Owner's Manual
Stationary Emergency Generator
1.6L
25/30kW Models
EPA Certified
nNOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT
APPLICATIONS.
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS
SHOULD ATTEMPT INSTALLATION! DEADLY EXHAUST
FUMES! OUTDOOR INSTALLATION ONLY!
This manual should remain with the unit.
. 0 H 7 t N 2 r 3 o a 0 P
. A v 0 4 / 1 0 e v r 1 9 C 1 o R e
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Instructions
nSAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential
hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this
equipment.
This symbol points out potential fire hazard.
INTRODUCTION
Thank you for purchasing this model of the stationary emergency
generator product line.
This symbol points out potential electrical shock hazard.
Every effort was expended to make sure that the information and
instructions in this manual were both accurate and current at the
time the manual was written. However, the manufacturer reserves
the right to change, alter or otherwise improve this product(s) at
any time without prior notice.
The operator is responsible for proper and safe use of the equip-
ment. The manufacturer strongly recommends that the operator
read this Owner's Manual and thoroughly understand all instruc-
tions before using this equipment. The manufacturer also strongly
recommends instructing other users to properly start and operate
the unit. This prepares them if they need to operate the equipment
in an emergency.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest
Service Dealer for starting, operating and servicing procedures.
For safety reasons, the manufacturer recommends that this
equipment be installed, serviced and repaired by a Service
Dealer or other competent, qualified electrician or installation
technician who is familiar with applicable codes, standards and
regulations. The operator also must comply with all such codes,
standards and regulations.
Throughout this publication, and on tags and decals affixed to the
generator, DANGER, WARNING, CAUTION and NOTE blocks are
used to alert personnel to special instructions about a particular
service or operation that may be hazardous if performed incor-
rectly or carelessly. Observe them carefully. Their definitions are
as follows:
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to
make sure that all maintenance for safe operation is performed
promptly, and to have the equipment checked periodically by a
Service Dealer. Normal maintenance service and replacement of
parts are the responsibility of the owner/operator and, as such,
are not considered defects in materials or workmanship within the
terms of the warranty. Individual operating habits and usage con-
tribute to the need for maintenance service.
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF
NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.
Indicates a hazardous situation or action which, if not
avoided, could result in death or serious injury.
Proper maintenance and care of the generator ensure a minimum
number of problems and keep operating expenses at a minimum.
See a Service Dealer for service aids and accessories.
Indicates a hazardous situation or action which, if not
avoided, could result in minor or moderate injury.
NOTE:
Operating instructions presented in this manual assume that the
generator electric system has been installed by a Service Dealer or
other competent, qualified contractor. Installation of this equipment
is not a “do-it-yourself” project.
Notes contain additional information important to a procedure
and will be found within the regular text body of this manual.
These safety warnings cannot eliminate the hazards that they
indicate. Common sense and strict compliance with the special
instructions while performing the service are essential to prevent-
ing accidents.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, simply contact
a Service Dealer for assistance. Service technicians are factory-
trained and are capable of handling all service needs.
Four commonly used safety symbols accompany the DANGER,
WARNING and CAUTION blocks. The type of information each
indicates is as follows:
When contacting a dealer about parts and service, always supply
the complete Model Number, Serial Number and Type Code (where
applicable) from the DATA LABEL that is affixed to the unit.
This symbol points out important safety information that,
if not followed, could endanger personal safety and/or
n
property of others.
This symbol points out potential explosion hazard.
. F v e 0 5 / 1 0
S a f e t y 0 0 4 R
1-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Instructions
• The engine exhaust fumes contain carbon monoxide gas, which
SAFETY RULES
can be DEADLY. This dangerous gas, if breathed in sufficient
concentrations, can cause unconsciousness or even death. For
that reason, adequate ventilation must be provided. This should
be considered prior to installing the generator. The unit should
be positioned to direct exhaust gasses safely away from any
building where people, animals, etc., will not be harmed. Any
exhaust stacks that ship loose with the unit must be installed
properly per the manufacturer's instruction, and in strict compli-
ance with applicable codes and standards.
Study these SAFETY RULES carefully before installing, operating
or servicing this equipment. Become familiar with this Owner’s
Manual and with the unit. The generator can operate safely, effi-
ciently and reliably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to follow simple
and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance
that might involve a hazard. The warnings in this manual, and on
tags and decals affixed to the unit are, therefore, not all inclusive.
If a procedure, work method or operating technique is used that
the manufacturer does not specifically recommend, ensure that it
is safe for others. Also make sure the procedure, work method or
operating technique utilized does not render the generator unsafe.
• Keep hands, feet, clothing, etc., away from drive belts, fans,
and other moving or hot parts. Never remove any drive belt or
fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and ventilating air is
critical in any room or building housing the generator to prevent
buildup of explosive gases and to ensure correct generator
operation. Do not alter the installation or permit even partial
blockage of ventilation provisions, as this can seriously affect
safe operation of the generator.
• Keep the area around the generator clean and uncluttered.
Remove any materials that could become hazardous.
• When working on this equipment, remain alert at all times.
Never work on the equipment when physically or mentally
fatigued.
• Inspect the generator regularly, and promptly repair or replace
all worn, damaged or defective parts using only factory-
approved parts.
• Before performing any maintenance on the generator, discon-
nect its battery cables to prevent accidental start-up. Disconnect
the cable from the battery post indicated by a NEGATIVE, NEG
or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping
on the unit can stress and break parts, and may result in dan-
gerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
nDespite the safe design of this generator,
operating this equipment imprudently, neglect-
ing its maintenance or being careless can cause
possible injury or death. Permit only respon-
sible and capable persons to install, operate or
maintain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
nParts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
GENERAL HAZARDS
• For safety reasons, the manufacturer recommends that this
equipment be installed, serviced and repaired by a Service
Dealer or other competent, qualified electrician or installation
technician who is familiar with applicable codes, standards
and regulations. The operator also must comply with all such
codes, standards and regulations.
ELECTRICAL HAZARDS
• Installation, operation, servicing and repair of this (and related)
equipment must always comply with applicable codes, stan-
dards, laws and regulations. Adhere strictly to local, state and
national electrical and building codes. Comply with regulations
the Occupational Safety and Health Administration (OSHA) has
established. Also, ensure that the generator is installed, operat-
ed and serviced in accordance with the manufacturer’s instruc-
tions and recommendations. Following installation, do nothing
that might render the unit unsafe or in noncompliance with the
aforementioned codes, standards, laws and regulations.
• All stationary emergency generators covered by this manual
produce dangerous electrical voltages and can cause fatal
electrical shock. Utility power delivers extremely high and dan-
gerous voltages to the transfer switch as well as the generator.
Avoid contact with bare wires, terminals, connections, etc.,
on the generator as well as the transfer switch, if applicable.
Ensure all appropriate covers, guards and barriers are in place
before operating the generator. If work must be done around
an operating unit, stand on an insulated, dry surface to reduce
shock hazard.
• Do not handle any kind of electrical device while stand-
ing in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
. F v e 0 5 / 1 0
S a f e t y 0 0 4 R
1-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Instructions
• If personnel must stand on metal or concrete while installing,
FIRE HAZARDS
operating, servicing, adjusting or repairing this equipment,
place insulative mats over a dry wooden platform. Work on the
equipment only while standing on such insulative mats.
• The National Electrical Code (NEC) requires the frame and
external electrically conductive parts of the generator to be con-
nected to an approved earth ground. This grounding will help
prevent dangerous electrical shock that might be caused by a
ground fault condition in the generator or by static electricity.
Never disconnect the ground wire.
• Keep a fire extinguisher near the generator at all times. Do NOT
use any carbon tetra-chloride type extinguisher. Its fumes are
toxic, and the liquid can deteriorate wiring insulation. Keep the
extinguisher properly charged and be familiar with its use. If
there are any questions pertaining to fire extinguishers, consult
the local fire department.
EXPLOSION HAZARDS
• Wire gauge sizes of electrical wiring, cables and cord sets must
be adequate to handle the maximum electrical current (ampac-
ity) to which they will be subjected.
• Before installing or servicing this (and related) equipment, make
sure that all power voltage supplies are positively turned off at
their source. Failure to do so will result in hazardous and pos-
sibly fatal electrical shock.
• Properly ventilate any room or building housing the generator to
prevent build-up of explosive gas.
• Do not smoke around the generator. Wipe up any fuel or oil
spills immediately. Ensure that no combustible materials are left
in the generator compartment, or on or near the generator, as
FIRE or EXPLOSION may result. Keep the area surrounding the
generator clean and free from debris.
• Connecting this unit to an electrical system normally supplied
by an electric utility shall be by means of a transfer switch so as
to isolate the generator electric system from the electric utility
distribution system when the generator is operating. Failure to
isolate the two electric system power sources from each other
by such means will result in damage to the generator and may
also result in injury or death to utility power workers due to
backfeed of electrical energy.
• These generators may operate using one of several types
of fuels. All fuel types are potentially FLAMMABLE and/or
EXPLOSIVE and should be handled with care. Comply with all
laws regulating the storage and handling of fuels. Inspect the
unit’s fuel system frequently and correct any leaks immediately.
Fuel supply lines must be properly installed, purged and leak
tested according to applicable fuel-gas codes before placing
this equipment into service.
• Stationary emergency generators installed with an automatic
transfer switch will crank and start automatically when normal
(utility) source voltage is removed or is below an acceptable
preset level. To prevent such automatic start-up and possible
injury to personnel, disable the generator’s automatic start cir-
cuit (battery cables, etc.) before working on or around the unit.
Then, place a “Do Not Operate” tag on the generator control
panel and on the transfer switch.
• Diesel fuels are highly FLAMMABLE. Gaseous fluids such
as natural gas and liquid propane (LP) gas are extremely
EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier
than air; install leak detectors accordingly.
• In case of accident caused by electric shock, immediately
shut down the source of electrical power. If this is not pos-
sible, attempt to free the victim from the live conductor. AVOID
DIRECT CONTACT WITH THE VICTIM. Use a nonconducting
implement, such as a dry rope or board, to free the victim from
the live conductor. If the victim is unconscious, apply first aid
and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry
can conduct electricity resulting in electric shock, or may get
caught in moving components causing injury.
CALIFORNIA PROPOSITION 65 WARNING
Engine exhaust and some of its constituents are known
to the State of California to cause cancer, birth defects
and other reproductive harm.
CALIFORNIA PROPOSITION 65 WARNING
This product contains or emits chemicals known to the
State of California to cause cancer, birth defects and
other reproductive harm.
. F v e 0 5 / 1 0
S a f e t y 0 0 4 R
1-3
Download from Www.Somanuals.com. All Manuals Search And Download.
General Information
NOTE:
IDENTIFICATION RECORD
For actual information related to this particular model, please
refer to the Manual Drawing Listing located at the end of this
manual, or to the data label affixed to the unit.
DATA LABEL
Every generator set has a DATA LABEL that contains important
information pertinent to the generator. The data label, which can be
found attached to the generator’s lower connection box, lists the
unit’s serial number and its rated voltage, amps, wattage capacity,
phase, frequency, rpm, power factor, production date, etc.
Stationary Emergency Generator Model and Serial
Number
This number is the key to numerous engineering and manufactur-
ing details pertaining to your unit. Always supply this number
when requesting service, ordering parts or seeking information.
Data Label
. D v e 0 5 / 1 0
I d e n t y 0 0 5 R
2-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Equipment Description
EQUIPMENT DESCRIPTION
COOLANT RECOMMENDATIONS
Use a mixture of half low silicate ethylene glycol base anti-freeze
and deionized water. Cooling system capacity is listed in the
specifications. Use only deionized water and only low silicate
anti-freeze. If desired, add a high quality rust inhibitor to the rec-
ommended coolant mixture. When adding coolant, always add the
recommended 50-50 mixture.
This equipment is a revolving field, alternating current Stationary
Emergency Generator. It is powered by a gaseous fueled engine
operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for
2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear
units. See the Specifications section for exact numbers. The unit
comes complete with a sound attenuated enclosure, internally
mounted muffler, control console, mainline circuit breaker, bat-
tery charger, and protective alarms as explained in the following
paragraph.
Do not use any chromate base rust inhibitor
with ethylene glycol base anti-freeze or chro-
All AC connections, including the power leads from the alterna-
tor, 120 volt battery charger input and control connections to the
transfer switch are available in the main connection box.
mium hydroxide (“green slime”) forms and will
cause overheating. Engines that have been
operated with a chromate base rust inhibitor
must be chemically cleaned before adding eth-
ylene glycol base anti-freeze. Using any high
silicate anti-freeze boosters or additives will
also cause overheating. The manufacturer also
recommends that any soluble oil inhibitor is
NOT used for this equipment.
The Stationary Emergency Generator incorporates the following
alternator features:
• Rotor and Stator insulation is Class F rated as defined by NEMA
MG1-32.6, NEMA MG1-1.66. The generator is self ventilated
and drip-proof constructed.
• The voltage waveform deviation, total harmonic content of the
AC waveform and telephone influence factor have been evalu-
ated and are acceptable according to NEMA MG1-32.
Do not remove the radiator pressure cap while
the engine is hot or serious burns from boiling
liquid or steam could result.
ENGINE OIL RECOMMENDATIONS
The unit has been filled with 5W-20 engine oil at the factory. Use
a high-quality detergent oil classified “For Service SJ or SH.”
Detergent oils keep the engine cleaner and reduce carbon deposits.
When changing the engine oil, be sure to use 5W-30 engine oil
(synthetic oil is recommended).
Ethylene glycol base antifreeze is poisonous.
Do not use mouth to siphon coolant from the
radiator, recovery bottle or any container. Wash
hands thoroughly after handling. Never store
used antifreeze in an open container because
animals are attracted to the smell and taste of
antifreeze even though it is poisonous to them.
Any attempt to crank or start the engine before
it has been properly serviced with the recom-
mended oil may result in an engine failure.
NOTE:
For temperatures below 32° F, it is strongly recommended to
use the optional Cold Weather Start Kit. The oil grade for tem-
peratures below 32° F is 5W-30 synthetic oil.
. D v 0 7 / 1 1
E q u i p 0 0 7 R e
3-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Engine Protective Devices
OVERCRANK SHUTDOWN
ENGINE PROTECTIVE DEVICES
The Stationary Emergency Generator may be required to operate
for long periods of time without an operator on hand to monitor
such engine conditions as coolant temperature, oil pressure or
rpm. For that reason, the engine has several devices designed to
protect it against potentially damaging conditions by automatically
shutting down the unit when the oil pressure is too low, the coolant
temperature is too high, the coolant level is too low, or the engine
is running too fast.
After a prespecified duration of cranking, this function ends the
cranking if the engine has failed to start. The overcrank message
will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn
switch back to AUTO to reset the generator control board.
NOTE:
If the fault is not corrected, the overcrank feature will continue
to activate.
NOTE:
Approximate Crank Cycle Times
• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
Engine protective switches and sensors are mentioned here for
the reader’s convenience. Also refer to the applicable control
panel manual for additional automatic engine shutdown infor-
mation.
• 7 seconds OFF
• Repeat for 45 seconds
• Approximately 90 seconds total.
HIGH COOLANT TEMPERATURE SENDER
An analog coolant temperture sender, located in the engine's
cooling system will cause an engine shutdown if the temperature
should exceed approximately 125° C (257° F). The generator will
automatically restart once the temperature has returned to a safe
operating level.
OVERSPEED SHUTDOWN
A speed circuit controls engine cranking, start-up, operation and
shutdown. Engine speed signals are delivered to the circuit board
whenever the unit is running. Should the engine overspeed above
a safe, preset value, the circuit board initiates an automatic engine
shutdown. Contact the nearest Authorized Dealer if this failure
occurs.
LOW COOLANT LEVEL SENSOR
To prevent overheating, the engine has a low coolant level sensor.
If the level of engine coolant drops below the level of the low cool-
ant level sensor, the engine automatically shuts down.
RPM SENSOR LOSS SHUTDOWN
If the speed signal to the control panel is lost, engine shutdown
will occur.
LOW OIL PRESSURE SWITCH
This switch has normally closed contacts that are held open by
engine oil pressure during cranking and operating. Should oil pres-
sure drop below the 8 psi range, switch contacts close, and the
engine shuts down. The unit should not be restarted until oil is
added, and the AUTO/OFF/MANUAL switch must be turned to OFF
and then back to AUTO.
DC FUSES
A fuse (7.5 amp) is located on the control panel. It protects the
panel components from damaging overload. Always remove this
fuse before commencing work on the generator. The unit will not
start or crank if the fuse is blown.
A fuse (25 amp) is located in the engine wire harness adjacent
to the DC alternator. It is used to prevent circuit failure due to DC
alternator falure. It will also protect the system in the event of a
wiring short-dircuit. If this fuse is blown, the generator will not
operate. Replace these fuses with the same size, type, and rating.
. B v e 0 5 / 1 0 r o t 0 0 E 3 n g R P
4-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Fuel System
NATURAL GAS FUEL SYSTEM
FUEL SYSTEM
Natural gas is supplied in its vapor state. In most cases, the gas
distribution company provides piping from the main gas distribu-
tion line to the standby generator site. The following information
applies to natural gas fuel systems.
FUEL REQUIREMENTS
The Stationary Emergency Generator may be equipped with one of
the following fuel systems:
• Gas pressure in a building is usually regulated by national, state
and local codes.
