Generac Portable Generator 25 30kW User Manual

Owner's Manual  
Stationary Emergency Generator  
1.6L  
25/30kW Models  
EPA Certified  
nNOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT  
APPLICATIONS.  
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS  
SHOULD ATTEMPT INSTALLATION! DEADLY EXHAUST  
FUMES! OUTDOOR INSTALLATION ONLY!  
This manual should remain with the unit.  
. 0 H 7 t N 2 r 3 o a 0 P  
. A v 0 4 / 1 0 e v r 1 9 C 1 o R e  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Instructions  
nSAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential  
hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this  
equipment.  
This symbol points out potential fire hazard.  
INTRODUCTION  
Thank you for purchasing this model of the stationary emergency  
generator product line.  
This symbol points out potential electrical shock hazard.  
Every effort was expended to make sure that the information and  
instructions in this manual were both accurate and current at the  
time the manual was written. However, the manufacturer reserves  
the right to change, alter or otherwise improve this product(s) at  
any time without prior notice.  
The operator is responsible for proper and safe use of the equip-  
ment. The manufacturer strongly recommends that the operator  
read this Owner's Manual and thoroughly understand all instruc-  
tions before using this equipment. The manufacturer also strongly  
recommends instructing other users to properly start and operate  
the unit. This prepares them if they need to operate the equipment  
in an emergency.  
READ THIS MANUAL THOROUGHLY  
If any portion of this manual is not understood, contact the nearest  
Service Dealer for starting, operating and servicing procedures.  
For safety reasons, the manufacturer recommends that this  
equipment be installed, serviced and repaired by a Service  
Dealer or other competent, qualified electrician or installation  
technician who is familiar with applicable codes, standards and  
regulations. The operator also must comply with all such codes,  
standards and regulations.  
Throughout this publication, and on tags and decals affixed to the  
generator, DANGER, WARNING, CAUTION and NOTE blocks are  
used to alert personnel to special instructions about a particular  
service or operation that may be hazardous if performed incor-  
rectly or carelessly. Observe them carefully. Their definitions are  
as follows:  
OPERATION AND MAINTENANCE  
It is the operator's responsibility to perform all safety checks, to  
make sure that all maintenance for safe operation is performed  
promptly, and to have the equipment checked periodically by a  
Service Dealer. Normal maintenance service and replacement of  
parts are the responsibility of the owner/operator and, as such,  
are not considered defects in materials or workmanship within the  
terms of the warranty. Individual operating habits and usage con-  
tribute to the need for maintenance service.  
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF  
NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.  
Indicates a hazardous situation or action which, if not  
avoided, could result in death or serious injury.  
Proper maintenance and care of the generator ensure a minimum  
number of problems and keep operating expenses at a minimum.  
See a Service Dealer for service aids and accessories.  
Indicates a hazardous situation or action which, if not  
avoided, could result in minor or moderate injury.  
NOTE:  
Operating instructions presented in this manual assume that the  
generator electric system has been installed by a Service Dealer or  
other competent, qualified contractor. Installation of this equipment  
is not a “do-it-yourself” project.  
Notes contain additional information important to a procedure  
and will be found within the regular text body of this manual.  
These safety warnings cannot eliminate the hazards that they  
indicate. Common sense and strict compliance with the special  
instructions while performing the service are essential to prevent-  
ing accidents.  
HOW TO OBTAIN SERVICE  
When the generator requires servicing or repairs, simply contact  
a Service Dealer for assistance. Service technicians are factory-  
trained and are capable of handling all service needs.  
Four commonly used safety symbols accompany the DANGER,  
WARNING and CAUTION blocks. The type of information each  
indicates is as follows:  
When contacting a dealer about parts and service, always supply  
the complete Model Number, Serial Number and Type Code (where  
applicable) from the DATA LABEL that is affixed to the unit.  
This symbol points out important safety information that,  
if not followed, could endanger personal safety and/or  
n
property of others.  
This symbol points out potential explosion hazard.  
. F v e 0 5 / 1 0  
S a f e t y 0 0 4 R  
1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Instructions  
• The engine exhaust fumes contain carbon monoxide gas, which  
SAFETY RULES  
can be DEADLY. This dangerous gas, if breathed in sufficient  
concentrations, can cause unconsciousness or even death. For  
that reason, adequate ventilation must be provided. This should  
be considered prior to installing the generator. The unit should  
be positioned to direct exhaust gasses safely away from any  
building where people, animals, etc., will not be harmed. Any  
exhaust stacks that ship loose with the unit must be installed  
properly per the manufacturer's instruction, and in strict compli-  
ance with applicable codes and standards.  
Study these SAFETY RULES carefully before installing, operating  
or servicing this equipment. Become familiar with this Owner’s  
Manual and with the unit. The generator can operate safely, effi-  
ciently and reliably only if it is properly installed, operated and  
maintained. Many accidents are caused by failing to follow simple  
and fundamental rules or precautions.  
The manufacturer cannot anticipate every possible circumstance  
that might involve a hazard. The warnings in this manual, and on  
tags and decals affixed to the unit are, therefore, not all inclusive.  
If a procedure, work method or operating technique is used that  
the manufacturer does not specifically recommend, ensure that it  
is safe for others. Also make sure the procedure, work method or  
operating technique utilized does not render the generator unsafe.  
• Keep hands, feet, clothing, etc., away from drive belts, fans,  
and other moving or hot parts. Never remove any drive belt or  
fan guard while the unit is operating.  
• Adequate, unobstructed flow of cooling and ventilating air is  
critical in any room or building housing the generator to prevent  
buildup of explosive gases and to ensure correct generator  
operation. Do not alter the installation or permit even partial  
blockage of ventilation provisions, as this can seriously affect  
safe operation of the generator.  
• Keep the area around the generator clean and uncluttered.  
Remove any materials that could become hazardous.  
• When working on this equipment, remain alert at all times.  
Never work on the equipment when physically or mentally  
fatigued.  
• Inspect the generator regularly, and promptly repair or replace  
all worn, damaged or defective parts using only factory-  
approved parts.  
• Before performing any maintenance on the generator, discon-  
nect its battery cables to prevent accidental start-up. Disconnect  
the cable from the battery post indicated by a NEGATIVE, NEG  
or (–) first. Reconnect that cable last.  
• Never use the generator or any of its parts as a step. Stepping  
on the unit can stress and break parts, and may result in dan-  
gerous operating conditions from leaking exhaust gases, fuel  
leakage, oil leakage, etc.  
nDespite the safe design of this generator,  
operating this equipment imprudently, neglect-  
ing its maintenance or being careless can cause  
possible injury or death. Permit only respon-  
sible and capable persons to install, operate or  
maintain this equipment.  
Potentially lethal voltages are generated by  
these machines. Ensure all steps are taken to  
render the machine safe before attempting to  
work on the generator.  
nParts of the generator are rotating and/or hot  
during operation. Exercise care near running  
generators.  
GENERAL HAZARDS  
• For safety reasons, the manufacturer recommends that this  
equipment be installed, serviced and repaired by a Service  
Dealer or other competent, qualified electrician or installation  
technician who is familiar with applicable codes, standards  
and regulations. The operator also must comply with all such  
codes, standards and regulations.  
ELECTRICAL HAZARDS  
• Installation, operation, servicing and repair of this (and related)  
equipment must always comply with applicable codes, stan-  
dards, laws and regulations. Adhere strictly to local, state and  
national electrical and building codes. Comply with regulations  
the Occupational Safety and Health Administration (OSHA) has  
established. Also, ensure that the generator is installed, operat-  
ed and serviced in accordance with the manufacturer’s instruc-  
tions and recommendations. Following installation, do nothing  
that might render the unit unsafe or in noncompliance with the  
aforementioned codes, standards, laws and regulations.  
• All stationary emergency generators covered by this manual  
produce dangerous electrical voltages and can cause fatal  
electrical shock. Utility power delivers extremely high and dan-  
gerous voltages to the transfer switch as well as the generator.  
Avoid contact with bare wires, terminals, connections, etc.,  
on the generator as well as the transfer switch, if applicable.  
Ensure all appropriate covers, guards and barriers are in place  
before operating the generator. If work must be done around  
an operating unit, stand on an insulated, dry surface to reduce  
shock hazard.  
• Do not handle any kind of electrical device while stand-  
ing in water, while barefoot, or while hands or feet are wet.  
DANGEROUS ELECTRICAL SHOCK MAY RESULT.  
. F v e 0 5 / 1 0  
S a f e t y 0 0 4 R  
1-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Instructions  
• If personnel must stand on metal or concrete while installing,  
FIRE HAZARDS  
operating, servicing, adjusting or repairing this equipment,  
place insulative mats over a dry wooden platform. Work on the  
equipment only while standing on such insulative mats.  
• The National Electrical Code (NEC) requires the frame and  
external electrically conductive parts of the generator to be con-  
nected to an approved earth ground. This grounding will help  
prevent dangerous electrical shock that might be caused by a  
ground fault condition in the generator or by static electricity.  
Never disconnect the ground wire.  
• Keep a fire extinguisher near the generator at all times. Do NOT  
use any carbon tetra-chloride type extinguisher. Its fumes are  
toxic, and the liquid can deteriorate wiring insulation. Keep the  
extinguisher properly charged and be familiar with its use. If  
there are any questions pertaining to fire extinguishers, consult  
the local fire department.  
EXPLOSION HAZARDS  
• Wire gauge sizes of electrical wiring, cables and cord sets must  
be adequate to handle the maximum electrical current (ampac-  
ity) to which they will be subjected.  
• Before installing or servicing this (and related) equipment, make  
sure that all power voltage supplies are positively turned off at  
their source. Failure to do so will result in hazardous and pos-  
sibly fatal electrical shock.  
• Properly ventilate any room or building housing the generator to  
prevent build-up of explosive gas.  
• Do not smoke around the generator. Wipe up any fuel or oil  
spills immediately. Ensure that no combustible materials are left  
in the generator compartment, or on or near the generator, as  
FIRE or EXPLOSION may result. Keep the area surrounding the  
generator clean and free from debris.  
• Connecting this unit to an electrical system normally supplied  
by an electric utility shall be by means of a transfer switch so as  
to isolate the generator electric system from the electric utility  
distribution system when the generator is operating. Failure to  
isolate the two electric system power sources from each other  
by such means will result in damage to the generator and may  
also result in injury or death to utility power workers due to  
backfeed of electrical energy.  
• These generators may operate using one of several types  
of fuels. All fuel types are potentially FLAMMABLE and/or  
EXPLOSIVE and should be handled with care. Comply with all  
laws regulating the storage and handling of fuels. Inspect the  
unit’s fuel system frequently and correct any leaks immediately.  
Fuel supply lines must be properly installed, purged and leak  
tested according to applicable fuel-gas codes before placing  
this equipment into service.  
• Stationary emergency generators installed with an automatic  
transfer switch will crank and start automatically when normal  
(utility) source voltage is removed or is below an acceptable  
preset level. To prevent such automatic start-up and possible  
injury to personnel, disable the generator’s automatic start cir-  
cuit (battery cables, etc.) before working on or around the unit.  
Then, place a “Do Not Operate” tag on the generator control  
panel and on the transfer switch.  
• Diesel fuels are highly FLAMMABLE. Gaseous fluids such  
as natural gas and liquid propane (LP) gas are extremely  
EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier  
than air; install leak detectors accordingly.  
• In case of accident caused by electric shock, immediately  
shut down the source of electrical power. If this is not pos-  
sible, attempt to free the victim from the live conductor. AVOID  
DIRECT CONTACT WITH THE VICTIM. Use a nonconducting  
implement, such as a dry rope or board, to free the victim from  
the live conductor. If the victim is unconscious, apply first aid  
and get immediate medical help.  
• Never wear jewelry when working on this equipment. Jewelry  
can conduct electricity resulting in electric shock, or may get  
caught in moving components causing injury.  
CALIFORNIA PROPOSITION 65 WARNING  
Engine exhaust and some of its constituents are known  
to the State of California to cause cancer, birth defects  
and other reproductive harm.  
CALIFORNIA PROPOSITION 65 WARNING  
This product contains or emits chemicals known to the  
State of California to cause cancer, birth defects and  
other reproductive harm.  
. F v e 0 5 / 1 0  
S a f e t y 0 0 4 R  
1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
NOTE:  
IDENTIFICATION RECORD  
For actual information related to this particular model, please  
refer to the Manual Drawing Listing located at the end of this  
manual, or to the data label affixed to the unit.  
DATA LABEL  
Every generator set has a DATA LABEL that contains important  
information pertinent to the generator. The data label, which can be  
found attached to the generator’s lower connection box, lists the  
unit’s serial number and its rated voltage, amps, wattage capacity,  
phase, frequency, rpm, power factor, production date, etc.  
Stationary Emergency Generator Model and Serial  
Number  
This number is the key to numerous engineering and manufactur-  
ing details pertaining to your unit. Always supply this number  
when requesting service, ordering parts or seeking information.  
Data Label  
. D v e 0 5 / 1 0  
I d e n t y 0 0 5 R  
2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Equipment Description  
EQUIPMENT DESCRIPTION  
COOLANT RECOMMENDATIONS  
Use a mixture of half low silicate ethylene glycol base anti-freeze  
and deionized water. Cooling system capacity is listed in the  
specifications. Use only deionized water and only low silicate  
anti-freeze. If desired, add a high quality rust inhibitor to the rec-  
ommended coolant mixture. When adding coolant, always add the  
recommended 50-50 mixture.  
This equipment is a revolving field, alternating current Stationary  
Emergency Generator. It is powered by a gaseous fueled engine  
operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for  
2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear  
units. See the Specifications section for exact numbers. The unit  
comes complete with a sound attenuated enclosure, internally  
mounted muffler, control console, mainline circuit breaker, bat-  
tery charger, and protective alarms as explained in the following  
paragraph.  
Do not use any chromate base rust inhibitor  
with ethylene glycol base anti-freeze or chro-  
All AC connections, including the power leads from the alterna-  
tor, 120 volt battery charger input and control connections to the  
transfer switch are available in the main connection box.  
mium hydroxide (“green slime”) forms and will  
cause overheating. Engines that have been  
operated with a chromate base rust inhibitor  
must be chemically cleaned before adding eth-  
ylene glycol base anti-freeze. Using any high  
silicate anti-freeze boosters or additives will  
also cause overheating. The manufacturer also  
recommends that any soluble oil inhibitor is  
NOT used for this equipment.  
The Stationary Emergency Generator incorporates the following  
alternator features:  
• Rotor and Stator insulation is Class F rated as defined by NEMA  
MG1-32.6, NEMA MG1-1.66. The generator is self ventilated  
and drip-proof constructed.  
• The voltage waveform deviation, total harmonic content of the  
AC waveform and telephone influence factor have been evalu-  
ated and are acceptable according to NEMA MG1-32.  
Do not remove the radiator pressure cap while  
the engine is hot or serious burns from boiling  
liquid or steam could result.  
ENGINE OIL RECOMMENDATIONS  
The unit has been filled with 5W-20 engine oil at the factory. Use  
a high-quality detergent oil classified “For Service SJ or SH.”  
Detergent oils keep the engine cleaner and reduce carbon deposits.  
When changing the engine oil, be sure to use 5W-30 engine oil  
(synthetic oil is recommended).  
Ethylene glycol base antifreeze is poisonous.  
Do not use mouth to siphon coolant from the  
radiator, recovery bottle or any container. Wash  
hands thoroughly after handling. Never store  
used antifreeze in an open container because  
animals are attracted to the smell and taste of  
antifreeze even though it is poisonous to them.  
Any attempt to crank or start the engine before  
it has been properly serviced with the recom-  
mended oil may result in an engine failure.  
NOTE:  
For temperatures below 32° F, it is strongly recommended to  
use the optional Cold Weather Start Kit. The oil grade for tem-  
peratures below 32° F is 5W-30 synthetic oil.  
. D v 0 7 / 1 1  
E q u i p 0 0 7 R e  
3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Engine Protective Devices  
OVERCRANK SHUTDOWN  
ENGINE PROTECTIVE DEVICES  
The Stationary Emergency Generator may be required to operate  
for long periods of time without an operator on hand to monitor  
such engine conditions as coolant temperature, oil pressure or  
rpm. For that reason, the engine has several devices designed to  
protect it against potentially damaging conditions by automatically  
shutting down the unit when the oil pressure is too low, the coolant  
temperature is too high, the coolant level is too low, or the engine  
is running too fast.  
After a prespecified duration of cranking, this function ends the  
cranking if the engine has failed to start. The overcrank message  
will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn  
switch back to AUTO to reset the generator control board.  
NOTE:  
If the fault is not corrected, the overcrank feature will continue  
to activate.  
NOTE:  
Approximate Crank Cycle Times  
• 15 seconds ON  
• 7 seconds OFF  
• 7 seconds ON  
Engine protective switches and sensors are mentioned here for  
the reader’s convenience. Also refer to the applicable control  
panel manual for additional automatic engine shutdown infor-  
mation.  
• 7 seconds OFF  
• Repeat for 45 seconds  
• Approximately 90 seconds total.  
HIGH COOLANT TEMPERATURE SENDER  
An analog coolant temperture sender, located in the engine's  
cooling system will cause an engine shutdown if the temperature  
should exceed approximately 125° C (257° F). The generator will  
automatically restart once the temperature has returned to a safe  
operating level.  
OVERSPEED SHUTDOWN  
A speed circuit controls engine cranking, start-up, operation and  
shutdown. Engine speed signals are delivered to the circuit board  
whenever the unit is running. Should the engine overspeed above  
a safe, preset value, the circuit board initiates an automatic engine  
shutdown. Contact the nearest Authorized Dealer if this failure  
occurs.  
LOW COOLANT LEVEL SENSOR  
To prevent overheating, the engine has a low coolant level sensor.  
If the level of engine coolant drops below the level of the low cool-  
ant level sensor, the engine automatically shuts down.  
RPM SENSOR LOSS SHUTDOWN  
If the speed signal to the control panel is lost, engine shutdown  
will occur.  
LOW OIL PRESSURE SWITCH  
This switch has normally closed contacts that are held open by  
engine oil pressure during cranking and operating. Should oil pres-  
sure drop below the 8 psi range, switch contacts close, and the  
engine shuts down. The unit should not be restarted until oil is  
added, and the AUTO/OFF/MANUAL switch must be turned to OFF  
and then back to AUTO.  
DC FUSES  
A fuse (7.5 amp) is located on the control panel. It protects the  
panel components from damaging overload. Always remove this  
fuse before commencing work on the generator. The unit will not  
start or crank if the fuse is blown.  
A fuse (25 amp) is located in the engine wire harness adjacent  
to the DC alternator. It is used to prevent circuit failure due to DC  
alternator falure. It will also protect the system in the event of a  
wiring short-dircuit. If this fuse is blown, the generator will not  
operate. Replace these fuses with the same size, type, and rating.  
. B v e 0 5 / 1 0 r o t 0 0 E 3 n g R P  
4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fuel System  
NATURAL GAS FUEL SYSTEM  
FUEL SYSTEM  
Natural gas is supplied in its vapor state. In most cases, the gas  
distribution company provides piping from the main gas distribu-  
tion line to the standby generator site. The following information  
applies to natural gas fuel systems.  
FUEL REQUIREMENTS  
The Stationary Emergency Generator may be equipped with one of  
the following fuel systems:  
• Gas pressure in a building is usually regulated by national, state  
and local codes.  
To reduce gas pressure to a safe level before the gas enters a  
building, a primary regulator is needed. The natural gas supplier  
may or may not supply such a regulator.  
• It is the responsibility of the gas supplier to make sure sufficient  
gas pressure is available to operate the primary regulator.  
• Gas pressure at the inlet to the fuel shutoff solenoid must never  
exceed approximately 14 inches water column (0.5 psi).  
• Natural gas fuel system  
• Propane vapor (LPV) fuel system  
Recommended fuels should have a Btu content of at least 1,000  
Btu's per cubic foot for natural gas; or at least 2,520 Btu's per  
cubic foot for LP gas. Ask the fuel supplier for the Btu content of  
the fuel.  
NOTE:  
The fuel consumption requirements are identified in the  
Specifications section of the Owner's Manual. Refer to the  
Installation Manual if assistance is required for the sizing of  
the pipe diameter for the generator. Any piping used to connect  
the generator to the fuel supply should be of adequate size to  
achieve the 100% load fuel consumption requirements identi-  
fied in the Specifications section regardless of actual load.  
PROPANE VAPOR WITHDRAWAL FUEL SYSTEM  
This type of system utilizes the vapors formed above the liquid  
fuel in the supply tank. Approximately 10 to 20 percent of the tank  
capacity is needed for fuel expansion from the liquid to the vapor  
state. The vapor withdrawal system is generally best suited for  
smaller engines that require less fuel. The installer should be aware  
of the following:  
NOTE:  
TherecommendedfuelpressureisidentifiedintheSpecifications  
section this manual.  
• When ambient temperatures are low and engine fuel consump-  
tion is high, the vapor withdrawal system may not function  
efficiently.  
• Ambient temperatures around the supply tank must be high  
enough to sustain adequate vaporization, or the system will not  
deliver the needed fuel volume.  
NOTE:  
It is the responsibility of the installer to make sure that only  
the correct recommended fuel is supplied to the generator fuel  
system. Thereafter, the owner/operator must make certain that  
only the proper fuel is supplied.  
• In addition to the cooling effects of ambient air, the vaporization  
process itself provides an additional cooling effect.  
. F e v 0 4 / 1 1  
u F e l S y s 0 0 1 R  
5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Engine Lubrication System  
SPECIFICATIONS  
Type of Oil Pump ...............................................................Gear  
Oil Filter .......................................................Full Flow, Cartridge  
Crankcase Oil Capacity ............................................ 4 U.S. qts.  
STANDBY EMERGENCY GENERATOR  
Type......................................................................Synchronous  
Rotor Insulation.............................................................Class H  
Stator Insulation............................................................Class H  
Alternator Output Leads 3-phase.....................................4-wire  
Bearings ..................................................................Sealed Ball  
Coupling ................................................................Flexible Disc  
Load Capacity (Standby Rating)...............................25/30 kW*  
COOLING SYSTEM  
Type............................................................................... Closed  
Water Pump............................................................. Belt Driven  
Fan Speed.........................................................................2484  
Fan Diameter...........................................................17.7 inches  
Fan Mode....................................................................... Pusher  
Air Flow (inlet air including alternator and  
* NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE  
J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate  
with natural gas.  
3
combustion air) ..................................................1800 ft /min.  
Excitation System ............................................................Direct  
Generator Output Voltage/kW - 60 Hz  
kW  
120/240V, 1-phase, 1.0 pf 25/30  
120/208V, 3-phase, 0.8 pf 25/30  
120/240V, 3-phase, 0.8 pf 25/30  
Coolant Capacity....................................................2.0 U.S. gal.  
Heat Rejection to Coolant (25/35kW) ....112,000/135,000 Btu/h  
Maximum Operating Air Temp. on Radiator......... 60° C (150° F)  
Maximum Ambient Temperature......................... 50° C (140° F)  
Amp  
104/125  
87/104  
75/90  
CB Size  
125/150  
100/125  
90/100  
FUEL SYSTEM  
Generator Locked Rotor KVA Available @ Voltage Dip of 35%  
Type of Fuel ....................................Natural Gas, Propane Vapor  
Carburetor............................................................... Down Draft  
Secondary Fuel Regulator............................................ Standard  
Fuel Shut-off Solenoid................................................. Standard  
Operating Fuel Pressure .................5 in. - 14 in. Water Column  
25kW  
35 KVA  
30kW  
45 KVA  
ENGINE  
Make ........................................................................... Generac  
Model .............................................................................In Line  
Cylinders and Arrangement .....................................................4  
Displacement...............................................................1.6 Liter  
Bore..............................................................................3.15 in.  
Stroke...........................................................................3.13 in.  
Compression Ratio....................................................... 9.5-to-1  
Air Intake System......................................... Naturally Aspirated  
Valve Seats............................................................ Replaceable  
Lifter Type.................................................................. Hydraulic  
Spark Plug Gap........................................0.76mm (0.030 inch)  
Fuel Consumption - ft3/hr (Natural Gas/LPV)  
Exercise  
Cycle  
25%  
Load  
50%  
Load  
75%  
Load  
100%  
Load  
25kW  
30kW  
60/24  
60/24  
120/48 220/87 310/123 390/155  
145/58 260/103 370/147 470/187  
ELECTRICAL SYSTEM  
Battery Charge Alternator......................................12V, 15 Amp  
Static Battery Charger ....................................... 2.0 or 2.5 Amp  
Recommended Battery.................................Group 26, 525CCA  
System Voltage............................................................ 12 Volts  
Engine Parameters  
Rated Synchronous RPM .......................................60 Hz, 3600  
Voltage Regulator  
Type...........................................................................Electronic  
Sensing ................................................................Single-phase  
Regulation........................................................................± 1%  
Features.........................Adjustable Voltage and Automatic Gain  
Exhaust System  
Exhaust Flow at Rated Output 60 Hz: 25kW  
240 cfm  
30kW  
260 cfm  
1025°F  
Exhaust Temp. at Rated Output:  
975°F  
Power Adjustment for Ambient Conditions  
Temperature Deration:  
3% for every 10° C above °C  
Combustion Air Requirements (Natural Gas)  
25kW 30kW  
Flow at rated power, 60 Hz:  
25kW  
90 cfm  
30kW  
95 cfm  
40  
104  
25  
77  
1.65% for every 10° above °F  
Altitude Deration:  
1% for every 100 m above m  
Governor  
Type...........................................................................Electronic  
Frequency Regulation.............................................Isochronous  
Steady State Regulation ................................................± .25%  
Adjustments:  
25kW 30kW  
915  
2000  
182  
600  
3% for every 1000 ft. above ft.  
Controller ................................................................. Nexus  
Speed..................................................................... Selectable  
. C v e 1 2 / 1 1  
G e n S p e c 0 8 2  
6-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
9. Install the previously removed black pipe onto the outlet  
WEATHER AND MAINTENANCE KITS  
To keep the generator running at its peak, the following kits are  
offered:  
port of the demand regulator. Use pipe sealant on the pipe  
threads.  
10. Reverse steps 1-4 in this procedure to reactivate the demand  
• Cold Weather Kit  
regulator.  
~ Recommended for climates with temperatures below 32° F.  
• Extreme Cold Weather Kit  
11. Follow the instructions in the Control Panel section.  
~ Recommended Block Heater Kit for protection in tempera-  
tures below 32° F.  
• Scheduled Maintenance Kit  
~ Kit includes the recommended parts to maintain the genera-  
tor. Refer to the Service Schedule for regular maintenance  
intervals.  
Serious injury, including death, or damage  
will occur if not configured properly. Please  
consult an Authorized Dealer with any ques-  
tions.  
For additional information, or to order any of these kits, please  
contact an Authorized Service Dealer or Customer Service  
Representative.  
Figure 6.1 — Reconfigure the Fuel System  
RECONFIGURING THE FUEL  
SYSTEM  
NOTE:  
All models are configured to run on natural gas from the fac-  
tory.  
Before the generator can be operated using a LP fuel source, the  
fuel system and control panel (refer to the installation drawing for  
location) must be reconfigured. The steps to reconfigure the gen-  
erator from a natural gas (NG) to a liquidified petroleum (LP) fuel  
source are as follows:  
FUEL SYSTEM  
1. Turn the main gas supply off and disconnect the battery.  
2. Remove the carburetor fuel hose from the outlet port of the  
demand regulator (see Figure 6.1).  
3. Disconnect the power wires from the fuel solenoid located  
on top of the regulator assembly by removing the screw on  
the front of the connector and pulling the connector forward,  
away from the solenoid body.  
CONTROL PANEL  
The FUEL TYPE must be reconfigured in the control panel to final-  
ize the conversion process. This generator is configured at the  
factory to operate on natural gas. If conversion to LP is required,  
please complete the mechanical conversion process and then call  
888-9ACTIVATE for the control panel password. This fuel selection  
conversion is required to be password protected by Environmental  
Protection Agency [EPA] regulations.  
4. Loosen the spring clamp on the small fuel enrichment line and  
remove the hose from the hose barb.  
5. Remove the black pipe assembly from the outlet port of the  
demand regulator. The solenoid assembly may need to be  
removed before performing this operation (Figure 6.1).  
6. Remove the NG fuel jet (loosen counter clockwise) from the  
outlet port.  
7. Remove the LP fuel jet (loosen counter clockwise) from the jet  
keeper port on the side of the regulator housing. Install this jet  
into the outlet port in the regulator casting.  
Whenever the Generator’s Fuel Regulator is  
converted from one Fuel type to the other,  
the Control Panel must be reconfigured for  
the correct fuel type. Failure to convert both  
the Regulator and Control Panel will result in  
decreased performance and an increase in  
emissions, and is a violation of EPA regula-  
tions.  
NOTE:  
The jet sizes are stamped on the individual jets. The larger jet  
size is used for running on NG.  
8. Install the previously removed NG jet into the jet keeper port  
on the side of the regulator housing.  
. C v e 1 2 / 1 1  
G e n S p e c 0 8 2 R  
6-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
ALTERNATOR AC LEAD  
ALTERNATOR POWER WINDING  
CONNECTIONS  
CONNECTIONS  
The electrical wires in the unit’s AC connection (lower) panel  
should be installed according to the number of leads and the  
voltage/phase required for the application. The voltage and phase  
are described on the generator data label. The number of lead  
wires can be identified using the Specifications section and the  
power output rating on the generator data label. For example, if  
the generator produces 130kW, 277/480 Volt, 3-phase power, the  
generator has 12 alternator output leads. Figure 7.3 describes the  
stator power winding connection for the generator.  
3-PHASE ALTERNATORS ("Y" CONFIGURATION)  
The Stationary Emergency Generator is designed to supply  
3-phase electrical loads. Electric power is produced in the alterna-  
tor power windings. These windings were connected at the factory  
to the main circuit breaker with a “Y” configuration as shown in  
Figures 7.2 through 7.6.  
