloves when  
handling a battery. If fluid is spilled, flush the  
affected area immediately with clear water.  
Part Name  
Part Number  
!
Oil Filter  
Motorcraft FL-400-S (supplied with engine)  
Radiator Cap  
Air Cleaner  
Spark Plug  
Battery  
# 046627  
# 059402  
Motorcraft AWSF-52-C (supplied with engine)  
# 077483  
Do not use any jumper cables or booster bat-  
tery to crank and start the generator engine. If  
!
the battery has completely discharged, remove  
it from the generator for recharging.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Liquid-cooled 15, 20 and 25 kW Generators  
4.10 SCHEDULED MAINTENANCE  
The following is a recommended maintenance schedule for small standby and residential generator sets. The  
established intervals in the schedule are the maximum recommended when the unit is used in an average service  
application. They will need to be decreased (performed more frequently) if the unit is used in a severe application.  
Use calendar time from the previous maintenance interval to determine the next required maintenance interval.  
Service Maintenance Interval Information:  
The various service maintenance intervals are designated by interval numbers as follows:  
1 An early inspection of the generator set to insure it is ready to operate when required and to identify any poten-  
tial problem areas.  
Performed monthly this requires approximately .5 man-hours per unit to complete.  
This inspection may be performed by the end user providing the following safety steps are taken to prevent  
the engine from starting automatically without warning:  
To prevent injury, perform the following steps in the order indicated before starting any maintenance:  
Disable the generator set from starting and/or connecting to the load by setting the control panel  
AUTO/OFF/MANUAL switch to the OFF position.  
Remove the 5 amp and 15 amp control panel fuses.  
Turn off the battery charger (turn OFF utility supply to ATS).  
Remove the negative battery cable.  
The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condi-  
tion from burning out sensitive control panel components and circuits.  
Following all maintenance, reverse these steps to assure the unit is returned to standby setup for normal  
operation when required.  
2 A break-in service inspection of the generator set to insure it is ready to operate and carry the load when  
required, and to identify any potential problem areas.  
Performed ONLY ONCE following the first three months of operation after purchase of the unit and requires  
approximately 2.5 man-hours per unit to complete.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
3 An operational inspection of the generator set to insure it is ready to operate and carry the load when required,  
and to identify any potential problem areas.  
Performed semi-annually this requires approximately 1.5 man-hours per unit to complete.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
4 A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required, and  
to identify any potential problem areas.  
Performed annually this requires approximately 4.0 man-hours per unit to complete.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Liquid-cooled 15, 20 and 25 kW Generators  
Maintenance  
Tasks  
Level 1  
Recom-  
mended  
Level 2  
Required  
Level 3  
Required  
Level 4  
Task  
Task  
Task  
Task  
Comp.  
Comp. to be done Comp. to be done Comp.  
Required  
to be done (Date-  
monthly Initials)  
3 months/  
Break-in  
(Date-  
Initials)  
Semi-  
annually  
(Date-  
Initials)  
to be done (Date-  
Annually  
Initials)  
1. Disable the unit from  
operating per the first page  
warning.  
2. Check the engine oil level.  
Adjust as necessary.  
3. Check the engine coolant  
level. Adjust as necessary.  
4. Check the engine coolant  
thermal protection level.  
Correct as necessary.  
5. Check the natural gas  
delivery system on gas  
engine driven units.  
Tighten connections as  
necessary.  
6. Check the air inlets and  
outlets for debris. Clean as  
necessary.  
7. Check the battery  
electrolyte level if  
accessible. Adjust as  
necessary.  
8. Check the battery posts,  
cables, and charger for  
loose connections,  
corrosion, and proper  
operation. Correct as  
necessary.  
9. Check the unit wiring for  
loose connections,  
corrosion, and damage.  
Correct as necessary.  
10. Check the engine  
accessory drive belts for  
wear, weather cracking,  
and damage. Replace as  
necessary.  
11. Visually inspect the unit  
looking for leaks, wear or  
damage, loose connections  
or components, and  
corrosion. Correct as  
necessary.  
12. Test the engine and  
transfer switch safety  
devices. Correct and/or  
adjust as necessary.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Liquid-cooled 15, 20 and 25 kW Generators  
Maintenance  
Tasks  
Level 1  
Recom-  
mended  
Level 2  
Required  
Level 3  
Required  
Level 4  
Task  
Task  
Task  
Task  
Comp.  
Comp. to be done Comp. to be done Comp.  
Required  
to be done (Date-  
monthly Initials)  
3 months/  
Break-in  
(Date-  
Initials)  
Semi-  
annually  
(Date-  
Initials)  
to be done (Date-  
Annually Initials)  
13. Initiate an automatic start  
and transfer of the unit to  
site load and exercise it for  
at least 1 hour looking for  
leaks, loose connections  
or components, and  
abnormal operating  
conditions. Correct as  
necessary.  
14. Start and exercise the unit  
at full rated load (use a  
load bank if the site load is  
not enough) for at least 2  
hours looking for leaks,  
loose connections or  
components, and abnormal  
operating conditions.  
Correct as necessary.  
15. Change the engine oil.  
16. Replace the engine oil  
filter(s).  
17. Replace the engine air  
filter(s).  
18. Replace the engine fuel  
filter(s) on diesel engine  
driven units and re-prime  
the fuel system.  
19. Check the engine spark  
plugs on gas engine driven  
units. Clean and re-gap or  
replace as necessary.  
20. Perform a 5 minute no-load  
operational run of the unit  
looking for any post service  
problems.  
21. Return the unit to standby  
setup for operation when  
required.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Troubleshooting  
Liquid-cooled 15, 20 and 25 kW Generators  
TROUBLESHOOTING POINTS  
PROBLEM  
CAUSE  
CORRECTION  
Engine won’t crank.  
1. 15 amp fuse blown.  
1. Replace fuse.  
2. Loose or corroded or defective  
battery cables.  
2. Tighten, clean or replace  
battery cables as necessary.  