• To reduce gas pressure to a safe level before the gas enters a
building, a primary regulator is needed. The natural gas supplier
may or may not supply such a regulator.
• It is the responsibility of the gas supplier to make sure sufficient
gas pressure is available to operate the primary regulator.
• Gas pressure at the inlet to the fuel shutoff solenoid must never
exceed approximately 14 inches water column (0.5 psi).
• Natural gas fuel system
• Propane vapor (LPV) fuel system
Recommended fuels should have a Btu content of at least 1,000
Btu's per cubic foot for natural gas; or at least 2,520 Btu's per
cubic foot for LP gas. Ask the fuel supplier for the Btu content of
the fuel.
NOTE:
The fuel consumption requirements are identified in the
Specifications section of the Owner's Manual. Refer to the
Installation Manual if assistance is required for the sizing of
the pipe diameter for the generator. Any piping used to connect
the generator to the fuel supply should be of adequate size to
achieve the 100% load fuel consumption requirements identi-
fied in the Specifications section regardless of actual load.
PROPANE VAPOR WITHDRAWAL FUEL SYSTEM
This type of system utilizes the vapors formed above the liquid
fuel in the supply tank. Approximately 10 to 20 percent of the tank
capacity is needed for fuel expansion from the liquid to the vapor
state. The vapor withdrawal system is generally best suited for
smaller engines that require less fuel. The installer should be aware
of the following:
NOTE:
TherecommendedfuelpressureisidentifiedintheSpecifications
section this manual.
• When ambient temperatures are low and engine fuel consump-
tion is high, the vapor withdrawal system may not function
efficiently.
• Ambient temperatures around the supply tank must be high
enough to sustain adequate vaporization, or the system will not
deliver the needed fuel volume.
NOTE:
It is the responsibility of the installer to make sure that only
the correct recommended fuel is supplied to the generator fuel
system. Thereafter, the owner/operator must make certain that
only the proper fuel is supplied.
• In addition to the cooling effects of ambient air, the vaporization
process itself provides an additional cooling effect.
. F e v 0 4 / 1 1
u F e l S y s 0 0 1 R
5-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Engine Lubrication System
SPECIFICATIONS
Type of Oil Pump ...............................................................Gear
Oil Filter .......................................................Full Flow, Cartridge
Crankcase Oil Capacity ............................................ 4 U.S. qts.
STANDBY EMERGENCY GENERATOR
Type......................................................................Synchronous
Rotor Insulation.............................................................Class H
Stator Insulation............................................................Class H
Alternator Output Leads 3-phase.....................................4-wire
Bearings ..................................................................Sealed Ball
Coupling ................................................................Flexible Disc
Load Capacity (Standby Rating)...............................25/30 kW*
COOLING SYSTEM
Type............................................................................... Closed
Water Pump............................................................. Belt Driven
Fan Speed.........................................................................2484
Fan Diameter...........................................................17.7 inches
Fan Mode....................................................................... Pusher
Air Flow (inlet air including alternator and
* NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE
J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate
with natural gas.
3
combustion air) ..................................................1800 ft /min.
Excitation System ............................................................Direct
Generator Output Voltage/kW - 60 Hz
kW
120/240V, 1-phase, 1.0 pf 25/30
120/208V, 3-phase, 0.8 pf 25/30
120/240V, 3-phase, 0.8 pf 25/30
Coolant Capacity....................................................2.0 U.S. gal.
Heat Rejection to Coolant (25/35kW) ....112,000/135,000 Btu/h
Maximum Operating Air Temp. on Radiator......... 60° C (150° F)
Maximum Ambient Temperature......................... 50° C (140° F)
Amp
104/125
87/104
75/90
CB Size
125/150
100/125
90/100
FUEL SYSTEM
Generator Locked Rotor KVA Available @ Voltage Dip of 35%
Type of Fuel ....................................Natural Gas, Propane Vapor
Carburetor............................................................... Down Draft
Secondary Fuel Regulator............................................ Standard
Fuel Shut-off Solenoid................................................. Standard
Operating Fuel Pressure .................5 in. - 14 in. Water Column
25kW
35 KVA
30kW
45 KVA
ENGINE
Make ........................................................................... Generac
Model .............................................................................In Line
Cylinders and Arrangement .....................................................4
Displacement...............................................................1.6 Liter
Bore..............................................................................3.15 in.
Stroke...........................................................................3.13 in.
Compression Ratio....................................................... 9.5-to-1
Air Intake System......................................... Naturally Aspirated
Valve Seats............................................................ Replaceable
Lifter Type.................................................................. Hydraulic
Spark Plug Gap........................................0.76mm (0.030 inch)
Fuel Consumption - ft3/hr (Natural Gas/LPV)
Exercise
Cycle
25%
Load
50%
Load
75%
Load
100%
Load
25kW
30kW
60/24
60/24
120/48 220/87 310/123 390/155
145/58 260/103 370/147 470/187
ELECTRICAL SYSTEM
Battery Charge Alternator......................................12V, 15 Amp
Static Battery Charger ....................................... 2.0 or 2.5 Amp
Recommended Battery.................................Group 26, 525CCA
System Voltage............................................................ 12 Volts
Engine Parameters
Rated Synchronous RPM .......................................60 Hz, 3600
Voltage Regulator
Type...........................................................................Electronic
Sensing ................................................................Single-phase
Regulation........................................................................± 1%
Features.........................Adjustable Voltage and Automatic Gain
Exhaust System
Exhaust Flow at Rated Output 60 Hz: 25kW
240 cfm
30kW
260 cfm
1025°F
Exhaust Temp. at Rated Output:
975°F
Power Adjustment for Ambient Conditions
Temperature Deration:
3% for every 10° C above °C
Combustion Air Requirements (Natural Gas)
25kW 30kW
Flow at rated power, 60 Hz:
25kW
90 cfm
30kW
95 cfm
40
104
25
77
1.65% for every 10° above °F
Altitude Deration:
1% for every 100 m above m
Governor
Type...........................................................................Electronic
Frequency Regulation.............................................Isochronous
Steady State Regulation ................................................± .25%
Adjustments:
25kW 30kW
915
2000
182
600
3% for every 1000 ft. above ft.
Controller ................................................................. Nexus
Speed..................................................................... Selectable
. C v e 1 2 / 1 1
G e n S p e c 0 8 2
6-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
9. Install the previously removed black pipe onto the outlet
WEATHER AND MAINTENANCE KITS
To keep the generator running at its peak, the following kits are
offered:
port of the demand regulator. Use pipe sealant on the pipe
threads.
10. Reverse steps 1-4 in this procedure to reactivate the demand
• Cold Weather Kit
regulator.
~ Recommended for climates with temperatures below 32° F.
• Extreme Cold Weather Kit
11. Follow the instructions in the Control Panel section.
~ Recommended Block Heater Kit for protection in tempera-
tures below 32° F.
• Scheduled Maintenance Kit
~ Kit includes the recommended parts to maintain the genera-
tor. Refer to the Service Schedule for regular maintenance
intervals.
Serious injury, including death, or damage
will occur if not configured properly. Please
consult an Authorized Dealer with any ques-
tions.
For additional information, or to order any of these kits, please
contact an Authorized Service Dealer or Customer Service
Representative.
Figure 6.1 — Reconfigure the Fuel System
RECONFIGURING THE FUEL
SYSTEM
NOTE:
All models are configured to run on natural gas from the fac-
tory.
Before the generator can be operated using a LP fuel source, the
fuel system and control panel (refer to the installation drawing for
location) must be reconfigured. The steps to reconfigure the gen-
erator from a natural gas (NG) to a liquidified petroleum (LP) fuel
source are as follows:
FUEL SYSTEM
1. Turn the main gas supply off and disconnect the battery.
2. Remove the carburetor fuel hose from the outlet port of the
demand regulator (see Figure 6.1).
3. Disconnect the power wires from the fuel solenoid located
on top of the regulator assembly by removing the screw on
the front of the connector and pulling the connector forward,
away from the solenoid body.
CONTROL PANEL
The FUEL TYPE must be reconfigured in the control panel to final-
ize the conversion process. This generator is configured at the
factory to operate on natural gas. If conversion to LP is required,
please complete the mechanical conversion process and then call
888-9ACTIVATE for the control panel password. This fuel selection
conversion is required to be password protected by Environmental
Protection Agency [EPA] regulations.
4. Loosen the spring clamp on the small fuel enrichment line and
remove the hose from the hose barb.
5. Remove the black pipe assembly from the outlet port of the
demand regulator. The solenoid assembly may need to be
removed before performing this operation (Figure 6.1).
6. Remove the NG fuel jet (loosen counter clockwise) from the
outlet port.
7. Remove the LP fuel jet (loosen counter clockwise) from the jet
keeper port on the side of the regulator housing. Install this jet
into the outlet port in the regulator casting.
Whenever the Generator’s Fuel Regulator is
converted from one Fuel type to the other,
the Control Panel must be reconfigured for
the correct fuel type. Failure to convert both
the Regulator and Control Panel will result in
decreased performance and an increase in
emissions, and is a violation of EPA regula-
tions.
NOTE:
The jet sizes are stamped on the individual jets. The larger jet
size is used for running on NG.
8. Install the previously removed NG jet into the jet keeper port
on the side of the regulator housing.
. C v e 1 2 / 1 1
G e n S p e c 0 8 2 R
6-2
Download from Www.Somanuals.com. All Manuals Search And Download.
General Information
ALTERNATOR AC LEAD
ALTERNATOR POWER WINDING
CONNECTIONS
CONNECTIONS
The electrical wires in the unit’s AC connection (lower) panel
should be installed according to the number of leads and the
voltage/phase required for the application. The voltage and phase
are described on the generator data label. The number of lead
wires can be identified using the Specifications section and the
power output rating on the generator data label. For example, if
the generator produces 130kW, 277/480 Volt, 3-phase power, the
generator has 12 alternator output leads. Figure 7.3 describes the
stator power winding connection for the generator.
3-PHASE ALTERNATORS ("Y" CONFIGURATION)
The Stationary Emergency Generator is designed to supply
3-phase electrical loads. Electric power is produced in the alterna-
tor power windings. These windings were connected at the factory
to the main circuit breaker with a “Y” configuration as shown in
Figures 7.2 through 7.6.
The rated voltage between circuit breaker terminals E1-E2, E1-E3
and E2-E3 is 480V, 208V or 600V depending on the model.
The rated voltage between each circuit breaker terminal and the
neutral point 00 is 277V, 120V, or 346V depending on the model.
FOUR-LEAD, SINGLE-PHASE STATOR
Four-lead alternators (see Figure 7.1) are designed to supply elec-
trical loads with voltage code “A” (240V, 1-phase, 60 Hz). Electrical
power is produced in the stator power windings. These windings
were connected at the factory to the main circuit breaker as shown
in Figure 7.1.
Figure 7.2 — Stator Power Winding
Connections - 3-phase, 277/480V (6 Lead)
E1
The rated voltage between each circuit breaker terminal is 240V.
The rated voltage between each circuit breaker terminal and the
neutral point 00 is 120V.
S1
INTERNAL
CONNECTIONS
Figure 7.1 — Four-lead, Single-phase Stator
L - L
S4
S6
00 (NEUTRAL)
S5
S2
S3
E3
E2
L - N
Figure 7.3 — Stator Power Winding
Connections - 3-phase, 277/480V (12 Lead)
E1
S1
S4
S7
L - L
S12
S10
S9
S8
S11
S6
S5
S2
S3
E3
E2
L - N
. B v e 0 5 / 1 0
A C C o n n 0 0 7 R
7-1
Download from Www.Somanuals.com. All Manuals Search And Download.
General Information
Figure 7.4 — Stator Power Winding
Connections - 3-phase, 120/208V (6 Lead)
3-PHASE ALTERNATORS ("DELTA" CONFIGURATION)
The Stationary Emergency Generator is designed to supply
3-phase electrical loads. Electric power is produced in the alterna-
tor power windings. These windings were connected at the factory
to the main circuit breaker with a “Delta” configuration as shown
in Figures 7.7 and 7.8.
INTERNAL CONNECTIONS
E1
S1
S1
The rated voltage between circuit breaker terminals E1-E2, E1-E3
and E2-E3 is 240V.
The rated voltage between E1 or E3 and the neutral point 00 is
120V.
L-L
S4
S6
S4
00 (NEUTRAL)
S5
Figure 7.7 — Stator Power Winding
Connections - 3-phase, 120/240V (6 Lead)
S3
S2
S6 S5
E2
E3
E2
S3
S2
S6
S2
L-N
INTERNAL
CONNECTIONS
Figure 7.5 — Stator Power Winding
Connections - 3-phase, 120/208V (12 Lead)
L - L
E1
S7
S1
S3
S5
E1
E3
S4
S1
L-L
S10
S12
S4
L - N
S5
00 (NEUTRAL)
S9
S2
S6 S11
Figure 7.8 — Stator Power Winding
Connections - 3-phase, 120/240V (12 Lead)
E3
E2
S3
S8
L-N
E2
S12
S2
Figure 7.6 — Stator Power Winding
Connections - 3-phase, 346/600V (6 Lead)
E1
S5
S9
S1
INTERNAL
L - L
CONNECTIONS
S8
S6
L - L
S3
S11
S4
S6
00 (NEUTRAL)
E1
E3
S10
S1
S5
L - N
00 (NEUTRAL)
S2
E2
S3
E3
L - N
. B v e 0 5 / 1 0
A C C o n n 0 0 7 R
7-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
Upon power up, this controller will go through a system self test
CONTROL PANEL INTERFACE
which will check for the presence of utility voltage on the DC
circuits. This is done to prevent damage if the installer mistakenly
connects AC utility power sense wires into the DC terminal block.
If utility voltage is detected, the controller will display a warning
message and lock out the generator, preventing damage to the
controller. Power to the controller must be removed to clear this
warning.
USING THE AUTO/OFF/MANUAL SWITCH
With the switch set to AUTO, the engine may
crank and start at any time without warning.
Such automatic starting occurs when utility
power source voltage drops below a preset
level or during the normal exercise cycle. To
prevent possible injury that might be caused
by such sudden starts, always set the switch
to OFF and remove the fuse before work-
ing on or around the generator or transfer
switch. Then, place a “DO NOT OPERATE”
tag on the generator panel and on the trans-
fer switch.
Utility voltage must be turned on and present at the N1 and N2
terminals inside the generator control panel for this test to be
performed and pass.
NOTE:
DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT
WIRES IS NOT WARRANTABLE!
This test will be performed each time the controller is powered
up.
Next, the user must enter the minimum settings to operate. These
settings are current date and time and exercise day and time. The
maintenance intervals will be initialized (i.e. started) the first time
the clock is set. If the clock is never set at power up, the mainte-
nance intervals will be reset every time power is applied.
1. “AUTO” Position – Selecting this switch activates fully auto-
matic system operation. It also allows the unit to automati-
cally start and exercise the engine every seven days with the
setting of the exercise timer (see the Setting the Exercise
Timer section).
2. “OFF” Position – This switch position shuts down the engine.
If a subsequent power loss (loss of battery power) occurs the
Installation assistant will operate upon power restoration. The self
test routine will be run and then the customer will be required to
re-enter the time and date, as this is not retained during a power
loss. The unit will not require re-activation.
This position also prevents automatic operation.
3. “MANUAL” Position – Set the switch to MANUAL to crank
and start the engine. Transfer to standby power will not occur
unless there is a utility failure.
ACTIVATE THE GENERATOR
When battery power is applied to the generator during the instal-
lation process, the controller will turn ON and the LCD screen will
illuminate. However, the generator still needs to be activated before
it will automatically run in the event of a power outage.
DISPLAY INTERFACE MENUS
The LCD display is organized as detailed below:
• The “Home” page, this page is the default page which will be
displayed if no keys are pressed for 30 seconds. This page
normally shows the current Status message and the current
date and time. The highest priority active Alarm and/or Warning
will be automatically posted on this page as well as flashing
the backlight when such an event is detected. In the case of
multiple Alarms or Warnings, only the first message will be
displayed. To clear an Alarm or Warning, see the Protection
Systems section - Clear Alarm.
• The display backlight is normally off. If the user presses any
key, the backlight will come on automatically and remain on for
30 seconds after the last key was pressed.
• The “Main Menu” page will allow the user to navigate to all other
pages or sub-menus by using the Left/Right and Enter keys.
This page can be accessed at any time with several presses of
the dedicated Escape key. Each press of the Escape key takes
you back to the previous menu until the main menu is reached.
This page displays the following options: HISTORY; STATUS;
EDIT; AND DEBUG. (See the Appendix - "Menu System".)
Activating the generator is a simple one time process that is guided
by the controller screen prompts. Once the product is activated,
the controller screen will not prompt you again, even if you discon-
nect the generator battery.
To obtain the activation code, record the generator serial number
and log onto www.activategen.com or call 1-888-9ACTIVATE and
follow the steps to retrieve the activation code.
After obtaining your activation code, please complete the following
steps at the generator’s control panel in the Activation Chart on the
following page.
NOTE:
The generator will only run in manual until the passcode has
been entered.
. E v e 1 2 / 1 1
C n t r l N e x u s u s 0
8-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
ACTIVATION CHART
CHOOSE LANGUAGE
TROUBLESHOOTING
Display Reads:
Use ARROW keys to scroll to desired lan-
guage. Press ENTER to select.
If the wrong language is chosen, it can be
changed later using the “edit” menu.