The rated voltage between circuit breaker terminals E1-E2, E1-E3  
and E2-E3 is 480V, 208V or 600V depending on the model.  
The rated voltage between each circuit breaker terminal and the  
neutral point 00 is 277V, 120V, or 346V depending on the model.  
FOUR-LEAD, SINGLE-PHASE STATOR  
Four-lead alternators (see Figure 7.1) are designed to supply elec-  
trical loads with voltage code A” (240V, 1-phase, 60 Hz). Electrical  
power is produced in the stator power windings. These windings  
were connected at the factory to the main circuit breaker as shown  
in Figure 7.1.  
Figure 7.2 — Stator Power Winding  
Connections - 3-phase, 277/480V (6 Lead)  
E1  
The rated voltage between each circuit breaker terminal is 240V.  
The rated voltage between each circuit breaker terminal and the  
neutral point 00 is 120V.  
S1  
INTERNAL  
CONNECTIONS  
Figure 7.1 — Four-lead, Single-phase Stator  
L - L  
S4  
S6  
00 (NEUTRAL)  
S5  
S2  
S3  
E3  
E2  
L - N  
Figure 7.3 — Stator Power Winding  
Connections - 3-phase, 277/480V (12 Lead)  
E1  
S1  
S4  
S7  
L - L  
S12  
S10  
S9  
S8  
S11  
S6  
S5  
S2  
S3  
E3  
E2  
L - N  
. B v e 0 5 / 1 0  
A C C o n n 0 0 7 R  
7-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
Figure 7.4 — Stator Power Winding  
Connections - 3-phase, 120/208V (6 Lead)  
3-PHASE ALTERNATORS ("DELTA" CONFIGURATION)  
The Stationary Emergency Generator is designed to supply  
3-phase electrical loads. Electric power is produced in the alterna-  
tor power windings. These windings were connected at the factory  
to the main circuit breaker with a “Delta” configuration as shown  
in Figures 7.7 and 7.8.  
INTERNAL CONNECTIONS  
E1  
S1  
S1  
The rated voltage between circuit breaker terminals E1-E2, E1-E3  
and E2-E3 is 240V.  
The rated voltage between E1 or E3 and the neutral point 00 is  
120V.  
L-L  
S4  
S6  
S4  
00 (NEUTRAL)  
S5  
Figure 7.7 — Stator Power Winding  
Connections - 3-phase, 120/240V (6 Lead)  
S3  
S2  
S6 S5  
E2  
E3  
E2  
S3  
S2  
S6  
S2  
L-N  
INTERNAL  
CONNECTIONS  
Figure 7.5 — Stator Power Winding  
Connections - 3-phase, 120/208V (12 Lead)  
L - L  
E1  
S7  
S1  
S3  
S5  
E1  
E3  
S4  
S1  
L-L  
S10  
S12  
S4  
L - N  
S5  
00 (NEUTRAL)  
S9  
S2  
S6 S11  
Figure 7.8 — Stator Power Winding  
Connections - 3-phase, 120/240V (12 Lead)  
E3  
E2  
S3  
S8  
L-N  
E2  
S12  
S2  
Figure 7.6 — Stator Power Winding  
Connections - 3-phase, 346/600V (6 Lead)  
E1  
S5  
S9  
S1  
INTERNAL  
L - L  
CONNECTIONS  
S8  
S6  
L - L  
S3  
S11  
S4  
S6  
00 (NEUTRAL)  
E1  
E3  
S10  
S1  
S5  
L - N  
00 (NEUTRAL)  
S2  
E2  
S3  
E3  
L - N  
. B v e 0 5 / 1 0  
A C C o n n 0 0 7 R  
7-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
Upon power up, this controller will go through a system self test  
CONTROL PANEL INTERFACE  
which will check for the presence of utility voltage on the DC  
circuits. This is done to prevent damage if the installer mistakenly  
connects AC utility power sense wires into the DC terminal block.  
If utility voltage is detected, the controller will display a warning  
message and lock out the generator, preventing damage to the  
controller. Power to the controller must be removed to clear this  
warning.  
USING THE AUTO/OFF/MANUAL SWITCH  
With the switch set to AUTO, the engine may  
crank and start at any time without warning.  
Such automatic starting occurs when utility  
power source voltage drops below a preset  
level or during the normal exercise cycle. To  
prevent possible injury that might be caused  
by such sudden starts, always set the switch  
to OFF and remove the fuse before work-  
ing on or around the generator or transfer  
switch. Then, place a “DO NOT OPERATE”  
tag on the generator panel and on the trans-  
fer switch.  
Utility voltage must be turned on and present at the N1 and N2  
terminals inside the generator control panel for this test to be  
performed and pass.  
NOTE:  
DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT  
WIRES IS NOT WARRANTABLE!  
This test will be performed each time the controller is powered  
up.  
Next, the user must enter the minimum settings to operate. These  
settings are current date and time and exercise day and time. The  
maintenance intervals will be initialized (i.e. started) the first time  
the clock is set. If the clock is never set at power up, the mainte-  
nance intervals will be reset every time power is applied.  
1. AUTO” Position – Selecting this switch activates fully auto-  
matic system operation. It also allows the unit to automati-  
cally start and exercise the engine every seven days with the  
setting of the exercise timer (see the Setting the Exercise  
Timer section).  
2. “OFF” Position – This switch position shuts down the engine.  
If a subsequent power loss (loss of battery power) occurs the  
Installation assistant will operate upon power restoration. The self  
test routine will be run and then the customer will be required to  
re-enter the time and date, as this is not retained during a power  
loss. The unit will not require re-activation.  
This position also prevents automatic operation.  
3. “MANUAL Position – Set the switch to MANUAL to crank  
and start the engine. Transfer to standby power will not occur  
unless there is a utility failure.  
ACTIVATE THE GENERATOR  
When battery power is applied to the generator during the instal-  
lation process, the controller will turn ON and the LCD screen will  
illuminate. However, the generator still needs to be activated before  
it will automatically run in the event of a power outage.  
DISPLAY INTERFACE MENUS  
The LCD display is organized as detailed below:  
• The “Home” page, this page is the default page which will be  
displayed if no keys are pressed for 30 seconds. This page  
normally shows the current Status message and the current  
date and time. The highest priority active Alarm and/or Warning  
will be automatically posted on this page as well as flashing  
the backlight when such an event is detected. In the case of  
multiple Alarms or Warnings, only the first message will be  
displayed. To clear an Alarm or Warning, see the Protection  
Systems section - Clear Alarm.  
• The display backlight is normally off. If the user presses any  
key, the backlight will come on automatically and remain on for  
30 seconds after the last key was pressed.  
• The “Main Menu” page will allow the user to navigate to all other  
pages or sub-menus by using the Left/Right and Enter keys.  
This page can be accessed at any time with several presses of  
the dedicated Escape key. Each press of the Escape key takes  
you back to the previous menu until the main menu is reached.  
This page displays the following options: HISTORY; STATUS;  
EDIT; AND DEBUG. (See the Appendix - "Menu System".)  
Activating the generator is a simple one time process that is guided  
by the controller screen prompts. Once the product is activated,  
the controller screen will not prompt you again, even if you discon-  
nect the generator battery.  
To obtain the activation code, record the generator serial number  
and log onto www.activategen.com or call 1-888-9ACTIVATE and  
follow the steps to retrieve the activation code.  
After obtaining your activation code, please complete the following  
steps at the generator’s control panel in the Activation Chart on the  
following page.  
NOTE:  
The generator will only run in manual until the passcode has  
been entered.  
. E v e 1 2 / 1 1  
C n t r l N e x u s u s 0  
8-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
ACTIVATION CHART  
CHOOSE LANGUAGE  
TROUBLESHOOTING  
Display Reads:  
Use ARROW keys to scroll to desired lan-  
guage. Press ENTER to select.  
If the wrong language is chosen, it can be  
changed later using the “edit” menu.  
Language  
-
English  
+
Escape  
Enter  
Display Reads:  
Press ENTER to begin the activation pro-  
cess.  
If ESCAPE is pressed instead of ENTER,  
your generator will only run in manual mode  
(for test purposes) and NOT ACTIVATED will  
be displayed. You will need to remove the  
generator control panel fuse AND disconnect  
the T1, N1 and N2 connector in the external  
connection box (if equipped); or disconnect  
utility input (main breaker) to the transfer  
switch for 3-5 seconds and reconnect, then  
begin with Step 1.  
Activate me (ENT) or  
ESC to run in manual  
Escape  
Enter  
Display Reads:  
If you do not have your activation code,  
go to www.activategen.com or call  
1-888-9ACTIVATE (922-8482).  
To Activate go to  
www.activategen.com  
If you already have your activation code,  
wait 3-5 seconds for the next display.  
Escape  
Enter  
ENTER ACTIVATION CODE (Passcode)  
TROUBLESHOOTING  
Display Reads:  
Use ARROW keys to scroll and find the first  
number of your Activation Code.  
Serial 123456789  
Passcode XXXXX +/-  
Press ENTER to select.  
Repeat this step until all digits have been  
entered.  
Escape  
Enter  
Use ESCAPE to correct previous digits.  
Display Reads:  
Activation is complete when all digits are  
entered above and your screen shows this  
display.  
What happens if “Wrong Passcode Try  
Again” appears?  
“SELECT HOUR (0-23)”  
“-  
Re-enter the activation code. If a second  
attempt is unsuccessful, check the number  
against the code given on activategen.com.  
If it is correct and the generator will not  
accept it, contact 1-888-9ACTIVATE (922-  
8482).  
6
+”  
Follow the controller prompts to continue  
setting the time function. Refer to your  
Owner’s Manual with questions.  
Escape  
Enter  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1 R  
8-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
• If utility is still lost after the “line interrupt period”, run the engine  
INSTALLATION ASSISTANT  
Interconnect System Self Test Feature (follow the on-screen  
prompts).  
up to normal RPM and transfer the load. At this time the con-  
troller will exit the exercise routine and assume full automatic  
operation.  
Upon power up, this controller will go through a system self test  
which will check for the presence of utility voltage on the DC  
circuits. This is done to prevent damage if the installer mistakenly  
connects AC utility power sense wires into the DC terminal block.  
If utility voltage is detected, the controller will display a warning  
message and lock out the generator, preventing damage to the  
controller. Power to the controller must be removed to clear this  
warning.  
USER ADJUSTABLE SETTINGS  
Factory  
Default  
Minimum  
Setting  
Maximum  
Setting  
Setting  
Increment  
1 min  
Exercise  
time  
23:59  
(11:59 pm)  
2 pm  
Wed  
00:00 (12 am)  
Sun  
Exercise  
day  
Utility voltage must be turned on and present at the N1 and N2  
terminals inside the generator control panel for this test to be  
performed and pass.  
Sat  
1 day  
Current  
Time  
23:59  
(11:59 pm)  
12 am 00:00 (12 am)  
1 min  
NOTE:  
Current  
Day  
Sun  
Jan  
Sun  
Jan  
Sat  
Dec  
1 day  
DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT  
WIRES IS NOT WARRANTABLE!  
Current  
Month  
1 month  
1 year  
This test will be performed each time the controller is powered  
up.  
Current  
Year  
2008  
2008  
2100  
Upon first power up of the generator, the display interface will  
begin an installation assistant. The assistant will prompt the user  
to set the minimum settings to operate. These settings are simply:  
Current Date/Time and Exercise Day/Time. The maintenance inter-  
vals will be initialized when the exercise time is entered.  
Language  
Contrast  
English  
80%  
French  
0%  
Spanish  
100%  
N/A  
1%  
The exercise settings can be changed at any time via the "EDIT"  
menu (see Appendix, "Menu System").  
FUEL CONVERSION  
For fuel conversion steps, refer to the GenSpec section,  
RECONFIGURING THE FUEL SYSTEM.  
If the 12 volt battery is disconnected or the fuse removed, the  
Installation Assistant will operate upon power restoration. The  
only difference is the display will only prompt the customer for the  
current Time and Date.  
OPERATION  
IF THE INSTALLER TESTS THE GENERATOR PRIOR TO  
INSTALLATION, PRESS THE “ENTER” KEY TO AVOID SETTING  
UP THE EXERCISE TIME. THIS WILL ENSURE THAT WHEN  
THE CUSTOMER POWERS UP THE UNIT, HE WILL STILL BE  
PROMPTED TO ENTER AN EXERCISE TIME.  
This system is intended to supply standby power in the event of a  
utility failure. The control system will monitor the utility voltage to  
determine if stand-by power is required. Should the utility voltage  
fail, the generator will start and run normally, detaching from the  
utility and supplying the customer load from the generator. When  
utility power returns, the controller will re-transfer the customer  
load back to utility and shut down the generator.  
SETTING THE EXERCISE TIMER  
This generator is equipped with an exercise timer. Once it is set,  
the generator will start and exercise every seven days, on the day  
of the week and at the time of day specified. During this exercise  
period, the unit runs for approximately 12 minutes and then shuts  
down. Transfer of loads to the generator output does not occur  
during the exercise cycle unless utility power is lost.  
AUTOMATIC TRANSFER OPERATION  
To select automatic operation, do the following:  
1. Make sure the transfer switch main contacts are set to their  
UTILITY position, i.e., loads connected to the utility power  
source.  
2. Be sure that normal UTILITY power source voltage is avail-  
able to transfer switch terminal lugs N1 and N2 (Refer to the  
Electrical Data section).  
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO.  
4. Set the generator’s main circuit breaker to its ON (or CLOSED)  
position.  
With the preceding steps complete, the generator will start auto-  
matically when utility source voltage drops below a preset level.  
After the unit starts, loads are transferred to the standby power  
source. Refer to the Sequence of Automatic Operation section.  
LOW SPEED EXERCISE  
The standard start sequence will be initiated.  
• All 1800 rpm units will exercise at 1400 RPM  
• All 3600 rpm units will exercise at 1800 RPM  
If utility is lost during exercise the controller will do the following:  
• Wait for the “line interrupt period” for utility to return. If utility  
returns within the “line interrupt period”, continue to exercise  
at low RPM.  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1  
8-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
SEQUENCE OF AUTOMATIC OPERATION  
Initial Conditions: Generator in Auto ready to run, load being sup-  
plied by the Utility Source through the transfer switch.  
MANUAL START  
Allows the user to start and run the generator manually.  
Transfer of the load to the generator will occur if utility is lost while  
the unit is running in the manual mode (only if activated).  
1. When the utility voltage fails (falls below 60% of nominal), a  
10-30 second (programmable) “line interrupt” delay timer is  
started. The factory set time delay is 10 seconds. If at the  
end of the line interrupt time the utility voltage is above 60%  
the engine will not crank. If the utility voltage is still below  
the 60% of nominal at the end of the line interrupt time, the  
unit will crank and start. If the unit cranks for more than 10  
seconds and the utility voltage rises above 80% of nominal  
(programmed pickup voltage) and the unit has not started, the  
crank cycle will abort.  
2. As soon as the unit starts a 5 second “warm-up” timer is initi-  
ated. When the warm-up timer expires the control will transfer  
the load to the generator (through the RTS switch) if the utility  
voltage is less than 80% of nominal. If the utility voltage is  
greater than the 80% of nominal at the end of the warm-up  
time the load will not be transferred to the generator and a one  
minute low-speed cool down period will start. At the end of  
the one minute cool down period the generator will stop.  
3. Once the unit is running and the switch has transferred the  
load to the generator the unit will monitor utility voltage.  
When utility voltage returns (above the programmable pickup  
voltage, normally 80% of nominal), a 15 second “Return to  
Utility” timer will start. At the end of the return to utility time,  
if the utility voltage is still above the pickup voltage, the unit  
will transfer the load back to the utility source and run the unit  
through a one minute cool down period. When the cool down  
period is over the unit will shut down and be ready for the next  
outage.  
ALARM AND WARNING MESSAGES  
Alarms are defined as “Latching” which means they must be  
cleared before the alarm message on the screen will clear. They  
can be of type “Shutdown” or not and are logged in the alarm log.  
Alarms are all annunciated on the display).  
Warnings are “Non Latching” meaning the message automati-  
cally clears when the warning condition goes away. Warnings can  
not be of type “Shutdown” but they are logged in the alarm log.  
Warnings are all annunciated on the display.  
LOW OIL PRESSURE SHUTDOWN ALARM  
There is a 10 second delay before oil pressure is monitored.  
HIGH COOLANT TEMPERATURE SHUTDOWN ALARM  
There is a 10 second delay before engine temperature is moni-  
tored.  
Once running there is a 1/4 second delay before shut down. The  
limit is set at 125° C or 257° F.  
OVERCRANK SHUTDOWN ALARM  
Occurs if the engine has not started within the specified crank  
cycle.  
4. If during the cool down period utility voltage should fall below  
60% of nominal the 5 second warm-up timer is initiated and  
the unit will transfer the load back to the generator and con-  
tinue to monitor the utility.  
OVERSPEED SHUTDOWN ALARM  
Warning indicator is measured and calculated by the microproces-  
sor. Overspeed is defined as +20% of nominal engine speed for 3  
seconds, or +25% immediate.  
CRANK CYCLES AND OVERCRANK SHUTDOWN  
If the unit fails to start during a cranking period it will display the  
Overcrank Shutdown Alarm. The system will control the cranking  
cycles as follows:  
Nominal engine speed = 60.0 Hz  
RPM SENSOR FAILURE SHUTDOWN ALARM  
During cranking: If the board does not see a valid RPM signal  
within four (4) seconds of cranking it will shut down and lock out  
on RPM sensor loss.  
The first crank cycle is a 16 second crank time followed by a 7  
second rest. The next 5 cycles will be 7 seconds of cranking time  
each followed by a 7 second rest time.  
If the unit fails to start by the end of the 6 crank/rest cycles  
the Overcrank Shutdown Alarm will display and the unit will not  
attempt to crank until the alarm is reset.  
During running: If the RPM signal is lost for one full second the  
board will shut the engine down, wait 15 seconds, then re-crank  
the engine if in AUTO, it will not re-crank in MANUAL.  
If no RPM signal is detected within the first four (4) seconds of  
cranking, the control board will shut the engine down and latch out  
on RPM sensor loss.  
AUTO START  
This unit is designed to automatically start in the event of a util-  
ity failure or brown out condition. Brown out is defined as utility  
voltage less than 60% nominal, while utility is considered good  
when it is restored to at least the pickup value, 80% of nominal.  
These levels are fixed. The “Line Interrupt period” is an adjustable  
parameter by the dealer. If 2-wire start mode is activated, the unit  
will start when 2-wire start is active.  
If the RPM signal is detected the engine will start and run normally.  
If the RPM signal is subsequently lost the control board will try  
two more re-cranks before latching out and flashing the RPM  
Sensor Failure message (if it is in AUTO).  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1 R  
8-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
Figure 1 – Generator Control Panel  
CHECK ENGINE MESSAGE  
MISSING CAM PULSE ALARM  
The control system has detected an emissions related fault. This  
fault cannot be cleared using the control panel interface. The unit  
will continue to operate in automatic mode. Contact your local  
servicing dealer.  
This is a shutdown alarm. The alarm will activate after five (5)  
seconds of continuously missing cam pulses.  
MISSING CRANK PULSE ALARM  
This is a shutdown alarm. The alarm will activate after 12 con-  
secutive revs where crank pulses are missing.  
UNDER-FREQUENCY SHUTDOWN ALARM  
After starting, if the generator stays under frequency for more than  
30 seconds, it will shutdown.  
LOW FUEL PRESSURE WARNING  
Fuel pressure is monitored by a digital sensor with a fixed setpoint  
of below five (5) inches water column.  
LOW BATTERY ALARM  
While running, if the average battery voltage falls below 11.9 volts  
for one (1) minute, the low battery alarm will be displayed.  
GOVERNOR SENSOR FAULT ALARM  
The governor position is monitored by an analog feedback signal. If  
the throttle position is seen outside of the normal operating range,  
a shutdown alarm is displayed. If the throttle is commanded to  
move, and no movement is seen, a shutdown alarm is displayed.  
LOW BATTERY WARNING  
The microprocessor will continually monitor the battery voltage  
and display the Low Battery Voltage message if the battery voltage  
falls below 12.2 Volts for one (1) minute.  
WIRING ERROR ALARM  
No other action is taken on a low battery warning condition. The  
warning will automatically clear if the battery voltage rises above  
12.2 volts.  
When power is first apllied to the contoller, the software will per-  
form a check on the wiring of the transfer output, and ensure it  
does not have high voltage on the wire. If this is the case, it will  
signal a miswire alarm and will not run. The test can be skipped  
by use of the escape key.  
NOTE:  
The battery sentinel is a separate feature that monitors battery  
condition.  
UNDERVOLTAGE ALARM  
If the generator voltage falls below 60% for >5 seconds, an alarm  
will be issued.  
LOW COOLANT LEVEL ALARM  
This is a shutdown alarm. The sensor will be continuously moni-  
tored. If an error condition is seen for five (5) consecutive sec-  
onds, the alarm will be displayed.  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1  
8-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
OVERVOLTAGE ALARM  
ALARM CANCEL  
If the generator voltage rises above 110% for >3 seconds, an  
alarm will be issued.  
When the generator is shut down due to a latching alarm, the Auto  
/Off/ Manual switch must be set to the off position and the ENTER  
key pressed to unlatch any active fault and clear the corresponding  
fault alarm message.  
If the generator voltage rises above 130% for >0.2 seconds, an  
alarm will be issued.  
INTERNAL FAILURE SHUTDOWN ALARM  
Any internal failure that can be detected such as corrupted  
firmware will cause this shutdown alarm. This alarm cannot be  
cleared.  
COMMON ALARM RELAY  
The common alarm relay will be activated if there is a shutdown  
alarm. It will not activate on warnings or indicate that the Auto/Off/  
Manual switch is in the OFF position. The OFF position will clear  
the alarms and the relay. The relay will not be used to indicate a  
generator is not activated.  
CANBUS ALARM  
The common alarm connections are wired to a set of potential-  
free (dry) contacts on the Nexus controller board. These Normally  
Open (N.O.) contacts close when an alarm condition occurs and  
are used to activate a remote signaling device. The circuit is rated  
for a maximum of 130mA at 24 VDC. The connections are a short  
set of free hanging wires that exit the engine harness loom directly  
behind the Nexus Control Panel and are labeled numbers 209 and  
210.  
Where applicable, if the Canbus communications link fails to com-  
municate, a “Canbus Alarm” will be generated. This only applies  
to systems with external ignition modules. The alarm may be  
generated if:  
1. The physical link is broken.  
2. The Ignition Module fails or resets.  
3. The Nexus Controller fails or resets.  
4. Having the Battery Chargers 120 VAC connected without a  
battery installed.  
MAINTENANCE ALERTS  
Maintenance alerts will be provided for these conditions.  
5. A blown 10 amp Ignition Module fuse (approximately 12  
inches away from the starter).  
6. A blown 25 amp system fuse (located approximately 12  
inches away from the DC alternator).  
NOTE:  
SERVICE SCHEDULE A’  
Inspect Accessory Drive Alert  
Coolant Change & Flush  
1yr / 100hrs*  
1yr / 100hrs  
1yr / 100hrs  
1yr / 100hrs*  
1yr / 100hrs  
1yr / 100hrs  
6mo / 50hrs*  
The “Canbus Alarm” will not clear on its own. To clear the  
alarm, press the “enter” key to acknowledge the alarm. The  
alarm will clear and if the fault is still present, the alarm will  
reoccur.  
Inspect Spark Plugs Alert  
Change Oil & Filter Alert  
IGNITION ALARM  
When an ignition alarm occurs, a generic message “Ignition Fault”  
will be displayed as the fault code.  
Inspect Battery Alert  
Change / Inspect Air Filter Alert  
Clean/Inspect Air Inlet & Exhaust  
* Items require a 3 month / 30 hour break-in change or check.  
MAINTENANCE WARNING  
When a maintenance period expires, a warning message will be  
posted. The warning can be reset by hitting the Enter key. Resetting  
will clear the warning and reset the maintenance counters for the  
condition annunciated. The history log will reflect the maintenance  
warning.  
SERVICE SCHEDULE ‘B’  
Change / Inspect spark plugs alert  
2yr/ 250hr  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1 R  
8-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1  
8-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
STATIONARY EMERGENCY  
GENERATOR CONTROL AND  
OPERATION  
Do not crank the engine continuously for lon-  
ger than 30 seconds, or the heat may  
damage the starter motor.  
n
Refer to the appropriate control panel operator’s manual for this  
unit.  
• Let engine stabilize and warm up.  
• Check all applicable instrument and gauge readings. When  
certain that all readings are correct, move the transfer switch  
manual handle to the STANDBY (or EMERGENCY STANDBY)  
position, i.e., load circuits supplied by the generator.  
• Set the generator’s main line circuit breaker to its ON (or  
CLOSED) position.  
OPERATING UNIT WITH MANUAL  
TRANSFER SWITCH  
If the Stationary Emergency Generator was installed in conjunction  
with a transfer switch capable of manual operation only, the fol-  
lowing procedure applies. A manually operated transfer switch is  
one that will not provide automatic start-up and does not include  
an intelligence circuit.  
• Load circuits are now powered by the generator.  
RETRANSFER AND SHUTDOWN  
For additional information, refer to the applicable control panel  
manual for this unit, as well as any literature pertaining to the  
specific transfer switch.  
ENGINE START-UP AND TRANSFER  
For additional information, refer to the applicable control panel  
manual for this unit, as well as any literature pertaining to the  
specific transfer switch.  
To transfer the load back to the utility power source and shut down  
the generator, follow these directions:  
• Set the generator’s main line circuit breaker to its OFF (or OPEN)  
position.  
• Manually move the transfer switch handle to its UTILITY  
(NORMAL) position, i.e., load circuits connected to the utility.  
• Turn ON the utility power supply to the transfer switch, using  
the means provided (such as the utility power source main line  
circuit breaker).  
• Let the generator run at no-load for a few minutes to stabilize  
internal temperatures.  
• Shut down the generator.  
nThe Maintenance Disconnect Switch and the  
AUTO/OFF/MANUAL switches (if so equipped)  
must be set properly, or the generator will  
crank and start as soon as the utility power to  
the transfer switch is turned off. Refer to appli-  
cable control panel and transfer switch manuals  
for more information.  
nDo not proceed until certain that utility source  
voltage is available to the transfer switch and  
OPERATING UNIT WITH AUTOMATIC  
the transfer switch main contacts are set to  
UTILITY.  
TRANSFER SWITCH  
Do not attempt manual operation until all  
power supplies to the transfer switch have been  
If the Stationary Emergency Generator has been installed with an  
automatic transfer switch, the engine may be started and stopped  
automatically or manually.  
positively turned off, or extremely dangerous -  
possibly lethal - electrical shock will result.  
NOTE:  
Transfer switch enclosure doors should be kept  
closed and locked. Only authorized personnel  
Refer to the applicable manual for your transfer switch and to  
“Transfer Switch Start Signal Connections”. In addition, please  
note the dangers under “Engine Start-up and Transfer.”  
should be allowed access to the transfer switch  
interior. Extremely high and dangerous voltages  
are present in the transfer switch.  
In order to transfer load from the utility source to the generator,  
follow these directions:  
• Turn OFF or disconnect the utility power circuit to the transfer  
switch, using the means provided (such as the utility source  
main line circuit breaker).  
• Set the transfer handle to its UTILITY (NORMAL) position with  
load circuits connected to the utility power supply.  
• Set the generator’s main line circuit breaker to its OFF (or OPEN)  
position.  
• Start the generator.  
. D v e 0 5 / 1 0  
O p e r 0 0 1 R  
9-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Refer to the Service Schedule for engine oil and filter change fre-  
quencies.  
GENERAL MAINTENANCE  
Drain the oil while the engine is still warm from running. This  
means warm up the engine, shut it down and drain immediately  
as follows:  
Before working on the Stationary Emergency  
Generator, ensure the following:  
• The AUTO/OFF/MANUAL switch is in the OFF position.  
• The control panel fuse has been removed from the control  
box.  
1. Remove the drain hose from its retaining clip or cut the zip-tie  
securing the oil drain hose.  
2. Loosen and remove OIL DRAIN HOSE CAP. Drain oil com-  
• The 120VAC supply to the battery charger is switched OFF.  
• The negative battery cable has been removed.  
pletely into suitable container.  
3. When all oil has drained, install and tighten OIL DRAIN HOSE  
CAP and secure drain hose with a new zip-tie, or place the  
hose in its retaining clip.  
CHECK ENGINE OIL  
Check engine crankcase oil level (Figure 10.1) according to the  
Service Schedule and SIB10-10-L24G.  
4. Turn OIL FILTER (Figure 10.1) counterclockwise and remove.  
Properly dispose of old filter.  
5. Apply light coating of new engine oil to seal of new oil fil-  
ter. Install FILTER and tighten by hand only. DO NOT OVER  
TIGHTEN.  
• Remove oil dipstick and wipe dry with a clean, lint-free cloth.  
• Install oil dipstick, then remove again.  
• Oil should be between FULL and ADD marks.  
• If oil level is below the dipstick ADD mark, remove oil fill cap-.  
Add the recommended oil to bring oil level up to the FULL  
mark. DO NOT FILL ABOVE THE “FULLMARK. See “Engine Oil  
Recommendations” for recommended oils.  
6. Remove OIL FILL CAP and add recommended oil. Crankcase  
oil capacity is listed in the "Specifications" section.  
After refilling the crankcase with oil, always  
check oil level on dipstick. NEVER OPERATE  
ENGINE WITH OIL BELOW THE DIPSTICK “ADD”  
MARK.  
n
Figure 10.1 - Oil Dipstick and Oil Fill Cap  
OIL FILL CAP  
7. Start engine and check for oil leaks.  
8. Shut OFF engine and wait 10 minutes for the oil to settle down  
into the oil pan. Recheck oil level on dipstick. DO NOT fill  
above the dipstick "FULL" mark.  