3. Defective starter contactor.  
4. Defective starter motor.  
5. Dead or Defective Battery.  
6. 5 amp fuse blown.  
3. Replace contactor.  
4. Replace starter motor.  
5. Remove, change or replace battery.  
6. Replace fuse.  
Engine cranks but won't start  
1. Out of fuel.  
2. Fuel solenoid (FS) is defective  
3. Open Wire #14A from Engine Control  
circuit board.  
1. Replenish fuel.  
2. Replace solenoid.  
3. Reconnect wire.  
4. Spark plugs defective.  
4. Clean, regap or replace plugs.  
1. Clean or replace as needed.  
Engine starts hard, runs rough.  
Engine starts then shuts down.  
1. Flame arrestor (air cleaner) plugged or  
damaged.  
2. Plugged fuel line.  
3. Defective spark plugs.  
2. Unclog fuel line.  
3. Clean, regap or replace plugs.  
1. Engine oil level is low.  
2. Engine is overheated.  
3. Defective Low Oil Pressure Switch  
4. Defective Coolant Temperature Switch  
5. Defective Control Module circuit board.  
6. Coolant Level is Low.  
1. Check oil and add oil as needed.  
2. Check cooling system for leaks.  
3. Replace switch.  
4. Replace switch.  
5. Replace board.  
6. Repair leak - Add coolant.  
7. Replace Switch.  
7. Defective Low Coolant Level Switch  
AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch  
1. Replace switch.  
engine continues to run  
2. Open/disconnected wire #15A between  
AUTO/OFF/MANUAL switch and Control  
Module circuit board.  
2. Reconnect/close wire.  
3. Defective Control Module circuit board  
3. Replace board.  
No AC output from generator.  
1. Main line circuit breaker open.  
2. Circuit breakers & fuses open.  
3. Transfer switch set to NORMAL position  
4. Generator internal failure.  
1. Reset to ON or CLOSED.  
2. Reset and replace, if necessary.  
3. Set to GENERATOR position.  
4. Contact an Authorized Service Dealer.  
5. Auto-reset - Wait 5 min. and attempt restart.  
5. Thermal circuit breaker open.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 — Notes  
Liquid-cooled 15, 20 and 25 kW Generators  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 — Notes  
Liquid-cooled 15, 20 and 25 kW Generators  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 - Electrical Data  
Liquid-cooled 15, 20 and 25 kW Generators  
Wiring Diagram — 2.5L Engine (15kW & 20kW units) —Drawing No. 0F2183-B  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 - Electrical Data  
Liquid-cooled 15, 20 and 25 kW Generators  
Wiring Diagram — 2.5L Engine (15kW & 20kW units) —Drawing No. 0F2183-B  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 - Electrical Data  
Liquid-cooled 15, 20 and 25 kW Generators  
Electrical Schematic — 2.5L Engine (15kW & 20kW units) —Drawing No. 0F2184-B  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 - Electrical Data  
Liquid-cooled 15, 20 and 25 kW Generators  
Electrical Schematic — 2.5L Engine (15kW & 20kW units) —Drawing No. 0F2184-B  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 - Electrical Data  
Liquid-cooled 15, 20 and 25 kW Generators  
Wiring Diagram — 2.5L Engine (25kW unit) —Drawing No. 0F1286-B  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 - Electrical Data  
Liquid-cooled 15, 20 and 25 kW Generators  
Wiring Diagram — 2.5L Engine (25kW unit) —Drawing No. 0F1286-B  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 - Electrical Data  
Liquid-cooled 15, 20 and 25 kW Generators  
Electrical Schematic — 2.5L (25kW unit) — Drawing No. 0F1287-B  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 - Electrical Data  
Liquid-cooled 15, 20 and 25 kW Generators  
Electrical Schematic — 2.5L (25kW unit) — Drawing No. 0F1287-B  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Mounting Base — Drawing No. 0F0104-B  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Mounting Base — Drawing No. 0F0104-B  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
0F1705  
0E8834  
0E9911  
049813  
022097  
026850  
055414  
022473  
047411  
052860  
052251  
052257  
052252  
052259  
052891  
0536210261  
074906  
077483  
0F0796  
025507  
060619  
046526  
022131  
021991  
038805G  
050331  
050331A  
038804J  
045771  
022129  
027482  
075763  
0E9748A  
0F0795  
0C2454  
065852  
045764  
1
1
1
1
4
2
1
4
4
4
4
4
4