Language
-
English
+
Escape
Enter
Display Reads:
Press ENTER to begin the activation pro-
cess.
If ESCAPE is pressed instead of ENTER,
your generator will only run in manual mode
(for test purposes) and NOT ACTIVATED will
be displayed. You will need to remove the
generator control panel fuse AND disconnect
the T1, N1 and N2 connector in the external
connection box (if equipped); or disconnect
utility input (main breaker) to the transfer
switch for 3-5 seconds and reconnect, then
begin with Step 1.
Activate me (ENT) or
ESC to run in manual
Escape
Enter
Display Reads:
If you do not have your activation code,
go to www.activategen.com or call
1-888-9ACTIVATE (922-8482).
To Activate go to
www.activategen.com
If you already have your activation code,
wait 3-5 seconds for the next display.
Escape
Enter
ENTER ACTIVATION CODE (Passcode)
TROUBLESHOOTING
Display Reads:
Use ARROW keys to scroll and find the first
number of your Activation Code.
Serial 123456789
Passcode XXXXX +/-
Press ENTER to select.
Repeat this step until all digits have been
entered.
Escape
Enter
Use ESCAPE to correct previous digits.
Display Reads:
Activation is complete when all digits are
entered above and your screen shows this
display.
What happens if “Wrong Passcode Try
Again” appears?
“SELECT HOUR (0-23)”
“-
Re-enter the activation code. If a second
attempt is unsuccessful, check the number
against the code given on activategen.com.
If it is correct and the generator will not
accept it, contact 1-888-9ACTIVATE (922-
8482).
6
+”
Follow the controller prompts to continue
setting the time function. Refer to your
Owner’s Manual with questions.
Escape
Enter
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1 R
8-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
• If utility is still lost after the “line interrupt period”, run the engine
INSTALLATION ASSISTANT
Interconnect System Self Test Feature (follow the on-screen
prompts).
up to normal RPM and transfer the load. At this time the con-
troller will exit the exercise routine and assume full automatic
operation.
Upon power up, this controller will go through a system self test
which will check for the presence of utility voltage on the DC
circuits. This is done to prevent damage if the installer mistakenly
connects AC utility power sense wires into the DC terminal block.
If utility voltage is detected, the controller will display a warning
message and lock out the generator, preventing damage to the
controller. Power to the controller must be removed to clear this
warning.
USER ADJUSTABLE SETTINGS
Factory
Default
Minimum
Setting
Maximum
Setting
Setting
Increment
1 min
Exercise
time
23:59
(11:59 pm)
2 pm
Wed
00:00 (12 am)
Sun
Exercise
day
Utility voltage must be turned on and present at the N1 and N2
terminals inside the generator control panel for this test to be
performed and pass.
Sat
1 day
Current
Time
23:59
(11:59 pm)
12 am 00:00 (12 am)
1 min
NOTE:
Current
Day
Sun
Jan
Sun
Jan
Sat
Dec
1 day
DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT
WIRES IS NOT WARRANTABLE!
Current
Month
1 month
1 year
This test will be performed each time the controller is powered
up.
Current
Year
2008
2008
2100
Upon first power up of the generator, the display interface will
begin an installation assistant. The assistant will prompt the user
to set the minimum settings to operate. These settings are simply:
Current Date/Time and Exercise Day/Time. The maintenance inter-
vals will be initialized when the exercise time is entered.
Language
Contrast
English
80%
French
0%
Spanish
100%
N/A
1%
The exercise settings can be changed at any time via the "EDIT"
menu (see Appendix, "Menu System").
FUEL CONVERSION
For fuel conversion steps, refer to the GenSpec section,
RECONFIGURING THE FUEL SYSTEM.
If the 12 volt battery is disconnected or the fuse removed, the
Installation Assistant will operate upon power restoration. The
only difference is the display will only prompt the customer for the
current Time and Date.
OPERATION
IF THE INSTALLER TESTS THE GENERATOR PRIOR TO
INSTALLATION, PRESS THE “ENTER” KEY TO AVOID SETTING
UP THE EXERCISE TIME. THIS WILL ENSURE THAT WHEN
THE CUSTOMER POWERS UP THE UNIT, HE WILL STILL BE
PROMPTED TO ENTER AN EXERCISE TIME.
This system is intended to supply standby power in the event of a
utility failure. The control system will monitor the utility voltage to
determine if stand-by power is required. Should the utility voltage
fail, the generator will start and run normally, detaching from the
utility and supplying the customer load from the generator. When
utility power returns, the controller will re-transfer the customer
load back to utility and shut down the generator.
SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer. Once it is set,
the generator will start and exercise every seven days, on the day
of the week and at the time of day specified. During this exercise
period, the unit runs for approximately 12 minutes and then shuts
down. Transfer of loads to the generator output does not occur
during the exercise cycle unless utility power is lost.
AUTOMATIC TRANSFER OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set to their
UTILITY position, i.e., loads connected to the utility power
source.
2. Be sure that normal UTILITY power source voltage is avail-
able to transfer switch terminal lugs N1 and N2 (Refer to the
Electrical Data section).
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO.
4. Set the generator’s main circuit breaker to its ON (or CLOSED)
position.
With the preceding steps complete, the generator will start auto-
matically when utility source voltage drops below a preset level.
After the unit starts, loads are transferred to the standby power
source. Refer to the Sequence of Automatic Operation section.
LOW SPEED EXERCISE
The standard start sequence will be initiated.
• All 1800 rpm units will exercise at 1400 RPM
• All 3600 rpm units will exercise at 1800 RPM
If utility is lost during exercise the controller will do the following:
• Wait for the “line interrupt period” for utility to return. If utility
returns within the “line interrupt period”, continue to exercise
at low RPM.
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1
8-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
SEQUENCE OF AUTOMATIC OPERATION
Initial Conditions: Generator in Auto ready to run, load being sup-
plied by the Utility Source through the transfer switch.
MANUAL START
Allows the user to start and run the generator manually.
Transfer of the load to the generator will occur if utility is lost while
the unit is running in the manual mode (only if activated).
1. When the utility voltage fails (falls below 60% of nominal), a
10-30 second (programmable) “line interrupt” delay timer is
started. The factory set time delay is 10 seconds. If at the
end of the line interrupt time the utility voltage is above 60%
the engine will not crank. If the utility voltage is still below
the 60% of nominal at the end of the line interrupt time, the
unit will crank and start. If the unit cranks for more than 10
seconds and the utility voltage rises above 80% of nominal
(programmed pickup voltage) and the unit has not started, the
crank cycle will abort.
2. As soon as the unit starts a 5 second “warm-up” timer is initi-
ated. When the warm-up timer expires the control will transfer
the load to the generator (through the RTS switch) if the utility
voltage is less than 80% of nominal. If the utility voltage is
greater than the 80% of nominal at the end of the warm-up
time the load will not be transferred to the generator and a one
minute low-speed cool down period will start. At the end of
the one minute cool down period the generator will stop.
3. Once the unit is running and the switch has transferred the
load to the generator the unit will monitor utility voltage.
When utility voltage returns (above the programmable pickup
voltage, normally 80% of nominal), a 15 second “Return to
Utility” timer will start. At the end of the return to utility time,
if the utility voltage is still above the pickup voltage, the unit
will transfer the load back to the utility source and run the unit
through a one minute cool down period. When the cool down
period is over the unit will shut down and be ready for the next
outage.
ALARM AND WARNING MESSAGES
Alarms are defined as “Latching” which means they must be
cleared before the alarm message on the screen will clear. They
can be of type “Shutdown” or not and are logged in the alarm log.
Alarms are all annunciated on the display).
Warnings are “Non Latching” meaning the message automati-
cally clears when the warning condition goes away. Warnings can
not be of type “Shutdown” but they are logged in the alarm log.
Warnings are all annunciated on the display.
LOW OIL PRESSURE SHUTDOWN ALARM
There is a 10 second delay before oil pressure is monitored.
HIGH COOLANT TEMPERATURE SHUTDOWN ALARM
There is a 10 second delay before engine temperature is moni-
tored.
Once running there is a 1/4 second delay before shut down. The
limit is set at 125° C or 257° F.
OVERCRANK SHUTDOWN ALARM
Occurs if the engine has not started within the specified crank
cycle.
4. If during the cool down period utility voltage should fall below
60% of nominal the 5 second warm-up timer is initiated and
the unit will transfer the load back to the generator and con-
tinue to monitor the utility.
OVERSPEED SHUTDOWN ALARM
Warning indicator is measured and calculated by the microproces-
sor. Overspeed is defined as +20% of nominal engine speed for 3
seconds, or +25% immediate.
CRANK CYCLES AND OVERCRANK SHUTDOWN
If the unit fails to start during a cranking period it will display the
Overcrank Shutdown Alarm. The system will control the cranking
cycles as follows:
Nominal engine speed = 60.0 Hz
RPM SENSOR FAILURE SHUTDOWN ALARM
During cranking: If the board does not see a valid RPM signal
within four (4) seconds of cranking it will shut down and lock out
on RPM sensor loss.
The first crank cycle is a 16 second crank time followed by a 7
second rest. The next 5 cycles will be 7 seconds of cranking time
each followed by a 7 second rest time.
If the unit fails to start by the end of the 6 crank/rest cycles
the Overcrank Shutdown Alarm will display and the unit will not
attempt to crank until the alarm is reset.
During running: If the RPM signal is lost for one full second the
board will shut the engine down, wait 15 seconds, then re-crank
the engine if in AUTO, it will not re-crank in MANUAL.
If no RPM signal is detected within the first four (4) seconds of
cranking, the control board will shut the engine down and latch out
on RPM sensor loss.
AUTO START
This unit is designed to automatically start in the event of a util-
ity failure or brown out condition. Brown out is defined as utility
voltage less than 60% nominal, while utility is considered good
when it is restored to at least the pickup value, 80% of nominal.
These levels are fixed. The “Line Interrupt period” is an adjustable
parameter by the dealer. If 2-wire start mode is activated, the unit
will start when 2-wire start is active.
If the RPM signal is detected the engine will start and run normally.
If the RPM signal is subsequently lost the control board will try
two more re-cranks before latching out and flashing the RPM
Sensor Failure message (if it is in AUTO).
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1 R
8-4
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
Figure 1 – Generator Control Panel
CHECK ENGINE MESSAGE
MISSING CAM PULSE ALARM
The control system has detected an emissions related fault. This
fault cannot be cleared using the control panel interface. The unit
will continue to operate in automatic mode. Contact your local
servicing dealer.
This is a shutdown alarm. The alarm will activate after five (5)
seconds of continuously missing cam pulses.
MISSING CRANK PULSE ALARM
This is a shutdown alarm. The alarm will activate after 12 con-
secutive revs where crank pulses are missing.
UNDER-FREQUENCY SHUTDOWN ALARM
After starting, if the generator stays under frequency for more than
30 seconds, it will shutdown.
LOW FUEL PRESSURE WARNING
Fuel pressure is monitored by a digital sensor with a fixed setpoint
of below five (5) inches water column.
LOW BATTERY ALARM
While running, if the average battery voltage falls below 11.9 volts
for one (1) minute, the low battery alarm will be displayed.
GOVERNOR SENSOR FAULT ALARM
The governor position is monitored by an analog feedback signal. If
the throttle position is seen outside of the normal operating range,
a shutdown alarm is displayed. If the throttle is commanded to
move, and no movement is seen, a shutdown alarm is displayed.
LOW BATTERY WARNING
The microprocessor will continually monitor the battery voltage
and display the Low Battery Voltage message if the battery voltage
falls below 12.2 Volts for one (1) minute.
WIRING ERROR ALARM
No other action is taken on a low battery warning condition. The
warning will automatically clear if the battery voltage rises above
12.2 volts.
When power is first apllied to the contoller, the software will per-
form a check on the wiring of the transfer output, and ensure it
does not have high voltage on the wire. If this is the case, it will
signal a miswire alarm and will not run. The test can be skipped
by use of the escape key.
NOTE:
The battery sentinel is a separate feature that monitors battery
condition.
UNDERVOLTAGE ALARM
If the generator voltage falls below 60% for >5 seconds, an alarm
will be issued.
LOW COOLANT LEVEL ALARM
This is a shutdown alarm. The sensor will be continuously moni-
tored. If an error condition is seen for five (5) consecutive sec-
onds, the alarm will be displayed.
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1
8-5
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
OVERVOLTAGE ALARM
ALARM CANCEL
If the generator voltage rises above 110% for >3 seconds, an
alarm will be issued.
When the generator is shut down due to a latching alarm, the Auto
/Off/ Manual switch must be set to the off position and the ENTER
key pressed to unlatch any active fault and clear the corresponding
fault alarm message.
If the generator voltage rises above 130% for >0.2 seconds, an
alarm will be issued.
INTERNAL FAILURE SHUTDOWN ALARM
Any internal failure that can be detected such as corrupted
firmware will cause this shutdown alarm. This alarm cannot be
cleared.
COMMON ALARM RELAY
The common alarm relay will be activated if there is a shutdown
alarm. It will not activate on warnings or indicate that the Auto/Off/
Manual switch is in the OFF position. The OFF position will clear
the alarms and the relay. The relay will not be used to indicate a
generator is not activated.
CANBUS ALARM
The common alarm connections are wired to a set of potential-
free (dry) contacts on the Nexus controller board. These Normally
Open (N.O.) contacts close when an alarm condition occurs and
are used to activate a remote signaling device. The circuit is rated
for a maximum of 130mA at 24 VDC. The connections are a short
set of free hanging wires that exit the engine harness loom directly
behind the Nexus Control Panel and are labeled numbers 209 and
210.
Where applicable, if the Canbus communications link fails to com-
municate, a “Canbus Alarm” will be generated. This only applies
to systems with external ignition modules. The alarm may be
generated if:
1. The physical link is broken.
2. The Ignition Module fails or resets.
3. The Nexus Controller fails or resets.
4. Having the Battery Chargers 120 VAC connected without a
battery installed.
MAINTENANCE ALERTS
Maintenance alerts will be provided for these conditions.
5. A blown 10 amp Ignition Module fuse (approximately 12
inches away from the starter).
6. A blown 25 amp system fuse (located approximately 12
inches away from the DC alternator).
NOTE:
SERVICE SCHEDULE ‘A’
Inspect Accessory Drive Alert
Coolant Change & Flush
1yr / 100hrs*
1yr / 100hrs
1yr / 100hrs
1yr / 100hrs*
1yr / 100hrs
1yr / 100hrs
6mo / 50hrs*
The “Canbus Alarm” will not clear on its own. To clear the
alarm, press the “enter” key to acknowledge the alarm. The
alarm will clear and if the fault is still present, the alarm will
reoccur.
Inspect Spark Plugs Alert
Change Oil & Filter Alert
IGNITION ALARM
When an ignition alarm occurs, a generic message “Ignition Fault”
will be displayed as the fault code.
Inspect Battery Alert
Change / Inspect Air Filter Alert
Clean/Inspect Air Inlet & Exhaust
* Items require a 3 month / 30 hour break-in change or check.
MAINTENANCE WARNING
When a maintenance period expires, a warning message will be
posted. The warning can be reset by hitting the Enter key. Resetting
will clear the warning and reset the maintenance counters for the
condition annunciated. The history log will reflect the maintenance
warning.
SERVICE SCHEDULE ‘B’
Change / Inspect spark plugs alert
2yr/ 250hr
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1 R
8-6
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1
8-7
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
STATIONARY EMERGENCY
GENERATOR CONTROL AND
OPERATION
Do not crank the engine continuously for lon-
ger than 30 seconds, or the heat may
damage the starter motor.
n
Refer to the appropriate control panel operator’s manual for this
unit.
• Let engine stabilize and warm up.
• Check all applicable instrument and gauge readings. When
certain that all readings are correct, move the transfer switch
manual handle to the STANDBY (or EMERGENCY STANDBY)
position, i.e., load circuits supplied by the generator.
• Set the generator’s main line circuit breaker to its ON (or
CLOSED) position.
OPERATING UNIT WITH MANUAL
TRANSFER SWITCH
If the Stationary Emergency Generator was installed in conjunction
with a transfer switch capable of manual operation only, the fol-
lowing procedure applies. A manually operated transfer switch is
one that will not provide automatic start-up and does not include
an intelligence circuit.
• Load circuits are now powered by the generator.
RETRANSFER AND SHUTDOWN
For additional information, refer to the applicable control panel
manual for this unit, as well as any literature pertaining to the
specific transfer switch.
ENGINE START-UP AND TRANSFER
For additional information, refer to the applicable control panel
manual for this unit, as well as any literature pertaining to the
specific transfer switch.
To transfer the load back to the utility power source and shut down
the generator, follow these directions:
• Set the generator’s main line circuit breaker to its OFF (or OPEN)
position.
• Manually move the transfer switch handle to its UTILITY
(NORMAL) position, i.e., load circuits connected to the utility.
• Turn ON the utility power supply to the transfer switch, using
the means provided (such as the utility power source main line
circuit breaker).
• Let the generator run at no-load for a few minutes to stabilize
internal temperatures.
• Shut down the generator.
nThe Maintenance Disconnect Switch and the
AUTO/OFF/MANUAL switches (if so equipped)
must be set properly, or the generator will
crank and start as soon as the utility power to
the transfer switch is turned off. Refer to appli-
cable control panel and transfer switch manuals
for more information.
nDo not proceed until certain that utility source
voltage is available to the transfer switch and
OPERATING UNIT WITH AUTOMATIC
the transfer switch main contacts are set to
UTILITY.