9. Dispose of used oil at a proper collection center.  
COOLING INTAKE/OUTLET  
Air intake and outlet openings in the generator compartment must  
be open and unobstructed for continued proper operation. This  
includes such obstructions as high grass, weeds, brush, leaves  
and snow.  
OIL  
Without sufficient cooling and ventilating air flow, the engine/gen-  
erator quickly overheats, which causes it to shut down. (See the  
installation diagram.)  
DIPSTICK  
The exhaust system parts from this product get  
extremely hot and remains hot after shutdown.  
High grass, weeds, brush, leaves, etc. must  
remain clear of the exhaust. Such materials may  
ignite and burn from the heat of the exhaust  
system.  
OIL  
FILTER  
CHANGING ENGINE OIL  
INSPECT COOLING SYSTEM  
• Inspect engine cooling system. See the Service Schedule.  
• Check hoses for damage, deterioration, leaks, etc. Correct any  
discrepancies found.  
Hot oil may cause burns. Allow engine to cool  
before draining oil. Avoid prolonged or repeat-  
n
ed skin exposure with used oil. Thoroughly  
wash exposed areas with soap.  
• Check hose clamps for tightness.  
. A v e 0 5 / 1 0  
M a i n t 0 2 7 R  
10-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
ENGINE COOLANT  
CHECK FAN BELT  
Checkcoolantlevelincoolantrecoverybottle.See theSpecifications  
and Service Schedule sections.  
• Inspect fan belts every year. Replace any damaged, deterio-  
rated, worn or otherwise defective belt.  
• Check fan belt tension. Thumb pressure, exerted midway  
between pulleys, should deflect about 3/8 to 5/8 of an inch.  
Adjust belt tension as required.  
• Add recommended coolant mixture as necessary.  
• Periodically remove radiator pressure cap (only when engine  
has cooled down) to make sure the coolant recovery system  
is functioning properly. Coolant should be at bottom of radia-  
tor filler neck. If coolant level is low, inspect gasket in radiator  
pressure cap. Replace cap, if necessary. To have pressure cap  
tested, contact a Service Facility. Inspect cooling system and  
coolant recovery system for leaks.  
• Check fan belt alignment (see Figure 10.2).  
Figure 10.2 – Fan Belt  
COOLANT CHANGE  
Every year, have a service facility drain, flush and refill the cooling  
system. See the Specifications and Service Schedule for cooling  
system recommendations.  
OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL  
SYSTEM  
Engine cranking, start up and running are controlled by a solid  
state Engine Controller circuit board. Battery voltage is delivered  
to that circuit board via the control panel fuse. This overcurrent  
protection device will open if the circuit is overloaded.  
INSPECT ENGINE GOVERNOR  
Visually inspect electronic governor.  
If a circuit breaker opens or a fuse element  
melts, find the cause of the overload before  
n
resetting the circuit breaker or replacing the  
fuse.  
Do not attempt to adjust the governor. Only  
EXERCISE SYSTEM  
Starts the Stationary Emergency Generator engine once every  
seven days and lets it run for 12 minutes.  
qualified service facilities should adjust the  
n
governor. Excessively high operating speeds  
are dangerous and increase the risk of personal  
injury. Low speeds impose a heavy load on the  
engine when adequate engine power is not  
available and may shorten engine life. Correct  
rated frequency and voltage are supplied only  
at the proper governed speed. Some connected  
electrical load devices may be damaged by  
incorrect frequency and/or voltage. Only quali-  
fied service technicians should adjust the gov-  
erned speed.  
PERFORM VISUAL INSPECTION  
Complete a thorough visual inspection of the entire engine-genera-  
tor monthly. Look for obvious damage, loose, missing or corroded  
nuts, bolts and other fasteners. Look for fuel, oil or coolant leaks.  
INSPECT EXHAUST SYSTEM  
Inspect the exhaust system at least once every year. Check all  
exhaust system pipes, mufflers, clamps, etc. for condition, tight-  
ness, leaks, security, damage.  
CHANGING THE ENGINE AIR FILTER  
To replace the engine air filter, remove the air filter cover and  
replace the air filter making sure it is positioned properly before  
reattaching the cover (Figure 10.3).  
See the Service Schedule for air filter maintenance.  
. A v e 0 5 / 1 0  
M a i n t 0 2 7 R  
10-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
nBattery electrolyte fluid is an extremely corro-  
sive sulfuric acid solution that can cause severe  
Figure 10.3 – Engine Air Filter  
burns. Do not permit fluid to contact eyes, skin,  
clothing, painted surfaces, etc. Wear protective  
goggles, protective clothing and gloves when  
handling a battery. If fluid is spilled, flush the  
affected area immediately with clear water.  
Do not use any jumper cables or booster bat-  
tery to crank and start the generator engine. If  
the battery has completely discharged, remove  
it from the generator for recharging.  
n
AIR  
FILTER  
Be sure the AUTO/OFF/MANUAL switch is set  
to the OFF position, before connecting the  
battery cables. If the switch is set to AUTO or  
MANUAL, the generator can crank and start as  
soon as the battery cables are connected.  
n
Be sure the 120VAC power supply to the battery  
is turned OFF, or sparking may occur at the bat-  
tery posts as the cables are attached and cause  
an explosion.  
SPARK PLUGS  
Reset the spark plug gap or replace the spark plugs as neces-  
sary.  
1. Clean the area around the base of the spark plugs to keep dirt  
and debris out of the engine. Clean by scraping or washing  
using a wire brush and commercial solvent. Do not blast the  
spark plugs to clean.  
2. Remove the spark plugs and check the condition. Replace  
the spark plugs if worn or if reuse is questionable. See the  
“Service Schedule” section for recommended inspection.  
3. Check the spark plug gap using a wire feeler gauge. See the  
Specifications section for the required spark plug gap.  
BATTERY REPLACEMENT  
NOTE:  
Unit DOES NOT include battery.  
When supplying or replacing the battery, the recommended num-  
ber and type of battery is listed in the Specifications Section.  
NOTE:  
The BCI number should be located directly on the battery.  
BATTERY MAINTENANCE  
The battery should be inspected per the Service Schedule section.  
The following procedure should be followed for inspection:  
BATTERY FLUID  
Check battery electrolyte fluid based on the Service Schedule.  
Fluid should cover separators in all battery cells. If fluid level is  
low, add distilled water to cover tops of separators. DO NOT USE  
TAP WATER IN BATTERY.  
1. Inspect the battery posts and cables for tightness and corro-  
sion. Tighten and clean as necessary.  
2. Check the battery fluid level of unsealed batteries and, if  
necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP  
WATER IN BATTERIES.  
CLEANING THE STATIONARY EMERGENCY GENERATOR  
Keep the generator as clean and as dry as possible. Dirt and  
moisture that accumulates on internal generator windings have an  
adverse effect on insulation resistance.  
3. Have the state of charge and condition checked. This should  
be done with an automotive-type battery hydrometer.  
Periodically clean generator exterior surfaces. A soft brush may be  
used to loosen caked on dirt. Use a vacuum system or dry, low  
pressure air to remove any accumulations of dirt. The generator is  
housed inside an all-weather enclosure, clean the enclosure with a  
soft, damp cloth or sponge and water.  
Storage batteries give off explosive hydrogen  
gas. This gas can form an explosive mixture  
around the battery for several hours after  
charging. The slightest spark can ignite the gas  
and cause an explosion. Such an explosion can  
shatter the battery and cause blindness or other  
injury. Any area that houses a storage battery  
must be properly ventilated. Do not allow smok-  
ing, open flame, sparks or any spark producing  
tools or equipment near the battery.  
Once each year have the generator cleaned and inspected by a  
Service Dealer. That dealer will use dry, low pressure air to clean  
internal windings.  
Finally, have the insulation resistance of stator and rotor windings  
checked. If insulation resistances are excessively low, the genera-  
tor may require drying.  
. A v e 0 5 / 1 0  
M a i n t 0 2 7 R  
10-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Service Schedule  
SERVICE SCHEDULE  
System / Component  
Frequency  
Procedure  
Weekly - W  
Monthly - M  
Yearly - Y  
Inspect  
Change  
Clean  
Fuel  
Fuel Lines & Connections  
Lubrication  
M
X
Oil Level  
M
Y
X*  
Oil  
X**  
X**  
Oil Filter  
Y
Cooling  
Engine Coolant Lines & Connections  
Engine Coolant Level  
Engine Coolant  
M
M
Y
X
X
X
Enclosure Louvers  
Engine  
W
X
X
Air Cleaner  
Y
Y
X
X
X***  
X***  
Spark Plugs  
Battery  
Remove Corrosion, Ensure Dryness  
Clean & Tighten Battery Terminals  
Check Charge State  
Check Electrolyte Level  
General Condition  
Vibration, Noise, Leakage, Temperature  
Generator System  
Complete Tune-up and System Inspection  
Footnotes  
M
M
M
M
X
X
X
X
X
X
X***  
X***  
M
Y
X
To be completed by an Authorized Service Dealer.  
* Inspect the oil level monthly or every 12 hours during continuous operation.  
** Change oil and oil filter after the first 30 hours of operation and then every 100 hours or annually thereafter, whichever occurs first.  
Change sooner when operating under heavy load or in a dusty or dirty environment or in high ambient temperatures.  
*** Replace as necessary.  
. B v e 0 5 / 1 0  
v S S c r h d 0 0 4 R  
11-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
TROUBLESHOOTING GUIDE  
PROBLEM  
Engine won’t crank.  
CAUSE  
CORRECTION  
1. Control panel 7.5 amp fuse blown.  
2. Loose or corroded or defective  
battery cables.  
1. Replace fuse.*  
2. Tighten, clean or replace  
battery cables as necessary.*  
3. Replace contactor.*  
4. Replace starter motor.*  
5. Remove, change or replace battery.*  
3. Defective starter contactor.  
4. Defective starter motor.  
5. Dead or Defective Battery.  
Engine cranks but won't start.  
Engine starts hard, runs rough.  
1. Out of fuel.  
2. Fuel solenoid (FS) is defective  
3. Spark plugs defective.  
1. Replenish fuel/turn on fuel valve.  
2. Replace solenoid.*  
3. Clean, regap or replace plugs.  
1. Air cleaner plugged or damaged.  
2. Defective spark plugs.  
3. Fuel pressure incorrect.  
1. Clean or replace as needed.  
2. Clean, regap or replace plugs.  
3. Confirm fuel pressure to regulator is as  
recommended in SPECIFICATIONS.*  
4. Confirm fuel pressure to regualtor is as  
recommended in SPECIFICATIONS.*  
5. Reconfigure the fuel system. (See  
RECONFIGURING THE FUEL SYSTEM in  
manual.*  
4. Insufficient fuel supply.  
5. Fuel system set to wrong fuel type.  
Engine starts then shuts down.  
1. Engine oil level is low.  
2. Engine is overheated.  
3. Defective Low Oil Pressure Switch  
4. Defective Coolant Temperature Switch  
5. Defective Control Module circuit board.  
6. Coolant Level is Low.  
1. Check oil and add oil as needed.  
2. Check cooling system for leaks.  
3. Replace switch.*  
4. Replace switch.*  
5. Replace board.*  
6. Repair leak - Add coolant.  
7. Replace Switch.*  
7. Defective Low Coolant Level Switch  
AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch  
1. Replace board.*  
2. Replace board.*  
engine continues to run.  
2. Defective Control Module circuit board  
No AC output from generator.  
1. Main line circuit breaker is tripped/open.  
2. Generator internal failure.  
1. Reset to ON/CLOSED.  
2. *  
3. Thermal circuit breaker open.  
3. Auto-reset - Wait 5 min. and attempt restart.  
*Contact the nearest Dealer for assistance.  
. B v e 0 5 / 1 0  
r b T l s h t 0 0 3 R  
12-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
United States Environmental Protection Agency Warranty Statement  
(Stationary Emergency Spark-Ignited Generators)  
Warranty Rights, Obligations and Coverage  
The United States Environmental Protection Agency (EPA) and Generac Power Systems, Inc. (Generac) are pleased to explain the  
Emission Control System Warranty on your new stationary emergency engine. If during the warranty period, any emission control system  
or component on your engine is found defective in materials or workmanship, Generac will repair your engine at no cost to you for diag-  
nosis, replacement parts and labor provided it be done by a Generac Authorized Warranty Service Facility. Your emission control system  
may include parts such as the fuel metering, ignition, and exhaust systems and other related emission related components listed below.  
Generac will warrant the emissions control systems on your 2009 and later model year engines provided there has been no abuse,  
neglect, unapproved modification or improper maintenance of your engine. For engines less than 130 HP the warranty period is two years  
from the date of sale to the ultimate purchaser. For engines greater than or equal to 130 HP the warranty period is three years from the  
date of the engine being placed into service.  
Purchaser's/Owner's Warranty Responsibilities  
As the engine purchaser/owner you are responsible for the following. 1.) The engine must be installed and configured in accordance  
to the Generac's installation specifications. 2.) The completion of all maintenance requirements listed in your Owner’s Manual. 3.) Any  
engine setting adjustment must be done in accordance and consistent with the instructions in the Owner’s Manual. 4.) Any emission con-  
trol system or component must be maintained and operated appropriately in order to ensure proper operation of the engine and control  
system to minimize emissions at all times.  
Generac may deny any/or all Emission Control System Warranty coverage or responsibility of the engine, or an emission control system  
or component on your engine thereof, if it has failed due to abuse, neglect, unapproved modification or improper maintenance, or the use  
of counterfeit and/or 'gray market' parts not made, supplied or approved by Generac. Warranty service can be arranged by contacting  
either your selling dealer or a Generac Authorized Warranty Service dealer, 1-800-333-1322 for the dealer nearest you. The purchaser/  
owner shall be responsible for any expenses or other charges incurred for service calls and/or transportation of the product to/from the  
inspection or repair facilities. The purchaser/owner shall be responsible for any and/or all damages or losses incurred while the engine  
is being transported/shipped for inspection or warranty repairs. Contact Generac Power Systems Inc. for additional Emission Control  
System Warranty related information, Generac Power Systems, Inc. P.O. Box 8, Waukesha, WI 53187, or call 1-800-333-1322 or www.  
generac.com.  
Important Note  
This warranty statement explains your rights and obligations under the Emission Control System Warranty, which is provided to you by  
Generac pursuant to federal law. Note that this warranty shall not apply to any incidental, consequential or indirect damages caused by  
defects in materials or workmanship or any delay in repair or replacement of the defective part(s). This warranty is in place of all other  
warranties, expressed or implied. Specifically, Generac makes no other warranties as to the merchantability or fitness for a particular pur-  
pose. Any implied warranties which are allowed by law, shall be limited in duration to the terms of the express warranty provided herein.  
Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.  
Emission Related Parts Include the Following (if so equipped)  
1) Fuel Metering System  
3)  
4)  
5)  
Ignition System Including  
1.1) Gasoline Carburetor Assembly And Internal  
Components A) Fuel Filter, B) Carburetor, C) Fuel  
Pump  
1.2) Carburetion Assembly And Its Components  
A) Fuel Controller, B) Carburetor And Its Gaskets, C)  
Mixer And It Gaskets, D) Primary Gas Regulator E)  
Liquid Vaporizer  
1.3) Fuel Regulator  
2) Air Induction System Including  
A) Intake Pipe/Manifold,  
A) Spark Plug, B) Ignition Module,  
C) Ignition Coil, D) Spark Plug Wires  
Exhaust System  
A) Catalyst Assembly, B) Exhaust Manifold,  
C) Muffler, D) Exhaust Pipe, E) Muffler Gasket  
Crankcase Breather Assembly Including  
A) Breather Connection Tube, B) Pcv Valve  
Oxygen Sensor  
6)  
7)  
Diagnostic Emission-Control System  
B) Air Cleaner  
. D v e 0 9 / 1 1 n t y 0 0 1 R E m s n W r  
13-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
United States Environmental Protection Agency Compliance Requirements  
(Stationary Emergency Spark-Ignited Generators)  
Purchaser's/Owner's Recordkeeping Responsibilities  
The United States Environmental Protection Agency (EPA) and Generac Power Systems, Inc. (Generac) are pleased to explain your record-  
keeping requirements for compliance with Subpart JJJJ- Standards of Performance for Stationary Spark Ignition Internal Combustion Engines  
as listed in the Electronic Code of Federal Regulations Title 40 Part 60. As the engine purchaser/owner who operates and maintains their  
certified emergency stationary engine and emission control system according to applicable emission related guidelines as specified in this  
Owner's Manual, you are required to meet the following notification and recordkeeping requirements to demonstrate compliance. 1.) Maintain  
documentation that the engine is certified to meet emission standards. 2.) Recordkeeping of maintenance conducted. 3.) Recordkeeping of  
the provision allowing natural gas engines to operate using propane for a maximum of 100 hours per year as an alternate fuel solely dur-  
ing emergency operations provided the engine is not certified to operate on propane. 4.) Meet all compliance notifications submitted to the  
purchaser/owner and maintain all supporting documentation. 5.) Recordkeeping of hours of operation, including what classified the operation  
as emergency and how many hours are spent for non-emergency operation. For emergency engines greater than or equal to 130 HP, record-  
keeping of hours of operation begins January 1, 2011. For emergency engines less than 130 HP, recordkeeping of hours of operation begins  
January 1, 2009; Engines are equipped with non-resettable hour meters to facilitate recordkeeping.  
Specific Air Quality Management or Air Pollution Control Districts may have different and additional record keeping/reporting requirements.  
Your permit to construct and/or operate the engine may be contingent upon compliance with those requirements. Check with your local Air  
Quality Management or Air Pollution Control District for specific requirements.  
Emergency stationary internal combustion engines (ICE) may be operated for the purpose of maintenance checks and readiness testing,  
provided that the tests are recommended by Federal, State or local government, Generac, or the insurance company associated with the en-  
gine. Maintenance checks and readiness testing of such units is limited to 100 hours per year. There is no time limit on the use of emergency  
stationary ICE in emergency situations. The purchaser/owner may petition the Administrator for approval of additional hours to be used for  
maintenance checks and readiness testing, but a petition is not required if the owner maintains records indicating that Federal, State, or local  
standards require maintenance and testing of emergency ICE beyond 100 hours per year. Emergency stationary ICE may operate up to 50  
hours per year in non emergency situations, but those 50 hours are counted towards the 100 hours per year provided for maintenance and  
testing.  
The 50 hours per year for non-emergency situations cannot be used for peak shaving or to generate income for a facility to supply power to  
an electric grid or otherwise supply power as part of a financial arrangement with another entity. For purchaser/owner of emergency engines,  
any operation other than emergency operation, maintenance and testing, and operation in non-emergency situations for 50 hours per year, as  
permitted in this section is prohibited.  
If you operate and maintain your certified emergency stationary SI internal combustion engine and emissions control systems in accordance  
to the specifications and guidelines in this Owner’s Manual EPA will not require engine performance testing. If not, your engine will be consid-  
ered non-certified and you must demonstrate compliance according to Subpart JJJJ - Standards of Performance for Stationary Spark Ignition  
Internal Combustion Engines as listed in the Electronic Code of Federal Regulations Title 40 Part 60.  
Emission-Related Installation Instructions  
Your certified emergency stationary engine has pre-set emission control systems or components that require no adjustment. Inspection and  
replacement of an emissions related component is required to be done so in accordance with the requirements cited in the United States  
Environmental Protection Agency Warranty Statement or can be arranged by contacting either your selling dealer or a Generac Authorized  
Warranty Service dealer, 1-800-333-1322 for the dealer nearest you. Failing to follow these instructions when installing a certified engine in a  
piece of nonroad equipment violates federal law 40 CFR 1068.105 (b), subject to fines or penalties as described in the Clean Air Act.  
. D v e 0 9 / 1 1 n t y 0 0 1 R E m s n W r  
13-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
0G4827  
0G2927  
0G2827  
0G3451  
0G0820A  
0G4452  
020746  
049226  
051713  
022129  
0G4825  
0G4826  
0G2926  
0G3682  
0G5584  
0G3685  
0G2826  
0G3683  
0G6573  
0G3686  
0G3684  
0G3687  
0G5909  
0G6103  
0A5382A  
075591  
051787  
0A5601A  
0G8827  
0G8827A  
0A9375  
022152  
0G4196  
042558  
0J6102  
0G0965B  
053607  
051769  
023365  
0F3353  
072578  
0G3787  
0A8830  
077043E  
0G2070  
0G2070A  
045771  
0D8427  
0J6853A  
0J6853B  
0J6853C  
0C2454  
1
1
1
1
1
1
4
4
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
4
4
4
4
1
1
4
1
1
1
4
6
1
6
4
1
1
1
4
4
1
1
1
6
ASSY RTR 104 KD1 HI EFF (18KW)  
RTR-102-20.0AD1 CPL (2006) (20KW)  
ASSY RTR 25KW 2P (2006) (25KW)  
ASSY RTR 30KW 2P 10"(2006)  
HOUSING BLOWER LG PILOT  
BLOWER HOUSING SCREEN  
SCREW PPHM M5-0.8 X 8 ZINC  
WASHER LOCK M5  
WASHER FLAT M5  
2
3
4
5
6
7
8
WASHER LOCK M8-5/16  
ASSY STR 104-18AD1 HI EFF (18KW)  
ASSY STR 104 18GD1 HI EFF (18KW)  
STR-102-20.0AD1 CPL (2006) (20KW)  
STR-102-20.0GD1 CPL (2006) (20KW)  
STR-102-20.0JD1 CPL (2006) (20KW)  
STR-102-20.0KD1 CPL (2006) (20KW)  
ASSY STR 102 25AD1 (2006) (25KW)  
STR-102-25.0GD1 CPL (2006) (25KW)  
STR-102-25.0-JD1 CPL (2006) (25KW)  
STR-102-25.0KD1 CPL (2006) (25KW)  
STR-102-30.0GD2 CPL (30KW)  
STR-102-30.0KD2 CPL (30KW)  
ASSY STR 102 30AD2 10" (30KW)  
STR-102-30.0JD2  
BEARING CARRIER REAR LG PILOT  
ASSY HOLDER BRUSH  
SCREW HHC M4-0.7 X 16 G8.8  
COVER REAR BEARING  
STUD M8-1.25 475 LONG  
STUD M8-1.25 418 LONG  
SCREW RHM #10-24 X 2  
WASHER LOCK #10  
FLYWHEEL & RINGGEAR ASSY 1.6L  
KEY SQ 3/8 X 1 STEEL  
SCREW HHFC M10-1.5 X 16 C10.9  
PLATE FLEX 1.6L R12.7  
SCREW HHC M12-1.75 X 35 G8.8  
WASHER LOCK M12  
WASHER SHAKEPROOF INT #8  
SCREW HHC M10-1.0 X 20 G10.9  
SPACER ROTOR SHAFT  
WASHER .41 ID .94 OD .12 THK  
WASHER FLAT .34 ID X .75 OD  
FLEX CONDUIT 1" BLACK (NOT SHOWN)  
PLATE SPACER 14GA 1.6L (TO BE USED WITH ENGINE PLATE P/N 0G0834.)  
PLATE SPACER 16GA 1.6L (TO BE USED WITH ENGINE PLATE P/N 0G0834A.)  
NUT HEX M8-1.25 G8 CLEAR ZINC  
WASHER LOCK M10 RIBBED ZINC  
SUPPORT LH ALT COVER  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
(1) 23  
24  
25  
26  
27  
28  
29  
30  
(2)31  
(2)32  
(2)33  
(2)34  
SUPPORT RH ALT COVER  
COVER REAR 10" ALT  
SCREW HWHT M6-1 X 16 N WA Z/JS  
(1) APPLY LOCTITE 242 BEFORE THREADING SCREW INTO CRANKSHAFT.  
(2) ALTERNATE CONFIGURATION REQUIRES ALL NOTED PARTS.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: CONNECTION BOX C1 CPL  
DRAWING #: 0H7234  
APPLICABLE TO:  
GROUP A  
ITEM  
PART#  
QTY.  
DESCRIPTION  
1
2
(4)3  
4
0H6795  
0H6796  
0H67330ST0R  
0H7115  
022097  
1
1
1
2
2
CONBOX BACK/SIDES C1 CPL  
CONBOX TOP C1 CPL  
BRACKET GIMBAL CONTROL PNL RAW  
KNOB M6-1.0 CONTROL PANEL  
WASHER LOCK M6-1/4  
5
6
(3)7  
8
022473  
SEE CHART  
052777  
4
1
3
WASHER FLAT 1/4-M6 ZINC  
CIRCUIT BREAKER  
WASHER FLAT M3  
9
043182  
3
WASHER LOCK M3  
10  
(4)11  
12  
051714  
0H81040AS0R  
045764  
3
1
2
3
NUT HEX M3-0.5 G8 CLEAR ZINC  
COVER DPE BREAKER NEXUS  
SCREW HHTT M4-0.7 X 8 ZP  
WASHER LOCK #8-M4  
13  
022264  
14  
0A9457  
1
DECAL NEUTRAL  
15  
16  
(2)17  
18  
(4)19  
20  
21  
22  
23  
24  
REF  
1
18  
1
6
1
1
12  
2
2
2
ASSY CTRL PROGRAMMED  
SCREW HWHT M6-1 X 16 N WA Z/JS  
REGULATOR - DC ALT  
NUT FLANGE M6-1.0 NYLOK  
SHIELD HIGH/LOW C1 RAW  
RELAY SOLENOID 12VDC PNL MNT  
SCREW HHSP #10 X 3/8 HI-LOW  
SCREW HHC M6-1.0 X 20 C8.8  
NUT HEX M5-0.8 G8 CLEAR ZINC  
WASHER LOCK M5  
0C2454  
0A1354A  
0D3700  
0H88380ST0R  
056739  
0F5458  
042568  
051716  
049226  
25  
051713  
2
WASHER FLAT M5  
26  
27  
28  
29  
0D7177V  
0F5752F  
0H6267  
056326  
0G3524  
0D7393T  
0D7393U  
0F5376S0AR  
0F5396S0AR  
057073  
2
1
1
1
DIODE BRIDGE 1P 35A 1000V  
RES WW 15R 5% 25W QK CONN  
COVER VOLTAGE SHIELD  
TRIM VINYL BLACK 1/8GP (3”LG)  
COVER BELL HOUSING CONBOX  
TERM BLOCK 3P UL 12-20AWG  
TERM BLOCK 4P UL 12-20AWG  
MX150L SLRRMNT 22-18 8P W/O GA  
MX150L SLRRMNT 22-18 12P W/OGA  
JUNCTION BLOCK 3/8-16  
30  
1
(1)31  
(1)32  
(1)33  
(1)34  
35  
REF  
REF  
REF  
REF  
1
36  
37  
38  
0C2265  
057329  
022237  
3
1
1
SCREW PHTT M4-0.7 X 12 ZP  
LUG SLDLSS 350-#6X13/32 AL/CU  
WASHER LOCK 3/8  
39  
022241  
1
NUT HEX 3/8-16 STEEL  
40  
41  
42  
43  
44  
45  
46  
025433  
023762  
0H7292  
0H7293  
029289  
1
1
1
1
1
1
2
LUG SLDLSS #6-14 X 13/64 CU  
WASHER LOCK EXT #10 STL  
DECAL CUSTOMER CONTROL CONNECT  
DECAL CONBOX TB1 CONNECTIONS  
TAPE ELEC 1/2 FOAM (62” LG)  
DECAL CUSTOMER POWER CONNECT  
WASHER NYLON .257  
0J0489  
0A2115  
47  
48  
49  
50  
51  
52  
0F6146  
1
1
REF  
1
1
HANG TAG 2 WIRE START (NOT SHOWN)  
HARN CONBOX NEXUS (NOT SHOWN)  
FUSE ATO TYPE 7.5AMP (BROWN)  
DECAL GROUND LUG  
GASKET WIRE ENTRY COVER  
DECAL CAUTION ELEC SHOCK SM  
0H6692  
0D7178T  
067210A  
0J6701  
0H8006  
1
UL CIRCUIT BREAKER (225AF)  
A
B
C
D
E
F
G
H
J
0G5249  
REF  
1
1
1
2
2
2
10  
2
2
CB 150A 2 POLE 240V 225AF  
COVER CB G 225AF C1 CONBOX  
INSULATOR CB 2P 225AF  
SPRT CIRCUIT BREAKER G 225AF  
WASHER FLAT #8 ZINC  
WASHER LOCK #8-M4  
NUT HEX #8-32 STEEL  
SCREW HWHT M6-1 X 16 N WA Z/JS  
SCREW RHM #8-32 X 3-1/4  
BUS BAR 200A LUG ADAPTOR  
SCREW SHC M8-1.25 X 20 G8  
0H6846  
0F8432A  
0G5734  
038150  
022264  
022471  
0C2454  
053640  
0F8843  
049897  
K
L
4
REVISION: J-1182-J  
DATE: 12/16/11  
Page 4 of 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: CONNECTION BOX C1 CPL  
DRAWING #: 0H7234  
APPLICABLE TO:  
GROUP A  
ITEM  
PART#  
QTY.  
DESCRIPTION  
M
N
P
R
S
T
U
V
W
022129  
022145  
045771  
058306  
0F8451  
6
4
2
2
2
1
1
1
4
WASHER LOCK M8-5/16  
WASHER FLAT 5/16-M8 ZINC  
NUT HEX M8-1.25 G8 CLEAR ZINC  
SCREW SHC M8-1.25 X 25 C12.9  
LUG SLDLSS 300 MCM-6 AL/CU  
DECAL TERMINAL SHOCK HZD BI  
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
0G3259  
0J78230AS0R  
029289  
036261  
RIVET POP .125 X .275 SS  
(1) ITEMS INCLUDED WITH HARNESS P/N 0H6692.  
(2) ITEMS USED ON 1.6L MODELS ONLY.  
(3) SEE “C1 DPE BREAKER SELECTION” TABLE.  
(4) SHEET METAL PARTS LISTED IN THE BOM TABLE ARE REPRESENTING GENERIC PARTS (NO COLOR)  
MANUFACTURING: FOR CORRECT MATERIAL AND COLOR REFER TO AS400 BOM.  