4
4
1
1
REF  
3
3
1
1
1
1
1
REF  
REF  
1
REF  
REF  
1
1
1
3
33  
1
SUPPORT BATTERY TRAY  
HOLD DOWN BATTERY  
ASSEMBLY BATTERY TRAY  
NUT HEX M6 X 1.0 G8 YEL CHR  
WASHER LOCK M6-1/4  
WASHER SHAKEPROOF EXT 1/4 STL  
LUG SLDLSS #2-#8 X 17/64 CU  
WASHER FLAT 1/4-M6 ZINC  
SCREW HHC M6-1.0 X 16 G8.8  
NUT FLANGED HEX M12-1.75  
DAMPENER VIBRATION 40 BLUE  
SPACER .49 X .62 X 1.87 PWDR/ZNC  
DAMPENER VIBRATION  
WASHER FLAT M12  
SCREW HHC M12-1.75 X 80 G8.8  
ASSY WIRE #0 12.00"  
SCREW HHTT M6-1.0 X 20 BP  
BATT 12VDC 75-AH 26 (NOT SHOWN)  
BRACKET CONTROL PANEL SUPPORT  
WASHER SHAKEPROOF EXT 7/16 STL  
SCREW SHC M10-1.50 X 40 G12.9  
WASHER LOCK M10  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
WASHER FLAT 3/8-M10 ZINC  
EARTH STRAP  
CABLE BATT BLK #1 X 41.50  
BATTERY POST COVER (BLACK)  
BATTERY POST COVER (RED)  
CABLE BATT RED #1 X 40.50  
NUT HEX M8-1.25 G8 YEL CHR  
WASHER LOCK M8-5/16  
WASHER SHAKEPROOF EXT 5/16 STL  
BOOT BATTERY CABLE  
ASSY MTG BASE 2.5L AL ENCL  
SUPPORT CONTROL PANEL 2.5L  
SCREW THF M6-1 X 16 N WA Z/JS  
SPRING CLIP HOLDER .37-.62  
SCREW HHTT M4-0.7 X 8 BP  
1
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Enclosure — Drawing No. 0F1645-H  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Enclosure — Drawing No. 0F1645-H  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
0F0783  
0F0781  
0F0780  
0C2454  
0F0779  
0E0072AB  
0E0072AC  
0E0072AD  
0E5912  
0F0787  
1
1
1
34  
1
1
1
1
2
1
2
4
1
1
1
13  
13  
2
4
4
4
1
1
3
8
1
1
2
1
2
1
2
1
1
1
1
1
4
2
2
10  
1
1
1
1
1
1
DUCT INTAKE MID AL 2.5L  
DUCT DISCHARGE RH AL 2.5L  
DUCT DISCHARGE LH AL 2.5L  
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
SUPPORT RADIATOR 2.5L AL  
AI INSULATION SIDE REAR CORNER POST RH  
AI INSULATION INTAKE DUCT TOP PANEL  
AI INSULATION LH SIDE REAR CORNER POST PANEL (BOTTOM)  
DOOR SIDE HSB AL  
SUPPORT RH SIDE AL 2.5L  
FOAM STRIP 3/4" WIDE X 3/16" THK (40" LG)  
WASHER NYLON .257  
AI NSULATION LH SIDE REAR CORNER POST PANEL (TOP)  
HINGE TYPE B W/STUDS, SOCKET  
HINGE TYPE B W/STUDS, PIN  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4-M6 ZINC  
GAS SPRING  
BALL STUD GAS SPRING MOUNT  
NUT HEX 5/16-18 LOCK  
SCREW WING M6-1.00 X 25  
HINGE TYPE A W/STUDS, SOCKET  
HINGE TYPE A W/STUDS, PIN  
GASKET CLIP-ON SELF GRIPPING (84" LG)  
WASHER SELF LOCKING DOME  
KIT SAE FOAM 2.5L QUIET SOURCE  
ROOF 2.5L FORD AL  
AI DOOR PANEL  
LATCH 1/4 TURN NONLOCKING  
PAWL DOOR HSB  
10  
11  
12  
13  
14  
15  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
089961  
0A2115  
0E0072AE  
0F0165A  
0F0165  
022097  
022473  
0E7570  
0E7571  
070015  
0E7662  
0F0164A  
0F0164  
0D2023  
078115  
0F2179  
0F0788  
0E7829B  
0D3037A  
0C7781  
0F0786  
0E0072Q  
0D3037  
0E0072Y  
0E0072AF  
0E0072AA  
0F0782  
SUPPORT LH SIDE AL 2.5L  
AI INSULATION RAD SUPPORT PANEL  
LATCH QUARTER TURN LOCKING  
AI INSULATION SIDE BRACE PANEL RH  
AI INSULATION SIDE BRACE PANEL LH  
AI INSULATION ROOF PANEL  
DUCT DISCHARGE MID AL 2.5L  
WASHER SHAKEPROOF EXT 1/4 STL  
ASSY WIRE 14AWG 7.5 #0 GRN/YEL  
ASSY WIRE 14AWG 7.5 #0 GRN/YEL  
NUT HEX M6 X 1.0 G8 YEL CHR  
CORNER POST REAR LH SIDE AL  
CORNER POST REAR RH SIDE AL  
BRACKET STIFFENER LH FRONT  
DOOR BATTERY COMPARTMENT  
SCREW BHSC M6-1.0 X 16 SS  
BRACKET STIFFENER RH FRONT  
026850  
0912970064  
0912970063  
049813  
0F0784  
0F0785  
0E8665  
0E8837  
0A3359  
0E8404  
* ALL ITEMS NOTATED WITH "AI" ARE COMPONENTS OF 0F2179  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Control Panel (15kW and 20kW) — Drawing No. 0F2267-D  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Control Panel (15kW and 20kW) — Drawing No. 0F2267-D  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
0F0790  
0F0789  
0F0791  
0E9704  
067680  
0E6875A  
0C3910  
048468  
0D5070A  
057073  
040213  
0C2265  
029673  
0F0793  
0E7890  
0D5541*  
0D5544**  
0F1264  
0F1263  
0F1262  
0E7403A  
0E7403C  
0E2514  
020911  
023897  
022152  
051716  
082573  
0E4494  
0C4167  
0C2699  
0C2212  
047411  
022097  
022473  
0E7358  
064733  
0F0798A  
0E6881  
048352  
0C1127  
0C1229  
0F2632  
0F2629  
0E7193  
0F6146  
1
1
1
1
1
2
1
1
1
1
2
18  
1
1
1
1
1
1
1
2
1
1
1
2
4
2
2
1
1
REF.  