TRANSFER SWITCH
Do not attempt manual operation until all
power supplies to the transfer switch have been
If the Stationary Emergency Generator has been installed with an
automatic transfer switch, the engine may be started and stopped
automatically or manually.
positively turned off, or extremely dangerous -
possibly lethal - electrical shock will result.
NOTE:
Transfer switch enclosure doors should be kept
closed and locked. Only authorized personnel
Refer to the applicable manual for your transfer switch and to
“Transfer Switch Start Signal Connections”. In addition, please
note the dangers under “Engine Start-up and Transfer.”
should be allowed access to the transfer switch
interior. Extremely high and dangerous voltages
are present in the transfer switch.
In order to transfer load from the utility source to the generator,
follow these directions:
• Turn OFF or disconnect the utility power circuit to the transfer
switch, using the means provided (such as the utility source
main line circuit breaker).
• Set the transfer handle to its UTILITY (NORMAL) position with
load circuits connected to the utility power supply.
• Set the generator’s main line circuit breaker to its OFF (or OPEN)
position.
• Start the generator.
. D v e 0 5 / 1 0
O p e r 0 0 1 R
9-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Refer to the Service Schedule for engine oil and filter change fre-
quencies.
GENERAL MAINTENANCE
Drain the oil while the engine is still warm from running. This
means warm up the engine, shut it down and drain immediately
as follows:
Before working on the Stationary Emergency
Generator, ensure the following:
• The AUTO/OFF/MANUAL switch is in the OFF position.
• The control panel fuse has been removed from the control
box.
1. Remove the drain hose from its retaining clip or cut the zip-tie
securing the oil drain hose.
2. Loosen and remove OIL DRAIN HOSE CAP. Drain oil com-
• The 120VAC supply to the battery charger is switched OFF.
• The negative battery cable has been removed.
pletely into suitable container.
3. When all oil has drained, install and tighten OIL DRAIN HOSE
CAP and secure drain hose with a new zip-tie, or place the
hose in its retaining clip.
CHECK ENGINE OIL
Check engine crankcase oil level (Figure 10.1) according to the
Service Schedule and SIB10-10-L24G.
4. Turn OIL FILTER (Figure 10.1) counterclockwise and remove.
Properly dispose of old filter.
5. Apply light coating of new engine oil to seal of new oil fil-
ter. Install FILTER and tighten by hand only. DO NOT OVER
TIGHTEN.
• Remove oil dipstick and wipe dry with a clean, lint-free cloth.
• Install oil dipstick, then remove again.
• Oil should be between FULL and ADD marks.
• If oil level is below the dipstick ADD mark, remove oil fill cap-.
Add the recommended oil to bring oil level up to the FULL
mark. DO NOT FILL ABOVE THE “FULL” MARK. See “Engine Oil
Recommendations” for recommended oils.
6. Remove OIL FILL CAP and add recommended oil. Crankcase
oil capacity is listed in the "Specifications" section.
After refilling the crankcase with oil, always
check oil level on dipstick. NEVER OPERATE
ENGINE WITH OIL BELOW THE DIPSTICK “ADD”
MARK.
n
Figure 10.1 - Oil Dipstick and Oil Fill Cap
OIL FILL CAP
7. Start engine and check for oil leaks.
8. Shut OFF engine and wait 10 minutes for the oil to settle down
into the oil pan. Recheck oil level on dipstick. DO NOT fill
above the dipstick "FULL" mark.
9. Dispose of used oil at a proper collection center.
COOLING INTAKE/OUTLET
Air intake and outlet openings in the generator compartment must
be open and unobstructed for continued proper operation. This
includes such obstructions as high grass, weeds, brush, leaves
and snow.
OIL
Without sufficient cooling and ventilating air flow, the engine/gen-
erator quickly overheats, which causes it to shut down. (See the
installation diagram.)
DIPSTICK
The exhaust system parts from this product get
extremely hot and remains hot after shutdown.
High grass, weeds, brush, leaves, etc. must
remain clear of the exhaust. Such materials may
ignite and burn from the heat of the exhaust
system.
OIL
FILTER
CHANGING ENGINE OIL
INSPECT COOLING SYSTEM
• Inspect engine cooling system. See the Service Schedule.
• Check hoses for damage, deterioration, leaks, etc. Correct any
discrepancies found.
Hot oil may cause burns. Allow engine to cool
before draining oil. Avoid prolonged or repeat-
n
ed skin exposure with used oil. Thoroughly
wash exposed areas with soap.
• Check hose clamps for tightness.
. A v e 0 5 / 1 0
M a i n t 0 2 7 R
10-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
ENGINE COOLANT
CHECK FAN BELT
Checkcoolantlevelincoolantrecoverybottle.See theSpecifications
and Service Schedule sections.
• Inspect fan belts every year. Replace any damaged, deterio-
rated, worn or otherwise defective belt.
• Check fan belt tension. Thumb pressure, exerted midway
between pulleys, should deflect about 3/8 to 5/8 of an inch.
Adjust belt tension as required.
• Add recommended coolant mixture as necessary.
• Periodically remove radiator pressure cap (only when engine
has cooled down) to make sure the coolant recovery system
is functioning properly. Coolant should be at bottom of radia-
tor filler neck. If coolant level is low, inspect gasket in radiator
pressure cap. Replace cap, if necessary. To have pressure cap
tested, contact a Service Facility. Inspect cooling system and
coolant recovery system for leaks.
• Check fan belt alignment (see Figure 10.2).
Figure 10.2 – Fan Belt
COOLANT CHANGE
Every year, have a service facility drain, flush and refill the cooling
system. See the Specifications and Service Schedule for cooling
system recommendations.
OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL
SYSTEM
Engine cranking, start up and running are controlled by a solid
state Engine Controller circuit board. Battery voltage is delivered
to that circuit board via the control panel fuse. This overcurrent
protection device will open if the circuit is overloaded.
INSPECT ENGINE GOVERNOR
Visually inspect electronic governor.
If a circuit breaker opens or a fuse element
melts, find the cause of the overload before
n
resetting the circuit breaker or replacing the
fuse.
Do not attempt to adjust the governor. Only
EXERCISE SYSTEM
Starts the Stationary Emergency Generator engine once every
seven days and lets it run for 12 minutes.
qualified service facilities should adjust the
n
governor. Excessively high operating speeds
are dangerous and increase the risk of personal
injury. Low speeds impose a heavy load on the
engine when adequate engine power is not
available and may shorten engine life. Correct
rated frequency and voltage are supplied only
at the proper governed speed. Some connected
electrical load devices may be damaged by
incorrect frequency and/or voltage. Only quali-
fied service technicians should adjust the gov-
erned speed.
PERFORM VISUAL INSPECTION
Complete a thorough visual inspection of the entire engine-genera-
tor monthly. Look for obvious damage, loose, missing or corroded
nuts, bolts and other fasteners. Look for fuel, oil or coolant leaks.
INSPECT EXHAUST SYSTEM
Inspect the exhaust system at least once every year. Check all
exhaust system pipes, mufflers, clamps, etc. for condition, tight-
ness, leaks, security, damage.
CHANGING THE ENGINE AIR FILTER
To replace the engine air filter, remove the air filter cover and
replace the air filter making sure it is positioned properly before
reattaching the cover (Figure 10.3).
See the Service Schedule for air filter maintenance.
. A v e 0 5 / 1 0
M a i n t 0 2 7 R
10-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
nBattery electrolyte fluid is an extremely corro-
sive sulfuric acid solution that can cause severe
Figure 10.3 – Engine Air Filter
burns. Do not permit fluid to contact eyes, skin,
clothing, painted surfaces, etc. Wear protective
goggles, protective clothing and gloves when
handling a battery. If fluid is spilled, flush the
affected area immediately with clear water.
Do not use any jumper cables or booster bat-
tery to crank and start the generator engine. If
the battery has completely discharged, remove
it from the generator for recharging.
n
AIR
FILTER
Be sure the AUTO/OFF/MANUAL switch is set
to the OFF position, before connecting the
battery cables. If the switch is set to AUTO or
MANUAL, the generator can crank and start as
soon as the battery cables are connected.
n
Be sure the 120VAC power supply to the battery
is turned OFF, or sparking may occur at the bat-
tery posts as the cables are attached and cause
an explosion.
SPARK PLUGS
Reset the spark plug gap or replace the spark plugs as neces-
sary.
1. Clean the area around the base of the spark plugs to keep dirt
and debris out of the engine. Clean by scraping or washing
using a wire brush and commercial solvent. Do not blast the
spark plugs to clean.
2. Remove the spark plugs and check the condition. Replace
the spark plugs if worn or if reuse is questionable. See the
“Service Schedule” section for recommended inspection.
3. Check the spark plug gap using a wire feeler gauge. See the
Specifications section for the required spark plug gap.
BATTERY REPLACEMENT
NOTE:
Unit DOES NOT include battery.
When supplying or replacing the battery, the recommended num-
ber and type of battery is listed in the Specifications Section.
NOTE:
The BCI number should be located directly on the battery.
BATTERY MAINTENANCE
The battery should be inspected per the Service Schedule section.
The following procedure should be followed for inspection:
BATTERY FLUID
Check battery electrolyte fluid based on the Service Schedule.
Fluid should cover separators in all battery cells. If fluid level is
low, add distilled water to cover tops of separators. DO NOT USE
TAP WATER IN BATTERY.
1. Inspect the battery posts and cables for tightness and corro-
sion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries and, if
necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP
WATER IN BATTERIES.
CLEANING THE STATIONARY EMERGENCY GENERATOR
Keep the generator as clean and as dry as possible. Dirt and
moisture that accumulates on internal generator windings have an
adverse effect on insulation resistance.
3. Have the state of charge and condition checked. This should
be done with an automotive-type battery hydrometer.
Periodically clean generator exterior surfaces. A soft brush may be
used to loosen caked on dirt. Use a vacuum system or dry, low
pressure air to remove any accumulations of dirt. The generator is
housed inside an all-weather enclosure, clean the enclosure with a
soft, damp cloth or sponge and water.
Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture
around the battery for several hours after
charging. The slightest spark can ignite the gas
and cause an explosion. Such an explosion can
shatter the battery and cause blindness or other
injury. Any area that houses a storage battery
must be properly ventilated. Do not allow smok-
ing, open flame, sparks or any spark producing
tools or equipment near the battery.
Once each year have the generator cleaned and inspected by a
Service Dealer. That dealer will use dry, low pressure air to clean
internal windings.
Finally, have the insulation resistance of stator and rotor windings
checked. If insulation resistances are excessively low, the genera-
tor may require drying.
. A v e 0 5 / 1 0
M a i n t 0 2 7 R
10-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Schedule
SERVICE SCHEDULE
System / Component
Frequency
Procedure
Weekly - W
Monthly - M
Yearly - Y
Inspect
Change
Clean
Fuel
Fuel Lines & Connections
Lubrication
M
X
Oil Level
M
Y
X*
Oil
X**
X**
Oil Filter
Y
Cooling
Engine Coolant Lines & Connections
Engine Coolant Level
Engine Coolant
M
M
Y
X
X
X
Enclosure Louvers
Engine
W
X
X
Air Cleaner
Y
Y
X
X
X***
X***
Spark Plugs
Battery
Remove Corrosion, Ensure Dryness
Clean & Tighten Battery Terminals
Check Charge State
Check Electrolyte Level
General Condition
Vibration, Noise, Leakage, Temperature
Generator System
Complete Tune-up and System Inspection
Footnotes
M
M
M
M
X
X
X
X
X
X
X***
X***
M
Y
X
To be completed by an Authorized Service Dealer.
* Inspect the oil level monthly or every 12 hours during continuous operation.
** Change oil and oil filter after the first 30 hours of operation and then every 100 hours or annually thereafter, whichever occurs first.
Change sooner when operating under heavy load or in a dusty or dirty environment or in high ambient temperatures.
*** Replace as necessary.
. B v e 0 5 / 1 0
v S S c r h d 0 0 4 R
11-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
TROUBLESHOOTING GUIDE
PROBLEM
Engine won’t crank.
CAUSE
CORRECTION
1. Control panel 7.5 amp fuse blown.
2. Loose or corroded or defective
battery cables.
1. Replace fuse.*
2. Tighten, clean or replace
battery cables as necessary.*
3. Replace contactor.*
4. Replace starter motor.*
5. Remove, change or replace battery.*
3. Defective starter contactor.
4. Defective starter motor.
5. Dead or Defective Battery.
Engine cranks but won't start.
Engine starts hard, runs rough.
1. Out of fuel.
2. Fuel solenoid (FS) is defective
3. Spark plugs defective.
1. Replenish fuel/turn on fuel valve.
2. Replace solenoid.*
3. Clean, regap or replace plugs.
1. Air cleaner plugged or damaged.
2. Defective spark plugs.
3. Fuel pressure incorrect.
1. Clean or replace as needed.
2. Clean, regap or replace plugs.
3. Confirm fuel pressure to regulator is as
recommended in SPECIFICATIONS.*
4. Confirm fuel pressure to regualtor is as
recommended in SPECIFICATIONS.*
5. Reconfigure the fuel system. (See
RECONFIGURING THE FUEL SYSTEM in
manual.*
4. Insufficient fuel supply.
5. Fuel system set to wrong fuel type.
Engine starts then shuts down.
1. Engine oil level is low.
2. Engine is overheated.
3. Defective Low Oil Pressure Switch
4. Defective Coolant Temperature Switch
5. Defective Control Module circuit board.
6. Coolant Level is Low.
1. Check oil and add oil as needed.
2. Check cooling system for leaks.
3. Replace switch.*
4. Replace switch.*
5. Replace board.*
6. Repair leak - Add coolant.
7. Replace Switch.*
7. Defective Low Coolant Level Switch
AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch
1. Replace board.*
2. Replace board.*
engine continues to run.
2. Defective Control Module circuit board
No AC output from generator.
1. Main line circuit breaker is tripped/open.
2. Generator internal failure.
1. Reset to ON/CLOSED.
2. *
3. Thermal circuit breaker open.
3. Auto-reset - Wait 5 min. and attempt restart.
*Contact the nearest Dealer for assistance.
. B v e 0 5 / 1 0
r b T l s h t 0 0 3 R
12-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty
United States Environmental Protection Agency Warranty Statement
(Stationary Emergency Spark-Ignited Generators)
Warranty Rights, Obligations and Coverage
The United States Environmental Protection Agency (EPA) and Generac Power Systems, Inc. (Generac) are pleased to explain the
Emission Control System Warranty on your new stationary emergency engine. If during the warranty period, any emission control system
or component on your engine is found defective in materials or workmanship, Generac will repair your engine at no cost to you for diag-
nosis, replacement parts and labor provided it be done by a Generac Authorized Warranty Service Facility. Your emission control system
may include parts such as the fuel metering, ignition, and exhaust systems and other related emission related components listed below.
Generac will warrant the emissions control systems on your 2009 and later model year engines provided there has been no abuse,
neglect, unapproved modification or improper maintenance of your engine. For engines less than 130 HP the warranty period is two years
from the date of sale to the ultimate purchaser. For engines greater than or equal to 130 HP the warranty period is three years from the
date of the engine being placed into service.
Purchaser's/Owner's Warranty Responsibilities
As the engine purchaser/owner you are responsible for the following. 1.) The engine must be installed and configured in accordance
to the Generac's installation specifications. 2.) The completion of all maintenance requirements listed in your Owner’s Manual. 3.) Any
engine setting adjustment must be done in accordance and consistent with the instructions in the Owner’s Manual. 4.) Any emission con-
trol system or component must be maintained and operated appropriately in order to ensure proper operation of the engine and control
system to minimize emissions at all times.
Generac may deny any/or all Emission Control System Warranty coverage or responsibility of the engine, or an emission control system
or component on your engine thereof, if it has failed due to abuse, neglect, unapproved modification or improper maintenance, or the use
of counterfeit and/or 'gray market' parts not made, supplied or approved by Generac. Warranty service can be arranged by contacting
either your selling dealer or a Generac Authorized Warranty Service dealer, 1-800-333-1322 for the dealer nearest you. The purchaser/
owner shall be responsible for any expenses or other charges incurred for service calls and/or transportation of the product to/from the
inspection or repair facilities. The purchaser/owner shall be responsible for any and/or all damages or losses incurred while the engine
is being transported/shipped for inspection or warranty repairs. Contact Generac Power Systems Inc. for additional Emission Control
System Warranty related information, Generac Power Systems, Inc. P.O. Box 8, Waukesha, WI 53187, or call 1-800-333-1322 or www.
generac.com.
Important Note
This warranty statement explains your rights and obligations under the Emission Control System Warranty, which is provided to you by
Generac pursuant to federal law. Note that this warranty shall not apply to any incidental, consequential or indirect damages caused by
defects in materials or workmanship or any delay in repair or replacement of the defective part(s). This warranty is in place of all other
warranties, expressed or implied. Specifically, Generac makes no other warranties as to the merchantability or fitness for a particular pur-
pose. Any implied warranties which are allowed by law, shall be limited in duration to the terms of the express warranty provided herein.
Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
Emission Related Parts Include the Following (if so equipped)
1) Fuel Metering System
3)
4)
5)
Ignition System Including
1.1) Gasoline Carburetor Assembly And Internal
Components A) Fuel Filter, B) Carburetor, C) Fuel
Pump
1.2) Carburetion Assembly And Its Components
A) Fuel Controller, B) Carburetor And Its Gaskets, C)
Mixer And It Gaskets, D) Primary Gas Regulator E)
Liquid Vaporizer
1.3) Fuel Regulator
2) Air Induction System Including
A) Intake Pipe/Manifold,
A) Spark Plug, B) Ignition Module,
C) Ignition Coil, D) Spark Plug Wires
Exhaust System
A) Catalyst Assembly, B) Exhaust Manifold,
C) Muffler, D) Exhaust Pipe, E) Muffler Gasket
Crankcase Breather Assembly Including
A) Breather Connection Tube, B) Pcv Valve
Oxygen Sensor
6)
7)
Diagnostic Emission-Control System
B) Air Cleaner
. D v e 0 9 / 1 1 n t y 0 0 1 R E m s n W r
13-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty
United States Environmental Protection Agency Compliance Requirements
(Stationary Emergency Spark-Ignited Generators)
Purchaser's/Owner's Recordkeeping Responsibilities
The United States Environmental Protection Agency (EPA) and Generac Power Systems, Inc. (Generac) are pleased to explain your record-
keeping requirements for compliance with Subpart JJJJ- Standards of Performance for Stationary Spark Ignition Internal Combustion Engines
as listed in the Electronic Code of Federal Regulations Title 40 Part 60. As the engine purchaser/owner who operates and maintains their
certified emergency stationary engine and emission control system according to applicable emission related guidelines as specified in this
Owner's Manual, you are required to meet the following notification and recordkeeping requirements to demonstrate compliance. 1.) Maintain
documentation that the engine is certified to meet emission standards. 2.) Recordkeeping of maintenance conducted. 3.) Recordkeeping of
the provision allowing natural gas engines to operate using propane for a maximum of 100 hours per year as an alternate fuel solely dur-
ing emergency operations provided the engine is not certified to operate on propane. 4.) Meet all compliance notifications submitted to the
purchaser/owner and maintain all supporting documentation. 5.) Recordkeeping of hours of operation, including what classified the operation
as emergency and how many hours are spent for non-emergency operation. For emergency engines greater than or equal to 130 HP, record-
keeping of hours of operation begins January 1, 2011. For emergency engines less than 130 HP, recordkeeping of hours of operation begins
January 1, 2009; Engines are equipped with non-resettable hour meters to facilitate recordkeeping.
Specific Air Quality Management or Air Pollution Control Districts may have different and additional record keeping/reporting requirements.
Your permit to construct and/or operate the engine may be contingent upon compliance with those requirements. Check with your local Air
Quality Management or Air Pollution Control District for specific requirements.
Emergency stationary internal combustion engines (ICE) may be operated for the purpose of maintenance checks and readiness testing,
provided that the tests are recommended by Federal, State or local government, Generac, or the insurance company associated with the en-
gine. Maintenance checks and readiness testing of such units is limited to 100 hours per year. There is no time limit on the use of emergency
stationary ICE in emergency situations. The purchaser/owner may petition the Administrator for approval of additional hours to be used for
maintenance checks and readiness testing, but a petition is not required if the owner maintains records indicating that Federal, State, or local
standards require maintenance and testing of emergency ICE beyond 100 hours per year. Emergency stationary ICE may operate up to 50
hours per year in non emergency situations, but those 50 hours are counted towards the 100 hours per year provided for maintenance and
testing.
The 50 hours per year for non-emergency situations cannot be used for peak shaving or to generate income for a facility to supply power to
an electric grid or otherwise supply power as part of a financial arrangement with another entity. For purchaser/owner of emergency engines,
any operation other than emergency operation, maintenance and testing, and operation in non-emergency situations for 50 hours per year, as
permitted in this section is prohibited.
If you operate and maintain your certified emergency stationary SI internal combustion engine and emissions control systems in accordance
to the specifications and guidelines in this Owner’s Manual EPA will not require engine performance testing. If not, your engine will be consid-
ered non-certified and you must demonstrate compliance according to Subpart JJJJ - Standards of Performance for Stationary Spark Ignition
Internal Combustion Engines as listed in the Electronic Code of Federal Regulations Title 40 Part 60.
Emission-Related Installation Instructions
Your certified emergency stationary engine has pre-set emission control systems or components that require no adjustment. Inspection and
replacement of an emissions related component is required to be done so in accordance with the requirements cited in the United States
Environmental Protection Agency Warranty Statement or can be arranged by contacting either your selling dealer or a Generac Authorized
Warranty Service dealer, 1-800-333-1322 for the dealer nearest you. Failing to follow these instructions when installing a certified engine in a
piece of nonroad equipment violates federal law 40 CFR 1068.105 (b), subject to fines or penalties as described in the Clean Air Act.
. D v e 0 9 / 1 1 n t y 0 0 1 R E m s n W r
13-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Notes
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
1
0G4827
0G2927
0G2827
0G3451
0G0820A
0G4452
020746
049226
051713
022129
0G4825
0G4826
0G2926
0G3682
0G5584
0G3685
0G2826
0G3683
0G6573
0G3686
0G3684
0G3687
0G5909
0G6103
0A5382A
075591
051787
0A5601A
0G8827
0G8827A
0A9375
022152
0G4196
042558
0J6102
0G0965B
053607
051769
023365
0F3353
072578
0G3787
0A8830
077043E
0G2070
0G2070A
045771
0D8427
0J6853A
0J6853B
0J6853C
0C2454
1
1
1
1
1
1
4
4
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
4
4
4
4
1
1
4
1
1
1
4
6
1
6
4
1
1
1
4
4
1
1
1
6
ASSY RTR 104 KD1 HI EFF (18KW)
RTR-102-20.0AD1 CPL (2006) (20KW)
ASSY RTR 25KW 2P (2006) (25KW)
ASSY RTR 30KW 2P 10"(2006)
HOUSING BLOWER LG PILOT
BLOWER HOUSING SCREEN
SCREW PPHM M5-0.8 X 8 ZINC
WASHER LOCK M5
WASHER FLAT M5
2
3
4
5
6
7
8
WASHER LOCK M8-5/16
ASSY STR 104-18AD1 HI EFF (18KW)
ASSY STR 104 18GD1 HI EFF (18KW)
STR-102-20.0AD1 CPL (2006) (20KW)
STR-102-20.0GD1 CPL (2006) (20KW)
STR-102-20.0JD1 CPL (2006) (20KW)
STR-102-20.0KD1 CPL (2006) (20KW)
ASSY STR 102 25AD1 (2006) (25KW)
STR-102-25.0GD1 CPL (2006) (25KW)
STR-102-25.0-JD1 CPL (2006) (25KW)
STR-102-25.0KD1 CPL (2006) (25KW)
STR-102-30.0GD2 CPL (30KW)
STR-102-30.0KD2 CPL (30KW)
ASSY STR 102 30AD2 10" (30KW)
STR-102-30.0JD2
BEARING CARRIER REAR LG PILOT
ASSY HOLDER BRUSH
SCREW HHC M4-0.7 X 16 G8.8
COVER REAR BEARING
STUD M8-1.25 475 LONG
STUD M8-1.25 418 LONG
SCREW RHM #10-24 X 2
WASHER LOCK #10
FLYWHEEL & RINGGEAR ASSY 1.6L
KEY SQ 3/8 X 1 STEEL
SCREW HHFC M10-1.5 X 16 C10.9
PLATE FLEX 1.6L R12.7
SCREW HHC M12-1.75 X 35 G8.8
WASHER LOCK M12
WASHER SHAKEPROOF INT #8
SCREW HHC M10-1.0 X 20 G10.9
SPACER ROTOR SHAFT
WASHER .41 ID .94 OD .12 THK
WASHER FLAT .34 ID X .75 OD
FLEX CONDUIT 1" BLACK (NOT SHOWN)
PLATE SPACER 14GA 1.6L (TO BE USED WITH ENGINE PLATE P/N 0G0834.)
PLATE SPACER 16GA 1.6L (TO BE USED WITH ENGINE PLATE P/N 0G0834A.)
NUT HEX M8-1.25 G8 CLEAR ZINC
WASHER LOCK M10 RIBBED ZINC
SUPPORT LH ALT COVER
9
10
11
12
13
14
15
16
17
18
19
20
21
22
(1) 23
24
25
26
27
28
29
30
(2)31
(2)32
(2)33
(2)34
SUPPORT RH ALT COVER
COVER REAR 10" ALT
SCREW HWHT M6-1 X 16 N WA Z/JS
(1) APPLY LOCTITE 242 BEFORE THREADING SCREW INTO CRANKSHAFT.
(2) ALTERNATE CONFIGURATION REQUIRES ALL NOTED PARTS.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: CONNECTION BOX C1 CPL
DRAWING #: 0H7234
APPLICABLE TO:
GROUP A
ITEM
PART#
QTY.
DESCRIPTION
1
2
(4)3
4
0H6795
0H6796
0H67330ST0R
0H7115
022097
1
1
1
2
2
CONBOX BACK/SIDES C1 CPL
CONBOX TOP C1 CPL
BRACKET GIMBAL CONTROL PNL RAW
KNOB M6-1.0 CONTROL PANEL
WASHER LOCK M6-1/4
5
6
(3)7
8
022473
SEE CHART
052777
4
1
3
WASHER FLAT 1/4-M6 ZINC
CIRCUIT BREAKER
WASHER FLAT M3
9
043182
3
WASHER LOCK M3
10
(4)11
12
051714
0H81040AS0R
045764
3
1
2
3
NUT HEX M3-0.5 G8 CLEAR ZINC
COVER DPE BREAKER NEXUS
SCREW HHTT M4-0.7 X 8 ZP
WASHER LOCK #8-M4
13
022264
14
0A9457
1
DECAL NEUTRAL
15
16
(2)17
18
(4)19
20
21
22
23
24
REF
1
18
1
6
1
1
12
2
2
2
ASSY CTRL PROGRAMMED
SCREW HWHT M6-1 X 16 N WA Z/JS
REGULATOR - DC ALT
NUT FLANGE M6-1.0 NYLOK
SHIELD HIGH/LOW C1 RAW
RELAY SOLENOID 12VDC PNL MNT
SCREW HHSP #10 X 3/8 HI-LOW
SCREW HHC M6-1.0 X 20 C8.8
NUT HEX M5-0.8 G8 CLEAR ZINC
WASHER LOCK M5
0C2454
0A1354A
0D3700
0H88380ST0R
056739
0F5458
042568
051716
049226
25
051713
2
WASHER FLAT M5
26
27
28
29
0D7177V
0F5752F
0H6267
056326
0G3524
0D7393T
0D7393U
0F5376S0AR
0F5396S0AR
057073
2
1
1
1
DIODE BRIDGE 1P 35A 1000V
RES WW 15R 5% 25W QK CONN
COVER VOLTAGE SHIELD
TRIM VINYL BLACK 1/8GP (3”LG)
COVER BELL HOUSING CONBOX
TERM BLOCK 3P UL 12-20AWG
TERM BLOCK 4P UL 12-20AWG
MX150L SLRRMNT 22-18 8P W/O GA
MX150L SLRRMNT 22-18 12P W/OGA
JUNCTION BLOCK 3/8-16
30
1
(1)31
(1)32
(1)33
(1)34
35
REF
REF
REF
REF
1
36
37
38
0C2265
057329
022237
3
1
1
SCREW PHTT M4-0.7 X 12 ZP
LUG SLDLSS 350-#6X13/32 AL/CU
WASHER LOCK 3/8
39
022241
1
NUT HEX 3/8-16 STEEL
40
41
42
43
44
45
46
025433
023762
0H7292
0H7293
029289
1
1
1
1
1
1
2
LUG SLDLSS #6-14 X 13/64 CU
WASHER LOCK EXT #10 STL
DECAL CUSTOMER CONTROL CONNECT
DECAL CONBOX TB1 CONNECTIONS
TAPE ELEC 1/2 FOAM (62” LG)
DECAL CUSTOMER POWER CONNECT
WASHER NYLON .257
0J0489
0A2115
47
48
49
50
51
52
0F6146
1
1
REF
1
1
HANG TAG 2 WIRE START (NOT SHOWN)
HARN CONBOX NEXUS (NOT SHOWN)
FUSE ATO TYPE 7.5AMP (BROWN)
DECAL GROUND LUG
GASKET WIRE ENTRY COVER
DECAL CAUTION ELEC SHOCK SM
0H6692
0D7178T
067210A
0J6701
0H8006
1
UL CIRCUIT BREAKER (225AF)
A
B
C
D
E
F
G
H
J
0G5249
REF
1
1
1
2
2
2
10
2
2
CB 150A 2 POLE 240V 225AF
COVER CB G 225AF C1 CONBOX
INSULATOR CB 2P 225AF
SPRT CIRCUIT BREAKER G 225AF
WASHER FLAT #8 ZINC
WASHER LOCK #8-M4
NUT HEX #8-32 STEEL
SCREW HWHT M6-1 X 16 N WA Z/JS
SCREW RHM #8-32 X 3-1/4
BUS BAR 200A LUG ADAPTOR
SCREW SHC M8-1.25 X 20 G8
0H6846
0F8432A
0G5734
038150
022264
022471
0C2454
053640
0F8843
049897
K
L
4
REVISION: J-1182-J
DATE: 12/16/11
Page 4 of 8
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: CONNECTION BOX C1 CPL
DRAWING #: 0H7234
APPLICABLE TO:
GROUP A
ITEM
PART#
QTY.
DESCRIPTION
M
N
P
R
S
T
U
V
W
022129
022145
045771
058306
0F8451
6
4
2
2
2
1
1
1
4
WASHER LOCK M8-5/16
WASHER FLAT 5/16-M8 ZINC
NUT HEX M8-1.25 G8 CLEAR ZINC
SCREW SHC M8-1.25 X 25 C12.9
LUG SLDLSS 300 MCM-6 AL/CU
DECAL TERMINAL SHOCK HZD BI
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
0G3259
0J78230AS0R
029289
036261
RIVET POP .125 X .275 SS
(1) ITEMS INCLUDED WITH HARNESS P/N 0H6692.
(2) ITEMS USED ON 1.6L MODELS ONLY.
(3) SEE “C1 DPE BREAKER SELECTION” TABLE.
(4) SHEET METAL PARTS LISTED IN THE BOM TABLE ARE REPRESENTING GENERIC PARTS (NO COLOR)
•
•
MANUFACTURING: FOR CORRECT MATERIAL AND COLOR REFER TO AS400 BOM.
CUSTOMER: WHEN ORDERING REPLACEMENT PARTS ENTER BASE NUMBER (FIRST 6 DIGITS ONLY) IN THE
SYSTEM FOR CORRECT MATERIAL AND COLOR (FOR REFERENCE SEE GUIDELINE 0H7169).
REVISION: J-1182-J
DATE: 12/16/11
Page 5 of 8
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: CONNECTION BOX C1 CPL
DRAWING #: 0H7234
APPLICABLE TO:
GROUP A
ITEM
PART#
QTY.
DESCRIPTION
UL CIRCUIT BREAKER (CC 2P)
A
0H4745
REF
CB 0100A 2P 240V E CC LL
CB 0125A 2P 240V E CC LL
CB 0150A 2P 240V E CC LL
COVER CB E CC 2P C1 CONBOX
NUT HEX M5-0.8 G8 CLEAR ZINC
CIRCUIT BREAKER SUPPORT (CC)
WASHER FLAT #8 ZINC
WASHER LOCK #8-M4
NUT HEX #8-32 STEEL
SCREW HWHT M6-1 X 16 N WA Z/JS
SCREW RHM #8-32 X 3-1/4
SCREW PPHM M5-0.8 X 12 ZNC
WASHER FLAT #10 ZINC
0H4746
0H4747
0H6847
051716
0H4656
038150
022264
022471
0C2454
053640
091526
023897
049226
0H4698
0J78230AS0R
029289
036261
REF
REF
1
2
1
2
2
2
10
2
2
4
2
1
1
1
4
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
WASHER LOCK M5
INSULATOR CB 2P E TYPE CC
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
RIVET POP .125 X .275 SS
UL CIRCUIT BREAKER (CC/FG (3P) )
A
0H4913
REF
REF
REF
REF
1
CB 0100 3P 240V E CC LL
CB 0125 3P 240V E CC LL
CB 0080 3P 600V E FG LL
CB 0090 3P 600V E FG LL
CB COVER E CC/FG 3P C1 CONBOX
INSULATOR CB 3P E TYPE CC/FG
CIRCUIT BREAKER SUPPORT (CC)
CIRCUIT BREAKER SUPPORT (FG)
WASHER FLAT #8 ZINC
WASHER LOCK #8-M4
NUT HEX #8-32 STEEL
SCREW HWHT M6-1 X 16 N WA Z/JS
SCREW RHM #8-32 X 3-1/4 (CC)
0H4914
0H5488
0H5489
0H7294
0H4698A
0H4656
0H5604
038150
022264
022471
0C2454
053640
B
C
D
1
REF
REF
4
4
4
E
F
G
H
J
10
4
0H5721
091526
023897
4
3
6
SCREW PPHM #8-32 X 1-3/4 ZINC (FG)
SCREW PPHM M5-0.8 X 12 ZNC
WASHER FLAT #10 ZINC
K
L
M
N
P
Q
R
049226
051716
0J78230AS0R
029289
3
3
1
1
WASHER LOCK M5
NUT HEX M5-0.8 G8 CLEAR ZINC
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
036261
4
RIVET POP .125 X .275 SS
REVISION: J-1182-J
DATE: 12/16/11
Page 6 of 8
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: CONNECTION BOX C1 CPL
DRAWING #: 0H7234
APPLICABLE TO:
GROUP A
ITEM
PART#
QTY.