CUSTOMER: WHEN ORDERING REPLACEMENT PARTS ENTER BASE NUMBER (FIRST 6 DIGITS ONLY) IN THE  
SYSTEM FOR CORRECT MATERIAL AND COLOR (FOR REFERENCE SEE GUIDELINE 0H7169).  
REVISION: J-1182-J  
DATE: 12/16/11  
Page 5 of 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: CONNECTION BOX C1 CPL  
DRAWING #: 0H7234  
APPLICABLE TO:  
GROUP A  
ITEM  
PART#  
QTY.  
DESCRIPTION  
UL CIRCUIT BREAKER (CC 2P)  
A
0H4745  
REF  
CB 0100A 2P 240V E CC LL  
CB 0125A 2P 240V E CC LL  
CB 0150A 2P 240V E CC LL  
COVER CB E CC 2P C1 CONBOX  
NUT HEX M5-0.8 G8 CLEAR ZINC  
CIRCUIT BREAKER SUPPORT (CC)  
WASHER FLAT #8 ZINC  
WASHER LOCK #8-M4  
NUT HEX #8-32 STEEL  
SCREW HWHT M6-1 X 16 N WA Z/JS  
SCREW RHM #8-32 X 3-1/4  
SCREW PPHM M5-0.8 X 12 ZNC  
WASHER FLAT #10 ZINC  
0H4746  
0H4747  
0H6847  
051716  
0H4656  
038150  
022264  
022471  
0C2454  
053640  
091526  
023897  
049226  
0H4698  
0J78230AS0R  
029289  
036261  
REF  
REF  
1
2
1
2
2
2
10  
2
2
4
2
1
1
1
4
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
WASHER LOCK M5  
INSULATOR CB 2P E TYPE CC  
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
RIVET POP .125 X .275 SS  
UL CIRCUIT BREAKER (CC/FG (3P) )  
A
0H4913  
REF  
REF  
REF  
REF  
1
CB 0100 3P 240V E CC LL  
CB 0125 3P 240V E CC LL  
CB 0080 3P 600V E FG LL  
CB 0090 3P 600V E FG LL  
CB COVER E CC/FG 3P C1 CONBOX  
INSULATOR CB 3P E TYPE CC/FG  
CIRCUIT BREAKER SUPPORT (CC)  
CIRCUIT BREAKER SUPPORT (FG)  
WASHER FLAT #8 ZINC  
WASHER LOCK #8-M4  
NUT HEX #8-32 STEEL  
SCREW HWHT M6-1 X 16 N WA Z/JS  
SCREW RHM #8-32 X 3-1/4 (CC)  
0H4914  
0H5488  
0H5489  
0H7294  
0H4698A  
0H4656  
0H5604  
038150  
022264  
022471  
0C2454  
053640  
B
C
D
1
REF  
REF  
4
4
4
E
F
G
H
J
10  
4
0H5721  
091526  
023897  
4
3
6
SCREW PPHM #8-32 X 1-3/4 ZINC (FG)  
SCREW PPHM M5-0.8 X 12 ZNC  
WASHER FLAT #10 ZINC  
K
L
M
N
P
Q
R
049226  
051716  
0J78230AS0R  
029289  
3
3
1
1
WASHER LOCK M5  
NUT HEX M5-0.8 G8 CLEAR ZINC  
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
036261  
4
RIVET POP .125 X .275 SS  
REVISION: J-1182-J  
DATE: 12/16/11  
Page 6 of 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: CONNECTION BOX C1 CPL  
DRAWING #: 0H7234  
APPLICABLE TO:  
GROUP A  
ITEM  
PART#  
QTY.  
DESCRIPTION  
UL CIRCUIT BREAKER (BQ 2P)  
A
0D5543  
REF  
CB 0090A 2P 240V S BQ2 LL  
CB 0100A 2P 240V S BQ2 LL  
CB 0125A 2P 240V S BQ2 LL  
COVER CB S BQ2 C1 CONBOX  
BRKT CB MTG BACK  
CIRCUIT BREAKER SUPPORT (BQ)  
SCREW HHC M5-0.8 X 20 G8.8  
WASHER FLAT #10 ZINC  
0D5544  
0A2077  
0H6842  
0E7890  
0G4497  
052619  
REF  
REF  
1
1
1
B
C
D
E
F
2
4
023897  
G
H
J
K
L
049226  
0C2454  
051716  
0G9708  
022264  
2
10  
2
2
2
WASHER LOCK M5  
SCREW HWHT M6-1 X 16 N WA Z/JS  
NUT HEX M5-0.8 G8 CLEAR ZINC  
SCREW PHTT M4-0.7 X 8 ZP  
WASHER LOCK #8-M4  
M
N
P
0J78230AS0R  
029289  
1
1
4
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
RIVET POP .125 X .275 SS  
036261  
UL CIRCUIT BREAKER (BQ 3P)  
A
062812  
053691  
040532  
0H6843  
0E6002  
0G4497  
052619  
REF  
CB 0080A 3P 240V S BQ3 LL  
CIRCT BRK 90 X 3 ITE BQ3-B090  
CB 0100A 3P 240V S BQ3 LL  
COVER CB S BQ3 C1 CONBOX  
MTG TRACK BQ SIEMENS CB 3P  
CIRCUIT BREAKER SUPPORT (BQ)  
SCREW HHC M5-0.8 X 20 G8.8  
WASHER FLAT #10 ZINC  
REF  
REF  
1
1
1
B
C
D
E
F
3
6
023897  
G
H
J
K
L
049226  
0C2454  
051716  
0G9708  
022264  
3
10  
3
2
2
WASHER LOCK M5  
SCREW HWHT M6-1 X 16 N WA Z/JS  
NUT HEX M5-0.8 G8 CLEAR ZINC  
SCREW PHTT M4-0.7 X 8 ZP  
WASHER LOCK #8-M4  
M
N
P
0J78230AS0R  
029289  
1
1
4
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
RIVET POP .125 X .275 SS  
036261  
UL CIRCUIT BREAKER (ED 3P)  
A
0D5552  
REF  
REF  
REF  
REF  
1
1
4
4
4
CB 0050A 3P 480V S ED4 LL  
CB 0090A 3P 480V S ED4 LL  
CB 0100A 3P 480V S ED4 LL  
CB 0125A 3P 480V S ED4 LL  
COVER CB S ED3 C1 CONBOX  
CIRCUIT BREAKER SUPPORT (ED)  
WASHER FLAT #8 ZINC  
0D5556  
0D5557  
0D9693  
0H6844  
0G4498  
038150  
B
C
D
E
F
022264  
022471  
WASHER LOCK #8-M4  
NUT HEX #8-32 STEEL  
G
H
J
K
L
M
N
P
0A8278  
0C2454  
066715  
3
10  
4
3
3
1
1
4
SCREW SHC 1/4-28 X 3/4 G8.8 NZ  
SCREW HWHT M6-1 X 16 N WA Z/JS  
SCREW RHM #8-32 X 4-1/2  
WASHER LOCK M6-1/4  
WASHER-STEP 1/2ODX9/32ID BRASS  
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
022097  
0D5621  
0J78230AS0R  
029289  
036261  
RIVET POP .125 X .275 SS  
UL CIRCUIT BREAKER (QN2 2P)  
A
B
C
D
E
F
G
H
J
0E7283  
0H6845  
0E3664  
0G4112  
074908  
REF  
1
1
1
2
10  
1
1
CB 0150A 2P 240V S QN2 LL  
COVER CB S QN2 C1 CONBOX  
BASE, QN CIRCUIT BREAKER  
BREAKER SUPPORT BRACKET 30KW  
SCREW HHTT M5-0.8 X 10 BP  
SCREW HWHT M6-1 X 16 N WA Z/JS  
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
0C2454  
0J78230AS0R  
029289  
036261  
4
RIVET POP .125 X .2  
REVISION: J-1182-J  
DATE: 12/16/11  
Page 7 of 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: CONNECTION BOX C1 CPL  
DRAWING #: 0H7234  
APPLICABLE TO:  
GROUP A  
THIS PAGE LEFT INTENTIONALLY BLANK  
REVISION: J-1182-J  
DATE: 12/16/11  
Page 8 of 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
0G3418  
0G3421  
0G3419  
0E9837B  
0G3553  
0E3257  
0G4080  
099502  
0G4070  
0G4072  
0G4071  
046627  
052250  
022473  
022097  
0C8566  
045771  
0C2454A  
042568  
0G3573  
0G3574  
0G3420  
080713  
076749  
048031C  
029032  
0G4451  
055934N  
0F9504  
0G0568  
0G3433  
0E2507  
0H1827  
0A2628  
029333A  
042907  
027482  
022129  
039253  
0H1851  
1
1
1
1
1
2
1
6
1
1
1
1
2
8
8
4
4
28  
4
1
1
1
1
1
2
1
REF  
2
1
1
1
1
1
1
10  
4
RADIATOR SUPPORT LH SIDE 1.6L  
VENTURI 1.6L  
RADIATOR SUPPORT RH SIDE 1.6L  
RADIATOR 1.6L CHY  
FAN COOL 450MM DIA 7 BLADE  
SCREW HWHTF M6-1.0 X 16  
HOSE LOWER RADIATOR 1.6L  
CLAMP HOSE #24 B1.06-2.00  
HOSE REAR COOLANT 1.6L  
TUBE ENGINE COOLANT 1.6L  
HOSE UPPER RADIATOR 1.6L  
CAP RADIATOR  
TAPE FOAM 1 X 1 (24” LG)  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
SCREW HHFC M6-1.0 X 20 G8.8  
NUT HEX M8-1.25 G8 CLEAR ZINC  
SCREW THF M6-1 X 12 N WA Z/JS  
SCREW HHC M6-1.0 X 20 G8.8  
GUARD FAN LH C1  
GUARD FAN RH C1  
RADIATOR BLOCK-OFF  
BRACKET COOLANT TANK  
TANK COOLANT RECOVERY  
CLAMP HOSE BAND 1/4  
HOSE 9/32 ID (43” LG)  
BRACKET STEPPER MOTOR COOLANT  
CLAMP VINYL 1.31 X .281 Z  
GROMMET 5/8"X 1 1/8"X 5/16"  
ASSY FAN BEARING SUPPORT  
BRACKET FAN ALT ADAPTER 1.6L  
PROBE COOLANT LEVEL 3/8NPTF  
PROBE COOLANT LEVEL 3/8-18NPTF (USE WITH I/N 40, P/N 0H1851)  
PULLEY - FAN 95 DIA  
TIE WRAP UL 7.4" X .19" BLK (NOT SHOWN)  
SCREW HHC M8-1.25 X 16 G8.8  
WASHER SHAKEPROOF EXT 5/16 STL  
WASHER LOCK M8-5/16  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
(1) 36  
37  
38  
39  
4
4
4
1
SCREW HHC M8-1.25 X 20 G8.8  
ASSY PCB LCL SENSOR (USE WITH I/N 33, P/N 0H1827 ONLY)  
(2) 40  
(1) APPLY LOCTITE 242 TO I/N 36 BEFORE THREADING INTO I/N 31.  
(2) USE WITH R-200 CONTROL PANEL ONLY.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: MOUNTING BASE 1.6L  
DRAWING #: 0G3531  
APPLICABLE TO:  
GROUP C  
ITEM  
PART#  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
13  
14  
15  
16  
17  
18  
19  
0G3343  
027482  
070936  
070936C  
039253  
022145  
022129  
045771  
071956  
051730  
021991  
026850  
0G3461  
055414  
047411  
022097  
022473  
025507  
1
1
2
MOUNTING BASE 1.6L 2007 C1  
WASHER SHAKEPROOF EXT 5/16 STL  
DAMPENER VIBRATION  
VIB. ISO. 70-75 DURO  
SCREW HHC M8-1.25 X 20 G8.8  
WASHER FLAT 5/16 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 YEL CHR  
WASHER FLAT M8  
SCREW HHC M8-1.25 X 60 G8.8  
EARTH STRAP  
WASHER SHAKEPROOF EXT 1/4 STL  
ALTERNATOR SUPPORT BLOCK OFF  
LUG SLDLSS #2-#8 X 17/64 CU  
SCREW HHC M6-1.0 X 16 G8.8  
WASHER LOCK M6-1/4  
2
12  
16  
16  
4
4
4
1
1
2
1
1
1
5
1
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK EXT 7/16 STL  
REVISION: H-5975-B  
DATE: 2/5/10  
Page 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
0F3408C  
0F3411  
025507  
059980  
046526  
077483  
050331A  
050331  
038805J  
038804M  
045771  
022131  
027482  
0F3976  
0C2454  
022145  
1
1
1
1
1
REF  
REF  
REF  
1
1
REF  
1
BATTERY TRAY, C1 & C2  
STRAP BATTERY RETAINMENT  
WASHER SHAKEPROOF EXT 7/16 STL  
SCREW HHC M10-1.5 X 25 G10.9  
WASHER LOCK M10  
BATTERY 12VDC 75-AH 26  
BATTERY POST COVER RED +  
BATTERY POST COVER BLK -  
CABLE BATTERY BLACK #1 X 30.00  
CABLE BATTERY RED #1 X 21.00  
NUT HEX M8-1.25 G8 YEL CHR  
WASHER FLAT 3/8-M10 ZINC  
WASHER SHAKEPROOF EXT 5/16 STL  
BOOT CONTACTOR CABLES  
SCREW THF M6-1 X 16 N WA Z/JS  
WASHER FLAT 5/16-M8 ZINC  
1
1
4
REF  
NOTE: WHEN INSTALLING BATTERY, TUCK BATTERY’S LIFTING STRAP ALONG  
THE LEFT SIDE OF BATTERY ( SIDE OPPOSITE RADIATOR) BEFORE  
CONNECTING THE BATTERY CABLES.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: ENGINE COMMON PARTS 1.6L  
DRAWING #: 0H7219  
APPLICABLE TO:  
GROUP D  
ITEM  
PART#  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
0H1734  
0G0834A  
0G0820A  
0G7461  
0G0839  
0G0781  
0G0722  
0G4059  
0G4604  
0G3424  
0G0786  
0G4605  
0F9617A  
0A1354B  
0G0823  
0G3900  
0D2244M  
036710  
REF  
1
REF  
1
2
1
1
1
1
1
1
1
1
1
1
1
1
2
ENGINE GENERAC 1.6L G11 CERT  
ENGINE PLATE 1.6L 6MM (TO BE USED WITH PLATE SPACER P/N 0G2070A.)  
HOUSING BLOWER LG PILOT  
STARTER MOTOR 12V  
ENGINE MOUNTING FOOT STAMPING  
EXHAUST MANIFOLD 1.6L MACHINED  
INTAKE MANIFOLD MACHINED 1.6L  
SHIELD 1.6L EXHAUST HEAT  
DC ALTERNATOR ADAPTER MACHINED  
PULLEY CRANKSHAFT MACHINED  
WASHER PULLEY  
BRACKET TENSIONER DC ALT  
SPACER ALTERNATOR  
DC ALTERNATR HAN-KOK  
V-BELT 3/8 X 30.6  
CAP, 1.5" HOLE SHALLOW  
ASSY MAGPICKUP (3/8-24 MALE)  
PIN SPRING 1/4 X 3/4  
SCREW HHC M12-1.5 X 40 G10.9  
SCREW HHC M10-1.5 X 25 G10.9  
WASHER LOCK M10  
WASHER FLAT 3/8-M10 ZINC  
NUT HEX M10-1.5 CLASS 10 ZINC  
GASKET INTAKE MANIFOLD 1.6L  
GASKET EXHAUST MANIFOLD 1.6L  
NUT TOP LOCK FL M8-1.25  
SCREW HHC M10-1.5 X 70 G8.8  
SCREW HHC M10-1.5 X 110 G10.9  
SCREW HHC M10-1.5 X 40 G10.9  
SCREW HHC M8-1.25 X 35 G8.8  
WASHER LOCK M8-5/16  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
61  
62  
63  
64  
65  
0C5479  
059980  
046526  
1
13  
22  
18  
9
1
1
14  
1
4
4
1
4
3
1
3
3
4
4
5
3
5
1
1
1
1
1
1
1
1
1
3
29  
1
1
1
1
022131  
0G3922  
0G0464  
0G0465  
052858  
051735  
0G3920  
0A7387  
039414  
022129  
022145  
029333A  
057821  
045771  
022507  
022097  
WASHER FLAT 5/16-M8 ZINC  
TIE WRAP UL 7.4" X .19" BLK  
SCREW HHC M8-1.25 X 40 G8.8  
NUT HEX M8-1.25 G8 CLEAR ZINC  
SCREW HHC 1/4-20 X 1/2 G5  
WASHER LOCK M6-1/4  
022473  
090388  
WASHER FLAT 1/4-M6 ZINC  
SCREW HHTT M6-1.0 X 12 ZINC  
WASHER FLAT M10 HEAVY DUTY  
TEMPERATURE SENDER, DELPHI  
BSHG RDCR HEX 1/4 TO 1/8  
HARN LOW OIL PRESS SWITCH ASSY  
ADAPTER DRAIN OIL  
0A5768  
0E0502  
035579  
0H7435  
0C1852  
069860C  
069811  
HOSE OIL DRAIN ASSY 21"  
CAP HEX 1/4 NPT BRASS  
0G38580ST03  
025065  
STRUT LH 1.6L ENG ADAPT PLATE  
NIPPLE PIPE 3/8 NPT X 1-1/2  
PIPE TEE 3/8 NPT  
SCREW HWHTF M6-1.0 X 16  
WASHER FLAT .34 ID X .75 OD  
HARN ENG G1.6L G11 NEXUS (NOT SHOWN)  
OIL FILTER 1.6L  
CONDUIT FLEX .25"ID (6” LG)  
STRUT RH 1.6L ENG ADAPT PLATE  
BARBED STR 3/8 NPT X 3/8  
027738A  
0E3257  
0A8830  
0H6690  
0G02070100  
077043H  
0G38620ST03  
055596  
0C7649  
0H2250  
0G3433  
049541  
0G7311  
0G4451  
0F4001E  
1
3
1
REF  
1
REF  
1
1
CLAMP HOSE .38-.87  
HOSE COOLANT 3/8 ID 20R3 (11” LG)  
BRACKET FAN ALT ADAPTER 1.6L  
SCREW HHC M10-1.5 X 35 G8.8  
DECAL EMISSION CTRL INFO 1.6L  
BRACKET STEPPER MOTOR COOLANT  
ANCHOR HARNESS  
REVISION: H-8414-C  
DATE: 3/1/11  
Page 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: FUELSYS NG/LPV 1.6L CPL  
DRAWING #: 0H6671  
APPLICABLE TO:  
GROUP E  
ITEM  
PART#  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
037561  
0A5547  
062522  
022127  
059402  
091526  
049226  
0E0519A  
048031J  
0E6586  
0G1397E  
0F7790  
0E7121  
0G4573C  
0E8286  
047527  
057823  
035685  
057753B  
0E4395  
022129  
0A6344  
048031L  
0G1985  
047290  
047290  
0F3994  
0G3178  
048031P  
057147  
045771  
051767  
022097  
039253  
0G9348  
026812  
076691  
026490  
075580  
0D1509  
075436  
022145  
026915  
0E6586A  
1
1
1
1
1
4
4
1
4
1
1
1
2
1
1
1
2
2
1
1
2
1
4
1
1
1
1
1
1
1
2
4
5
2
1
2
1
1
1
1
1
2
1
1
NUT WING 1/4-20 NYLK  
COVER AIR CLEANER  
STUD TH 1/4-20 X 3 G2 ZNC FULL  
NUT HEX 1/4-20 STEEL  
FILTER ELEMENT  
SCREW PPHM M5-0.8 X 12 ZNC  
WASHER LOCK M5  
ADAPTER, CARBURETOR W/PVC CONN  
CLAMP HOSE BAND .63  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
(1)36  
(1)37  
(1)38  
(1)39  
40  
41  
42  
(1)43  
44  
GASKET BOSCH 32 & 40  
FUEL REG. REWORK 1.6L  
VENTURI THROTTLE 21MM  
O-RING 47.625 ID X 2.38 WIDTH  
MIXER ACTUATOR 32MM MACHINED  
STREET EL 45D 1/2 NPT BRASS  
BARBED STR 1/2 NPT X 3/4  
CLAMP HOSE #10 .56-1.06  
CLAMP HOSE #28 1.32-2.25  
HOSE 1.5 ID X 2 LG 20R4  
ACTUATOR BOSCH 32 GOVERNOR  
WASHER LOCK M8-5/16  
BARBED EL 90 1/8 NPT X 3/8  
CLAMP HOSE BAND 1.0"  
HOSE BARB REDUCR TEE 3/4"-3/8"  
HOSE 3/8 ID SINGLE BRAID (11.5” LG)  
HOSE 3/8 ID SINGLE BRAID (12” LG)  
PCV VALVE 2.5L FORD  
HOSE BREATHER 1.6L  
CLAMP HOSE BAND .88"  
HOSE 3/4 ID LPG & NG (16"LG)  
NUT HEX M8-1.25 G8 YEL CHR  
SCREW HHC M6-1.0 X 45 C8.8 FTH  
WASHER LOCK M6-1/4  
SCREW HHC M8-1.25 X 20 G8.8  
ASSY REG INLET NPT FITTINGS  
ELBOW 90D 3/4 NPT  
NIPPLE PIPE 3/4NPTX4.5 BLK IRN  
NIPPLE PIPE 3/4NPT X 2  
FLANGE FUEL INLET  
DECAL INLET PRESSURE  
DECAL FUEL INLET  
WASHER FLAT 5/16 ZINC  
NIPPLE CLOSE 3/4 X 1.375  
GASKET BOSCH 32  
(1) INCLUDED IN ITEM 35 (ASSY REG INLET NPT FITTINGS)  
 
REVISION: H-9610-B  
DATE: 9/9/11  
Page 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: EV ENCLOSURE C1 CPL  
DRAWING #: 0G3534  
GROUP F  
ITEM  
PART#  
QTY.  
DESCRIPTION  
(2) 1  
(2) 2  
(1) 3  
(2) 4  
6
0G33370AL0R  
0J14640AL0R  
077992  
0J14630AL0R  
0F4487A  
022127  
1
1
10  
2
1
ROOF 1.6L C1  
REAR INTAKE WRAP C1  
NUT HEX LOCK M6-1.0 SS NY INS  
DOOR LEFT/RIGHT SIDE C1  
ASSY ACCESS COVER  
7
1
NUT HEX 1/4-20 STEEL  
8
9
022097  
022473  
0C2454  
0F5048D  
0F5049  
1
1
8
2
WASHER LOCK M6-1/4  
WASHER FLAT 1/4-M6 ZINC  
SCREW THF M6-1 X 16 N WA Z/JS  
VISE-ACTION LATCH, SLOTTED CIR  
TAB PULL  
(1)10  
11  
12  
2
13  
14  
15  
16  
17  
(1)19  
20  
21  
0F8869D  
089961  
078115  
0H7518  
0H7518A  
0E3257  
0912970090  
0H7518B  
0C8566  
0H0412  
022097  
1
1
8
2
1
6
2
1
KEY VISE-ACTION LATCH,SLOT CIR  
FOAM STRIP 3/4"WIDE X 3/16"THK (294”LG)  
WASHER SELF LOCKING DOME  
INSULATION SIDE DOOR C1  
INSULATION ROOF C1  
SCREW HWHTF M6-1.0 X 16  
ASSY WIRE 14AWG GRN/YEL (32.25”LG)  
INSULATION REAR C1  
23  
24  
25  
10  
10  
8
SCREW HHFC M6-1.0 X 20 G8.8  
NUT SPRINGCLIP M6-1.0  
WASHER LOCK M6-1/4  
(3) 26  
27  
0H7529  
1
1
1
1
FOIL ALUMINUM WITH ADHESIVE  
RF COVER PLATE-PLASTIC-BISQUE  
RF COVER PLATE-PLASTIC-GREY  
FRONT DISCHARGE WRAP 1.6L C1  
WASHER LOCK SPECIAL 1/4"  
0H1208A  
0H1208B  
0G33350AL0R  
0A1658  
(2) 28  
(1)29  
2
(1)ENCLOSURE NOTE: ALL PANELS THAT FASTEN TO THE ROOF MUST BE SECURED USING I/N 10 (THREAD FORMING FASTENER) AND I/N 3 (LOCK NUT) AND  
TO INCLUDE AT LEAST ONE CONNECTION POINT USING I/N 19 (THREAD FORMING FASTENER) WITH I/N 3 (LOCK NUT) TO EACH PANEL. LOCK NUT IS TO BE  
INSTALLED AFTER THREAD FORMING FASTENER HAS PENETRATED THROUGH EXTRUSION IN ENCLOSURE PANELS. ALL PANEL TO BASEFRAME  
CONNECTIONS TO INCLUDE AT LEAST ONE CONNECTION POINT USING I/N 29 (WASHER SPECIAL).  
(2) SHEET METAL PARTS LISTED IN THE BOM TABLE ARE REPRESENTING GENERIC PARTS (NO COLOR)  
MANUFACTURING: FOR CORRECT MATERIAL AND COLOR REFER TO AS400 BOM.  
CUSTOMER: WHEN ORDERING REPLACEMENT PARTS ENTER BASE NUMBER (FIRST 6 DIGITS ONLY) IN THE SYSTEM FOR CORRECT MATERIAL  
AND COLOR (FOR REFERENCE SEE GUIDELINE 0H7169).  
(3) USED ON 1.5L / 1.6L UNITS ONLY.1  
REVISION: -A-  
DATE: 11/14/11  
Page 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
0F7366  
0F7647  
0F8095  
0G3576  
0E3257  
0F7644  
0C6119  
036434  
036449  
022129  
022259  
038750  
0G3575  
0F3794A  
022097  
049813  
022473  
1
1
1
1
4
2
1
3
3
6
6
1
1
1
1
1
6
MUFFLER C1  
MUFFLER SADDLE  
PIPE EXHAUST OUTLET  
EXHAUST PIPE LOWER 1.6L  
SCREW HWHTF M6-1.0 X 16  
MUFFLER STRAP  
BOLT U 5/16-18 X 2-1/4  
BOLT U 5/16-18 X 2.09  
SADDLE 2 INCH  
WASHER LOCK M8-5/16  
NUT HEX 5/16-18 STEEL  
SCREW HHC M6-1.0 X 30 G8.8  
EXHAUST PIPE UPPER 1.6L SS  
EXHAUST BLANKET 500MM LONG  
WASHER LOCK M6-1/4  
NUT HEX M6 X 1.0 G8 YEL CHR  
WASHER FLAT 1/4-M6 ZINC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
. A v 0 4 / 0 7 k P g B 0 0 a 1 c R e  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Owner's Manual  
Stationary Emergency Generator  
1.6L  
25/30kW Models  
EPA Certified  
nNOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT  
APPLICATIONS.  
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS  
SHOULD ATTEMPT INSTALLATION! DEADLY EXHAUST  
FUMES! OUTDOOR INSTALLATION ONLY!  
This manual should remain with the unit.  