4
1
4
4
4
TOP, CONTROL PANEL  
BACK & BOTTOM, CONTROL PANEL  
PANEL, FRONT 2.5L CONTROL PNL  
ASSY PCB HSB CONTROLLER 2.5L  
ASSY VOLTAGE REGULATOR 60HZ  
RELAY, 12VDC C FORM W/DIODE  
XFMR 240/16V 1VA&56VA  
CIRCT BRK 8 X 1 ETA 46-500-P  
ASSY PCB 2A 12V UL BATT CHRGR  
JUNCTION BLOCK 3/8-16  
PCB SUPPORT SNAP-IN 1/4"  
SCREW PHTT M4-0.7 X 12 ZYC  
DIO BRIDGE 25A 600V  
BRACKET, CB SIEMENS BQ  
BRKT CB MTG BACK  
CB 0070A 2P 240V S BQ2 LL  
CB 0100A 2P 240V S BQ2 LL  
ADPTR,LH SIDE WICKMAN 178.6192  
ADPTR,RH SIDE WICKMAN 178.6191  
HOLDER, FUSE WICKMANN 178.6150  
FUSE ATO TYPE 5 AMP (TAN)  
FUSE, ATO TYPE 15 AMP (BLUE)  
FITTING CONDUIT STR 1-1/2"  
SCREW PPHM M5-0.8 X 30 ZINC  
WASHER FLAT #10 ZINC  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
WASHER LOCK #10  
NUT HEX M5-0.8 G8 YEL CHR  
SWITCH ROC DPST 125V SPD  
SWITCH ROC DPDT ON-OFF-ON  
BLOCK TERM 20A 14 X 6 X 1100V  
SCREW PHTT #6-32 X 3/8 ZYC  
SCREW PHTT M4-0.7 X 16 ZYC  
SCREW HHC M6-1.0 X 16 G8.8  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4-M6 ZINC  
SCREW PPPH HI-LO #4-24 X 3/8  
RES MTG BRACKET  
HARNESS, C-PNL 2.5L QS 15&20KW (NOT SHOWN)  
SOCKET, RELAY  
4
2
1
REF  
1
1
1
1
1
RES 5R 5% 25W  
DECAL AVR COVER  
DECAL WARNING ELECTRICAL SHOCK  
DECAL TERMINAL BLOCK  
DECAL CONTROL HSB  
1
1
DECAL, WARNINGS HSB  
HANG TAG 2 WIRE START (NOT SHOWN)  
* 15KW  
** 20KW  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Control Panel (25kW) — Drawing No. 0E7615-C  
28  
27  
32  
33  
34  
42  
43  
1
4
21  
11  
6
20  
17  
18  
35  
30  
5
12  
12  
38  
7
23  
24  
12  
41  
2
12  
3
2
9
24  
13  
25  
31  
26  
8
39  
12  
14  
40  
12  
16  
34  
15  
33  
32  
12  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Control Panel (25kW) — Drawing No. 0E7615-C  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
0F0790  
0F0789  
0F0791  
0E9704  
067680  
0E6875A  
0C3910  
054450  
0D5070A  
057073  
040213  
0C2265  
029673  
0F0793  
0E7890  
0A2077  
0F1264  
0F1263  
0F1262  
0E7403A  
0E7403C  
0E2514  
020911  
023897  
022152  
051716  
082573  
0E4494  
0C4167  
0C2699  
0C2212  
047411  
022097  
022473  
0E7358  
0F0798  
0E6881  
0C1127  
0C1229  
0F2632  
0F2629  
0E7193  
0F6146  
1
1
1
1
1
2
1
1
1
1
2
16  
1
1
1
1
1
1
2
1
1
1
2
4
2
2
1
1
REF.  
4
1
4
4
4
4
TOP, CONTROL PANEL  
BACK & BOTTOM, CONTROL PANEL  
PANEL, FRONT 2.5L CONTROL PNL  
ASSY PCB HSB CONTROLLER 2.5L  
ASSY VOLTAGE REGULATOR 60HZ  
RELAY, 12VDC C FORM W/DIODE  
XFMR 240/16V 1VA&56VA  
CIRCT BRK 5.5 X 1 ETA 46-500-P  
ASSY PCB 2A 12V UL BATT CHRGR  
JUNCTION BLOCK 3/8-16  
PCB SUPPORT SNAP-IN 1/4"  
SCREW PHTT M4-0.7 X 12 ZYC  
DIO BRIDGE 25A 600V  
BRACKET, CB SIEMENS BQ  
BRKT CB MTG BACK  
CB 0125A 2P 240V S BQ2 LL  
ADPTR,LH SIDE WICKMAN 178.6192  
ADPTR,RH SIDE WICKMAN 178.6191  
HOLDER, FUSE WICKMANN 178.6150  
FUSE ATO TYPE 5 AMP (TAN)  
FUSE, ATO TYPE 15 AMP (BLUE)  
FITTING CONDUIT STR 1-1/2"  
SCREW PPHM M5-0.8 X 30 ZINC  
WASHER FLAT #10 ZINC  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
37  
38  
39  
40  
41  
42  
43  
44  
WASHER LOCK #10  
NUT HEX M5-0.8 G8 YEL CHR  
SWITCH ROC DPST 125V SPD  
SWITCH ROC DPDT ON-OFF-ON  
BLOCK TERM 20A 14 X 6 X 1100V  
SCREW PHTT #6-32 X 3/8 ZYC  
SCREW PHTT M4-0.7 X 16 ZYC  
SCREW HHC M6-1.0 X 16 G8.8  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4-M6 ZINC  
SCREW PPPH HI-LO #4-24 X 3/8  
HARNESS CTRL PNL 2.5L FORD AL (NOT SHOWN)  
SOCKET, RELAY  
DECAL AVR COVER  
DECAL WARNING ELECTRICAL SHOCK  
DECAL TERMINAL BLOCK  
DECAL CONTROL HSB  
DECAL, WARNINGS HSB  
1
REF  
1
1
1
1
1
1
HANG TAG 2 WIRE START (NOT SHOWN)  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Engine — Drawing No. 0E9918-F  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Engine — Drawing No. 0E9918-F  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
3
4
5
6
7
0E9909  
0E9739  
049814  
0F0001  
0D3488B  
0A8584  
0E0561  
REF  
ENGINE 2.5L FORD  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
0E9930  
049821  
0E9747  
043116  
022473  
045772  
064416  
0F0252  
0E9868  
0F0035  
026082  
0E9928  
0F0383  
1
3
1
5
6
2
2
1
1
1
1
1
1
HEAT SHIELD, EXHAUST MANIFOLD  
SCREW SHC M8-1.25 X 30 G12.9  
STARTER, 12 VOLT  
SCREW HHC M6-1.0 X 12 G8.8  
WASHER FLAT 1/4-M6 ZINC  
NUT HEX M10-1.5 G8 YEL CHR  
SCREW HHC M10-1.5 X 45 G8.8  
SPRING BUSHING  
1
8
1
1
1
1
PULLEY, 2.5L FORD WATER PUMP  
SCREW HHC M10-1.5 X 25 G8.8  
CLUTCH, COOLING FAN 2.5L FORD  
SERPENTINE BELT - 40.85" LENGTH  
SWITCH,OIL PRESSURE,10PSI,2POL  
ASSY WATER LEVEL SENSOR C/E  
PL  
8
9
10  
11  
0A6751  
035579  
026925  
0E9611  
1
1
1
1
SW-TMP 245DEG 3/8NPT  
ALTERNATOR, D.C  
BUSHING REDUCER 1/4 TO 1/8  
PLUG STD PIPE 3/8 STEEL SQ HD  
MANIFOLD, INTAKE (MACHINED)  
(STEPPER MOTOR)  
MANIFOLD INTAKE MACH BOSCH32  
(BOSCH GOV.) (NOT SHOWN)  
GASKET, 2.5L FORD INTAKE MAN.  