DESCRIPTION
UL CIRCUIT BREAKER (BQ 2P)
A
0D5543
REF
CB 0090A 2P 240V S BQ2 LL
CB 0100A 2P 240V S BQ2 LL
CB 0125A 2P 240V S BQ2 LL
COVER CB S BQ2 C1 CONBOX
BRKT CB MTG BACK
CIRCUIT BREAKER SUPPORT (BQ)
SCREW HHC M5-0.8 X 20 G8.8
WASHER FLAT #10 ZINC
0D5544
0A2077
0H6842
0E7890
0G4497
052619
REF
REF
1
1
1
B
C
D
E
F
2
4
023897
G
H
J
K
L
049226
0C2454
051716
0G9708
022264
2
10
2
2
2
WASHER LOCK M5
SCREW HWHT M6-1 X 16 N WA Z/JS
NUT HEX M5-0.8 G8 CLEAR ZINC
SCREW PHTT M4-0.7 X 8 ZP
WASHER LOCK #8-M4
M
N
P
0J78230AS0R
029289
1
1
4
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
RIVET POP .125 X .275 SS
036261
UL CIRCUIT BREAKER (BQ 3P)
A
062812
053691
040532
0H6843
0E6002
0G4497
052619
REF
CB 0080A 3P 240V S BQ3 LL
CIRCT BRK 90 X 3 ITE BQ3-B090
CB 0100A 3P 240V S BQ3 LL
COVER CB S BQ3 C1 CONBOX
MTG TRACK BQ SIEMENS CB 3P
CIRCUIT BREAKER SUPPORT (BQ)
SCREW HHC M5-0.8 X 20 G8.8
WASHER FLAT #10 ZINC
REF
REF
1
1
1
B
C
D
E
F
3
6
023897
G
H
J
K
L
049226
0C2454
051716
0G9708
022264
3
10
3
2
2
WASHER LOCK M5
SCREW HWHT M6-1 X 16 N WA Z/JS
NUT HEX M5-0.8 G8 CLEAR ZINC
SCREW PHTT M4-0.7 X 8 ZP
WASHER LOCK #8-M4
M
N
P
0J78230AS0R
029289
1
1
4
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
RIVET POP .125 X .275 SS
036261
UL CIRCUIT BREAKER (ED 3P)
A
0D5552
REF
REF
REF
REF
1
1
4
4
4
CB 0050A 3P 480V S ED4 LL
CB 0090A 3P 480V S ED4 LL
CB 0100A 3P 480V S ED4 LL
CB 0125A 3P 480V S ED4 LL
COVER CB S ED3 C1 CONBOX
CIRCUIT BREAKER SUPPORT (ED)
WASHER FLAT #8 ZINC
0D5556
0D5557
0D9693
0H6844
0G4498
038150
B
C
D
E
F
022264
022471
WASHER LOCK #8-M4
NUT HEX #8-32 STEEL
G
H
J
K
L
M
N
P
0A8278
0C2454
066715
3
10
4
3
3
1
1
4
SCREW SHC 1/4-28 X 3/4 G8.8 NZ
SCREW HWHT M6-1 X 16 N WA Z/JS
SCREW RHM #8-32 X 4-1/2
WASHER LOCK M6-1/4
WASHER-STEP 1/2ODX9/32ID BRASS
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
022097
0D5621
0J78230AS0R
029289
036261
RIVET POP .125 X .275 SS
UL CIRCUIT BREAKER (QN2 2P)
A
B
C
D
E
F
G
H
J
0E7283
0H6845
0E3664
0G4112
074908
REF
1
1
1
2
10
1
1
CB 0150A 2P 240V S QN2 LL
COVER CB S QN2 C1 CONBOX
BASE, QN CIRCUIT BREAKER
BREAKER SUPPORT BRACKET 30KW
SCREW HHTT M5-0.8 X 10 BP
SCREW HWHT M6-1 X 16 N WA Z/JS
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
0C2454
0J78230AS0R
029289
036261
4
RIVET POP .125 X .2
REVISION: J-1182-J
DATE: 12/16/11
Page 7 of 8
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: CONNECTION BOX C1 CPL
DRAWING #: 0H7234
APPLICABLE TO:
GROUP A
THIS PAGE LEFT INTENTIONALLY BLANK
REVISION: J-1182-J
DATE: 12/16/11
Page 8 of 8
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
1
2
3
4
5
6
7
8
0G3418
0G3421
0G3419
0E9837B
0G3553
0E3257
0G4080
099502
0G4070
0G4072
0G4071
046627
052250
022473
022097
0C8566
045771
0C2454A
042568
0G3573
0G3574
0G3420
080713
076749
048031C
029032
0G4451
055934N
0F9504
0G0568
0G3433
0E2507
0H1827
0A2628
029333A
042907
027482
022129
039253
0H1851
1
1
1
1
1
2
1
6
1
1
1
1
2
8
8
4
4
28
4
1
1
1
1
1
2
1
REF
2
1
1
1
1
1
1
10
4
RADIATOR SUPPORT LH SIDE 1.6L
VENTURI 1.6L
RADIATOR SUPPORT RH SIDE 1.6L
RADIATOR 1.6L CHY
FAN COOL 450MM DIA 7 BLADE
SCREW HWHTF M6-1.0 X 16
HOSE LOWER RADIATOR 1.6L
CLAMP HOSE #24 B1.06-2.00
HOSE REAR COOLANT 1.6L
TUBE ENGINE COOLANT 1.6L
HOSE UPPER RADIATOR 1.6L
CAP RADIATOR
TAPE FOAM 1 X 1 (24” LG)
WASHER FLAT 1/4-M6 ZINC
WASHER LOCK M6-1/4
SCREW HHFC M6-1.0 X 20 G8.8
NUT HEX M8-1.25 G8 CLEAR ZINC
SCREW THF M6-1 X 12 N WA Z/JS
SCREW HHC M6-1.0 X 20 G8.8
GUARD FAN LH C1
GUARD FAN RH C1
RADIATOR BLOCK-OFF
BRACKET COOLANT TANK
TANK COOLANT RECOVERY
CLAMP HOSE BAND 1/4
HOSE 9/32 ID (43” LG)
BRACKET STEPPER MOTOR COOLANT
CLAMP VINYL 1.31 X .281 Z
GROMMET 5/8"X 1 1/8"X 5/16"
ASSY FAN BEARING SUPPORT
BRACKET FAN ALT ADAPTER 1.6L
PROBE COOLANT LEVEL 3/8NPTF
PROBE COOLANT LEVEL 3/8-18NPTF (USE WITH I/N 40, P/N 0H1851)
PULLEY - FAN 95 DIA
TIE WRAP UL 7.4" X .19" BLK (NOT SHOWN)
SCREW HHC M8-1.25 X 16 G8.8
WASHER SHAKEPROOF EXT 5/16 STL
WASHER LOCK M8-5/16
9
10
11
12
13
14
15
16
17
18
19
20
21
23
24
25
26
27
28
29
30
31
32
33
34
35
(1) 36
37
38
39
4
4
4
1
SCREW HHC M8-1.25 X 20 G8.8
ASSY PCB LCL SENSOR (USE WITH I/N 33, P/N 0H1827 ONLY)
(2) 40
(1) APPLY LOCTITE 242 TO I/N 36 BEFORE THREADING INTO I/N 31.
(2) USE WITH R-200 CONTROL PANEL ONLY.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: MOUNTING BASE 1.6L
DRAWING #: 0G3531
APPLICABLE TO:
GROUP C
ITEM
PART#
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
13
14
15
16
17
18
19
0G3343
027482
070936
070936C
039253
022145
022129
045771
071956
051730
021991
026850
0G3461
055414
047411
022097
022473
025507
1
1
2
MOUNTING BASE 1.6L 2007 C1
WASHER SHAKEPROOF EXT 5/16 STL
DAMPENER VIBRATION
VIB. ISO. 70-75 DURO
SCREW HHC M8-1.25 X 20 G8.8
WASHER FLAT 5/16 ZINC
WASHER LOCK M8-5/16
NUT HEX M8-1.25 G8 YEL CHR
WASHER FLAT M8
SCREW HHC M8-1.25 X 60 G8.8
EARTH STRAP
WASHER SHAKEPROOF EXT 1/4 STL
ALTERNATOR SUPPORT BLOCK OFF
LUG SLDLSS #2-#8 X 17/64 CU
SCREW HHC M6-1.0 X 16 G8.8
WASHER LOCK M6-1/4
2
12
16
16
4
4
4
1
1
2
1
1
1
5
1
WASHER FLAT 1/4-M6 ZINC
WASHER LOCK EXT 7/16 STL
REVISION: H-5975-B
DATE: 2/5/10
Page 2 of 2
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
0F3408C
0F3411
025507
059980
046526
077483
050331A
050331
038805J
038804M
045771
022131
027482
0F3976
0C2454
022145
1
1
1
1
1
REF
REF
REF
1
1
REF
1
BATTERY TRAY, C1 & C2
STRAP BATTERY RETAINMENT
WASHER SHAKEPROOF EXT 7/16 STL
SCREW HHC M10-1.5 X 25 G10.9
WASHER LOCK M10
BATTERY 12VDC 75-AH 26
BATTERY POST COVER RED +
BATTERY POST COVER BLK -
CABLE BATTERY BLACK #1 X 30.00
CABLE BATTERY RED #1 X 21.00
NUT HEX M8-1.25 G8 YEL CHR
WASHER FLAT 3/8-M10 ZINC
WASHER SHAKEPROOF EXT 5/16 STL
BOOT CONTACTOR CABLES
SCREW THF M6-1 X 16 N WA Z/JS
WASHER FLAT 5/16-M8 ZINC
1
1
4
REF
NOTE: WHEN INSTALLING BATTERY, TUCK BATTERY’S LIFTING STRAP ALONG
THE LEFT SIDE OF BATTERY ( SIDE OPPOSITE RADIATOR) BEFORE
CONNECTING THE BATTERY CABLES.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: ENGINE COMMON PARTS 1.6L
DRAWING #: 0H7219
APPLICABLE TO:
GROUP D
ITEM
PART#
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
0H1734
0G0834A
0G0820A
0G7461
0G0839
0G0781
0G0722
0G4059
0G4604
0G3424
0G0786
0G4605
0F9617A
0A1354B
0G0823
0G3900
0D2244M
036710
REF
1
REF
1
2
1
1
1
1
1
1
1
1
1
1
1
1
2
ENGINE GENERAC 1.6L G11 CERT
ENGINE PLATE 1.6L 6MM (TO BE USED WITH PLATE SPACER P/N 0G2070A.)
HOUSING BLOWER LG PILOT
STARTER MOTOR 12V
ENGINE MOUNTING FOOT STAMPING
EXHAUST MANIFOLD 1.6L MACHINED
INTAKE MANIFOLD MACHINED 1.6L
SHIELD 1.6L EXHAUST HEAT
DC ALTERNATOR ADAPTER MACHINED
PULLEY CRANKSHAFT MACHINED
WASHER PULLEY
BRACKET TENSIONER DC ALT
SPACER ALTERNATOR
DC ALTERNATR HAN-KOK
V-BELT 3/8 X 30.6
CAP, 1.5" HOLE SHALLOW
ASSY MAGPICKUP (3/8-24 MALE)
PIN SPRING 1/4 X 3/4
SCREW HHC M12-1.5 X 40 G10.9
SCREW HHC M10-1.5 X 25 G10.9
WASHER LOCK M10
WASHER FLAT 3/8-M10 ZINC
NUT HEX M10-1.5 CLASS 10 ZINC
GASKET INTAKE MANIFOLD 1.6L
GASKET EXHAUST MANIFOLD 1.6L
NUT TOP LOCK FL M8-1.25
SCREW HHC M10-1.5 X 70 G8.8
SCREW HHC M10-1.5 X 110 G10.9
SCREW HHC M10-1.5 X 40 G10.9
SCREW HHC M8-1.25 X 35 G8.8
WASHER LOCK M8-5/16
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
46
47
48
49
50
51
52
53
54
55
56
57
58
59
61
62
63
64
65
0C5479
059980
046526
1
13
22
18
9
1
1
14
1
4
4
1
4
3
1
3
3
4
4
5
3
5
1
1
1
1
1
1
1
1
1
3
29
1
1
1
1
022131
0G3922
0G0464
0G0465
052858
051735
0G3920
0A7387
039414
022129
022145
029333A
057821
045771
022507
022097
WASHER FLAT 5/16-M8 ZINC
TIE WRAP UL 7.4" X .19" BLK
SCREW HHC M8-1.25 X 40 G8.8
NUT HEX M8-1.25 G8 CLEAR ZINC
SCREW HHC 1/4-20 X 1/2 G5
WASHER LOCK M6-1/4
022473
090388
WASHER FLAT 1/4-M6 ZINC
SCREW HHTT M6-1.0 X 12 ZINC
WASHER FLAT M10 HEAVY DUTY
TEMPERATURE SENDER, DELPHI
BSHG RDCR HEX 1/4 TO 1/8
HARN LOW OIL PRESS SWITCH ASSY
ADAPTER DRAIN OIL
0A5768
0E0502
035579
0H7435
0C1852
069860C
069811
HOSE OIL DRAIN ASSY 21"
CAP HEX 1/4 NPT BRASS
0G38580ST03
025065
STRUT LH 1.6L ENG ADAPT PLATE
NIPPLE PIPE 3/8 NPT X 1-1/2
PIPE TEE 3/8 NPT
SCREW HWHTF M6-1.0 X 16
WASHER FLAT .34 ID X .75 OD
HARN ENG G1.6L G11 NEXUS (NOT SHOWN)
OIL FILTER 1.6L
CONDUIT FLEX .25"ID (6” LG)
STRUT RH 1.6L ENG ADAPT PLATE
BARBED STR 3/8 NPT X 3/8
027738A
0E3257
0A8830
0H6690
0G02070100
077043H
0G38620ST03
055596
0C7649
0H2250
0G3433
049541
0G7311
0G4451
0F4001E
1
3
1
REF
1
REF
1
1
CLAMP HOSE .38-.87
HOSE COOLANT 3/8 ID 20R3 (11” LG)
BRACKET FAN ALT ADAPTER 1.6L
SCREW HHC M10-1.5 X 35 G8.8
DECAL EMISSION CTRL INFO 1.6L
BRACKET STEPPER MOTOR COOLANT
ANCHOR HARNESS
REVISION: H-8414-C
DATE: 3/1/11
Page 2 of 2
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: FUELSYS NG/LPV 1.6L CPL
DRAWING #: 0H6671
APPLICABLE TO:
GROUP E
ITEM
PART#
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
037561
0A5547
062522
022127
059402
091526
049226
0E0519A
048031J
0E6586
0G1397E
0F7790
0E7121
0G4573C
0E8286
047527
057823
035685
057753B
0E4395
022129
0A6344
048031L
0G1985
047290
047290
0F3994
0G3178
048031P
057147
045771
051767
022097
039253
0G9348
026812
076691
026490
075580
0D1509
075436
022145
026915
0E6586A
1
1
1
1
1
4
4
1
4
1
1
1
2
1
1
1
2
2
1
1
2
1
4
1
1
1
1
1
1
1
2
4
5
2
1
2
1
1
1
1
1
2
1
1
NUT WING 1/4-20 NYLK
COVER AIR CLEANER
STUD TH 1/4-20 X 3 G2 ZNC FULL
NUT HEX 1/4-20 STEEL
FILTER ELEMENT
SCREW PPHM M5-0.8 X 12 ZNC
WASHER LOCK M5
ADAPTER, CARBURETOR W/PVC CONN
CLAMP HOSE BAND .63
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
(1)36
(1)37
(1)38
(1)39
40
41
42
(1)43
44
GASKET BOSCH 32 & 40
FUEL REG. REWORK 1.6L
VENTURI THROTTLE 21MM
O-RING 47.625 ID X 2.38 WIDTH
MIXER ACTUATOR 32MM MACHINED
STREET EL 45D 1/2 NPT BRASS
BARBED STR 1/2 NPT X 3/4
CLAMP HOSE #10 .56-1.06
CLAMP HOSE #28 1.32-2.25
HOSE 1.5 ID X 2 LG 20R4
ACTUATOR BOSCH 32 GOVERNOR
WASHER LOCK M8-5/16
BARBED EL 90 1/8 NPT X 3/8
CLAMP HOSE BAND 1.0"
HOSE BARB REDUCR TEE 3/4"-3/8"
HOSE 3/8 ID SINGLE BRAID (11.5” LG)
HOSE 3/8 ID SINGLE BRAID (12” LG)
PCV VALVE 2.5L FORD
HOSE BREATHER 1.6L
CLAMP HOSE BAND .88"
HOSE 3/4 ID LPG & NG (16"LG)
NUT HEX M8-1.25 G8 YEL CHR
SCREW HHC M6-1.0 X 45 C8.8 FTH
WASHER LOCK M6-1/4
SCREW HHC M8-1.25 X 20 G8.8
ASSY REG INLET NPT FITTINGS
ELBOW 90D 3/4 NPT
NIPPLE PIPE 3/4NPTX4.5 BLK IRN
NIPPLE PIPE 3/4NPT X 2
FLANGE FUEL INLET
DECAL INLET PRESSURE
DECAL FUEL INLET
WASHER FLAT 5/16 ZINC
NIPPLE CLOSE 3/4 X 1.375
GASKET BOSCH 32
(1) INCLUDED IN ITEM 35 (ASSY REG INLET NPT FITTINGS)
REVISION: H-9610-B
DATE: 9/9/11
Page 2 of 2
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: EV ENCLOSURE C1 CPL
DRAWING #: 0G3534
GROUP F
ITEM
PART#
QTY.