. 0 H 7 t N 2 r 3 o a 0 P  
. A v 0 4 / 1 0 e v r 1 9 C 1 o R e  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
SECTION  
PAGE  
Alarm and Warning Messages..........................................................8-4  
INTRODUCTION ........................................................... 1-1  
Read this Manual Thoroughly.......................................................1-1  
Operation and Maintenance..........................................................1-1  
How to Obtain Service .................................................................1-1  
SAFETY RULES ............................................................ 1-2  
GENERAL INFORMATION............................................ 2-1  
Identification Record ........................................................................2-1  
Data Label ...................................................................................2-1  
EQUIPMENT DESCRIPTION ........................................ 3-1  
Equipment Description .....................................................................3-1  
Engine Oil Recommendations...........................................................3-1  
Coolant Recommendations ..............................................................3-1  
ENGINE PROTECTIVE DEVICES ................................. 4-1  
Engine Protective Devices ................................................................4-1  
High Coolant Temperature Sender ................................................4-1  
Low Coolant Level Sensor............................................................4-1  
Low Oil Pressure Switch ..............................................................4-1  
Overcrank Shutdown....................................................................4-1  
Overspeed Shutdown...................................................................4-1  
RPM Sensor Loss Shutdown........................................................4-1  
DC Fuses.....................................................................................4-1  
FUEL SYSTEM .............................................................. 5-1  
Fuel Requirements .......................................................................5-1  
Natural Gas Fuel System..............................................................5-1  
Propane Vapor Withdrawal Fuel System........................................5-1  
LP Liquid Fuel System..................................................................5-1  
SPECIFICATIONS......................................................... 6-1  
Stationary Emergency Generator ..................................................6-1  
Engine .........................................................................................6-1  
Cooling System............................................................................6-1  
Fuel System.................................................................................6-1  
Electrical System .........................................................................6-1  
Weather and Maintenance Kits .....................................................6-2  
Reconfiguring the Fuel System.........................................................6-2  
Fuel System.................................................................................6-2  
Control Panel ...............................................................................6-2  
GENERAL INFORMATION............................................ 7-1  
Alternator AC Lead Connections.......................................................7-1  
Four-lead, Single-phase Stator......................................................7-1  
Alternator Power Winding Connections.............................................7-1  
3-phase Alternators ("Y" Configuration) ........................................7-1  
3-phase Alternators ("Delta" Configuration)...................................7-2  
CONTROL PANEL......................................................... 8-1  
Control Panel Interface.....................................................................8-1  
Using the Auto/Off/Manual Switch................................................8-1  
Activate the Generator......................................................................8-1  
Display Interface Menus...................................................................8-1  
Activation Chart ...........................................................................8-2  
Setting the Exercise Timer................................................................8-3  
Low Speed Exercise.....................................................................8-3  
User Adjustable Settings ..................................................................8-3  
Fuel Conversion ...............................................................................8-3  
Operation.........................................................................................8-3  
Automatic Transfer Operation .......................................................8-3  
Sequence of Automatic Operation ................................................8-4  
Crank Cycles and Overcrank Shutdown........................................8-4  
Auto Start........................................................................................8-4  
Manual Start....................................................................................8-4  
Low Oil Pressure Shutdown Alarm ...............................................8-4  
High Coolant Temperature Shutdown Alarm..................................8-4  
Overcrank Shutdown Alarm..........................................................8-4  
Overspeed Shutdown Alarm.........................................................8-4  
RPM Sensor Failure Shutdown Alarm...........................................8-4  
Under-frequency Shutdown Alarm................................................8-5  
Low Battery Alarm.......................................................................8-5  
Low Battery Warning....................................................................8-5  
Low Coolant Level Alarm .............................................................8-5  
Missing Cam Pulse Alarm............................................................8-5  
Missing Crank Pulse Alarm ..........................................................8-5  
Low Fuel Pressure Warning..........................................................8-5  
Governor Sensor Fault Alarm........................................................8-5  
Wiring Error Alarm .......................................................................8-5  
Undervoltage Alarm .....................................................................8-5  
Overvoltage Alarm .......................................................................8-6  
Internal Failure Shutdown Alarm...................................................8-6  
Canbus Alarm..............................................................................8-6  
Ignition Alarm ..............................................................................8-6  
Maintenance Warning...................................................................8-6  
Alarm Cancel ...............................................................................8-6  
Common Alarm Relay......................................................................8-6  
Maintenance Alerts ..........................................................................8-6  
Menu System...................................................................................8-7  
OPERATION.................................................................. 9-1  
Stationary Emergency Generator Control and Operation....................9-1  
Operating Unit with Manual Transfer Switch......................................9-1  
Engine Start-up and Transfer........................................................9-1  
Retransfer and Shutdown.............................................................9-1  
Operating Unit with Automatic Transfer Switch .................................9-1  
MAINTENANCE........................................................... 10-1  
General Maintenance......................................................................10-1  
Check Engine Oil........................................................................10-1  
Changing Engine Oil...................................................................10-1  
Cooling Intake/Outlet..................................................................10-1  
Inspect Cooling System .............................................................10-1  
Engine Coolant...........................................................................10-2  
Coolant Change .........................................................................10-2  
Overload Protection for Engine DC Electrical System ..................10-2  
Exercise System ........................................................................10-2  
Perform Visual Inspection ..........................................................10-2  
Inspect Exhaust System.............................................................10-2  
Check Fan Belt...........................................................................10-2  
Inspect Engine Governor ............................................................10-2  
Changing the Engine Air Filter.....................................................10-2  
Spark Plugs ...............................................................................10-3  
Battery Maintenance ..................................................................10-3  
Battery Replacement..................................................................10-3  
Battery Fluid...............................................................................10-3  
Cleaning the Stationary Emergency Generator ............................10-3  
SERVICE SCHEDULE ................................................. 11-1  
TROUBLESHOOTING................................................. 12-1  
Troubleshooting Guide....................................................................12-1  
EMISSIONS WARRANTY............................................ 13-1  
NOTES  
EXPLODED VIEWS & PARTS LISTS  
WIRING DIAGRAMS & SCHEMATICS  
. A v e 0 5 / 1 0  
C o n t e n t 0 4 8 R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Instructions  
nSAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential  
hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this  
equipment.  
This symbol points out potential fire hazard.  
INTRODUCTION  
Thank you for purchasing this model of the stationary emergency  
generator product line.  
This symbol points out potential electrical shock hazard.  
Every effort was expended to make sure that the information and  
instructions in this manual were both accurate and current at the  
time the manual was written. However, the manufacturer reserves  
the right to change, alter or otherwise improve this product(s) at  
any time without prior notice.  
The operator is responsible for proper and safe use of the equip-  
ment. The manufacturer strongly recommends that the operator  
read this Owner's Manual and thoroughly understand all instruc-  
tions before using this equipment. The manufacturer also strongly  
recommends instructing other users to properly start and operate  
the unit. This prepares them if they need to operate the equipment  
in an emergency.  
READ THIS MANUAL THOROUGHLY  
If any portion of this manual is not understood, contact the nearest  
Service Dealer for starting, operating and servicing procedures.  
For safety reasons, the manufacturer recommends that this  
equipment be installed, serviced and repaired by a Service  
Dealer or other competent, qualified electrician or installation  
technician who is familiar with applicable codes, standards and  
regulations. The operator also must comply with all such codes,  
standards and regulations.  
Throughout this publication, and on tags and decals affixed to the  
generator, DANGER, WARNING, CAUTION and NOTE blocks are  
used to alert personnel to special instructions about a particular  
service or operation that may be hazardous if performed incor-  
rectly or carelessly. Observe them carefully. Their definitions are  
as follows:  
OPERATION AND MAINTENANCE  
It is the operator's responsibility to perform all safety checks, to  
make sure that all maintenance for safe operation is performed  
promptly, and to have the equipment checked periodically by a  
Service Dealer. Normal maintenance service and replacement of  
parts are the responsibility of the owner/operator and, as such,  
are not considered defects in materials or workmanship within the  
terms of the warranty. Individual operating habits and usage con-  
tribute to the need for maintenance service.  
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF  
NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.  
Indicates a hazardous situation or action which, if not  
avoided, could result in death or serious injury.  
Proper maintenance and care of the generator ensure a minimum  
number of problems and keep operating expenses at a minimum.  
See a Service Dealer for service aids and accessories.  
Indicates a hazardous situation or action which, if not  
avoided, could result in minor or moderate injury.  
NOTE:  
Operating instructions presented in this manual assume that the  
generator electric system has been installed by a Service Dealer or  
other competent, qualified contractor. Installation of this equipment  
is not a “do-it-yourself” project.  
Notes contain additional information important to a procedure  
and will be found within the regular text body of this manual.  
These safety warnings cannot eliminate the hazards that they  
indicate. Common sense and strict compliance with the special  
instructions while performing the service are essential to prevent-  
ing accidents.  
HOW TO OBTAIN SERVICE  
When the generator requires servicing or repairs, simply contact  
a Service Dealer for assistance. Service technicians are factory-  
trained and are capable of handling all service needs.  
Four commonly used safety symbols accompany the DANGER,  
WARNING and CAUTION blocks. The type of information each  
indicates is as follows:  
When contacting a dealer about parts and service, always supply  
the complete Model Number, Serial Number and Type Code (where  
applicable) from the DATA LABEL that is affixed to the unit.  
This symbol points out important safety information that,  
if not followed, could endanger personal safety and/or  
n
property of others.  
This symbol points out potential explosion hazard.  
. F v e 0 5 / 1 0  
S a f e t y 0 0 4 R  
1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Instructions  
• The engine exhaust fumes contain carbon monoxide gas, which  
SAFETY RULES  
can be DEADLY. This dangerous gas, if breathed in sufficient  
concentrations, can cause unconsciousness or even death. For  
that reason, adequate ventilation must be provided. This should  
be considered prior to installing the generator. The unit should  
be positioned to direct exhaust gasses safely away from any  
building where people, animals, etc., will not be harmed. Any  
exhaust stacks that ship loose with the unit must be installed  
properly per the manufacturer's instruction, and in strict compli-  
ance with applicable codes and standards.  
Study these SAFETY RULES carefully before installing, operating  
or servicing this equipment. Become familiar with this Owner’s  
Manual and with the unit. The generator can operate safely, effi-  
ciently and reliably only if it is properly installed, operated and  
maintained. Many accidents are caused by failing to follow simple  
and fundamental rules or precautions.  
The manufacturer cannot anticipate every possible circumstance  
that might involve a hazard. The warnings in this manual, and on  
tags and decals affixed to the unit are, therefore, not all inclusive.  
If a procedure, work method or operating technique is used that  
the manufacturer does not specifically recommend, ensure that it  
is safe for others. Also make sure the procedure, work method or  
operating technique utilized does not render the generator unsafe.  
• Keep hands, feet, clothing, etc., away from drive belts, fans,  
and other moving or hot parts. Never remove any drive belt or  
fan guard while the unit is operating.  
• Adequate, unobstructed flow of cooling and ventilating air is  
critical in any room or building housing the generator to prevent  
buildup of explosive gases and to ensure correct generator  
operation. Do not alter the installation or permit even partial  
blockage of ventilation provisions, as this can seriously affect  
safe operation of the generator.  
• Keep the area around the generator clean and uncluttered.  
Remove any materials that could become hazardous.  
• When working on this equipment, remain alert at all times.  
Never work on the equipment when physically or mentally  
fatigued.  
• Inspect the generator regularly, and promptly repair or replace  
all worn, damaged or defective parts using only factory-  
approved parts.  
• Before performing any maintenance on the generator, discon-  
nect its battery cables to prevent accidental start-up. Disconnect  
the cable from the battery post indicated by a NEGATIVE, NEG  
or (–) first. Reconnect that cable last.  
• Never use the generator or any of its parts as a step. Stepping  
on the unit can stress and break parts, and may result in dan-  
gerous operating conditions from leaking exhaust gases, fuel  
leakage, oil leakage, etc.  
nDespite the safe design of this generator,  
operating this equipment imprudently, neglect-  
ing its maintenance or being careless can cause  
possible injury or death. Permit only respon-  
sible and capable persons to install, operate or  
maintain this equipment.  
Potentially lethal voltages are generated by  
these machines. Ensure all steps are taken to  
render the machine safe before attempting to  
work on the generator.  
nParts of the generator are rotating and/or hot  
during operation. Exercise care near running  
generators.  
GENERAL HAZARDS  
• For safety reasons, the manufacturer recommends that this  
equipment be installed, serviced and repaired by a Service  
Dealer or other competent, qualified electrician or installation  
technician who is familiar with applicable codes, standards  
and regulations. The operator also must comply with all such  
codes, standards and regulations.  
ELECTRICAL HAZARDS  
• Installation, operation, servicing and repair of this (and related)  
equipment must always comply with applicable codes, stan-  
dards, laws and regulations. Adhere strictly to local, state and  
national electrical and building codes. Comply with regulations  
the Occupational Safety and Health Administration (OSHA) has  
established. Also, ensure that the generator is installed, operat-  
ed and serviced in accordance with the manufacturer’s instruc-  
tions and recommendations. Following installation, do nothing  
that might render the unit unsafe or in noncompliance with the  
aforementioned codes, standards, laws and regulations.  
• All stationary emergency generators covered by this manual  
produce dangerous electrical voltages and can cause fatal  
electrical shock. Utility power delivers extremely high and dan-  
gerous voltages to the transfer switch as well as the generator.  
Avoid contact with bare wires, terminals, connections, etc.,  
on the generator as well as the transfer switch, if applicable.  
Ensure all appropriate covers, guards and barriers are in place  
before operating the generator. If work must be done around  
an operating unit, stand on an insulated, dry surface to reduce  
shock hazard.  
• Do not handle any kind of electrical device while stand-  
ing in water, while barefoot, or while hands or feet are wet.  
DANGEROUS ELECTRICAL SHOCK MAY RESULT.  
. F v e 0 5 / 1 0  
S a f e t y 0 0 4 R  
1-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Instructions  
• If personnel must stand on metal or concrete while installing,  
FIRE HAZARDS  
operating, servicing, adjusting or repairing this equipment,  
place insulative mats over a dry wooden platform. Work on the  
equipment only while standing on such insulative mats.  
• The National Electrical Code (NEC) requires the frame and  
external electrically conductive parts of the generator to be con-  
nected to an approved earth ground. This grounding will help  
prevent dangerous electrical shock that might be caused by a  
ground fault condition in the generator or by static electricity.  
Never disconnect the ground wire.  
• Keep a fire extinguisher near the generator at all times. Do NOT  
use any carbon tetra-chloride type extinguisher. Its fumes are  
toxic, and the liquid can deteriorate wiring insulation. Keep the  
extinguisher properly charged and be familiar with its use. If  
there are any questions pertaining to fire extinguishers, consult  
the local fire department.  
EXPLOSION HAZARDS  
• Wire gauge sizes of electrical wiring, cables and cord sets must  
be adequate to handle the maximum electrical current (ampac-  
ity) to which they will be subjected.  
• Before installing or servicing this (and related) equipment, make  
sure that all power voltage supplies are positively turned off at  
their source. Failure to do so will result in hazardous and pos-  
sibly fatal electrical shock.  
• Properly ventilate any room or building housing the generator to  
prevent build-up of explosive gas.  
• Do not smoke around the generator. Wipe up any fuel or oil  
spills immediately. Ensure that no combustible materials are left  
in the generator compartment, or on or near the generator, as  
FIRE or EXPLOSION may result. Keep the area surrounding the  
generator clean and free from debris.  
• Connecting this unit to an electrical system normally supplied  
by an electric utility shall be by means of a transfer switch so as  
to isolate the generator electric system from the electric utility  
distribution system when the generator is operating. Failure to  
isolate the two electric system power sources from each other  
by such means will result in damage to the generator and may  
also result in injury or death to utility power workers due to  
backfeed of electrical energy.  
• These generators may operate using one of several types  
of fuels. All fuel types are potentially FLAMMABLE and/or  
EXPLOSIVE and should be handled with care. Comply with all  
laws regulating the storage and handling of fuels. Inspect the  
unit’s fuel system frequently and correct any leaks immediately.  
Fuel supply lines must be properly installed, purged and leak  
tested according to applicable fuel-gas codes before placing  
this equipment into service.  
• Stationary emergency generators installed with an automatic  
transfer switch will crank and start automatically when normal  
(utility) source voltage is removed or is below an acceptable  
preset level. To prevent such automatic start-up and possible  
injury to personnel, disable the generator’s automatic start cir-  
cuit (battery cables, etc.) before working on or around the unit.  
Then, place a “Do Not Operate” tag on the generator control  
panel and on the transfer switch.  
• Diesel fuels are highly FLAMMABLE. Gaseous fluids such  
as natural gas and liquid propane (LP) gas are extremely  
EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier  
than air; install leak detectors accordingly.  
• In case of accident caused by electric shock, immediately  
shut down the source of electrical power. If this is not pos-  
sible, attempt to free the victim from the live conductor. AVOID  
DIRECT CONTACT WITH THE VICTIM. Use a nonconducting  
implement, such as a dry rope or board, to free the victim from  
the live conductor. If the victim is unconscious, apply first aid  
and get immediate medical help.  
• Never wear jewelry when working on this equipment. Jewelry  
can conduct electricity resulting in electric shock, or may get  
caught in moving components causing injury.  
CALIFORNIA PROPOSITION 65 WARNING  
Engine exhaust and some of its constituents are known  
to the State of California to cause cancer, birth defects  
and other reproductive harm.  
CALIFORNIA PROPOSITION 65 WARNING  
This product contains or emits chemicals known to the  
State of California to cause cancer, birth defects and  
other reproductive harm.  
. F v e 0 5 / 1 0  
S a f e t y 0 0 4 R  
1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
NOTE:  
IDENTIFICATION RECORD  
For actual information related to this particular model, please  
refer to the Manual Drawing Listing located at the end of this  
manual, or to the data label affixed to the unit.  
DATA LABEL  
Every generator set has a DATA LABEL that contains important  
information pertinent to the generator. The data label, which can be  
found attached to the generator’s lower connection box, lists the  
unit’s serial number and its rated voltage, amps, wattage capacity,  
phase, frequency, rpm, power factor, production date, etc.  
Stationary Emergency Generator Model and Serial  
Number  
This number is the key to numerous engineering and manufactur-  
ing details pertaining to your unit. Always supply this number  
when requesting service, ordering parts or seeking information.  
Data Label  
. D v e 0 5 / 1 0  
I d e n t y 0 0 5 R  
2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Equipment Description  
EQUIPMENT DESCRIPTION  
COOLANT RECOMMENDATIONS  
Use a mixture of half low silicate ethylene glycol base anti-freeze  
and deionized water. Cooling system capacity is listed in the  
specifications. Use only deionized water and only low silicate  
anti-freeze. If desired, add a high quality rust inhibitor to the rec-  
ommended coolant mixture. When adding coolant, always add the  
recommended 50-50 mixture.  
This equipment is a revolving field, alternating current Stationary  
Emergency Generator. It is powered by a gaseous fueled engine  
operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for  
2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear  
units. See the Specifications section for exact numbers. The unit  
comes complete with a sound attenuated enclosure, internally  
mounted muffler, control console, mainline circuit breaker, bat-  
tery charger, and protective alarms as explained in the following  
paragraph.  
Do not use any chromate base rust inhibitor  
with ethylene glycol base anti-freeze or chro-  
All AC connections, including the power leads from the alterna-  
tor, 120 volt battery charger input and control connections to the  
transfer switch are available in the main connection box.  
mium hydroxide (“green slime”) forms and will  
cause overheating. Engines that have been  
operated with a chromate base rust inhibitor  
must be chemically cleaned before adding eth-  
ylene glycol base anti-freeze. Using any high  
silicate anti-freeze boosters or additives will  
also cause overheating. The manufacturer also  
recommends that any soluble oil inhibitor is  
NOT used for this equipment.  
The Stationary Emergency Generator incorporates the following  
alternator features:  
• Rotor and Stator insulation is Class F rated as defined by NEMA  
MG1-32.6, NEMA MG1-1.66. The generator is self ventilated  
and drip-proof constructed.  
• The voltage waveform deviation, total harmonic content of the  
AC waveform and telephone influence factor have been evalu-  
ated and are acceptable according to NEMA MG1-32.  
Do not remove the radiator pressure cap while  
the engine is hot or serious burns from boiling  
liquid or steam could result.  
ENGINE OIL RECOMMENDATIONS  
The unit has been filled with 5W-20 engine oil at the factory. Use  
a high-quality detergent oil classified “For Service SJ or SH.”  
Detergent oils keep the engine cleaner and reduce carbon deposits.  
When changing the engine oil, be sure to use 5W-30 engine oil  
(synthetic oil is recommended).  
Ethylene glycol base antifreeze is poisonous.  
Do not use mouth to siphon coolant from the  
radiator, recovery bottle or any container. Wash  
hands thoroughly after handling. Never store  
used antifreeze in an open container because  
animals are attracted to the smell and taste of  
antifreeze even though it is poisonous to them.  
Any attempt to crank or start the engine before  
it has been properly serviced with the recom-  
mended oil may result in an engine failure.  
NOTE:  
For temperatures below 32° F, it is strongly recommended to  
use the optional Cold Weather Start Kit. The oil grade for tem-  
peratures below 32° F is 5W-30 synthetic oil.  
. D v 0 7 / 1 1  
E q u i p 0 0 7 R e  
3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Engine Protective Devices  
OVERCRANK SHUTDOWN  
ENGINE PROTECTIVE DEVICES  
The Stationary Emergency Generator may be required to operate  
for long periods of time without an operator on hand to monitor  
such engine conditions as coolant temperature, oil pressure or  
rpm. For that reason, the engine has several devices designed to  
protect it against potentially damaging conditions by automatically  
shutting down the unit when the oil pressure is too low, the coolant  
temperature is too high, the coolant level is too low, or the engine  
is running too fast.  
After a prespecified duration of cranking, this function ends the  
cranking if the engine has failed to start. The overcrank message  
will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn  
switch back to AUTO to reset the generator control board.  
NOTE:  
If the fault is not corrected, the overcrank feature will continue  
to activate.  
NOTE:  
Approximate Crank Cycle Times  
• 15 seconds ON  
• 7 seconds OFF  
• 7 seconds ON  
Engine protective switches and sensors are mentioned here for  
the reader’s convenience. Also refer to the applicable control  
panel manual for additional automatic engine shutdown infor-  
mation.  
• 7 seconds OFF  
• Repeat for 45 seconds  
• Approximately 90 seconds total.  
HIGH COOLANT TEMPERATURE SENDER  
An analog coolant temperture sender, located in the engine's  
cooling system will cause an engine shutdown if the temperature  
should exceed approximately 125° C (257° F). The generator will  
automatically restart once the temperature has returned to a safe  
operating level.  
OVERSPEED SHUTDOWN  
A speed circuit controls engine cranking, start-up, operation and  
shutdown. Engine speed signals are delivered to the circuit board  
whenever the unit is running. Should the engine overspeed above  
a safe, preset value, the circuit board initiates an automatic engine  
shutdown. Contact the nearest Authorized Dealer if this failure  
occurs.  
LOW COOLANT LEVEL SENSOR  
To prevent overheating, the engine has a low coolant level sensor.  
If the level of engine coolant drops below the level of the low cool-  
ant level sensor, the engine automatically shuts down.  
RPM SENSOR LOSS SHUTDOWN  
If the speed signal to the control panel is lost, engine shutdown  
will occur.  
LOW OIL PRESSURE SWITCH  
This switch has normally closed contacts that are held open by  
engine oil pressure during cranking and operating. Should oil pres-  
sure drop below the 8 psi range, switch contacts close, and the  
engine shuts down. The unit should not be restarted until oil is  
added, and the AUTO/OFF/MANUAL switch must be turned to OFF  
and then back to AUTO.  
DC FUSES  
A fuse (7.5 amp) is located on the control panel. It protects the  
panel components from damaging overload. Always remove this  
fuse before commencing work on the generator. The unit will not  
start or crank if the fuse is blown.  
A fuse (25 amp) is located in the engine wire harness adjacent  
to the DC alternator. It is used to prevent circuit failure due to DC  
alternator falure. It will also protect the system in the event of a  
wiring short-dircuit. If this fuse is blown, the generator will not  
operate. Replace these fuses with the same size, type, and rating.  
. B v e 0 5 / 1 0 r o t 0 0 E 3 n g R P  
4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fuel System  
NATURAL GAS FUEL SYSTEM  
FUEL SYSTEM  
Natural gas is supplied in its vapor state. In most cases, the gas  
distribution company provides piping from the main gas distribu-  
tion line to the standby generator site. The following information  
applies to natural gas fuel systems.  
FUEL REQUIREMENTS  
The Stationary Emergency Generator may be equipped with one of  
the following fuel systems:  
• Gas pressure in a building is usually regulated by national, state  
and local codes.  
To reduce gas pressure to a safe level before the gas enters a  
building, a primary regulator is needed. The natural gas supplier  
may or may not supply such a regulator.  
• It is the responsibility of the gas supplier to make sure sufficient  
gas pressure is available to operate the primary regulator.  
• Gas pressure at the inlet to the fuel shutoff solenoid must never  
exceed approximately 14 inches water column (0.5 psi).  
• Natural gas fuel system  
• Propane vapor (LPV) fuel system  
Recommended fuels should have a Btu content of at least 1,000  
Btu's per cubic foot for natural gas; or at least 2,520 Btu's per  
cubic foot for LP gas. Ask the fuel supplier for the Btu content of  
the fuel.  
NOTE:  
The fuel consumption requirements are identified in the  
Specifications section of the Owner's Manual. Refer to the  
Installation Manual if assistance is required for the sizing of  
the pipe diameter for the generator. Any piping used to connect  
the generator to the fuel supply should be of adequate size to  
achieve the 100% load fuel consumption requirements identi-  
fied in the Specifications section regardless of actual load.  
PROPANE VAPOR WITHDRAWAL FUEL SYSTEM  
This type of system utilizes the vapors formed above the liquid  
fuel in the supply tank. Approximately 10 to 20 percent of the tank  
capacity is needed for fuel expansion from the liquid to the vapor  
state. The vapor withdrawal system is generally best suited for  
smaller engines that require less fuel. The installer should be aware  
of the following:  
NOTE:  
TherecommendedfuelpressureisidentifiedintheSpecifications  
section this manual.  
• When ambient temperatures are low and engine fuel consump-  
tion is high, the vapor withdrawal system may not function  
efficiently.  
• Ambient temperatures around the supply tank must be high  
enough to sustain adequate vaporization, or the system will not  
deliver the needed fuel volume.  
NOTE:  
It is the responsibility of the installer to make sure that only  
the correct recommended fuel is supplied to the generator fuel  
system. Thereafter, the owner/operator must make certain that  
only the proper fuel is supplied.  
• In addition to the cooling effects of ambient air, the vaporization  
process itself provides an additional cooling effect.  
. F e v 0 4 / 1 1  
u F e l S y s 0 0 1 R  
5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Engine Lubrication System  
SPECIFICATIONS  
Type of Oil Pump ...............................................................Gear  
Oil Filter .......................................................Full Flow, Cartridge  
Crankcase Oil Capacity ............................................ 4 U.S. qts.  
STANDBY EMERGENCY GENERATOR  
Type......................................................................Synchronous  
Rotor Insulation.............................................................Class H  
Stator Insulation............................................................Class H  
Alternator Output Leads 3-phase.....................................4-wire  
Bearings ..................................................................Sealed Ball  
Coupling ................................................................Flexible Disc  
Load Capacity (Standby Rating)...............................25/30 kW*  
COOLING SYSTEM  
Type............................................................................... Closed  
Water Pump............................................................. Belt Driven  
Fan Speed.........................................................................2484  
Fan Diameter...........................................................17.7 inches  
Fan Mode....................................................................... Pusher  
Air Flow (inlet air including alternator and  
* NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE  
J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate  
with natural gas.  
3
combustion air) ..................................................1800 ft /min.  
Excitation System ............................................................Direct  
Generator Output Voltage/kW - 60 Hz  
kW  
120/240V, 1-phase, 1.0 pf 25/30  
120/208V, 3-phase, 0.8 pf 25/30  
120/240V, 3-phase, 0.8 pf 25/30  
Coolant Capacity....................................................2.0 U.S. gal.  
Heat Rejection to Coolant (25/35kW) ....112,000/135,000 Btu/h  
Maximum Operating Air Temp. on Radiator......... 60° C (150° F)  
Maximum Ambient Temperature......................... 50° C (140° F)  
Amp  
104/125  
87/104  
75/90  
CB Size  
125/150  
100/125  
90/100  
FUEL SYSTEM  
Generator Locked Rotor KVA Available @ Voltage Dip of 35%  
Type of Fuel ....................................Natural Gas, Propane Vapor  
Carburetor............................................................... Down Draft  
Secondary Fuel Regulator............................................ Standard  
Fuel Shut-off Solenoid................................................. Standard  
Operating Fuel Pressure .................5 in. - 14 in. Water Column  
25kW  
35 KVA  
30kW  
45 KVA  
ENGINE  
Make ........................................................................... Generac  
Model .............................................................................In Line  
Cylinders and Arrangement .....................................................4  
Displacement...............................................................1.6 Liter  
Bore..............................................................................3.15 in.  
Stroke...........................................................................3.13 in.  
Compression Ratio....................................................... 9.5-to-1  
Air Intake System......................................... Naturally Aspirated  
Valve Seats............................................................ Replaceable  
Lifter Type.................................................................. Hydraulic  
Spark Plug Gap........................................0.76mm (0.030 inch)  
Fuel Consumption - ft3/hr (Natural Gas/LPV)  
Exercise  
Cycle  
25%  
Load  
50%  
Load  
75%  
Load  
100%  
Load  
25kW  
30kW  
60/24  
60/24  
120/48 220/87 310/123 390/155  
145/58 260/103 370/147 470/187  
ELECTRICAL SYSTEM  
Battery Charge Alternator......................................12V, 15 Amp  
Static Battery Charger ....................................... 2.0 or 2.5 Amp  
Recommended Battery.................................Group 26, 525CCA  
System Voltage............................................................ 12 Volts  
Engine Parameters  
Rated Synchronous RPM .......................................60 Hz, 3600  
Voltage Regulator  
Type...........................................................................Electronic  
Sensing ................................................................Single-phase  
Regulation........................................................................± 1%  
Features.........................Adjustable Voltage and Automatic Gain  
Exhaust System  
Exhaust Flow at Rated Output 60 Hz: 25kW  
240 cfm  
30kW  
260 cfm  
1025°F  
Exhaust Temp. at Rated Output:  
975°F  
Power Adjustment for Ambient Conditions  
Temperature Deration:  
3% for every 10° C above °C  
Combustion Air Requirements (Natural Gas)  
25kW 30kW  
Flow at rated power, 60 Hz:  
25kW  
90 cfm  
30kW  
95 cfm  
40  
104  
25  
77  
1.65% for every 10° above °F  
Altitude Deration:  
1% for every 100 m above m  
Governor  
Type...........................................................................Electronic  
Frequency Regulation.............................................Isochronous  
Steady State Regulation ................................................± .25%  
Adjustments:  
25kW 30kW  
915  
2000  
182  
600  
3% for every 1000 ft. above ft.  
Controller ................................................................. Nexus  
Speed..................................................................... Selectable  
. C v e 1 2 / 1 1  
G e n S p e c 0 8 2  
6-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
9. Install the previously removed black pipe onto the outlet  
WEATHER AND MAINTENANCE KITS  
To keep the generator running at its peak, the following kits are  
offered:  
port of the demand regulator. Use pipe sealant on the pipe  
threads.  
10. Reverse steps 1-4 in this procedure to reactivate the demand  
• Cold Weather Kit  
regulator.  
~ Recommended for climates with temperatures below 32° F.  
• Extreme Cold Weather Kit  
11. Follow the instructions in the Control Panel section.  
~ Recommended Block Heater Kit for protection in tempera-  
tures below 32° F.  
• Scheduled Maintenance Kit  
~ Kit includes the recommended parts to maintain the genera-  
tor. Refer to the Service Schedule for regular maintenance  
intervals.  
Serious injury, including death, or damage  
will occur if not configured properly. Please  
consult an Authorized Dealer with any ques-  
tions.  
For additional information, or to order any of these kits, please  
contact an Authorized Service Dealer or Customer Service  
Representative.  
Figure 6.1 — Reconfigure the Fuel System  
RECONFIGURING THE FUEL  
SYSTEM  
NOTE:  
All models are configured to run on natural gas from the fac-  
tory.  
Before the generator can be operated using a LP fuel source, the  
fuel system and control panel (refer to the installation drawing for  
location) must be reconfigured. The steps to reconfigure the gen-  
erator from a natural gas (NG) to a liquidified petroleum (LP) fuel  
source are as follows:  
FUEL SYSTEM  
1. Turn the main gas supply off and disconnect the battery.  
2. Remove the carburetor fuel hose from the outlet port of the  
demand regulator (see Figure 6.1).  