SCREW HHC M8-1.25 X 20 G8.8  
SCREW SHC M6-1.0 X 25 G12.9 ZP  
WASHER FLAT 5/16-M8 ZINC  
WASHER LOCK M6-1/4  
BRKT,D.C. ALTERNATOR(MACHINED)  
SCREW HHC 3/8-16 X 2-1/4 G5  
TENSIONER, D.C. ALTERNATOR  
HOSE,2.5L FORD COOLANT BY-  
PASS  
0E9611A  
1
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
057823  
0E9737  
0F0393  
045757  
069860C  
048031J  
055596  
077456  
052677  
049813  
0E9738A  
0F1132  
2
1
1
2
1
REF  
1
1
1
1
CLAMP HOSE #10 .56-1.06  
LOWER HOSE ADAPTER,2.5L FORD  
O-RING 1-3/16 X 1-7/16 X 1/8  
SCREW HHC M6-1.0 X 25 G8.8  
HOSE OIL DRAIN ASSY 21"  
HOSE CLAMP BAND 5/8"  
BARBED STR 3/8NPT X 3/8  
ADAPTER M12-1.75 3/8NPT  
WASHER NYLON .50 X .87 X .06  
NUT HEX M6 X 1.0 G8 YEL CHR  
DIPSTICK TUBE, 2.5L FORD  
COVER, R/H SIDE ENGINE  
ADAPTOR  
COVER, L/H SIDE ENGINE ADAPTOR  
SCREW SHC M10-1.50 X 50 G12.9  
TANK COOLANT RECOVERY  
HOSE 9/32 ID (39"LG)  
BRACKET,2.5L FORD WATER  
BOTTLE  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
0E9681  
039253  
097962  
022145  
022097  
022129  
043107  
022131  
046526  
052625  
0E9708  
0E9738  
0E9929  
0F0230  
0E9834  
1
4
4
8
11  
16  
11  
19  
22  
2
2
1
1
1
WASHER LOCK M8-5/16  
SCREW HHC M8-1.25 X 25 G8.8  
WASHER FLAT 3/8-M10 ZINC  
WASHER LOCK M10  
SCREW SHC M10-1.5 X 35 G12.9  
ENGINE FOOT, 2.5L FORD  
DIPSTICK, 2.5L FORD  
BRACKET, DIPSTICK TUBE  
FAN 16" COOLING  
HARNESS, 2.5L FORD ENGINE (NOT  
SHOWN)  
1
1
60  
61*  
62  
63  
64  
0F1133  
059355  
076749  
029032  
0F1433  
1
8
1
1
1
1
0E9834A  
1
HARNESS,2.5L FORD (BOSCH GOV.)  
(NOT SHOWN)  
27  
28  
29  
30  
31  
32  
33  
34  
0D5417  
0E5048B  
0E9655  
057192  
060619  
0E8940  
0E9680  
0E9609  
6
1
1
4
2
1
1
1
SCREW HHC M10-1.0 X 25 G10.9  
FLEXPLATE 2.5L FORD  
ADAPT CASTING MACH 2.5L FORD  
SCREW SHC M10-1.5 X 30 G12.9  
SCREW SHC M10-1.50 X 40 G12.9  
SPACER FLEXPLATE HSB  
65  
66  
67  
68  
69  
070007  
070005  
080826  
045771  
048031C  
3
3
3
1
2
WASHER FLAT M6 SS  
WASHER LOCK M6 SS  
SCREW HHC M6-1.0 X 12 SS  
NUT HEX M8-1.25 G8 YEL CHR  
CLAMP HOSE BAND 1/4  
GASKET, 2.5L FORD EXHAUST MAN.  
MANIFOLD, EXHAUST ( MACHINED)  
* NOTE: TORQUE TO 44 FT/LBS.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Fuel System — Drawing No. 0E9980-D  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Fuel System — Drawing No. 0E9980-D  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8 *  
9
0E8456  
075580  
0E9967  
039253  
022145  
022129  
045771  
0F1570  
0A6344  
0F3994  
0E1056  
0F0397  
0A5547  
048031C  
0D1509  
0E0591  
059402  
037561  
0E1028A  
059401  
091526  
049226  
026307  
062522  
022127  
022259  
050279  
0A6125  
0C2454  
0E1104  
0E0668  
0E0590A  
0C5133  
0E0665  
0E1108  
033138  
022152  
0E0645  
034339  
059194  
057823  
0F0382  
1
1
1
4
2
6
2
1
1
REF.  
1
1
1
2
1
1
1
1
1
1
4
4
1
1
1
2
1
2
3
1
1
1
1
1
BRACKET FUEL REGULATOR  
FLANGE FUEL INLET  
ASSY FUEL REG 2.5L FRD N/G-L/P  
SCREW HHC M8-1.25 X 20 G8.8  
WASHER FLAT 5/16 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 YEL CHR  
BODY CARBURETOR ASSEMBLY  
BARBED EL 90 1/8 NPT X 3/8  
PCV VALVE 2.5L FORD  
FUEL HOSE ASSM. NAT. GAS/L.P.V.  