DESCRIPTION
(2) 1
(2) 2
(1) 3
(2) 4
6
0G33370AL0R
0J14640AL0R
077992
0J14630AL0R
0F4487A
022127
1
1
10
2
1
ROOF 1.6L C1
REAR INTAKE WRAP C1
NUT HEX LOCK M6-1.0 SS NY INS
DOOR LEFT/RIGHT SIDE C1
ASSY ACCESS COVER
7
1
NUT HEX 1/4-20 STEEL
8
9
022097
022473
0C2454
0F5048D
0F5049
1
1
8
2
WASHER LOCK M6-1/4
WASHER FLAT 1/4-M6 ZINC
SCREW THF M6-1 X 16 N WA Z/JS
VISE-ACTION LATCH, SLOTTED CIR
TAB PULL
(1)10
11
12
2
13
14
15
16
17
(1)19
20
21
0F8869D
089961
078115
0H7518
0H7518A
0E3257
0912970090
0H7518B
0C8566
0H0412
022097
1
1
8
2
1
6
2
1
KEY VISE-ACTION LATCH,SLOT CIR
FOAM STRIP 3/4"WIDE X 3/16"THK (294”LG)
WASHER SELF LOCKING DOME
INSULATION SIDE DOOR C1
INSULATION ROOF C1
SCREW HWHTF M6-1.0 X 16
ASSY WIRE 14AWG GRN/YEL (32.25”LG)
INSULATION REAR C1
23
24
25
10
10
8
SCREW HHFC M6-1.0 X 20 G8.8
NUT SPRINGCLIP M6-1.0
WASHER LOCK M6-1/4
(3) 26
27
0H7529
1
1
1
1
FOIL ALUMINUM WITH ADHESIVE
RF COVER PLATE-PLASTIC-BISQUE
RF COVER PLATE-PLASTIC-GREY
FRONT DISCHARGE WRAP 1.6L C1
WASHER LOCK SPECIAL 1/4"
0H1208A
0H1208B
0G33350AL0R
0A1658
(2) 28
(1)29
2
(1)ENCLOSURE NOTE: ALL PANELS THAT FASTEN TO THE ROOF MUST BE SECURED USING I/N 10 (THREAD FORMING FASTENER) AND I/N 3 (LOCK NUT) AND
TO INCLUDE AT LEAST ONE CONNECTION POINT USING I/N 19 (THREAD FORMING FASTENER) WITH I/N 3 (LOCK NUT) TO EACH PANEL. LOCK NUT IS TO BE
INSTALLED AFTER THREAD FORMING FASTENER HAS PENETRATED THROUGH EXTRUSION IN ENCLOSURE PANELS. ALL PANEL TO BASEFRAME
CONNECTIONS TO INCLUDE AT LEAST ONE CONNECTION POINT USING I/N 29 (WASHER SPECIAL).
(2) SHEET METAL PARTS LISTED IN THE BOM TABLE ARE REPRESENTING GENERIC PARTS (NO COLOR)
•
•
MANUFACTURING: FOR CORRECT MATERIAL AND COLOR REFER TO AS400 BOM.
CUSTOMER: WHEN ORDERING REPLACEMENT PARTS ENTER BASE NUMBER (FIRST 6 DIGITS ONLY) IN THE SYSTEM FOR CORRECT MATERIAL
AND COLOR (FOR REFERENCE SEE GUIDELINE 0H7169).
(3) USED ON 1.5L / 1.6L UNITS ONLY.1
REVISION: -A-
DATE: 11/14/11
Page 2 of 2
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
0F7366
0F7647
0F8095
0G3576
0E3257
0F7644
0C6119
036434
036449
022129
022259
038750
0G3575
0F3794A
022097
049813
022473
1
1
1
1
4
2
1
3
3
6
6
1
1
1
1
1
6
MUFFLER C1
MUFFLER SADDLE
PIPE EXHAUST OUTLET
EXHAUST PIPE LOWER 1.6L
SCREW HWHTF M6-1.0 X 16
MUFFLER STRAP
BOLT U 5/16-18 X 2-1/4
BOLT U 5/16-18 X 2.09
SADDLE 2 INCH
WASHER LOCK M8-5/16
NUT HEX 5/16-18 STEEL
SCREW HHC M6-1.0 X 30 G8.8
EXHAUST PIPE UPPER 1.6L SS
EXHAUST BLANKET 500MM LONG
WASHER LOCK M6-1/4
NUT HEX M6 X 1.0 G8 YEL CHR
WASHER FLAT 1/4-M6 ZINC
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
. A v 0 4 / 0 7 k P g B 0 0 a 1 c R e
Download from Www.Somanuals.com. All Manuals Search And Download.
Owner's Manual
Stationary Emergency Generator
1.6L
25/30kW Models
EPA Certified
nNOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT
APPLICATIONS.
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS
SHOULD ATTEMPT INSTALLATION! DEADLY EXHAUST
FUMES! OUTDOOR INSTALLATION ONLY!
This manual should remain with the unit.
. 0 H 7 t N 2 r 3 o a 0 P
. A v 0 4 / 1 0 e v r 1 9 C 1 o R e
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
SECTION
PAGE
Alarm and Warning Messages..........................................................8-4
INTRODUCTION ........................................................... 1-1
Read this Manual Thoroughly.......................................................1-1
Operation and Maintenance..........................................................1-1
How to Obtain Service .................................................................1-1
SAFETY RULES ............................................................ 1-2
GENERAL INFORMATION............................................ 2-1
Identification Record ........................................................................2-1
Data Label ...................................................................................2-1
EQUIPMENT DESCRIPTION ........................................ 3-1
Equipment Description .....................................................................3-1
Engine Oil Recommendations...........................................................3-1
Coolant Recommendations ..............................................................3-1
ENGINE PROTECTIVE DEVICES ................................. 4-1
Engine Protective Devices ................................................................4-1
High Coolant Temperature Sender ................................................4-1
Low Coolant Level Sensor............................................................4-1
Low Oil Pressure Switch ..............................................................4-1
Overcrank Shutdown....................................................................4-1
Overspeed Shutdown...................................................................4-1
RPM Sensor Loss Shutdown........................................................4-1
DC Fuses.....................................................................................4-1
FUEL SYSTEM .............................................................. 5-1
Fuel Requirements .......................................................................5-1
Natural Gas Fuel System..............................................................5-1
Propane Vapor Withdrawal Fuel System........................................5-1
LP Liquid Fuel System..................................................................5-1
SPECIFICATIONS......................................................... 6-1
Stationary Emergency Generator ..................................................6-1
Engine .........................................................................................6-1
Cooling System............................................................................6-1
Fuel System.................................................................................6-1
Electrical System .........................................................................6-1
Weather and Maintenance Kits .....................................................6-2
Reconfiguring the Fuel System.........................................................6-2
Fuel System.................................................................................6-2
Control Panel ...............................................................................6-2
GENERAL INFORMATION............................................ 7-1
Alternator AC Lead Connections.......................................................7-1
Four-lead, Single-phase Stator......................................................7-1
Alternator Power Winding Connections.............................................7-1
3-phase Alternators ("Y" Configuration) ........................................7-1
3-phase Alternators ("Delta" Configuration)...................................7-2
CONTROL PANEL......................................................... 8-1
Control Panel Interface.....................................................................8-1
Using the Auto/Off/Manual Switch................................................8-1
Activate the Generator......................................................................8-1
Display Interface Menus...................................................................8-1
Activation Chart ...........................................................................8-2
Setting the Exercise Timer................................................................8-3
Low Speed Exercise.....................................................................8-3
User Adjustable Settings ..................................................................8-3
Fuel Conversion ...............................................................................8-3
Operation.........................................................................................8-3
Automatic Transfer Operation .......................................................8-3
Sequence of Automatic Operation ................................................8-4
Crank Cycles and Overcrank Shutdown........................................8-4
Auto Start........................................................................................8-4
Manual Start....................................................................................8-4
Low Oil Pressure Shutdown Alarm ...............................................8-4
High Coolant Temperature Shutdown Alarm..................................8-4
Overcrank Shutdown Alarm..........................................................8-4
Overspeed Shutdown Alarm.........................................................8-4
RPM Sensor Failure Shutdown Alarm...........................................8-4
Under-frequency Shutdown Alarm................................................8-5
Low Battery Alarm.......................................................................8-5
Low Battery Warning....................................................................8-5
Low Coolant Level Alarm .............................................................8-5
Missing Cam Pulse Alarm............................................................8-5
Missing Crank Pulse Alarm ..........................................................8-5
Low Fuel Pressure Warning..........................................................8-5
Governor Sensor Fault Alarm........................................................8-5
Wiring Error Alarm .......................................................................8-5
Undervoltage Alarm .....................................................................8-5
Overvoltage Alarm .......................................................................8-6
Internal Failure Shutdown Alarm...................................................8-6
Canbus Alarm..............................................................................8-6
Ignition Alarm ..............................................................................8-6
Maintenance Warning...................................................................8-6
Alarm Cancel ...............................................................................8-6
Common Alarm Relay......................................................................8-6
Maintenance Alerts ..........................................................................8-6
Menu System...................................................................................8-7
OPERATION.................................................................. 9-1
Stationary Emergency Generator Control and Operation....................9-1
Operating Unit with Manual Transfer Switch......................................9-1
Engine Start-up and Transfer........................................................9-1
Retransfer and Shutdown.............................................................9-1
Operating Unit with Automatic Transfer Switch .................................9-1
MAINTENANCE........................................................... 10-1
General Maintenance......................................................................10-1
Check Engine Oil........................................................................10-1
Changing Engine Oil...................................................................10-1
Cooling Intake/Outlet..................................................................10-1
Inspect Cooling System .............................................................10-1
Engine Coolant...........................................................................10-2
Coolant Change .........................................................................10-2
Overload Protection for Engine DC Electrical System ..................10-2
Exercise System ........................................................................10-2
Perform Visual Inspection ..........................................................10-2
Inspect Exhaust System.............................................................10-2
Check Fan Belt...........................................................................10-2
Inspect Engine Governor ............................................................10-2
Changing the Engine Air Filter.....................................................10-2
Spark Plugs ...............................................................................10-3
Battery Maintenance ..................................................................10-3
Battery Replacement..................................................................10-3
Battery Fluid...............................................................................10-3
Cleaning the Stationary Emergency Generator ............................10-3
SERVICE SCHEDULE ................................................. 11-1
TROUBLESHOOTING................................................. 12-1
Troubleshooting Guide....................................................................12-1
EMISSIONS WARRANTY............................................ 13-1
NOTES
EXPLODED VIEWS & PARTS LISTS
WIRING DIAGRAMS & SCHEMATICS
. A v e 0 5 / 1 0
C o n t e n t 0 4 8 R
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Instructions
nSAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential
hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this
equipment.
This symbol points out potential fire hazard.
INTRODUCTION
Thank you for purchasing this model of the stationary emergency
generator product line.
This symbol points out potential electrical shock hazard.
Every effort was expended to make sure that the information and
instructions in this manual were both accurate and current at the
time the manual was written. However, the manufacturer reserves
the right to change, alter or otherwise improve this product(s) at
any time without prior notice.
The operator is responsible for proper and safe use of the equip-
ment. The manufacturer strongly recommends that the operator
read this Owner's Manual and thoroughly understand all instruc-
tions before using this equipment. The manufacturer also strongly
recommends instructing other users to properly start and operate
the unit. This prepares them if they need to operate the equipment
in an emergency.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest
Service Dealer for starting, operating and servicing procedures.
For safety reasons, the manufacturer recommends that this
equipment be installed, serviced and repaired by a Service
Dealer or other competent, qualified electrician or installation
technician who is familiar with applicable codes, standards and
regulations. The operator also must comply with all such codes,
standards and regulations.
Throughout this publication, and on tags and decals affixed to the
generator, DANGER, WARNING, CAUTION and NOTE blocks are
used to alert personnel to special instructions about a particular
service or operation that may be hazardous if performed incor-
rectly or carelessly. Observe them carefully. Their definitions are
as follows:
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to
make sure that all maintenance for safe operation is performed
promptly, and to have the equipment checked periodically by a
Service Dealer. Normal maintenance service and replacement of
parts are the responsibility of the owner/operator and, as such,
are not considered defects in materials or workmanship within the
terms of the warranty. Individual operating habits and usage con-
tribute to the need for maintenance service.
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF
NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.
Indicates a hazardous situation or action which, if not
avoided, could result in death or serious injury.
Proper maintenance and care of the generator ensure a minimum
number of problems and keep operating expenses at a minimum.
See a Service Dealer for service aids and accessories.
Indicates a hazardous situation or action which, if not
avoided, could result in minor or moderate injury.
NOTE:
Operating instructions presented in this manual assume that the
generator electric system has been installed by a Service Dealer or
other competent, qualified contractor. Installation of this equipment
is not a “do-it-yourself” project.
Notes contain additional information important to a procedure
and will be found within the regular text body of this manual.
These safety warnings cannot eliminate the hazards that they
indicate. Common sense and strict compliance with the special
instructions while performing the service are essential to prevent-
ing accidents.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, simply contact
a Service Dealer for assistance. Service technicians are factory-
trained and are capable of handling all service needs.
Four commonly used safety symbols accompany the DANGER,
WARNING and CAUTION blocks. The type of information each
indicates is as follows:
When contacting a dealer about parts and service, always supply
the complete Model Number, Serial Number and Type Code (where
applicable) from the DATA LABEL that is affixed to the unit.
This symbol points out important safety information that,
if not followed, could endanger personal safety and/or
n
property of others.
This symbol points out potential explosion hazard.
. F v e 0 5 / 1 0
S a f e t y 0 0 4 R
1-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Instructions
• The engine exhaust fumes contain carbon monoxide gas, which
SAFETY RULES
can be DEADLY. This dangerous gas, if breathed in sufficient
concentrations, can cause unconsciousness or even death. For
that reason, adequate ventilation must be provided. This should
be considered prior to installing the generator. The unit should
be positioned to direct exhaust gasses safely away from any
building where people, animals, etc., will not be harmed. Any
exhaust stacks that ship loose with the unit must be installed
properly per the manufacturer's instruction, and in strict compli-
ance with applicable codes and standards.
Study these SAFETY RULES carefully before installing, operating
or servicing this equipment. Become familiar with this Owner’s
Manual and with the unit. The generator can operate safely, effi-
ciently and reliably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to follow simple
and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance
that might involve a hazard. The warnings in this manual, and on
tags and decals affixed to the unit are, therefore, not all inclusive.
If a procedure, work method or operating technique is used that
the manufacturer does not specifically recommend, ensure that it
is safe for others. Also make sure the procedure, work method or
operating technique utilized does not render the generator unsafe.
• Keep hands, feet, clothing, etc., away from drive belts, fans,
and other moving or hot parts. Never remove any drive belt or
fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and ventilating air is
critical in any room or building housing the generator to prevent
buildup of explosive gases and to ensure correct generator
operation. Do not alter the installation or permit even partial
blockage of ventilation provisions, as this can seriously affect
safe operation of the generator.
• Keep the area around the generator clean and uncluttered.
Remove any materials that could become hazardous.
• When working on this equipment, remain alert at all times.
Never work on the equipment when physically or mentally
fatigued.
• Inspect the generator regularly, and promptly repair or replace
all worn, damaged or defective parts using only factory-
approved parts.
• Before performing any maintenance on the generator, discon-
nect its battery cables to prevent accidental start-up. Disconnect
the cable from the battery post indicated by a NEGATIVE, NEG
or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping
on the unit can stress and break parts, and may result in dan-
gerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
nDespite the safe design of this generator,
operating this equipment imprudently, neglect-
ing its maintenance or being careless can cause
possible injury or death. Permit only respon-
sible and capable persons to install, operate or
maintain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
nParts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
GENERAL HAZARDS
• For safety reasons, the manufacturer recommends that this
equipment be installed, serviced and repaired by a Service
Dealer or other competent, qualified electrician or installation
technician who is familiar with applicable codes, standards
and regulations. The operator also must comply with all such
codes, standards and regulations.
ELECTRICAL HAZARDS
• Installation, operation, servicing and repair of this (and related)
equipment must always comply with applicable codes, stan-
dards, laws and regulations. Adhere strictly to local, state and
national electrical and building codes. Comply with regulations
the Occupational Safety and Health Administration (OSHA) has
established. Also, ensure that the generator is installed, operat-
ed and serviced in accordance with the manufacturer’s instruc-
tions and recommendations. Following installation, do nothing
that might render the unit unsafe or in noncompliance with the
aforementioned codes, standards, laws and regulations.
• All stationary emergency generators covered by this manual
produce dangerous electrical voltages and can cause fatal
electrical shock. Utility power delivers extremely high and dan-
gerous voltages to the transfer switch as well as the generator.