3. Disconnect the power wires from the fuel solenoid located  
on top of the regulator assembly by removing the screw on  
the front of the connector and pulling the connector forward,  
away from the solenoid body.  
CONTROL PANEL  
The FUEL TYPE must be reconfigured in the control panel to final-  
ize the conversion process. This generator is configured at the  
factory to operate on natural gas. If conversion to LP is required,  
please complete the mechanical conversion process and then call  
888-9ACTIVATE for the control panel password. This fuel selection  
conversion is required to be password protected by Environmental  
Protection Agency [EPA] regulations.  
4. Loosen the spring clamp on the small fuel enrichment line and  
remove the hose from the hose barb.  
5. Remove the black pipe assembly from the outlet port of the  
demand regulator. The solenoid assembly may need to be  
removed before performing this operation (Figure 6.1).  
6. Remove the NG fuel jet (loosen counter clockwise) from the  
outlet port.  
7. Remove the LP fuel jet (loosen counter clockwise) from the jet  
keeper port on the side of the regulator housing. Install this jet  
into the outlet port in the regulator casting.  
Whenever the Generator’s Fuel Regulator is  
converted from one Fuel type to the other,  
the Control Panel must be reconfigured for  
the correct fuel type. Failure to convert both  
the Regulator and Control Panel will result in  
decreased performance and an increase in  
emissions, and is a violation of EPA regula-  
tions.  
NOTE:  
The jet sizes are stamped on the individual jets. The larger jet  
size is used for running on NG.  
8. Install the previously removed NG jet into the jet keeper port  
on the side of the regulator housing.  
. C v e 1 2 / 1 1  
G e n S p e c 0 8 2 R  
6-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
ALTERNATOR AC LEAD  
ALTERNATOR POWER WINDING  
CONNECTIONS  
CONNECTIONS  
The electrical wires in the unit’s AC connection (lower) panel  
should be installed according to the number of leads and the  
voltage/phase required for the application. The voltage and phase  
are described on the generator data label. The number of lead  
wires can be identified using the Specifications section and the  
power output rating on the generator data label. For example, if  
the generator produces 130kW, 277/480 Volt, 3-phase power, the  
generator has 12 alternator output leads. Figure 7.3 describes the  
stator power winding connection for the generator.  
3-PHASE ALTERNATORS ("Y" CONFIGURATION)  
The Stationary Emergency Generator is designed to supply  
3-phase electrical loads. Electric power is produced in the alterna-  
tor power windings. These windings were connected at the factory  
to the main circuit breaker with a “Y” configuration as shown in  
Figures 7.2 through 7.6.  
The rated voltage between circuit breaker terminals E1-E2, E1-E3  
and E2-E3 is 480V, 208V or 600V depending on the model.  
The rated voltage between each circuit breaker terminal and the  
neutral point 00 is 277V, 120V, or 346V depending on the model.  
FOUR-LEAD, SINGLE-PHASE STATOR  
Four-lead alternators (see Figure 7.1) are designed to supply elec-  
trical loads with voltage code A” (240V, 1-phase, 60 Hz). Electrical  
power is produced in the stator power windings. These windings  
were connected at the factory to the main circuit breaker as shown  
in Figure 7.1.  
Figure 7.2 — Stator Power Winding  
Connections - 3-phase, 277/480V (6 Lead)  
E1  
The rated voltage between each circuit breaker terminal is 240V.  
The rated voltage between each circuit breaker terminal and the  
neutral point 00 is 120V.  
S1  
INTERNAL  
CONNECTIONS  
Figure 7.1 — Four-lead, Single-phase Stator  
L - L  
S4  
S6  
00 (NEUTRAL)  
S5  
S2  
S3  
E3  
E2  
L - N  
Figure 7.3 — Stator Power Winding  
Connections - 3-phase, 277/480V (12 Lead)  
E1  
S1  
S4  
S7  
L - L  
S12  
S10  
S9  
S8  
S11  
S6  
S5  
S2  
S3  
E3  
E2  
L - N  
. B v e 0 5 / 1 0  
A C C o n n 0 0 7 R  
7-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
Figure 7.4 — Stator Power Winding  
Connections - 3-phase, 120/208V (6 Lead)  
3-PHASE ALTERNATORS ("DELTA" CONFIGURATION)  
The Stationary Emergency Generator is designed to supply  
3-phase electrical loads. Electric power is produced in the alterna-  
tor power windings. These windings were connected at the factory  
to the main circuit breaker with a “Delta” configuration as shown  
in Figures 7.7 and 7.8.  
INTERNAL CONNECTIONS  
E1  
S1  
S1  
The rated voltage between circuit breaker terminals E1-E2, E1-E3  
and E2-E3 is 240V.  
The rated voltage between E1 or E3 and the neutral point 00 is  
120V.  
L-L  
S4  
S6  
S4  
00 (NEUTRAL)  
S5  
Figure 7.7 — Stator Power Winding  
Connections - 3-phase, 120/240V (6 Lead)  
S3  
S2  
S6 S5  
E2  
E3  
E2  
S3  
S2  
S6  
S2  
L-N  
INTERNAL  
CONNECTIONS  
Figure 7.5 — Stator Power Winding  
Connections - 3-phase, 120/208V (12 Lead)  
L - L  
E1  
S7  
S1  
S3  
S5  
E1  
E3  
S4  
S1  
L-L  
S10  
S12  
S4  
L - N  
S5  
00 (NEUTRAL)  
S9  
S2  
S6 S11  
Figure 7.8 — Stator Power Winding  
Connections - 3-phase, 120/240V (12 Lead)  
E3  
E2  
S3  
S8  
L-N  
E2  
S12  
S2  
Figure 7.6 — Stator Power Winding  
Connections - 3-phase, 346/600V (6 Lead)  
E1  
S5  
S9  
S1  
INTERNAL  
L - L  
CONNECTIONS  
S8  
S6  
L - L  
S3  
S11  
S4  
S6  
00 (NEUTRAL)  
E1  
E3  
S10  
S1  
S5  
L - N  
00 (NEUTRAL)  
S2  
E2  
S3  
E3  
L - N  
. B v e 0 5 / 1 0  
A C C o n n 0 0 7 R  
7-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
Upon power up, this controller will go through a system self test  
CONTROL PANEL INTERFACE  
which will check for the presence of utility voltage on the DC  
circuits. This is done to prevent damage if the installer mistakenly  
connects AC utility power sense wires into the DC terminal block.  
If utility voltage is detected, the controller will display a warning  
message and lock out the generator, preventing damage to the  
controller. Power to the controller must be removed to clear this  
warning.  
USING THE AUTO/OFF/MANUAL SWITCH  
With the switch set to AUTO, the engine may  
crank and start at any time without warning.  
Such automatic starting occurs when utility  
power source voltage drops below a preset  
level or during the normal exercise cycle. To  
prevent possible injury that might be caused  
by such sudden starts, always set the switch  
to OFF and remove the fuse before work-  
ing on or around the generator or transfer  
switch. Then, place a “DO NOT OPERATE”  
tag on the generator panel and on the trans-  
fer switch.  
Utility voltage must be turned on and present at the N1 and N2  
terminals inside the generator control panel for this test to be  
performed and pass.  
NOTE:  
DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT  
WIRES IS NOT WARRANTABLE!  
This test will be performed each time the controller is powered  
up.  
Next, the user must enter the minimum settings to operate. These  
settings are current date and time and exercise day and time. The  
maintenance intervals will be initialized (i.e. started) the first time  
the clock is set. If the clock is never set at power up, the mainte-  
nance intervals will be reset every time power is applied.  
1. AUTO” Position – Selecting this switch activates fully auto-  
matic system operation. It also allows the unit to automati-  
cally start and exercise the engine every seven days with the  
setting of the exercise timer (see the Setting the Exercise  
Timer section).  
2. “OFF” Position – This switch position shuts down the engine.  
If a subsequent power loss (loss of battery power) occurs the  
Installation assistant will operate upon power restoration. The self  
test routine will be run and then the customer will be required to  
re-enter the time and date, as this is not retained during a power  
loss. The unit will not require re-activation.  
This position also prevents automatic operation.  
3. “MANUAL Position – Set the switch to MANUAL to crank  
and start the engine. Transfer to standby power will not occur  
unless there is a utility failure.  
ACTIVATE THE GENERATOR  
When battery power is applied to the generator during the instal-  
lation process, the controller will turn ON and the LCD screen will  
illuminate. However, the generator still needs to be activated before  
it will automatically run in the event of a power outage.  
DISPLAY INTERFACE MENUS  
The LCD display is organized as detailed below:  
• The “Home” page, this page is the default page which will be  
displayed if no keys are pressed for 30 seconds. This page  
normally shows the current Status message and the current  
date and time. The highest priority active Alarm and/or Warning  
will be automatically posted on this page as well as flashing  
the backlight when such an event is detected. In the case of  
multiple Alarms or Warnings, only the first message will be  
displayed. To clear an Alarm or Warning, see the Protection  
Systems section - Clear Alarm.  
• The display backlight is normally off. If the user presses any  
key, the backlight will come on automatically and remain on for  
30 seconds after the last key was pressed.  
• The “Main Menu” page will allow the user to navigate to all other  
pages or sub-menus by using the Left/Right and Enter keys.  
This page can be accessed at any time with several presses of  
the dedicated Escape key. Each press of the Escape key takes  
you back to the previous menu until the main menu is reached.  
This page displays the following options: HISTORY; STATUS;  
EDIT; AND DEBUG. (See the Appendix - "Menu System".)  
Activating the generator is a simple one time process that is guided  
by the controller screen prompts. Once the product is activated,  
the controller screen will not prompt you again, even if you discon-  
nect the generator battery.  
To obtain the activation code, record the generator serial number  
and log onto www.activategen.com or call 1-888-9ACTIVATE and  
follow the steps to retrieve the activation code.  
After obtaining your activation code, please complete the following  
steps at the generator’s control panel in the Activation Chart on the  
following page.  
NOTE:  
The generator will only run in manual until the passcode has  
been entered.  
. E v e 1 2 / 1 1  
C n t r l N e x u s u s 0  
8-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
ACTIVATION CHART  
CHOOSE LANGUAGE  
TROUBLESHOOTING  
Display Reads:  
Use ARROW keys to scroll to desired lan-  
guage. Press ENTER to select.  
If the wrong language is chosen, it can be  
changed later using the “edit” menu.  
Language  
-
English  
+
Escape  
Enter  
Display Reads:  
Press ENTER to begin the activation pro-  
cess.  
If ESCAPE is pressed instead of ENTER,  
your generator will only run in manual mode  
(for test purposes) and NOT ACTIVATED will  
be displayed. You will need to remove the  
generator control panel fuse AND disconnect  
the T1, N1 and N2 connector in the external  
connection box (if equipped); or disconnect  
utility input (main breaker) to the transfer  
switch for 3-5 seconds and reconnect, then  
begin with Step 1.  
Activate me (ENT) or  
ESC to run in manual  
Escape  
Enter  
Display Reads:  
If you do not have your activation code,  
go to www.activategen.com or call  
1-888-9ACTIVATE (922-8482).  
To Activate go to  
www.activategen.com  
If you already have your activation code,  
wait 3-5 seconds for the next display.  
Escape  
Enter  
ENTER ACTIVATION CODE (Passcode)  
TROUBLESHOOTING  
Display Reads:  
Use ARROW keys to scroll and find the first  
number of your Activation Code.  
Serial 123456789  
Passcode XXXXX +/-  
Press ENTER to select.  
Repeat this step until all digits have been  
entered.  
Escape  
Enter  
Use ESCAPE to correct previous digits.  
Display Reads:  
Activation is complete when all digits are  
entered above and your screen shows this  
display.  
What happens if “Wrong Passcode Try  
Again” appears?  
“SELECT HOUR (0-23)”  
“-  
Re-enter the activation code. If a second  
attempt is unsuccessful, check the number  
against the code given on activategen.com.  
If it is correct and the generator will not  
accept it, contact 1-888-9ACTIVATE (922-  
8482).  
6
+”  
Follow the controller prompts to continue  
setting the time function. Refer to your  
Owner’s Manual with questions.  
Escape  
Enter  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1 R  
8-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
• If utility is still lost after the “line interrupt period”, run the engine  
INSTALLATION ASSISTANT  
Interconnect System Self Test Feature (follow the on-screen  
prompts).  
up to normal RPM and transfer the load. At this time the con-  
troller will exit the exercise routine and assume full automatic  
operation.  
Upon power up, this controller will go through a system self test  
which will check for the presence of utility voltage on the DC  
circuits. This is done to prevent damage if the installer mistakenly  
connects AC utility power sense wires into the DC terminal block.  
If utility voltage is detected, the controller will display a warning  
message and lock out the generator, preventing damage to the  
controller. Power to the controller must be removed to clear this  
warning.  
USER ADJUSTABLE SETTINGS  
Factory  
Default  
Minimum  
Setting  
Maximum  
Setting  
Setting  
Increment  
1 min  
Exercise  
time  
23:59  
(11:59 pm)  
2 pm  
Wed  
00:00 (12 am)  
Sun  
Exercise  
day  
Utility voltage must be turned on and present at the N1 and N2  
terminals inside the generator control panel for this test to be  
performed and pass.  
Sat  
1 day  
Current  
Time  
23:59  
(11:59 pm)  
12 am 00:00 (12 am)  
1 min  
NOTE:  
Current  
Day  
Sun  
Jan  
Sun  
Jan  
Sat  
Dec  
1 day  
DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT  
WIRES IS NOT WARRANTABLE!  
Current  
Month  
1 month  
1 year  
This test will be performed each time the controller is powered  
up.  
Current  
Year  
2008  
2008  
2100  
Upon first power up of the generator, the display interface will  
begin an installation assistant. The assistant will prompt the user  
to set the minimum settings to operate. These settings are simply:  
Current Date/Time and Exercise Day/Time. The maintenance inter-  
vals will be initialized when the exercise time is entered.  
Language  
Contrast  
English  
80%  
French  
0%  
Spanish  
100%  
N/A  
1%  
The exercise settings can be changed at any time via the "EDIT"  
menu (see Appendix, "Menu System").  
FUEL CONVERSION  
For fuel conversion steps, refer to the GenSpec section,  
RECONFIGURING THE FUEL SYSTEM.  
If the 12 volt battery is disconnected or the fuse removed, the  
Installation Assistant will operate upon power restoration. The  
only difference is the display will only prompt the customer for the  
current Time and Date.  
OPERATION  
IF THE INSTALLER TESTS THE GENERATOR PRIOR TO  
INSTALLATION, PRESS THE “ENTER” KEY TO AVOID SETTING  
UP THE EXERCISE TIME. THIS WILL ENSURE THAT WHEN  
THE CUSTOMER POWERS UP THE UNIT, HE WILL STILL BE  
PROMPTED TO ENTER AN EXERCISE TIME.  
This system is intended to supply standby power in the event of a  
utility failure. The control system will monitor the utility voltage to  
determine if stand-by power is required. Should the utility voltage  
fail, the generator will start and run normally, detaching from the  
utility and supplying the customer load from the generator. When  
utility power returns, the controller will re-transfer the customer  
load back to utility and shut down the generator.  
SETTING THE EXERCISE TIMER  
This generator is equipped with an exercise timer. Once it is set,  
the generator will start and exercise every seven days, on the day  
of the week and at the time of day specified. During this exercise  
period, the unit runs for approximately 12 minutes and then shuts  
down. Transfer of loads to the generator output does not occur  
during the exercise cycle unless utility power is lost.  
AUTOMATIC TRANSFER OPERATION  
To select automatic operation, do the following:  
1. Make sure the transfer switch main contacts are set to their  
UTILITY position, i.e., loads connected to the utility power  
source.  
2. Be sure that normal UTILITY power source voltage is avail-  
able to transfer switch terminal lugs N1 and N2 (Refer to the  
Electrical Data section).  
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO.  
4. Set the generator’s main circuit breaker to its ON (or CLOSED)  
position.  
With the preceding steps complete, the generator will start auto-  
matically when utility source voltage drops below a preset level.  
After the unit starts, loads are transferred to the standby power  
source. Refer to the Sequence of Automatic Operation section.  
LOW SPEED EXERCISE  
The standard start sequence will be initiated.  
• All 1800 rpm units will exercise at 1400 RPM  
• All 3600 rpm units will exercise at 1800 RPM  
If utility is lost during exercise the controller will do the following:  
• Wait for the “line interrupt period” for utility to return. If utility  
returns within the “line interrupt period”, continue to exercise  
at low RPM.  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1  
8-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
SEQUENCE OF AUTOMATIC OPERATION  
Initial Conditions: Generator in Auto ready to run, load being sup-  
plied by the Utility Source through the transfer switch.  
MANUAL START  
Allows the user to start and run the generator manually.  
Transfer of the load to the generator will occur if utility is lost while  
the unit is running in the manual mode (only if activated).  
1. When the utility voltage fails (falls below 60% of nominal), a  
10-30 second (programmable) “line interrupt” delay timer is  
started. The factory set time delay is 10 seconds. If at the  
end of the line interrupt time the utility voltage is above 60%  
the engine will not crank. If the utility voltage is still below  
the 60% of nominal at the end of the line interrupt time, the  
unit will crank and start. If the unit cranks for more than 10  
seconds and the utility voltage rises above 80% of nominal  
(programmed pickup voltage) and the unit has not started, the  
crank cycle will abort.  
2. As soon as the unit starts a 5 second “warm-up” timer is initi-  
ated. When the warm-up timer expires the control will transfer  
the load to the generator (through the RTS switch) if the utility  
voltage is less than 80% of nominal. If the utility voltage is  
greater than the 80% of nominal at the end of the warm-up  
time the load will not be transferred to the generator and a one  
minute low-speed cool down period will start. At the end of  
the one minute cool down period the generator will stop.  
3. Once the unit is running and the switch has transferred the  
load to the generator the unit will monitor utility voltage.  
When utility voltage returns (above the programmable pickup  
voltage, normally 80% of nominal), a 15 second “Return to  
Utility” timer will start. At the end of the return to utility time,  
if the utility voltage is still above the pickup voltage, the unit  
will transfer the load back to the utility source and run the unit  
through a one minute cool down period. When the cool down  
period is over the unit will shut down and be ready for the next  
outage.  
ALARM AND WARNING MESSAGES  
Alarms are defined as “Latching” which means they must be  
cleared before the alarm message on the screen will clear. They  
can be of type “Shutdown” or not and are logged in the alarm log.  
Alarms are all annunciated on the display).  
Warnings are “Non Latching” meaning the message automati-  
cally clears when the warning condition goes away. Warnings can  
not be of type “Shutdown” but they are logged in the alarm log.  
Warnings are all annunciated on the display.  
LOW OIL PRESSURE SHUTDOWN ALARM  
There is a 10 second delay before oil pressure is monitored.  
HIGH COOLANT TEMPERATURE SHUTDOWN ALARM  
There is a 10 second delay before engine temperature is moni-  
tored.  
Once running there is a 1/4 second delay before shut down. The  
limit is set at 125° C or 257° F.  
OVERCRANK SHUTDOWN ALARM  
Occurs if the engine has not started within the specified crank  
cycle.  
4. If during the cool down period utility voltage should fall below  
60% of nominal the 5 second warm-up timer is initiated and  
the unit will transfer the load back to the generator and con-  
tinue to monitor the utility.  
OVERSPEED SHUTDOWN ALARM  
Warning indicator is measured and calculated by the microproces-  
sor. Overspeed is defined as +20% of nominal engine speed for 3  
seconds, or +25% immediate.  
CRANK CYCLES AND OVERCRANK SHUTDOWN  
If the unit fails to start during a cranking period it will display the  
Overcrank Shutdown Alarm. The system will control the cranking  
cycles as follows:  
Nominal engine speed = 60.0 Hz  
RPM SENSOR FAILURE SHUTDOWN ALARM  
During cranking: If the board does not see a valid RPM signal  
within four (4) seconds of cranking it will shut down and lock out  
on RPM sensor loss.  
The first crank cycle is a 16 second crank time followed by a 7  
second rest. The next 5 cycles will be 7 seconds of cranking time  
each followed by a 7 second rest time.  
If the unit fails to start by the end of the 6 crank/rest cycles  
the Overcrank Shutdown Alarm will display and the unit will not  
attempt to crank until the alarm is reset.  
During running: If the RPM signal is lost for one full second the  
board will shut the engine down, wait 15 seconds, then re-crank  
the engine if in AUTO, it will not re-crank in MANUAL.  
If no RPM signal is detected within the first four (4) seconds of  
cranking, the control board will shut the engine down and latch out  
on RPM sensor loss.  
AUTO START  
This unit is designed to automatically start in the event of a util-  
ity failure or brown out condition. Brown out is defined as utility  
voltage less than 60% nominal, while utility is considered good  
when it is restored to at least the pickup value, 80% of nominal.  
These levels are fixed. The “Line Interrupt period” is an adjustable  
parameter by the dealer. If 2-wire start mode is activated, the unit  
will start when 2-wire start is active.  
If the RPM signal is detected the engine will start and run normally.  
If the RPM signal is subsequently lost the control board will try  
two more re-cranks before latching out and flashing the RPM  
Sensor Failure message (if it is in AUTO).  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1 R  
8-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
Figure 1 – Generator Control Panel  
CHECK ENGINE MESSAGE  
MISSING CAM PULSE ALARM  
The control system has detected an emissions related fault. This  
fault cannot be cleared using the control panel interface. The unit  
will continue to operate in automatic mode. Contact your local  
servicing dealer.  
This is a shutdown alarm. The alarm will activate after five (5)  
seconds of continuously missing cam pulses.  
MISSING CRANK PULSE ALARM  
This is a shutdown alarm. The alarm will activate after 12 con-  
secutive revs where crank pulses are missing.  
UNDER-FREQUENCY SHUTDOWN ALARM  
After starting, if the generator stays under frequency for more than  
30 seconds, it will shutdown.  
LOW FUEL PRESSURE WARNING  
Fuel pressure is monitored by a digital sensor with a fixed setpoint  
of below five (5) inches water column.  
LOW BATTERY ALARM  
While running, if the average battery voltage falls below 11.9 volts  
for one (1) minute, the low battery alarm will be displayed.  
GOVERNOR SENSOR FAULT ALARM  
The governor position is monitored by an analog feedback signal. If  
the throttle position is seen outside of the normal operating range,  
a shutdown alarm is displayed. If the throttle is commanded to  
move, and no movement is seen, a shutdown alarm is displayed.  
LOW BATTERY WARNING  
The microprocessor will continually monitor the battery voltage  
and display the Low Battery Voltage message if the battery voltage  
falls below 12.2 Volts for one (1) minute.  
WIRING ERROR ALARM  
No other action is taken on a low battery warning condition. The  
warning will automatically clear if the battery voltage rises above  
12.2 volts.  
When power is first apllied to the contoller, the software will per-  
form a check on the wiring of the transfer output, and ensure it  
does not have high voltage on the wire. If this is the case, it will  
signal a miswire alarm and will not run. The test can be skipped  
by use of the escape key.  
NOTE:  
The battery sentinel is a separate feature that monitors battery  
condition.  
UNDERVOLTAGE ALARM  
If the generator voltage falls below 60% for >5 seconds, an alarm  
will be issued.  
LOW COOLANT LEVEL ALARM  
This is a shutdown alarm. The sensor will be continuously moni-  
tored. If an error condition is seen for five (5) consecutive sec-  
onds, the alarm will be displayed.  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1  
8-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
OVERVOLTAGE ALARM  
ALARM CANCEL  
If the generator voltage rises above 110% for >3 seconds, an  
alarm will be issued.  
When the generator is shut down due to a latching alarm, the Auto  
/Off/ Manual switch must be set to the off position and the ENTER  
key pressed to unlatch any active fault and clear the corresponding  
fault alarm message.  
If the generator voltage rises above 130% for >0.2 seconds, an  
alarm will be issued.  
INTERNAL FAILURE SHUTDOWN ALARM  
Any internal failure that can be detected such as corrupted  
firmware will cause this shutdown alarm. This alarm cannot be  
cleared.  
COMMON ALARM RELAY  
The common alarm relay will be activated if there is a shutdown  
alarm. It will not activate on warnings or indicate that the Auto/Off/  
Manual switch is in the OFF position. The OFF position will clear  
the alarms and the relay. The relay will not be used to indicate a  
generator is not activated.  
CANBUS ALARM  
The common alarm connections are wired to a set of potential-  
free (dry) contacts on the Nexus controller board. These Normally  
Open (N.O.) contacts close when an alarm condition occurs and  
are used to activate a remote signaling device. The circuit is rated  
for a maximum of 130mA at 24 VDC. The connections are a short  
set of free hanging wires that exit the engine harness loom directly  
behind the Nexus Control Panel and are labeled numbers 209 and  
210.  
Where applicable, if the Canbus communications link fails to com-  
municate, a “Canbus Alarm” will be generated. This only applies  
to systems with external ignition modules. The alarm may be  
generated if:  
1. The physical link is broken.  
2. The Ignition Module fails or resets.  
3. The Nexus Controller fails or resets.  
4. Having the Battery Chargers 120 VAC connected without a  
battery installed.  
MAINTENANCE ALERTS  
Maintenance alerts will be provided for these conditions.  
5. A blown 10 amp Ignition Module fuse (approximately 12  
inches away from the starter).  
6. A blown 25 amp system fuse (located approximately 12  
inches away from the DC alternator).  
NOTE:  
SERVICE SCHEDULE A’  
Inspect Accessory Drive Alert  
Coolant Change & Flush  
1yr / 100hrs*  
1yr / 100hrs  
1yr / 100hrs  
1yr / 100hrs*  
1yr / 100hrs  
1yr / 100hrs  
6mo / 50hrs*  
The “Canbus Alarm” will not clear on its own. To clear the  
alarm, press the “enter” key to acknowledge the alarm. The  
alarm will clear and if the fault is still present, the alarm will  
reoccur.  
Inspect Spark Plugs Alert  
Change Oil & Filter Alert  
IGNITION ALARM  
When an ignition alarm occurs, a generic message “Ignition Fault”  
will be displayed as the fault code.  
Inspect Battery Alert  
Change / Inspect Air Filter Alert  
Clean/Inspect Air Inlet & Exhaust  
* Items require a 3 month / 30 hour break-in change or check.  
MAINTENANCE WARNING  
When a maintenance period expires, a warning message will be  
posted. The warning can be reset by hitting the Enter key. Resetting  
will clear the warning and reset the maintenance counters for the  
condition annunciated. The history log will reflect the maintenance  
warning.  
SERVICE SCHEDULE ‘B’  
Change / Inspect spark plugs alert  
2yr/ 250hr  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1 R  
8-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
. E v e 1 2 / 1 1  
C n t r l N e x u s 0 0 1  
8-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
STATIONARY EMERGENCY  
GENERATOR CONTROL AND  
OPERATION  
Do not crank the engine continuously for lon-  
ger than 30 seconds, or the heat may  
damage the starter motor.  
n
Refer to the appropriate control panel operator’s manual for this  
unit.  
• Let engine stabilize and warm up.  
• Check all applicable instrument and gauge readings. When  
certain that all readings are correct, move the transfer switch  
manual handle to the STANDBY (or EMERGENCY STANDBY)  
position, i.e., load circuits supplied by the generator.  
• Set the generator’s main line circuit breaker to its ON (or  
CLOSED) position.  
OPERATING UNIT WITH MANUAL  
TRANSFER SWITCH  
If the Stationary Emergency Generator was installed in conjunction  
with a transfer switch capable of manual operation only, the fol-  
lowing procedure applies. A manually operated transfer switch is  
one that will not provide automatic start-up and does not include  
an intelligence circuit.  
• Load circuits are now powered by the generator.  
RETRANSFER AND SHUTDOWN  
For additional information, refer to the applicable control panel  
manual for this unit, as well as any literature pertaining to the  
specific transfer switch.  
ENGINE START-UP AND TRANSFER  
For additional information, refer to the applicable control panel  
manual for this unit, as well as any literature pertaining to the  
specific transfer switch.  
To transfer the load back to the utility power source and shut down  
the generator, follow these directions:  
• Set the generator’s main line circuit breaker to its OFF (or OPEN)  
position.  
• Manually move the transfer switch handle to its UTILITY  
(NORMAL) position, i.e., load circuits connected to the utility.  
• Turn ON the utility power supply to the transfer switch, using  
the means provided (such as the utility power source main line  
circuit breaker).  
• Let the generator run at no-load for a few minutes to stabilize  
internal temperatures.  
• Shut down the generator.  
nThe Maintenance Disconnect Switch and the  
AUTO/OFF/MANUAL switches (if so equipped)  
must be set properly, or the generator will  
crank and start as soon as the utility power to  
the transfer switch is turned off. Refer to appli-  
cable control panel and transfer switch manuals  
for more information.  
nDo not proceed until certain that utility source  
voltage is available to the transfer switch and  
OPERATING UNIT WITH AUTOMATIC  
the transfer switch main contacts are set to  
UTILITY.  
TRANSFER SWITCH  
Do not attempt manual operation until all  
power supplies to the transfer switch have been  
If the Stationary Emergency Generator has been installed with an  
automatic transfer switch, the engine may be started and stopped  
automatically or manually.  
positively turned off, or extremely dangerous -  
possibly lethal - electrical shock will result.  
NOTE:  
Transfer switch enclosure doors should be kept  
closed and locked. Only authorized personnel  
Refer to the applicable manual for your transfer switch and to  
“Transfer Switch Start Signal Connections”. In addition, please  
note the dangers under “Engine Start-up and Transfer.”  
should be allowed access to the transfer switch  
interior. Extremely high and dangerous voltages  
are present in the transfer switch.  
In order to transfer load from the utility source to the generator,  
follow these directions:  
• Turn OFF or disconnect the utility power circuit to the transfer  
switch, using the means provided (such as the utility source  
main line circuit breaker).  
• Set the transfer handle to its UTILITY (NORMAL) position with  
load circuits connected to the utility power supply.  