HOSE CRANKCASE BREATHER  
COVER AIR CLEANER  
10  
11  
12  
13  
14  
15  
16 *  
17  
18  
19  
20  
21 *  
22 *  
23  
24  
25  
26  
27  
28  
29  
30*  
31*  
32*  
33*  
34*  
35*  
36*  
37*  
38*  
39*  
40  
41  
42  
CLAMP HOSE BAND 1/4  
DECAL INLET PRESSURE  
ADAPTER CARB. TO AIR CLNR  
FILTER ELEMENT  
NUT WING 1/4-20 NYLK  
CARBURETOR ASSY. 2.5L FORD  
CARBURETOR GASKET  
SCREW PPHM M5-0.8 X 12 ZNC  
WASHER LOCK M5  
ELBOW 90D STREET 3/4  
STUD TH 1/4-20 X 3 G2 ZNC FULL  
NUT HEX 1/4-20 STEEL  
NUT HEX 5/16-18 STEEL  
DECAL FUEL INLET NG  
STUD 5/16-18 X 1.25 F THR  
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
GASKET, AIR CLEANER ADAPTER  
O-RING 2-028 1.38 X 1.50 X .06  
VENTURI 20MM  
0-RING 29.82 X 2.62  
SCREW THROTTLE PIN STOP  
THROTTLE ARM REWORK  
SCREW HHM #10-32 X 5/8  
WASHER LOCK #10  
LEVER,THROTTLE STOP  
BARBED EL 90 3/8 NPT X 5/8  
HOSE 5/8 ID LPG & NG (24" LG)  
CLAMP HOSE #10 .56 - 1.06  
HOSE 3/8" 90 DEG 2.5L PVC  
1
1
1
1
1
1
2
1
* INCLUDED IN ITEM 19 (CARBURETOR ASSY )  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Alternator — Drawing No. 0E8660-C  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Alternator — Drawing No. 0E8660-C  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
0F1659A  
0F1657A  
0F1655A  
0E5093A  
0E7413A  
0F1660A  
0F1658A  
0F1656A  
0E5094A  
0E7412A  
0E5706  
1
1
1
1
1
1
1
1
1
1
1
REF  
REF  
REF  
1
1
8
4
4
ROTOR 390 15KW 1P DIRECT HSB (2.5L FORD)  
ROTOR 390 20KW 1P DIRECT HSB (2.5L FORD)  
ROTOR 390 25KW 1P DIRECT HSB (2.5L FORD)  
ROTOR 390 30KW 1P DIRECT HSB (3.0L FORD & 2.5L FORD)  
ROTOR 390 40KW 1P DIRECT HSB (3.9L CHRYSLER)  
STR 390 15AD HSB (382MM LONG)(2.5L FORD)  
STR 390 20AD HSB (382MM LONG)(2.5L FORD)  
STR 390 25AD HSB (382MM LONG)(2.5L FORD)  
STR 390 35AD1 HSB (382MM LONG)(3.0L FORD & 2.5L FORD)  
STR 390 40AD HSB (433MM LONG)(3.9L CHRYSLER)  
REAR BEARING CARRIER 390/DRCT  
FLEXPLATE 3.0L FORD  
FLEXPLATE 3.9L HSB  
FLEXPLATE 2.5L FORD  
FLYWHEEL ASSY 3.0L HSB LG GEAR  
REVCOR FAN 10.75 X 2 W/PRESS DIS  
WASHER LOCK M10  
2
3
4
0E5048  
0E5048A  
0E5048B  
0E6668  
0E6076  
046526  
5
6
7
8
9
051755  
SCREW HHC M10-1.5 X 16 G8.8  
04576100BK  
04576100BF  
043123  
STUD M14-2.0 X 490 G5 ZINC (3.0L FORD & 2.5L FORD)  
STUD M14-2.0 X 540 G5 ZINC (3.9L CHRYSLER)  
WASHER LOCK M14  
4
4
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
051779  
0E7587  
023365  
0C3993  
057192  
0A2602  
042558  
0A2601  
022264  
4
1
1
4
4
1
1
1
4
4
1
1
NUT HEX M14-2.0 G8 YEL CHR  
ASSY BRUSH HOLDER 390/HSB  
WASHER SHAKEPROOF INT #8  
SCREW HHTT M4-0.7 X 25 BP  
SCREW SHC M10-1.5 X 30 G12.9  
WASHER FLAT .688 ID X 3.25 OD  
KEY SQ 3/8 X 1 STEEL  
SCREW HHC M16-2.0 X 45 G8.8  
WASHER LOCK #8-M4  
WASHER FLAT #8 ZINC  
CONDUIT FLEX 1-1/4" (30" LG - 3.0L FORD & 3.9L CHRYSLER)  
CONDUIT FLEX 1-1/4" (18" LG - 2.5L FORD)  
038150  
077043F  
077043F  
ROTOR REPLACEMENT PARTS  
30  
31  
047248  
070892  
1
1
BALL BEARING-45 MM  
SLIP RING -MACHINED-  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Muffler — Drawing No. 0F2930-C  
1
4
24  
5
6
7
11  
13  
3
15  
17  
20  
20  
12  
19  
11  
20  
6
18  
4
5
6
7
15  
14  
16  
9
8
10  
2
21  
22  
23  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
3
4
5
6
7
8
9
0F2912  
0F2869  
0F2823  
036434  
036449  
022129  
022259  
0E0170A  
044149  
0E8816  
0F2925  
0F2926  
1
1
1
2
2
6
4
1
1
1
2
1
PIPE MUFFLER OUT  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
042568  
022097  
022473  
049813  
039253  
045771  
0A4010  
022145  
022131  
085917  
0D2611  
052858  
4
4
8
4
2
2
1
5
2
2
2
1
SCREW HHC M6-1.0 X 20 G8.8  
WASHER LOCK M6-1/4  
PIPE EXHAUST 2.5L FORD  
MUFFLER 2.5L FORD  
BOLT U 5/16-18 X 2.09  
SADDLE 2 INCH  
WASHER LOCK M8-5/16  
NUT HEX 5/16-18 STEEL  
EXHAUST BLANKET 800MM  
GASKET EXHAUST RING  
EXHAUST FLANGE 2" PIPE  
STRAP MUFFLER  
WASHER FLAT 1/4-M6 ZINC  
NUT HEX M6 X 1.0 G8 YEL CHR  
SCREW HHC M8-1.25 X 20 G8.8  
NUT HEX M8-1.25 G8 YEL CHR  
SCREW HHC M8-1.25 X 60 G8.8 FT  
WASHER FLAT 5/16-M8 ZINC  
WASHER FLAT 3/8-M10 ZINC  
WASHER LOCK 3/8 SS  
10  
11  
12  
SCREW HHC 3/8-16 X 1-3/4 SS  
NUT TOP LOCK FL M8-1.25  
BRACKET, MUFFLER  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Stepper Motor — Drawing No. 0E9979-C  
5
4
3
ITEM (13) NEOPRENE  
COATING  
2
1
14  
6
7
10  
WIRE HARNESS  
15  
SECURE WIRE HARNESS  
WITH TIE WRAP AS SHOWN.  