• Set the generator’s main line circuit breaker to its OFF (or OPEN)  
position.  
• Start the generator.  
. D v e 0 5 / 1 0  
O p e r 0 0 1 R  
9-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Refer to the Service Schedule for engine oil and filter change fre-  
quencies.  
GENERAL MAINTENANCE  
Drain the oil while the engine is still warm from running. This  
means warm up the engine, shut it down and drain immediately  
as follows:  
Before working on the Stationary Emergency  
Generator, ensure the following:  
• The AUTO/OFF/MANUAL switch is in the OFF position.  
• The control panel fuse has been removed from the control  
box.  
1. Remove the drain hose from its retaining clip or cut the zip-tie  
securing the oil drain hose.  
2. Loosen and remove OIL DRAIN HOSE CAP. Drain oil com-  
• The 120VAC supply to the battery charger is switched OFF.  
• The negative battery cable has been removed.  
pletely into suitable container.  
3. When all oil has drained, install and tighten OIL DRAIN HOSE  
CAP and secure drain hose with a new zip-tie, or place the  
hose in its retaining clip.  
CHECK ENGINE OIL  
Check engine crankcase oil level (Figure 10.1) according to the  
Service Schedule and SIB10-10-L24G.  
4. Turn OIL FILTER (Figure 10.1) counterclockwise and remove.  
Properly dispose of old filter.  
5. Apply light coating of new engine oil to seal of new oil fil-  
ter. Install FILTER and tighten by hand only. DO NOT OVER  
TIGHTEN.  
• Remove oil dipstick and wipe dry with a clean, lint-free cloth.  
• Install oil dipstick, then remove again.  
• Oil should be between FULL and ADD marks.  
• If oil level is below the dipstick ADD mark, remove oil fill cap-.  
Add the recommended oil to bring oil level up to the FULL  
mark. DO NOT FILL ABOVE THE “FULLMARK. See “Engine Oil  
Recommendations” for recommended oils.  
6. Remove OIL FILL CAP and add recommended oil. Crankcase  
oil capacity is listed in the "Specifications" section.  
After refilling the crankcase with oil, always  
check oil level on dipstick. NEVER OPERATE  
ENGINE WITH OIL BELOW THE DIPSTICK “ADD”  
MARK.  
n
Figure 10.1 - Oil Dipstick and Oil Fill Cap  
OIL FILL CAP  
7. Start engine and check for oil leaks.  
8. Shut OFF engine and wait 10 minutes for the oil to settle down  
into the oil pan. Recheck oil level on dipstick. DO NOT fill  
above the dipstick "FULL" mark.  
9. Dispose of used oil at a proper collection center.  
COOLING INTAKE/OUTLET  
Air intake and outlet openings in the generator compartment must  
be open and unobstructed for continued proper operation. This  
includes such obstructions as high grass, weeds, brush, leaves  
and snow.  
OIL  
Without sufficient cooling and ventilating air flow, the engine/gen-  
erator quickly overheats, which causes it to shut down. (See the  
installation diagram.)  
DIPSTICK  
The exhaust system parts from this product get  
extremely hot and remains hot after shutdown.  
High grass, weeds, brush, leaves, etc. must  
remain clear of the exhaust. Such materials may  
ignite and burn from the heat of the exhaust  
system.  
OIL  
FILTER  
CHANGING ENGINE OIL  
INSPECT COOLING SYSTEM  
• Inspect engine cooling system. See the Service Schedule.  
• Check hoses for damage, deterioration, leaks, etc. Correct any  
discrepancies found.  
Hot oil may cause burns. Allow engine to cool  
before draining oil. Avoid prolonged or repeat-  
n
ed skin exposure with used oil. Thoroughly  
wash exposed areas with soap.  
• Check hose clamps for tightness.  
. A v e 0 5 / 1 0  
M a i n t 0 2 7 R  
10-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
ENGINE COOLANT  
CHECK FAN BELT  
Checkcoolantlevelincoolantrecoverybottle.See theSpecifications  
and Service Schedule sections.  
• Inspect fan belts every year. Replace any damaged, deterio-  
rated, worn or otherwise defective belt.  
• Check fan belt tension. Thumb pressure, exerted midway  
between pulleys, should deflect about 3/8 to 5/8 of an inch.  
Adjust belt tension as required.  
• Add recommended coolant mixture as necessary.  
• Periodically remove radiator pressure cap (only when engine  
has cooled down) to make sure the coolant recovery system  
is functioning properly. Coolant should be at bottom of radia-  
tor filler neck. If coolant level is low, inspect gasket in radiator  
pressure cap. Replace cap, if necessary. To have pressure cap  
tested, contact a Service Facility. Inspect cooling system and  
coolant recovery system for leaks.  
• Check fan belt alignment (see Figure 10.2).  
Figure 10.2 – Fan Belt  
COOLANT CHANGE  
Every year, have a service facility drain, flush and refill the cooling  
system. See the Specifications and Service Schedule for cooling  
system recommendations.  
OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL  
SYSTEM  
Engine cranking, start up and running are controlled by a solid  
state Engine Controller circuit board. Battery voltage is delivered  
to that circuit board via the control panel fuse. This overcurrent  
protection device will open if the circuit is overloaded.  
INSPECT ENGINE GOVERNOR  
Visually inspect electronic governor.  
If a circuit breaker opens or a fuse element  
melts, find the cause of the overload before  
n
resetting the circuit breaker or replacing the  
fuse.  
Do not attempt to adjust the governor. Only  
EXERCISE SYSTEM  
Starts the Stationary Emergency Generator engine once every  
seven days and lets it run for 12 minutes.  
qualified service facilities should adjust the  
n
governor. Excessively high operating speeds  
are dangerous and increase the risk of personal  
injury. Low speeds impose a heavy load on the  
engine when adequate engine power is not  
available and may shorten engine life. Correct  
rated frequency and voltage are supplied only  
at the proper governed speed. Some connected  
electrical load devices may be damaged by  
incorrect frequency and/or voltage. Only quali-  
fied service technicians should adjust the gov-  
erned speed.  
PERFORM VISUAL INSPECTION  
Complete a thorough visual inspection of the entire engine-genera-  
tor monthly. Look for obvious damage, loose, missing or corroded  
nuts, bolts and other fasteners. Look for fuel, oil or coolant leaks.  
INSPECT EXHAUST SYSTEM  
Inspect the exhaust system at least once every year. Check all  
exhaust system pipes, mufflers, clamps, etc. for condition, tight-  
ness, leaks, security, damage.  
CHANGING THE ENGINE AIR FILTER  
To replace the engine air filter, remove the air filter cover and  
replace the air filter making sure it is positioned properly before  
reattaching the cover (Figure 10.3).  
See the Service Schedule for air filter maintenance.  
. A v e 0 5 / 1 0  
M a i n t 0 2 7 R  
10-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
nBattery electrolyte fluid is an extremely corro-  
sive sulfuric acid solution that can cause severe  
Figure 10.3 – Engine Air Filter  
burns. Do not permit fluid to contact eyes, skin,  
clothing, painted surfaces, etc. Wear protective  
goggles, protective clothing and gloves when  
handling a battery. If fluid is spilled, flush the  
affected area immediately with clear water.  
Do not use any jumper cables or booster bat-  
tery to crank and start the generator engine. If  
the battery has completely discharged, remove  
it from the generator for recharging.  
n
AIR  
FILTER  
Be sure the AUTO/OFF/MANUAL switch is set  
to the OFF position, before connecting the  
battery cables. If the switch is set to AUTO or  
MANUAL, the generator can crank and start as  
soon as the battery cables are connected.  
n
Be sure the 120VAC power supply to the battery  
is turned OFF, or sparking may occur at the bat-  
tery posts as the cables are attached and cause  
an explosion.  
SPARK PLUGS  
Reset the spark plug gap or replace the spark plugs as neces-  
sary.  
1. Clean the area around the base of the spark plugs to keep dirt  
and debris out of the engine. Clean by scraping or washing  
using a wire brush and commercial solvent. Do not blast the  
spark plugs to clean.  
2. Remove the spark plugs and check the condition. Replace  
the spark plugs if worn or if reuse is questionable. See the  
“Service Schedule” section for recommended inspection.  
3. Check the spark plug gap using a wire feeler gauge. See the  
Specifications section for the required spark plug gap.  
BATTERY REPLACEMENT  
NOTE:  
Unit DOES NOT include battery.  
When supplying or replacing the battery, the recommended num-  
ber and type of battery is listed in the Specifications Section.  
NOTE:  
The BCI number should be located directly on the battery.  
BATTERY MAINTENANCE  
The battery should be inspected per the Service Schedule section.  
The following procedure should be followed for inspection:  
BATTERY FLUID  
Check battery electrolyte fluid based on the Service Schedule.  
Fluid should cover separators in all battery cells. If fluid level is  
low, add distilled water to cover tops of separators. DO NOT USE  
TAP WATER IN BATTERY.  
1. Inspect the battery posts and cables for tightness and corro-  
sion. Tighten and clean as necessary.  
2. Check the battery fluid level of unsealed batteries and, if  
necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP  
WATER IN BATTERIES.  
CLEANING THE STATIONARY EMERGENCY GENERATOR  
Keep the generator as clean and as dry as possible. Dirt and  
moisture that accumulates on internal generator windings have an  
adverse effect on insulation resistance.  
3. Have the state of charge and condition checked. This should  
be done with an automotive-type battery hydrometer.  
Periodically clean generator exterior surfaces. A soft brush may be  
used to loosen caked on dirt. Use a vacuum system or dry, low  
pressure air to remove any accumulations of dirt. The generator is  
housed inside an all-weather enclosure, clean the enclosure with a  
soft, damp cloth or sponge and water.  
Storage batteries give off explosive hydrogen  
gas. This gas can form an explosive mixture  
around the battery for several hours after  
charging. The slightest spark can ignite the gas  
and cause an explosion. Such an explosion can  
shatter the battery and cause blindness or other  
injury. Any area that houses a storage battery  
must be properly ventilated. Do not allow smok-  
ing, open flame, sparks or any spark producing  
tools or equipment near the battery.  
Once each year have the generator cleaned and inspected by a  
Service Dealer. That dealer will use dry, low pressure air to clean  
internal windings.  
Finally, have the insulation resistance of stator and rotor windings  
checked. If insulation resistances are excessively low, the genera-  
tor may require drying.  
. A v e 0 5 / 1 0  
M a i n t 0 2 7 R  
10-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Service Schedule  
SERVICE SCHEDULE  
System / Component  
Frequency  
Procedure  
Weekly - W  
Monthly - M  
Yearly - Y  
Inspect  
Change  
Clean  
Fuel  
Fuel Lines & Connections  
Lubrication  
M
X
Oil Level  
M
Y
X*  
Oil  
X**  
X**  
Oil Filter  
Y
Cooling  
Engine Coolant Lines & Connections  
Engine Coolant Level  
Engine Coolant  
M
M
Y
X
X
X
Enclosure Louvers  
Engine  
W
X
X
Air Cleaner  
Y
Y
X
X
X***  
X***  
Spark Plugs  
Battery  
Remove Corrosion, Ensure Dryness  
Clean & Tighten Battery Terminals  
Check Charge State  
Check Electrolyte Level  
General Condition  
Vibration, Noise, Leakage, Temperature  
Generator System  
Complete Tune-up and System Inspection  
Footnotes  
M
M
M
M
X
X
X
X
X
X
X***  
X***  
M
Y
X
To be completed by an Authorized Service Dealer.  
* Inspect the oil level monthly or every 12 hours during continuous operation.  
** Change oil and oil filter after the first 30 hours of operation and then every 100 hours or annually thereafter, whichever occurs first.  
Change sooner when operating under heavy load or in a dusty or dirty environment or in high ambient temperatures.  
*** Replace as necessary.  
. B v e 0 5 / 1 0  
v S S c r h d 0 0 4 R  
11-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
TROUBLESHOOTING GUIDE  
PROBLEM  
Engine won’t crank.  
CAUSE  
CORRECTION  
1. Control panel 7.5 amp fuse blown.  
2. Loose or corroded or defective  
battery cables.  
1. Replace fuse.*  
2. Tighten, clean or replace  
battery cables as necessary.*  
3. Replace contactor.*  
4. Replace starter motor.*  
5. Remove, change or replace battery.*  
3. Defective starter contactor.  
4. Defective starter motor.  
5. Dead or Defective Battery.  
Engine cranks but won't start.  
Engine starts hard, runs rough.  
1. Out of fuel.  
2. Fuel solenoid (FS) is defective  
3. Spark plugs defective.  
1. Replenish fuel/turn on fuel valve.  
2. Replace solenoid.*  
3. Clean, regap or replace plugs.  
1. Air cleaner plugged or damaged.  
2. Defective spark plugs.  
3. Fuel pressure incorrect.  
1. Clean or replace as needed.  
2. Clean, regap or replace plugs.  
3. Confirm fuel pressure to regulator is as  
recommended in SPECIFICATIONS.*  
4. Confirm fuel pressure to regualtor is as  
recommended in SPECIFICATIONS.*  
5. Reconfigure the fuel system. (See  
RECONFIGURING THE FUEL SYSTEM in  
manual.*  
4. Insufficient fuel supply.  
5. Fuel system set to wrong fuel type.  
Engine starts then shuts down.  
1. Engine oil level is low.  
2. Engine is overheated.  
3. Defective Low Oil Pressure Switch  
4. Defective Coolant Temperature Switch  
5. Defective Control Module circuit board.  
6. Coolant Level is Low.  
1. Check oil and add oil as needed.  
2. Check cooling system for leaks.  
3. Replace switch.*  
4. Replace switch.*  
5. Replace board.*  
6. Repair leak - Add coolant.  
7. Replace Switch.*  
7. Defective Low Coolant Level Switch  
AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch  
1. Replace board.*  
2. Replace board.*  
engine continues to run.  
2. Defective Control Module circuit board  
No AC output from generator.  
1. Main line circuit breaker is tripped/open.  
2. Generator internal failure.  
1. Reset to ON/CLOSED.  
2. *  
3. Thermal circuit breaker open.  
3. Auto-reset - Wait 5 min. and attempt restart.  
*Contact the nearest Dealer for assistance.  
. B v e 0 5 / 1 0  
r b T l s h t 0 0 3 R  
12-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
United States Environmental Protection Agency Warranty Statement  
(Stationary Emergency Spark-Ignited Generators)  
Warranty Rights, Obligations and Coverage  
The United States Environmental Protection Agency (EPA) and Generac Power Systems, Inc. (Generac) are pleased to explain the  
Emission Control System Warranty on your new stationary emergency engine. If during the warranty period, any emission control system  
or component on your engine is found defective in materials or workmanship, Generac will repair your engine at no cost to you for diag-  
nosis, replacement parts and labor provided it be done by a Generac Authorized Warranty Service Facility. Your emission control system  
may include parts such as the fuel metering, ignition, and exhaust systems and other related emission related components listed below.  
Generac will warrant the emissions control systems on your 2009 and later model year engines provided there has been no abuse,  
neglect, unapproved modification or improper maintenance of your engine. For engines less than 130 HP the warranty period is two years  
from the date of sale to the ultimate purchaser. For engines greater than or equal to 130 HP the warranty period is three years from the  
date of the engine being placed into service.  
Purchaser's/Owner's Warranty Responsibilities  
As the engine purchaser/owner you are responsible for the following. 1.) The engine must be installed and configured in accordance  
to the Generac's installation specifications. 2.) The completion of all maintenance requirements listed in your Owner’s Manual. 3.) Any  
engine setting adjustment must be done in accordance and consistent with the instructions in the Owner’s Manual. 4.) Any emission con-  
trol system or component must be maintained and operated appropriately in order to ensure proper operation of the engine and control  
system to minimize emissions at all times.  
Generac may deny any/or all Emission Control System Warranty coverage or responsibility of the engine, or an emission control system  
or component on your engine thereof, if it has failed due to abuse, neglect, unapproved modification or improper maintenance, or the use  
of counterfeit and/or 'gray market' parts not made, supplied or approved by Generac. Warranty service can be arranged by contacting  
either your selling dealer or a Generac Authorized Warranty Service dealer, 1-800-333-1322 for the dealer nearest you. The purchaser/  
owner shall be responsible for any expenses or other charges incurred for service calls and/or transportation of the product to/from the  
inspection or repair facilities. The purchaser/owner shall be responsible for any and/or all damages or losses incurred while the engine  
is being transported/shipped for inspection or warranty repairs. Contact Generac Power Systems Inc. for additional Emission Control  
System Warranty related information, Generac Power Systems, Inc. P.O. Box 8, Waukesha, WI 53187, or call 1-800-333-1322 or www.  
generac.com.  
Important Note  
This warranty statement explains your rights and obligations under the Emission Control System Warranty, which is provided to you by  
Generac pursuant to federal law. Note that this warranty shall not apply to any incidental, consequential or indirect damages caused by  
defects in materials or workmanship or any delay in repair or replacement of the defective part(s). This warranty is in place of all other  
warranties, expressed or implied. Specifically, Generac makes no other warranties as to the merchantability or fitness for a particular pur-  
pose. Any implied warranties which are allowed by law, shall be limited in duration to the terms of the express warranty provided herein.  
Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.  
Emission Related Parts Include the Following (if so equipped)  
1) Fuel Metering System  
3)  
4)  
5)  
Ignition System Including  
1.1) Gasoline Carburetor Assembly And Internal  
Components A) Fuel Filter, B) Carburetor, C) Fuel  
Pump  
1.2) Carburetion Assembly And Its Components  
A) Fuel Controller, B) Carburetor And Its Gaskets, C)  
Mixer And It Gaskets, D) Primary Gas Regulator E)  
Liquid Vaporizer  
1.3) Fuel Regulator  
2) Air Induction System Including  
A) Intake Pipe/Manifold,  
A) Spark Plug, B) Ignition Module,  
C) Ignition Coil, D) Spark Plug Wires  
Exhaust System  
A) Catalyst Assembly, B) Exhaust Manifold,  
C) Muffler, D) Exhaust Pipe, E) Muffler Gasket  
Crankcase Breather Assembly Including  
A) Breather Connection Tube, B) Pcv Valve  
Oxygen Sensor  
6)  
7)  
Diagnostic Emission-Control System  
B) Air Cleaner  
. D v e 0 9 / 1 1 n t y 0 0 1 R E m s n W r  
13-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
United States Environmental Protection Agency Compliance Requirements  
(Stationary Emergency Spark-Ignited Generators)  
Purchaser's/Owner's Recordkeeping Responsibilities  
The United States Environmental Protection Agency (EPA) and Generac Power Systems, Inc. (Generac) are pleased to explain your record-  
keeping requirements for compliance with Subpart JJJJ- Standards of Performance for Stationary Spark Ignition Internal Combustion Engines  
as listed in the Electronic Code of Federal Regulations Title 40 Part 60. As the engine purchaser/owner who operates and maintains their  
certified emergency stationary engine and emission control system according to applicable emission related guidelines as specified in this  
Owner's Manual, you are required to meet the following notification and recordkeeping requirements to demonstrate compliance. 1.) Maintain  
documentation that the engine is certified to meet emission standards. 2.) Recordkeeping of maintenance conducted. 3.) Recordkeeping of  
the provision allowing natural gas engines to operate using propane for a maximum of 100 hours per year as an alternate fuel solely dur-  
ing emergency operations provided the engine is not certified to operate on propane. 4.) Meet all compliance notifications submitted to the  
purchaser/owner and maintain all supporting documentation. 5.) Recordkeeping of hours of operation, including what classified the operation  
as emergency and how many hours are spent for non-emergency operation. For emergency engines greater than or equal to 130 HP, record-  
keeping of hours of operation begins January 1, 2011. For emergency engines less than 130 HP, recordkeeping of hours of operation begins  
January 1, 2009; Engines are equipped with non-resettable hour meters to facilitate recordkeeping.  
Specific Air Quality Management or Air Pollution Control Districts may have different and additional record keeping/reporting requirements.  
Your permit to construct and/or operate the engine may be contingent upon compliance with those requirements. Check with your local Air  
Quality Management or Air Pollution Control District for specific requirements.  
Emergency stationary internal combustion engines (ICE) may be operated for the purpose of maintenance checks and readiness testing,  
provided that the tests are recommended by Federal, State or local government, Generac, or the insurance company associated with the en-  
gine. Maintenance checks and readiness testing of such units is limited to 100 hours per year. There is no time limit on the use of emergency  
stationary ICE in emergency situations. The purchaser/owner may petition the Administrator for approval of additional hours to be used for  
maintenance checks and readiness testing, but a petition is not required if the owner maintains records indicating that Federal, State, or local  
standards require maintenance and testing of emergency ICE beyond 100 hours per year. Emergency stationary ICE may operate up to 50  
hours per year in non emergency situations, but those 50 hours are counted towards the 100 hours per year provided for maintenance and  
testing.  
The 50 hours per year for non-emergency situations cannot be used for peak shaving or to generate income for a facility to supply power to  
an electric grid or otherwise supply power as part of a financial arrangement with another entity. For purchaser/owner of emergency engines,  
any operation other than emergency operation, maintenance and testing, and operation in non-emergency situations for 50 hours per year, as  
permitted in this section is prohibited.  
If you operate and maintain your certified emergency stationary SI internal combustion engine and emissions control systems in accordance  
to the specifications and guidelines in this Owner’s Manual EPA will not require engine performance testing. If not, your engine will be consid-  
ered non-certified and you must demonstrate compliance according to Subpart JJJJ - Standards of Performance for Stationary Spark Ignition  
Internal Combustion Engines as listed in the Electronic Code of Federal Regulations Title 40 Part 60.  
Emission-Related Installation Instructions  
Your certified emergency stationary engine has pre-set emission control systems or components that require no adjustment. Inspection and  
replacement of an emissions related component is required to be done so in accordance with the requirements cited in the United States  
Environmental Protection Agency Warranty Statement or can be arranged by contacting either your selling dealer or a Generac Authorized  
Warranty Service dealer, 1-800-333-1322 for the dealer nearest you. Failing to follow these instructions when installing a certified engine in a  
piece of nonroad equipment violates federal law 40 CFR 1068.105 (b), subject to fines or penalties as described in the Clean Air Act.  
. D v e 0 9 / 1 1 n t y 0 0 1 R E m s n W r  
13-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
0G4827  
0G2927  
0G2827  
0G3451  
0G0820A  
0G4452  
020746  
049226  
051713  
022129  
0G4825  
0G4826  
0G2926  
0G3682  
0G5584  
0G3685  
0G2826  
0G3683  
0G6573  
0G3686  
0G3684  
0G3687  
0G5909  
0G6103  
0A5382A  
075591  
051787  
0A5601A  
0G8827  
0G8827A  
0A9375  
022152  
0G4196  
042558  
051756  
0G0965B  
053607  
051769  
023365  
0F3353  
072578  
0G3787  
0A8830  
077043E  
0G2070  
0G2070A  
045771  
1
1
1
1
1
1
4
4
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
4
4
4
4
1
1
4
1
1
1
4
6
1
10  
4
1
1
1
4
ASSY RTR 104 KD1 HI EFF (18KW)  
RTR-102-20.0AD1 CPL (2006) (20KW)  
ASSY RTR 25KW 2P (2006) (25KW)  
ASSY RTR 30KW 2P 10"(2006)  
HOUSINGBLOWER L GPILOT  
BLOWER HOUSINGSCREEN  
SCREW PPHM M5-0.8 X 8 ZINC  
WASHER LOCK M5  
WASHER FLAT M5  
2
3
4
5
6
7
8
WASHER LOCK M8-5/16  
ASSY STR 104-18AD1 HI EFF (18KW)  
ASSY STR 104 18GD1 HI EFF (18KW)  
STR-102-20.0AD1 CPL (2006) (20KW)  
STR-102-20.0GD1 CPL (2006) (20KW)  
STR-102-20.0JD1 CPL (2006) (20KW)  
STR-102-20.0KD1 CPL (2006) (20KW)  
ASSY STR 102 25AD1 (2006) (25KW)  
STR-102-25.0GD1 CPL (2006) (25KW)  
STR-102-25.0-JD1 CPL (2006) (25KW)  
STR-102-25.0KD1 CPL (2006) (25KW)  
STR-102-30.0GD2 CPL (30KW)  
STR-102-30.0KD2 CPL (30KW)  
ASSY STR 102 30AD2 10" (30KW)  
STR-102-30.0JD2  
BEARING CARRIER REAR L G PILOT  
ASSY HOLDER BRUSH  
SCREW HHC M4-0.7 X 16 G8.8  
COVER REAR BEARING  
STUD M8-1.25 475 LONG  
STUD M8-1.25 418 LONG  
SCREW RHM #10-24 X 2  
WASHER LOCK #10  
FLYWHEEL & RINGGEAR ASSY 1.6L  
KEY SQ 3/8 X 1 STEEL  
SCREW HHC M10-1.5 X 20 C8.8  
PLATE FLEX 1.6L R12.7  
SCREW HHC M12-1.75 X 35 G8.8  
WASHER LOCK M12  
WASHER SHAKEPROOF INT #8  
SCREW HHC M10-1.0 X 20 G10.9  
SPACER ROTOR SHAFT  
WASHER .41 ID .94 OD .12 THK  
WASHER FLAT .34 ID X .75 O D  
FLEX CONDUIT 1" BLACK (NOT SHOWN)  
PLATE SPACER 14GA 1.6L (TO BE USED WITH ENGINE PLATE P/N 0G0834.)  
PLATE SPACER 16GA 1.6L (TO BE USED WITH ENGINE PLATE P/N 0G0834A.)  
NUT HEX M8-1.25 G8 CLEAR ZINC  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
(1) 23  
24  
25  
26  
27  
28  
29  
(1) APPLY LOCTITE 242 BEFORE THREADING SCREW INTO CRANKSHAFT.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: CONNECTION BOX C1 CPL  
DRAWING #: 0H7234  
APPLICABLE TO:  
GROUP A  
ITEM  
PART#  
QTY.  
DESCRIPTION  
1
2
(4)3  
4
0H6795  
0H6796  
0H67330ST0R  
0H7115  
022097  
1
1
1
2
2
CONBOX BACK/SIDES C1 CPL  
CONBOX TOP C1 CPL  
BRACKET GIMBAL CONTROL PNL RAW  
KNOB M6-1.0 CONTROL PANEL  
WASHER LOCK M6-1/4  
5
6
(3)7  
8
022473  
SEE CHART  
052777  
4
1
3
WASHER FLAT 1/4-M6 ZINC  
CIRCUIT BREAKER  
WASHER FLAT M3  
9
043182  
3
WASHER LOCK M3  
10  
(4)11  
12  
051714  
0H81040AS0R  
045764  
3
1
2
3
NUT HEX M3-0.5 G8 CLEAR ZINC  
COVER DPE BREAKER NEXUS  
SCREW HHTT M4-0.7 X 8 ZP  
WASHER LOCK #8-M4  
13  
022264  
14  
0A9457  
1
DECAL NEUTRAL  
15  
16  
(2)17  
18  
(4)19  
20  
21  
22  
23  
24  
REF  
1
18  
1
6
1
1
12  
2
2
2
ASSY CTRL PROGRAMMED  
SCREW HWHT M6-1 X 16 N WA Z/JS  
REGULATOR - DC ALT  
NUT FLANGE M6-1.0 NYLOK  
SHIELD HIGH/LOW C1 RAW  
RELAY SOLENOID 12VDC PNL MNT  
SCREW HHSP #10 X 3/8 HI-LOW  
SCREW HHC M6-1.0 X 20 C8.8  
NUT HEX M5-0.8 G8 CLEAR ZINC  
WASHER LOCK M5  
0C2454  
0A1354A  
0D3700  
0H88380ST0R  
056739  
0F5458  
042568  
051716  
049226  
25  
051713  
2
WASHER FLAT M5  
26  
27  
28  
29  
0D7177V  
0F5752F  
0H6267  
056326  
0G3524  
0D7393T  
0D7393U  
0F5376S0AR  
0F5396S0AR  
057073  
2
1
1
1
DIODE BRIDGE 1P 35A 1000V  
RES WW 15R 5% 25W QK CONN  
COVER VOLTAGE SHIELD  
TRIM VINYL BLACK 1/8GP (3”LG)  
COVER BELL HOUSING CONBOX  
TERM BLOCK 3P UL 12-20AWG  
TERM BLOCK 4P UL 12-20AWG  
MX150L SLRRMNT 22-18 8P W/O GA  
MX150L SLRRMNT 22-18 12P W/OGA  
JUNCTION BLOCK 3/8-16  
30  
1
(1)31  
(1)32  
(1)33  
(1)34  
35  
REF  
REF  
REF  
REF  
1
36  
37  
38  
0C2265  
057329  
022237  
3
1
1
SCREW PHTT M4-0.7 X 12 ZP  
LUG SLDLSS 350-#6X13/32 AL/CU  
WASHER LOCK 3/8  
39  
022241  
1
NUT HEX 3/8-16 STEEL  
40  
41  
42  
43  
44  
45  
46  
025433  
023762  
0H7292  
0H7293  
029289  
1
1
1
1
1
1
2
LUG SLDLSS #6-14 X 13/64 CU  
WASHER LOCK EXT #10 STL  
DECAL CUSTOMER CONTROL CONNECT  
DECAL CONBOX TB1 CONNECTIONS  
TAPE ELEC 1/2 FOAM (62” LG)  
DECAL CUSTOMER POWER CONNECT  
WASHER NYLON .257  
0J0489  
0A2115  
47  
48  
49  
50  
51  
52  
0F6146  
1
1
REF  
1
1
HANG TAG 2 WIRE START (NOT SHOWN)  
HARN CONBOX NEXUS (NOT SHOWN)  
FUSE ATO TYPE 7.5AMP (BROWN)  
DECAL GROUND LUG  
GASKET WIRE ENTRY COVER  
DECAL CAUTION ELEC SHOCK SM  
0H6692  
0D7178T  
067210A  
0J6701  
0H8006  
1
UL CIRCUIT BREAKER (225AF)  
A
B
C
D
E
F
G
H
J
0G5249  
REF  
1
1
1
2
2
2
10  
2
2
CB 150A 2 POLE 240V 225AF  
COVER CB G 225AF C1 CONBOX  
INSULATOR CB 2P 225AF  
SPRT CIRCUIT BREAKER G 225AF  
WASHER FLAT #8 ZINC  
WASHER LOCK #8-M4  
NUT HEX #8-32 STEEL  
SCREW HWHT M6-1 X 16 N WA Z/JS  
SCREW RHM #8-32 X 3-1/4  
BUS BAR 200A LUG ADAPTOR  
SCREW SHC M8-1.25 X 20 G8  
0H6846  
0F8432A  
0G5734  
038150  
022264  
022471  
0C2454  
053640  
0F8843  
049897  
K
L
4
REVISION: J-6101-L  
DATE: 8/12/13  
Page 4 of 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: CONNECTION BOX C1 CPL  
DRAWING #: 0H7234  
APPLICABLE TO:  
GROUP A  
ITEM  
PART#  
QTY.  
DESCRIPTION  
M
N
P
R
S
T
U
V
W
X
022129  
022145  
045771  
058306  
0F8451  
6
4
2
2
2
1
1
1
4
1
WASHER LOCK M8-5/16  
WASHER FLAT 5/16-M8 ZINC  
NUT HEX M8-1.25 G8 CLEAR ZINC  
SCREW SHC M8-1.25 X 25 C12.9  
LUG SLDLSS 300 MCM-6 AL/CU  
DECAL TERMINAL SHOCK HZD BI  
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
0G3259  
0J78230AS0R  
029289  
036261  
0K4772  
RIVET POP .125 X .275 SS  
DECAL SERVICE DISCONNECT  
(1) ITEMS INCLUDED WITH HARNESS P/N 0H6692.  
(2) ITEMS USED ON 1.6L MODELS ONLY.  
(3) SEE “C1 DPE BREAKER SELECTION” TABLE.  
(4) SHEET METAL PARTS LISTED IN THE BOM TABLE ARE REPRESENTING GENERIC PARTS (NO COLOR)  
MANUFACTURING: FOR CORRECT MATERIAL AND COLOR REFER TO AS400 BOM.  
CUSTOMER: WHEN ORDERING REPLACEMENT PARTS ENTER BASE NUMBER (FIRST 6 DIGITS ONLY) IN THE  
SYSTEM FOR CORRECT MATERIAL AND COLOR (FOR REFERENCE SEE GUIDELINE 0H7169).  
REVISION: J-6101-L  
DATE: 8/12/13  
Page 5 of 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: CONNECTION BOX C1 CPL  
DRAWING #: 0H7234  
APPLICABLE TO:  
GROUP A  
ITEM  
PART#  
QTY.  
DESCRIPTION  
UL CIRCUIT BREAKER (CC 2P)  
A
0H4745  
REF  
CB 0100A 2P 240V E CC LL  
CB 0125A 2P 240V E CC LL  
CB 0150A 2P 240V E CC LL  
COVER CB E CC 2P C1 CONBOX  
NUT HEX M5-0.8 G8 CLEAR ZINC  
CIRCUIT BREAKER SUPPORT (CC)  
WASHER FLAT #8 ZINC  
WASHER LOCK #8-M4  
NUT HEX #8-32 STEEL  
SCREW HWHT M6-1 X 16 N WA Z/JS  
SCREW RHM #8-32 X 3-1/4  
SCREW PPHM M5-0.8 X 12 ZNC  
WASHER FLAT #10 ZINC  
0H4746  
0H4747  
0H6847  
051716  
0H4656  
038150  
022264  
022471  
0C2454  
053640  
091526  
023897  
049226  
0H4698  
0J78230AS0R  
029289  
036261  
0K4772  
REF  
REF  
1
2
1
2
2
2
10  
2
2
4
2
1
1
1
4
1
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
S
WASHER LOCK M5  
INSULATOR CB 2P E TYPE CC  
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
RIVET POP .125 X .275 SS  
DECAL SERVICE DISCONNECT  
UL CIRCUIT BREAKER (CC/FG (3P) )  
A
0H4913  
REF  
CB 0100 3P 240V E CC LL  
0H4914  
0H5488  
0H5489  
0H7294  
0H4698A  
0H4656  
0H5604  
038150  
022264  
022471  
0C2454  
053640  
0H5721  
091526  
023897  
049226  
051716  
0J78230AS0R  
029289  
036261  
0K4772  
REF  
REF  
REF  
1
1
REF  
REF  
4
4
4
10  
4
4
3
6
3
3
1
1
CB 0125 3P 240V E CC LL  
CB 0080 3P 600V E FG LL  
CB 0090 3P 600V E FG LL  
CB COVER E CC/FG 3P C1 CONBOX  
INSULATOR CB 3P E TYPE CC/FG  
CIRCUIT BREAKER SUPPORT (CC)  
CIRCUIT BREAKER SUPPORT (FG)  
WASHER FLAT #8 ZINC  
B
C
D
E
F
G
H
J
WASHER LOCK #8-M4  
NUT HEX #8-32 STEEL  
SCREW HWHT M6-1 X 16 N WA Z/JS  
SCREW RHM #8-32 X 3-1/4 (CC)  
SCREW PPHM #8-32 X 1-3/4 ZINC (FG)  
SCREW PPHM M5-0.8 X 12 ZNC  
WASHER FLAT #10 ZINC  
K
L
M
N
P
Q
R
S
WASHER LOCK M5  
NUT HEX M5-0.8 G8 CLEAR ZINC  
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
RIVET POP .125 X .275 SS  
DECAL SERVICE DISCONNECT  
4
1
REVISION: J-6101-L  
DATE: 8/12/13  
Page 6 of 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: CONNECTION BOX C1 CPL  
DRAWING #: 0H7234  
APPLICABLE TO:  
GROUP A  
ITEM  
PART#  
QTY.  
DESCRIPTION  
UL CIRCUIT BREAKER (BQ 2P)  
A
0D5543  
REF  
CB 0090A 2P 240V S BQ2 LL  
CB 0100A 2P 240V S BQ2 LL  
CB 0125A 2P 240V S BQ2 LL  
COVER CB S BQ2 C1 CONBOX  
BRKT CB MTG BACK  
CIRCUIT BREAKER SUPPORT (BQ)  
SCREW HHC M5-0.8 X 20 G8.8  
WASHER FLAT #10 ZINC  
0D5544  
0A2077  
0H6842  
0E7890  
0G4497  
052619  
REF  
REF  
1
1
1
B
C
D
E
F
2
4
023897  
G
H
J
K
L
049226  
0C2454  
051716  
0G9708  
022264  
2
10  
2
2
2
WASHER LOCK M5  
SCREW HWHT M6-1 X 16 N WA Z/JS  
NUT HEX M5-0.8 G8 CLEAR ZINC  
SCREW PHTT M4-0.7 X 8 ZP  
WASHER LOCK #8-M4  
M
N
P
R
0J78230AS0R  
029289  
1
1
4
1
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
RIVET POP .125 X .275 SS  
DECAL SERVICE DISCONNECT  
036261  
0K4772  
UL CIRCUIT BREAKER (BQ 3P)  
A
062812  
053691  
040532  
0H6843  
0E6002  
0G4497  
052619  
REF  
CB 0080A 3P 240V S BQ3 LL  
CIRCT BRK 90 X 3 ITE BQ3-B090  
CB 0100A 3P 240V S BQ3 LL  
COVER CB S BQ3 C1 CONBOX  
MTG TRACK BQ SIEMENS CB 3P  
CIRCUIT BREAKER SUPPORT (BQ)  
SCREW HHC M5-0.8 X 20 G8.8  
WASHER FLAT #10 ZINC  
REF  
REF  
1
1
1
B
C
D
E
F
3
6
023897  
G
H
J
K
L
049226  
0C2454  
051716  
0G9708  
022264  
3
10  
3
2
2
WASHER LOCK M5  
SCREW HWHT M6-1 X 16 N WA Z/JS  
NUT HEX M5-0.8 G8 CLEAR ZINC  
SCREW PHTT M4-0.7 X 8 ZP  
WASHER LOCK #8-M4  
M
N
P
R
0J78230AS0R  
029289  
1
1
4
1
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
RIVET POP .125 X .275 SS  
036261  
0K4772  
DECAL SERVICE DISCONNECT  
UL CIRCUIT BREAKER (ED 3P)  
A
0D5552  
REF  
REF  
REF  
REF  
1
1
4
4
4
CB 0050A 3P 480V S ED4 LL  
CB 0090A 3P 480V S ED4 LL  
CB 0100A 3P 480V S ED4 LL  
CB 0125A 3P 480V S ED4 LL  
COVER CB S ED3 C1 CONBOX  
CIRCUIT BREAKER SUPPORT (ED)  
WASHER FLAT #8 ZINC  
0D5556  
0D5557  
0D9693  
0H6844  
0G4498  
038150  
B
C
D
E
F
022264  
022471  
WASHER LOCK #8-M4  
NUT HEX #8-32 STEEL  
G
H
J
K
L
M
N
P
R
0A8278  
0C2454  
066715  
3
10  
4
3
3
1
1
4
1
SCREW SHC 1/4-28 X 3/4 G8.8 NZ  
SCREW HWHT M6-1 X 16 N WA Z/JS  
SCREW RHM #8-32 X 4-1/2  
WASHER LOCK M6-1/4  
WASHER-STEP 1/2ODX9/32ID BRASS  
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
022097  
0D5621  
0J78230AS0R  
029289  
036261  
0K4772  
RIVET POP .125 X .275 SS  
DECAL SERVICE DISCONNECT  
UL CIRCUIT BREAKER (QN2 2P)  
A
B
C
D
E
F
0E7283  
REF  
1
1
1
2
CB 0150A 2P 240V S QN2 LL  
0H6845  
0E3664  
0G4112  
074908  
0C2454  
COVER CB S QN2 C1 CONBOX  
BASE, QN CIRCUIT BREAKER  
BREAKER SUPPORT BRACKET 30KW  
SCREW HHTT M5-0.8 X 10 BP  
SCREW HWHT M6-1 X 16 N WA Z/JS  
10  
REVISION: J-6101-L  
DATE: 8/12/13  
Page 7 of 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: CONNECTION BOX C1 CPL  
DRAWING #: 0H7234  
APPLICABLE TO:  
GROUP A  
ITEM  
PART#  
QTY.  
DESCRIPTION  
G
H
J
0J78230AS0R  
029289  
1
1
4
1
SHIELD CB HANDLE CONBOX  
TAPE ELEC 1/2 FOAM  
RIVET POP .125 X .2  
036261  
0K4772  
K
DECAL SERVICE DISCONNECT  
REVISION: J-6101-L  
DATE: 8/12/13  
Page 8 of 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
0G3418  
0G3421  
0G3419  
0E9837B  
0G3553  
0E3257  
0G4080  
099502  
0G4070  
0G4072  
0G4071  
046627  
052250  
022473  
022097  
0C8566  
045771  
0C2454A  
042568  
0G3573  
0G3574  
0G3420  
080713  
076749  
048031C  
029032  
0G4451  
055934N  
0F9504  
0G0568  
0G3433  
0E2507  
0H1827  
0A2628  
029333A  
042907  
027482  
022129  
039253  
0H1851  
1
1
1
1
1
2
1
6
1
1
1
1
2
8
8
4
4
28  
4
1
1
1
1
1
2
1
REF  
2
1
1
1
1
1
1
10  
4
RADIATOR SUPPORT LH SIDE 1.6L  
VENTURI 1.6L  
RADIATOR SUPPORT RH SIDE 1.6L  
RADIATOR 1.6L CHY  
FAN COOL 450MM DIA 7 BLADE  
SCREW HWHTF M6-1.0 X 16  
HOSE LOWER RADIATOR 1.6L  
CLAMP HOSE #24 B1.06-2.00  
HOSE REAR COOLANT 1.6L  
TUBE ENGINE COOLANT 1.6L  
HOSE UPPER RADIATOR 1.6L  
CAP RADIATOR  
TAPE FOAM 1 X 1 (24” LG)  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
SCREW HHFC M6-1.0 X 20 G8.8  
NUT HEX M8-1.25 G8 CLEAR ZINC  
SCREW THF M6-1 X 12 N WA Z/JS  
SCREW HHC M6-1.0 X 20 G8.8  
GUARD FAN LH C1  
GUARD FAN RH C1  
RADIATOR BLOCK-OFF  
BRACKET COOLANT TANK  
TANK COOLANT RECOVERY  
CLAMP HOSE BAND 1/4  
HOSE 9/32 ID (43” LG)  
BRACKET STEPPER MOTOR COOLANT  
CLAMP VINYL 1.31 X .281 Z  
GROMMET 5/8"X 1 1/8"X 5/16"  
ASSY FAN BEARING SUPPORT  
BRACKET FAN ALT ADAPTER 1.6L  
PROBE COOLANT LEVEL 3/8NPTF  
PROBE COOLANT LEVEL 3/8-18NPTF (USE WITH I/N 40, P/N 0H1851)  
PULLEY - FAN 95 DIA  
TIE WRAP UL 7.4" X .19" BLK (NOT SHOWN)  
SCREW HHC M8-1.25 X 16 G8.8  
WASHER SHAKEPROOF EXT 5/16 STL  
WASHER LOCK M8-5/16  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
(1) 36  
37  
38  
39  
4
4
4
1
SCREW HHC M8-1.25 X 20 G8.8  
ASSY PCB LCL SENSOR (USE WITH I/N 33, P/N 0H1827 ONLY)  
(2) 40  
(1) APPLY LOCTITE 242 TO I/N 36 BEFORE THREADING INTO I/N 31.  
(2) USE WITH R-200 CONTROL PANEL ONLY.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: MOUNTING BASE 1.6L  
DRAWING #: 0G3531  
APPLICABLE TO:  
GROUP C  
ITEM  
PART#  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
13  
14  
15  
16  
17  
18  
19  
0G3343  
027482  
070936  
070936C  
039253  
022145  
022129  
045771  
071956  
051730  
021991  
026850  
0G3461  
055414  
047411  
022097  
022473  
025507  
1
1
2
MOUNTING BASE 1.6L 2007 C1  
WASHER SHAKEPROOF EXT 5/16 STL  
DAMPENER VIBRATION  
VIB. ISO. 70-75 DURO  
SCREW HHC M8-1.25 X 20 G8.8  
WASHER FLAT 5/16 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 YEL CHR  
WASHER FLAT M8  
SCREW HHC M8-1.25 X 60 G8.8  
EARTH STRAP  
WASHER SHAKEPROOF EXT 1/4 STL  
ALTERNATOR SUPPORT BLOCK OFF  
LUG SLDLSS #2-#8 X 17/64 CU  
SCREW HHC M6-1.0 X 16 G8.8  
WASHER LOCK M6-1/4  
2
12  
16  
16  
4
4
4
1
1
2
1
1
1
5
1
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK EXT 7/16 STL  
REVISION: H-5975-B  
DATE: 2/5/10  
Page 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
0F3408C  
0F3411  
025507  
059980  
046526  
077483  
050331A  
050331  
038805J  
038804M  
045771  
022131  
027482  
0F3976  
0C2454  
022145  
1
1
1
1
1
REF  
REF  
REF  
1
1
REF  
1
BATTERY TRAY, C1 & C2  
STRAP BATTERY RETAINMENT  
WASHER SHAKEPROOF EXT 7/16 STL  
SCREW HHC M10-1.5 X 25 G10.9  
WASHER LOCK M10  
BATTERY 12VDC 75-AH 26  
BATTERY POST COVER RED +  
BATTERY POST COVER BLK -  
CABLE BATTERY BLACK #1 X 30.00  
CABLE BATTERY RED #1 X 21.00  
NUT HEX M8-1.25 G8 YEL CHR  
WASHER FLAT 3/8-M10 ZINC  
WASHER SHAKEPROOF EXT 5/16 STL  
BOOT CONTACTOR CABLES  
SCREW THF M6-1 X 16 N WA Z/JS  
WASHER FLAT 5/16-M8 ZINC  
1
1
4
REF  
NOTE: WHEN INSTALLING BATTERY, TUCK BATTERY’S LIFTING STRAP ALONG  
THE LEFT SIDE OF BATTERY ( SIDE OPPOSITE RADIATOR) BEFORE  
CONNECTING THE BATTERY CABLES.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: ENGINE COMMON PARTS 1.6L  
DRAWING #: 0H7219  
APPLICABLE TO:  
GROUP D  
ITEM  
PART#  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
0H1734  
0G0834A  
0G0820A  
0G7461  
0G0839  
0G0781  
0G0722  
0G4059  
0G4604  
0G3424  
0G0786  
0G4605  
0F9617A  
0A1354B  
0G0823  
0G3900  
0D2244M  
036710  
REF  
1
REF  
1
2
1
1
1
1
1
1
1
1
1
1
1
1
2
ENGINE GENERAC 1.6L G11 CERT  
ENGINE PLATE 1.6L 6MM (TO BE USED WITH PLATE SPACER P/N 0G2070A.)  
HOUSING BLOWER LG PILOT  
STARTER MOTOR 12V  
ENGINE MOUNTING FOOT STAMPING  
EXHAUST MANIFOLD 1.6L MACHINED  
INTAKE MANIFOLD MACHINED 1.6L  
SHIELD 1.6L EXHAUST HEAT  
DC ALTERNATOR ADAPTER MACHINED  
PULLEY CRANKSHAFT MACHINED  
WASHER PULLEY  
BRACKET TENSIONER DC ALT  
SPACER ALTERNATOR  
DC ALTERNATR HAN-KOK  
V-BELT 3/8 X 30.6  
CAP, 1.5" HOLE SHALLOW  
ASSY MAGPICKUP (3/8-24 MALE)  
PIN SPRING 1/4 X 3/4  
SCREW HHC M12-1.5 X 40 G10.9  
SCREW HHC M10-1.5 X 25 G10.9  
WASHER LOCK M10  
WASHER FLAT 3/8-M10 ZINC  
NUT HEX M10-1.5 CLASS 10 ZINC  
GASKET INTAKE MANIFOLD 1.6L  
GASKET EXHAUST MANIFOLD 1.6L  
NUT TOP LOCK FL M8-1.25  
SCREW HHC M10-1.5 X 70 G8.8  
SCREW HHC M10-1.5 X 110 G10.9  
SCREW HHC M10-1.5 X 40 G10.9  
SCREW HHC M8-1.25 X 35 G8.8  
WASHER LOCK M8-5/16  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
61  
62  
63  
64  
65  
0C5479  
059980  
046526  
1
13  
22  
18  
9
1
1
14  
1
4
4
1
4
3
1
3
3
4
4
5
3
5
1
1
1
1
1
1
1
1
1
3
29  
1
1
1
1
022131  
0G3922  
0G0464  
0G0465  
052858  
051735  
0G3920  
0A7387  
039414  
022129  
022145  
029333A  
057821  
045771  
022507  
022097  
WASHER FLAT 5/16-M8 ZINC  
TIE WRAP UL 7.4" X .19" BLK  
SCREW HHC M8-1.25 X 40 G8.8  
NUT HEX M8-1.25 G8 CLEAR ZINC  
SCREW HHC 1/4-20 X 1/2 G5  
WASHER LOCK M6-1/4  
022473  
090388  
WASHER FLAT 1/4-M6 ZINC  
SCREW HHTT M6-1.0 X 12 ZINC  
WASHER FLAT M10 HEAVY DUTY  
TEMPERATURE SENDER, DELPHI  
BSHG RDCR HEX 1/4 TO 1/8  
HARN LOW OIL PRESS SWITCH ASSY  
ADAPTER DRAIN OIL  
0A5768  
0E0502  
035579  
0H7435  
0C1852  
069860C  
069811  
HOSE OIL DRAIN ASSY 21"  
CAP HEX 1/4 NPT BRASS  
0G38580ST03  
025065  
STRUT LH 1.6L ENG ADAPT PLATE  
NIPPLE PIPE 3/8 NPT X 1-1/2  
PIPE TEE 3/8 NPT  
SCREW HWHTF M6-1.0 X 16  
WASHER FLAT .34 ID X .75 OD  
HARN ENG G1.6L G11 NEXUS (NOT SHOWN)  
OIL FILTER 1.6L  
CONDUIT FLEX .25"ID (6” LG)  
STRUT RH 1.6L ENG ADAPT PLATE  
BARBED STR 3/8 NPT X 3/8  
027738A  
0E3257  
0A8830  
0H6690  
0G02070100  
077043H  
0G38620ST03  
055596  
0C7649  
0H2250  
0G3433  
049541  
0G7311  
0G4451  
0F4001E  
1
3
1
REF  
1
REF  
1
1
CLAMP HOSE .38-.87  
HOSE COOLANT 3/8 ID 20R3 (11” LG)  
BRACKET FAN ALT ADAPTER 1.6L  
SCREW HHC M10-1.5 X 35 G8.8  
DECAL EMISSION CTRL INFO 1.6L  
BRACKET STEPPER MOTOR COOLANT  
ANCHOR HARNESS  
REVISION: H-8414-C  
DATE: 3/1/11  
Page 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: FUELSYS NG/LPV 1.6L CPL  
DRAWING #: 0H6671  
APPLICABLE TO:  
GROUP E  
ITEM  
PART#  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
037561  
0A5547  
062522  
022127  
059402  
091526  
049226  
0E0519A  
048031J  
0E6586  
0G1397E  
0F7790  
0E7121  
0G4573C  
0E8286  
047527  
057823  
035685  
057753B  
0E4395  
022129  
0A6344  
048031L  
0G1985  
047290  
047290  
0F3994  
0G3178  
048031P  
059057  
045771  
051767  
022097  
039253  
0G9348  
026812  
076691  
026490  
075580  
0D1509  
075436  
022145  
026915  
0E6586A  
1
1
1
1
1
4
4
1
4
1
1
1
2
1
1
1
2
2
1
1
2
1
4
1
1
1
1
1
1
1
2
4
5
2
1
2
1
1
1
1
1
2
1
1
NUT WING 1/4-20 NYLK  
COVER AIR CLEANER  
STUD TH 1/4-20 X 3 G2 ZNC FULL  
NUT HEX 1/4-20 STEEL  
FILTER ELEMENT  
SCREW PPHM M5-0.8 X 12 ZNC  
WASHER LOCK M5  
ADAPTER, CARBURETOR W/PVC CONN  
CLAMP HOSE BAND .63  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
(1)36  
(1)37  
(1)38  
(1)39  
40  
41  
42  
(1)43  
44  
GASKET BOSCH 32 & 40  
FUEL REG. REWORK 1.6L  
VENTURI THROTTLE 21MM  
O-RING 47.625 ID X 2.38 WIDTH  
MIXER ACTUATOR 32MM MACHINED  
STREET EL 45D 1/2 NPT BRASS  
BARBED STR 1/2 NPT X 3/4  
CLAMP HOSE #10 .56-1.06  
CLAMP HOSE #28 1.32-2.25  
HOSE 1.5 ID X 2 LG 20R4  
ACTUATOR BOSCH 32 GOVERNOR  
WASHER LOCK M8-5/16  
BARBED EL 90 1/8 NPT X 3/8  
CLAMP HOSE BAND 1.0"  
HOSE BARB REDUCR TEE 3/4"-3/8"  
HOSE 3/8 ID SINGLE BRAID (11.5” LG)  
HOSE 3/8 ID SINGLE BRAID (12” LG)  
PCV VALVE 2.5L FORD  
HOSE BREATHER 1.6L  
CLAMP HOSE BAND .88"  
HOSE 3/4 ID SAE-30R2 (16"LG)  
NUT HEX M8-1.25 G8 YEL CHR  
SCREW HHC M6-1.0 X 45 C8.8 FTH  
WASHER LOCK M6-1/4  
SCREW HHC M8-1.25 X 20 G8.8  
ASSY REG INLET NPT FITTINGS  
ELBOW 90D 3/4 NPT  
NIPPLE PIPE 3/4NPTX4.5 BLK IRN  
NIPPLE PIPE 3/4NPT X 2  
FLANGE FUEL INLET  
DECAL INLET PRESSURE  
DECAL FUEL INLET  
WASHER FLAT 5/16 ZINC  
NIPPLE CLOSE 3/4 X 1.375  
GASKET BOSCH 32  
(1) INCLUDED IN ITEM 35 (ASSY REG INLET NPT FITTINGS)  
REGULATOR NOTES:  
REGULATOR (I/N 11) AS SHOWN IN ILLUSTRATION IS SET UP FOR NATURAL GAS APPLICATION.  
TO CONFIGURE REGULATOR FOR LP VAPOR, REFER TO THE “RECONFIGURING THE FUEL SYSTEM” SECTION OF THIS  
MANUAL.  
 
REVISION: -A-  
DATE: 1/21/10  
Page 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW: EV ENCLOSURE C1 CPL  
DRAWING #: 0G3534  
GROUP F  
ITEM  
PART#  
QTY.  
DESCRIPTION  
(2) 1  
(2) 2  
(1) 3  
(2) 4  
6
0G33370AL0R  
0J14640AL0R  
077992  
0J14630AL0R  
0F4487A  
022127  
1
1
10  
2
1
ROOF 1.6L C1  
REAR INTAKE WRAP C1  
NUT HEX LOCK M6-1.0 SS NY INS  
DOOR LEFT/RIGHT SIDE C1  
ASSY ACCESS COVER  
7
1
NUT HEX 1/4-20 STEEL  
8
9
022097  
022473  
0C2454  
0F5048D  
0F5049B  
0F8869D  
089961  
078115  
0H7518  
0H7518A  
0E3257  
0912970090  
0H7518B  
0C8566  
1
10  
8
2
2
1
1
8
2
1
6
2
1
10  
10  
8
WASHER LOCK M6-1/4  
WASHER FLAT 1/4-M6 ZINC  
SCREW THF M6-1 X 16 N WA Z/JS  
VISE-ACTION LATCH, SLOTTED CIR  
PULL TAB DOOR LOCK SS  
KEY VISE-ACTION LATCH,SLOT CIR  
FOAM STRIP 3/4"WIDE X 3/16"THK (294”LG)  
WASHER SELF LOCKING DOME  
INSULATION SIDE DOOR C1  
INSULATION ROOF C1  
SCREW HWHTF M6-1.0 X 16  
ASSY WIRE 14AWG GRN/YEL (32.25”LG)  
INSULATION REAR C1  
SCREW HHFC M6-1.0 X 20 G8.8  
NUT SPRINGCLIP M6-1.0  
(1)10  
11  
12  
13  
14  
15  
16  
17  
(1)19  
20  
21  
23  
24  
25  
0H0412  
022097  
WASHER LOCK M6-1/4  
(3) 26  
27  
0H7529  
1
1
1
1
FOIL ALUMINUM WITH ADHESIVE  
RF COVER PLATE-PLASTIC-BISQUE  
RF COVER PLATE-PLASTIC-GREY  
FRONT DISCHARGE WRAP 1.6L C1  
WASHER LOCK SPECIAL 1/4"  
0H1208A  
0H1208B  
0G33350AL0R  
0A1658  
(2) 28  
(1)29  
2
(1)ENCLOSURE NOTE: ALL PANELS THAT FASTEN TO THE ROOF MUST BE SECURED USING I/N 10 (THREAD FORMING FASTENER) AND I/N 3 (LOCK NUT) AND  
TO INCLUDE AT LEAST ONE CONNECTION POINT USING I/N 19 (THREAD FORMING FASTENER) WITH I/N 3 (LOCK NUT) TO EACH PANEL. LOCK NUT IS TO BE  
INSTALLED AFTER THREAD FORMING FASTENER HAS PENETRATED THROUGH EXTRUSION IN ENCLOSURE PANELS. ALL PANEL TO BASEFRAME  
CONNECTIONS TO INCLUDE AT LEAST ONE CONNECTION POINT USING I/N 29 (WASHER SPECIAL).  
(2) SHEET METAL PARTS LISTED IN THE BOM TABLE ARE REPRESENTING GENERIC PARTS (NO COLOR)  
MANUFACTURING: FOR CORRECT MATERIAL AND COLOR REFER TO AS400 BOM.  
CUSTOMER: WHEN ORDERING REPLACEMENT PARTS ENTER BASE NUMBER (FIRST 6 DIGITS ONLY) IN THE SYSTEM FOR CORRECT MATERIAL  
AND COLOR (FOR REFERENCE SEE GUIDELINE 0H7169).  
(3) USED ON 1.5L / 1.6L UNITS ONLY.1  
REVISION: J-1720-K  
DATE: 3/23/12  
Page 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
0F7366  
0F7647  
0F8095  
0G3576  
0E3257  
0F7644  
0C6119  
036434  
036449  
022129  
022259  
038750  
0G3575  
0F3794A  
022097  
049813  
022473  
1
1
1
1
4
2
1
3
3
6
6
1
1
1
1
1
6
MUFFLER C1  
MUFFLER SADDLE  
PIPE EXHAUST OUTLET  
EXHAUST PIPE LOWER 1.6L  
SCREW HWHTF M6-1.0 X 16  
MUFFLER STRAP  
BOLT U 5/16-18 X 2-1/4  
BOLT U 5/16-18 X 2.09  
SADDLE 2 INCH  
WASHER LOCK M8-5/16  
NUT HEX 5/16-18 STEEL  
SCREW HHC M6-1.0 X 30 G8.8  
EXHAUST PIPE UPPER 1.6L SS  
EXHAUST BLANKET 500MM LONG  
WASHER LOCK M6-1/4  
NUT HEX M6 X 1.0 G8 YEL CHR  
WASHER FLAT 1/4-M6 ZINC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
. A v 0 4 / 0 7 k P g B 0 0 a 1 c R e  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Generac Power Systems Switch 004945 1 User Manual
Generac Power Systems Portable Generator 0661 5 User Manual
Generac Power Systems Fan OG 2697 User Manual
Generac Power Systems Automobile Parts 0D9727 User Manual
Generac Portable Generator RD01523ADSE User Manual