12  
7
9
"A"  
16  
17  
TO "A"  
INTAKE MANIFOLD  
(REF.)  
10  
7
6
CARBURETOR ARM  
(REF.)  
11  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
098290  
098941A  
0F0454  
098942A  
098225  
043146  
022097  
0E7358  
098783  
037398  
0E1326  
0A7106  
074031  
029333A  
022507  
022473  
064526  
0E1694  
1
1
REF  
1
2
3
5
REF  
1
2
1
1
AR  
1
2
2
ASM MOTOR STEPPER  
HOUSING GOVERNOR CONNECTOR  
HARN GOV 2.5L FORD  
COVER CONNECTOR HOUSING  
SCREW PFHST #2 X 5/8  
SCREW HHC M6-1.0 X 10 G8.8  
WASHER LOCK M6-1/4  
SCREW PPPH HI-LO #4-24 X 3/8  
LEVER STEPPER MOTOR  
NUT LOCK HEX #10-32 NYL INS  
ASSY. CARBURETOR LINKAGE ROD  
BRACKET STEPPER MOTOR  
LIQUID NEOPRENE  
TIE WRAP 7.4"X.19" BLK UL  
SCREW HHC 1/4-20 X 1/2 G5  
WASHER FLAT 1/4 ZINC  
1
1
SCREW TAP HWH #6-25 X 3/8 ZINC  
SPRING,ANTI LASH  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Exploded Views and Parts Lists  
Liquid-cooled 15, 20 and 25 kW Generators  
Radiator — Drawing No. 0E9965-F  
1
19  
18  
5
11  
12  
2
14  
26  
TO THERMOSTAT  
ADAPTER  
5
9
18  
8
10  
TO BASE OF  
WATER INLET  
TUBE (ON BLOCK)  
7
5
25  
5
9
7
24  
15  
3
27  
4
16  
20  
21  
17  
6
27  
9
8
10  
24  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
0E9769  
0F0779  
0E9769A  
REF  
REF  
REF  
SUPPORT RADIATOR 2.5L FORD  
SUPPORT RADIATOR 2.5L AL  
SUPPORT RADIATOR 2.5L FORD  
ALM  
15  
0E9833  
1
HOSE, 2.5L FORD LOWER  
RADIATOR  
BARBED STR 1/4 NPT X 3/8  
HOSE OIL DRAIN ASSY 21"  
FOAM 1.5 X 1 ADHESIVE BACKING  
(21.5" LG)  
BOLT CARR 1/4-20 X 1-3/4 JS500  
SPRING CLIP HOLDER .37-.62  
SCREW SWAGE 10-32 X 5/16 Z/YC  
SCREW TH-FRM M6-1 X 16 N WA  
Z/JS  
SCREW HHC 1/4-20 X 3/4 G5  
NUT HEX LOCK M6-1.0 SS NY INS  
DECAL WARNING-FAN  
16  
17  
18  
035461  
069860C  
0A7275  
1
1
4
2
3
4
5
6
7
8
9
10  
11  
12  
14  
0E9837  
0F0123  
0F0118  
099502  
0C2454  
052250  
022097  
022473  
022127  
046627  
060035  
0F0127  
1
1
1
4
REF.  
2
8
12  
8
1
4
RADIATOR 2.5L FORD  
VENTURI 16" FAN 2.5L FORD  
GUARD FAN 2.5L FORD  
CLAMP HOSE #24 B1.06-2.00  
SCREW THF M6-1 X 16 N WA Z/JS  
TAPE FOAM 1 X 1(21" LG)  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4 ZINC  
NUT HEX 1/4-20 STEEL  
CAP RADIATOR  
19  
20  
21  
24  
031669  
065852  
0A2111  
0C2454  
4
1
1
6
25  
26  
27  
022287  
077992  
050275  
4
REF  
2
SPACER .41 X .75 X .87 ST/ZNC  
HOSE, UPPER RADIATOR 174MM  
TAL  
1
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Installation Diagram  
Liquid-cooled 15, 20 and 25 kW Generators  
Installation Diagram — Drawing No. 0F1022-A  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Liquid-cooled 15, 20 and 25 kW Generators  
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT  
YOUR WARRANTY RIGHTS AND OBLIGATIONS  
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission  
Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be  
designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control  
system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modifi-  
cation or improper maintenance of your engine.  
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will  
repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.  
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:  
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, dur-  
ing such warranty period, any emission-related component or system on your engine is found to be defective in materials or  
workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Dealer.  
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:  
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory  
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance  
on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the  
completion of all scheduled maintenance.  
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or  
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unap-  
proved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.  
You are responsible for presenting your engine to a Generac Authorized Warranty Service Dealer as soon as a prob-  
lem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.  
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Dealer.  
To locate the Generac Authorized Warranty Service Dealer nearest you, call our toll-free number:  
1-800-333-1322  
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System  
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Power  
Systems, Inc., Two Year Limited Warranty” which is enclosed herewith on a separate sheet, also provided to you by Generac.  
The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between  
the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac  
Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe important rights  
and obligations with respect to your new engine.  
Warranty service can be performed only by a Generac Authorized Warranty Service Dealer. When requesting warranty serv-  
ice, evidence must be presented showing the date of the sale to the original purchaser/owner.  
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the fol-  
lowing address:  
ATTENTION WARRANTY DEPARTMENT  
GENERAC POWER SYSTEMS, INC.  
P.O. BOX 297  
WHITEWATER, WI 53190  
Part 1  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Liquid-cooled 15, 20 and 25 kW Generators  
EMISSION CONTROL SYSTEM WARRANTY  
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:  
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on  
the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall con-  
tinue for 24 consecutive months thereafter.  
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or  
equipment and to each subsequent purchaser/owner that each of its engines is ...  
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its  
authority, and  
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a war-  
ranted emissions-related part to fail to be identical in all material respects to the part as described in the engine man-  
ufacturer’s application for certification.  
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:  
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s  
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall  
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the  
ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.  
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual  
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or  
replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS  
Warranty shall be warranted for the remainder of the ECS Warranty Period.  
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s  
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part  
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection  
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the  
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.  
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no  
charge to the owner at a Generac Authorized Warranty Service Dealer.  
(5) When the engine is inspected by a Generac Authorized Warranty Service Dealer, the owner shall not be held responsi-  
ble for diagnostic costs if the repair is deemed warrantable.  
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused  
by a failure under warranty of any emission-related part covered by the ECS Warranty.  
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient  
to meet the expected demand for such emission-related parts.  
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS  
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac  
ECS Warranty obligations.  
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac  
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.  
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of  
such an unapproved, add-on, modified, counterfeit and/or “grey market” part.  
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:  
1) Fuel Metering System:  
3) Ignition System including:  
a) Spark plug  
b) Ignition module  
1.2) LPG/Natural Gas carburetion assembly and its internal  
components.  
a) Fuel controller (if so equipped)  
4) Catalytic Muffler Assembly (if so equipped) including:  
a) Muffler gasket  
b) Exhaust manifold  
b) Mixer and its gaskets (if so equipped)  
c) Carburetor and its gaskets (if so equipped)  
d) Primary gas regulator (if so equipped)  
e) LP liquid vaporizer (if so equipped)  
5) Crankcase Breather Assembly including:  
a) Breather connection tube  
2) Air Induction System including:  
a) Intake pipe/manifold  
b) Air cleaner  
*Generac engine types covered by this warranty statement include the following:  
1) Prepackaged Standby Generator  
2) Auxiliary Power Unit (APU) Generator  
3) Standby Generator  
Part 2  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Liquid-cooled 15, 20 and 25 kW Generators  
GENERAC POWER SYSTEMS "TWO YEAR" LIMITED WARRANTY FOR QUIETSOURCE™  
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"  
For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) warrants that its Quietsource  
generator will be free from defects in material and workmanship for the items and period set forth below. Generac will, at its  
option, repair or replace any part which, upon examination, inspection and testing by Generac or an Authorized Warranty  
Service Dealer, is found to be defective. Any equipment that the purchaser/owner claims to be defective must be examined by  
the nearest Authorized Warranty Service Dealer. All transportation costs under the warranty, including return to the factory, are  
to be borne and prepaid by the purchaser/owner. This warranty applies only to Generac Quietsource prepackaged emergency  
automatic standby generators sold and rated for use in "Standby" applications.  
WARRANTY SCHEDULE  
YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase  
and maintenance is required):  
Engine - All Components  
Alternator - All Components  
Transfer System - All Components  
All warranty expense allowances are subject to the conditions defined in Generac's Warranty Policies, Procedures and Flat  
Rate Manual.  
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:  
• Quietsource generators that utilize non-Generac replacement parts.  
• Quietsource generators utilizing non-Generac automatic transfer switches.  
• Repairs or diagnostics performed by individuals other than Guardian/Generac authorized dealers not authorized in writing by  
Generac Power Systems.  
• Any Quietsource generators used as rental or trailer mounted applications.  
• Units used for prime power in place of existing utility power where utility power is present or in place of utility power where  
utility power service does not normally exist.  
• Costs of normal maintenance, adjustments, installation and start-up.  
• Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.  
• Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with  
all mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty  
will not cover repair when normal use has exhausted the life of a part(s) or engine.  
• Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire,  
freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.  
• Damage related to rodent and/or insect infestation.  
• Products that are modified or altered in a manner not authorized by Generac in writing.  
• Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or  
replacement of the defective part(s).  
• Failure due to misapplication.  
Telephone, cellular phone, facsimile, internet access or other communication expenses.  
• Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit  
warranty period.  
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.  
• Rental equipment used while warranty repairs are being performed.  
• Costs incurred for equipment used for removal and/or reinstallation of generator, (i.e.; cranes, hoists, lifts, etc.)  
• Overnight freight costs for replacement part(s).  
• Overtime labor.  
• Starting batteries, fuses, light bulbs and engine fluids.  
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC  
MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some  
states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.  
GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO  
EVENT SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH  
DAMAGES ARE A DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of  
incidental or consequential damages, so the above limitation may not apply to you.  
This warranty gives you specific legal rights. You also have other rights from state to state.  
P.O. BOX 297 • WHITEWATER, WI 53190  
Revision (2.05)  
Part No. 0F1007  
Revision F (07/25/05)  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Generac Welding System 005747 0 (XG8000E) User Manual
Generac Power Systems Portable Generator 09843 2 User Manual
Generac Power Systems Portable Generator 5747 0 User Manual
Generac Portable Generator 005028 0 User Manual
Generac Portable Generator 00941 3 User Manual