Avoid contact with bare wires, terminals, connections, etc.,
on the generator as well as the transfer switch, if applicable.
Ensure all appropriate covers, guards and barriers are in place
before operating the generator. If work must be done around
an operating unit, stand on an insulated, dry surface to reduce
shock hazard.
• Do not handle any kind of electrical device while stand-
ing in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
. F v e 0 5 / 1 0
S a f e t y 0 0 4 R
1-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Instructions
• If personnel must stand on metal or concrete while installing,
FIRE HAZARDS
operating, servicing, adjusting or repairing this equipment,
place insulative mats over a dry wooden platform. Work on the
equipment only while standing on such insulative mats.
• The National Electrical Code (NEC) requires the frame and
external electrically conductive parts of the generator to be con-
nected to an approved earth ground. This grounding will help
prevent dangerous electrical shock that might be caused by a
ground fault condition in the generator or by static electricity.
Never disconnect the ground wire.
• Keep a fire extinguisher near the generator at all times. Do NOT
use any carbon tetra-chloride type extinguisher. Its fumes are
toxic, and the liquid can deteriorate wiring insulation. Keep the
extinguisher properly charged and be familiar with its use. If
there are any questions pertaining to fire extinguishers, consult
the local fire department.
EXPLOSION HAZARDS
• Wire gauge sizes of electrical wiring, cables and cord sets must
be adequate to handle the maximum electrical current (ampac-
ity) to which they will be subjected.
• Before installing or servicing this (and related) equipment, make
sure that all power voltage supplies are positively turned off at
their source. Failure to do so will result in hazardous and pos-
sibly fatal electrical shock.
• Properly ventilate any room or building housing the generator to
prevent build-up of explosive gas.
• Do not smoke around the generator. Wipe up any fuel or oil
spills immediately. Ensure that no combustible materials are left
in the generator compartment, or on or near the generator, as
FIRE or EXPLOSION may result. Keep the area surrounding the
generator clean and free from debris.
• Connecting this unit to an electrical system normally supplied
by an electric utility shall be by means of a transfer switch so as
to isolate the generator electric system from the electric utility
distribution system when the generator is operating. Failure to
isolate the two electric system power sources from each other
by such means will result in damage to the generator and may
also result in injury or death to utility power workers due to
backfeed of electrical energy.
• These generators may operate using one of several types
of fuels. All fuel types are potentially FLAMMABLE and/or
EXPLOSIVE and should be handled with care. Comply with all
laws regulating the storage and handling of fuels. Inspect the
unit’s fuel system frequently and correct any leaks immediately.
Fuel supply lines must be properly installed, purged and leak
tested according to applicable fuel-gas codes before placing
this equipment into service.
• Stationary emergency generators installed with an automatic
transfer switch will crank and start automatically when normal
(utility) source voltage is removed or is below an acceptable
preset level. To prevent such automatic start-up and possible
injury to personnel, disable the generator’s automatic start cir-
cuit (battery cables, etc.) before working on or around the unit.
Then, place a “Do Not Operate” tag on the generator control
panel and on the transfer switch.
• Diesel fuels are highly FLAMMABLE. Gaseous fluids such
as natural gas and liquid propane (LP) gas are extremely
EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier
than air; install leak detectors accordingly.
• In case of accident caused by electric shock, immediately
shut down the source of electrical power. If this is not pos-
sible, attempt to free the victim from the live conductor. AVOID
DIRECT CONTACT WITH THE VICTIM. Use a nonconducting
implement, such as a dry rope or board, to free the victim from
the live conductor. If the victim is unconscious, apply first aid
and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry
can conduct electricity resulting in electric shock, or may get
caught in moving components causing injury.
CALIFORNIA PROPOSITION 65 WARNING
Engine exhaust and some of its constituents are known
to the State of California to cause cancer, birth defects
and other reproductive harm.
CALIFORNIA PROPOSITION 65 WARNING
This product contains or emits chemicals known to the
State of California to cause cancer, birth defects and
other reproductive harm.
. F v e 0 5 / 1 0
S a f e t y 0 0 4 R
1-3
Download from Www.Somanuals.com. All Manuals Search And Download.
General Information
NOTE:
IDENTIFICATION RECORD
For actual information related to this particular model, please
refer to the Manual Drawing Listing located at the end of this
manual, or to the data label affixed to the unit.
DATA LABEL
Every generator set has a DATA LABEL that contains important
information pertinent to the generator. The data label, which can be
found attached to the generator’s lower connection box, lists the
unit’s serial number and its rated voltage, amps, wattage capacity,
phase, frequency, rpm, power factor, production date, etc.
Stationary Emergency Generator Model and Serial
Number
This number is the key to numerous engineering and manufactur-
ing details pertaining to your unit. Always supply this number
when requesting service, ordering parts or seeking information.
Data Label
. D v e 0 5 / 1 0
I d e n t y 0 0 5 R
2-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Equipment Description
EQUIPMENT DESCRIPTION
COOLANT RECOMMENDATIONS
Use a mixture of half low silicate ethylene glycol base anti-freeze
and deionized water. Cooling system capacity is listed in the
specifications. Use only deionized water and only low silicate
anti-freeze. If desired, add a high quality rust inhibitor to the rec-
ommended coolant mixture. When adding coolant, always add the
recommended 50-50 mixture.
This equipment is a revolving field, alternating current Stationary
Emergency Generator. It is powered by a gaseous fueled engine
operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for
2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear
units. See the Specifications section for exact numbers. The unit
comes complete with a sound attenuated enclosure, internally
mounted muffler, control console, mainline circuit breaker, bat-
tery charger, and protective alarms as explained in the following
paragraph.
Do not use any chromate base rust inhibitor
with ethylene glycol base anti-freeze or chro-
All AC connections, including the power leads from the alterna-
tor, 120 volt battery charger input and control connections to the
transfer switch are available in the main connection box.
mium hydroxide (“green slime”) forms and will
cause overheating. Engines that have been
operated with a chromate base rust inhibitor
must be chemically cleaned before adding eth-
ylene glycol base anti-freeze. Using any high
silicate anti-freeze boosters or additives will
also cause overheating. The manufacturer also
recommends that any soluble oil inhibitor is
NOT used for this equipment.
The Stationary Emergency Generator incorporates the following
alternator features:
• Rotor and Stator insulation is Class F rated as defined by NEMA
MG1-32.6, NEMA MG1-1.66. The generator is self ventilated
and drip-proof constructed.
• The voltage waveform deviation, total harmonic content of the
AC waveform and telephone influence factor have been evalu-
ated and are acceptable according to NEMA MG1-32.
Do not remove the radiator pressure cap while
the engine is hot or serious burns from boiling
liquid or steam could result.
ENGINE OIL RECOMMENDATIONS
The unit has been filled with 5W-20 engine oil at the factory. Use
a high-quality detergent oil classified “For Service SJ or SH.”
Detergent oils keep the engine cleaner and reduce carbon deposits.
When changing the engine oil, be sure to use 5W-30 engine oil
(synthetic oil is recommended).
Ethylene glycol base antifreeze is poisonous.
Do not use mouth to siphon coolant from the
radiator, recovery bottle or any container. Wash
hands thoroughly after handling. Never store
used antifreeze in an open container because
animals are attracted to the smell and taste of
antifreeze even though it is poisonous to them.
Any attempt to crank or start the engine before
it has been properly serviced with the recom-
mended oil may result in an engine failure.
NOTE:
For temperatures below 32° F, it is strongly recommended to
use the optional Cold Weather Start Kit. The oil grade for tem-
peratures below 32° F is 5W-30 synthetic oil.
. D v 0 7 / 1 1
E q u i p 0 0 7 R e
3-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Engine Protective Devices
OVERCRANK SHUTDOWN
ENGINE PROTECTIVE DEVICES
The Stationary Emergency Generator may be required to operate
for long periods of time without an operator on hand to monitor
such engine conditions as coolant temperature, oil pressure or
rpm. For that reason, the engine has several devices designed to
protect it against potentially damaging conditions by automatically
shutting down the unit when the oil pressure is too low, the coolant
temperature is too high, the coolant level is too low, or the engine
is running too fast.
After a prespecified duration of cranking, this function ends the
cranking if the engine has failed to start. The overcrank message
will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn
switch back to AUTO to reset the generator control board.
NOTE:
If the fault is not corrected, the overcrank feature will continue
to activate.
NOTE:
Approximate Crank Cycle Times
• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
Engine protective switches and sensors are mentioned here for
the reader’s convenience. Also refer to the applicable control
panel manual for additional automatic engine shutdown infor-
mation.
• 7 seconds OFF
• Repeat for 45 seconds
• Approximately 90 seconds total.
HIGH COOLANT TEMPERATURE SENDER
An analog coolant temperture sender, located in the engine's
cooling system will cause an engine shutdown if the temperature
should exceed approximately 125° C (257° F). The generator will
automatically restart once the temperature has returned to a safe
operating level.
OVERSPEED SHUTDOWN
A speed circuit controls engine cranking, start-up, operation and
shutdown. Engine speed signals are delivered to the circuit board
whenever the unit is running. Should the engine overspeed above
a safe, preset value, the circuit board initiates an automatic engine
shutdown. Contact the nearest Authorized Dealer if this failure
occurs.
LOW COOLANT LEVEL SENSOR
To prevent overheating, the engine has a low coolant level sensor.
If the level of engine coolant drops below the level of the low cool-
ant level sensor, the engine automatically shuts down.
RPM SENSOR LOSS SHUTDOWN
If the speed signal to the control panel is lost, engine shutdown
will occur.
LOW OIL PRESSURE SWITCH
This switch has normally closed contacts that are held open by
engine oil pressure during cranking and operating. Should oil pres-
sure drop below the 8 psi range, switch contacts close, and the
engine shuts down. The unit should not be restarted until oil is
added, and the AUTO/OFF/MANUAL switch must be turned to OFF
and then back to AUTO.
DC FUSES
A fuse (7.5 amp) is located on the control panel. It protects the
panel components from damaging overload. Always remove this
fuse before commencing work on the generator. The unit will not
start or crank if the fuse is blown.
A fuse (25 amp) is located in the engine wire harness adjacent
to the DC alternator. It is used to prevent circuit failure due to DC
alternator falure. It will also protect the system in the event of a
wiring short-dircuit. If this fuse is blown, the generator will not
operate. Replace these fuses with the same size, type, and rating.
. B v e 0 5 / 1 0 r o t 0 0 E 3 n g R P
4-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Fuel System
NATURAL GAS FUEL SYSTEM
FUEL SYSTEM
Natural gas is supplied in its vapor state. In most cases, the gas
distribution company provides piping from the main gas distribu-
tion line to the standby generator site. The following information
applies to natural gas fuel systems.
FUEL REQUIREMENTS
The Stationary Emergency Generator may be equipped with one of
the following fuel systems:
• Gas pressure in a building is usually regulated by national, state
and local codes.
• To reduce gas pressure to a safe level before the gas enters a
building, a primary regulator is needed. The natural gas supplier
may or may not supply such a regulator.
• It is the responsibility of the gas supplier to make sure sufficient
gas pressure is available to operate the primary regulator.
• Gas pressure at the inlet to the fuel shutoff solenoid must never
exceed approximately 14 inches water column (0.5 psi).
• Natural gas fuel system
• Propane vapor (LPV) fuel system
Recommended fuels should have a Btu content of at least 1,000
Btu's per cubic foot for natural gas; or at least 2,520 Btu's per
cubic foot for LP gas. Ask the fuel supplier for the Btu content of
the fuel.
NOTE:
The fuel consumption requirements are identified in the
Specifications section of the Owner's Manual. Refer to the
Installation Manual if assistance is required for the sizing of
the pipe diameter for the generator. Any piping used to connect
the generator to the fuel supply should be of adequate size to
achieve the 100% load fuel consumption requirements identi-
fied in the Specifications section regardless of actual load.
PROPANE VAPOR WITHDRAWAL FUEL SYSTEM
This type of system utilizes the vapors formed above the liquid
fuel in the supply tank. Approximately 10 to 20 percent of the tank
capacity is needed for fuel expansion from the liquid to the vapor
state. The vapor withdrawal system is generally best suited for
smaller engines that require less fuel. The installer should be aware
of the following:
NOTE:
TherecommendedfuelpressureisidentifiedintheSpecifications
section this manual.
• When ambient temperatures are low and engine fuel consump-
tion is high, the vapor withdrawal system may not function
efficiently.
• Ambient temperatures around the supply tank must be high
enough to sustain adequate vaporization, or the system will not
deliver the needed fuel volume.
NOTE:
It is the responsibility of the installer to make sure that only
the correct recommended fuel is supplied to the generator fuel
system. Thereafter, the owner/operator must make certain that
only the proper fuel is supplied.
• In addition to the cooling effects of ambient air, the vaporization
process itself provides an additional cooling effect.
. F e v 0 4 / 1 1
u F e l S y s 0 0 1 R
5-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Engine Lubrication System
SPECIFICATIONS
Type of Oil Pump ...............................................................Gear
Oil Filter .......................................................Full Flow, Cartridge
Crankcase Oil Capacity ............................................ 4 U.S. qts.
STANDBY EMERGENCY GENERATOR
Type......................................................................Synchronous
Rotor Insulation.............................................................Class H
Stator Insulation............................................................Class H
Alternator Output Leads 3-phase.....................................4-wire
Bearings ..................................................................Sealed Ball
Coupling ................................................................Flexible Disc
Load Capacity (Standby Rating)...............................25/30 kW*
COOLING SYSTEM
Type............................................................................... Closed
Water Pump............................................................. Belt Driven
Fan Speed.........................................................................2484
Fan Diameter...........................................................17.7 inches
Fan Mode....................................................................... Pusher
Air Flow (inlet air including alternator and
* NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE
J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate
with natural gas.
3
combustion air) ..................................................1800 ft /min.
Excitation System ............................................................Direct
Generator Output Voltage/kW - 60 Hz
kW
120/240V, 1-phase, 1.0 pf 25/30
120/208V, 3-phase, 0.8 pf 25/30
120/240V, 3-phase, 0.8 pf 25/30
Coolant Capacity....................................................2.0 U.S. gal.
Heat Rejection to Coolant (25/35kW) ....112,000/135,000 Btu/h
Maximum Operating Air Temp. on Radiator......... 60° C (150° F)
Maximum Ambient Temperature......................... 50° C (140° F)
Amp
104/125
87/104
75/90
CB Size
125/150
100/125
90/100
FUEL SYSTEM
Generator Locked Rotor KVA Available @ Voltage Dip of 35%
Type of Fuel ....................................Natural Gas, Propane Vapor
Carburetor............................................................... Down Draft
Secondary Fuel Regulator............................................ Standard
Fuel Shut-off Solenoid................................................. Standard
Operating Fuel Pressure .................5 in. - 14 in. Water Column
25kW
35 KVA
30kW
45 KVA
ENGINE
Make ........................................................................... Generac
Model .............................................................................In Line
Cylinders and Arrangement .....................................................4
Displacement...............................................................1.6 Liter
Bore..............................................................................3.15 in.
Stroke...........................................................................3.13 in.
Compression Ratio....................................................... 9.5-to-1
Air Intake System......................................... Naturally Aspirated
Valve Seats............................................................ Replaceable
Lifter Type.................................................................. Hydraulic
Spark Plug Gap........................................0.76mm (0.030 inch)
Fuel Consumption - ft3/hr (Natural Gas/LPV)
Exercise
Cycle
25%
Load
50%
Load
75%
Load
100%
Load
25kW
30kW
60/24
60/24
120/48 220/87 310/123 390/155
145/58 260/103 370/147 470/187
ELECTRICAL SYSTEM
Battery Charge Alternator......................................12V, 15 Amp
Static Battery Charger ....................................... 2.0 or 2.5 Amp
Recommended Battery.................................Group 26, 525CCA
System Voltage............................................................ 12 Volts
Engine Parameters
Rated Synchronous RPM .......................................60 Hz, 3600
Voltage Regulator
Type...........................................................................Electronic
Sensing ................................................................Single-phase
Regulation........................................................................± 1%
Features.........................Adjustable Voltage and Automatic Gain
Exhaust System
Exhaust Flow at Rated Output 60 Hz: 25kW
240 cfm
30kW
260 cfm
1025°F
Exhaust Temp. at Rated Output:
975°F
Power Adjustment for Ambient Conditions
Temperature Deration:
3% for every 10° C above °C
Combustion Air Requirements (Natural Gas)
25kW 30kW
Flow at rated power, 60 Hz:
25kW
90 cfm
30kW
95 cfm
40
104
25
77
1.65% for every 10° above °F
Altitude Deration:
1% for every 100 m above m
Governor
Type...........................................................................Electronic
Frequency Regulation.............................................Isochronous
Steady State Regulation ................................................± .25%
Adjustments:
25kW 30kW
915
2000
182
600
3% for every 1000 ft. above ft.
Controller ................................................................. Nexus
Speed..................................................................... Selectable
. C v e 1 2 / 1 1
G e n S p e c 0 8 2
6-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
9. Install the previously removed black pipe onto the outlet
WEATHER AND MAINTENANCE KITS
To keep the generator running at its peak, the following kits are
offered:
port of the demand regulator. Use pipe sealant on the pipe
threads.
10. Reverse steps 1-4 in this procedure to reactivate the demand
• Cold Weather Kit
regulator.
~ Recommended for climates with temperatures below 32° F.
• Extreme Cold Weather Kit
11. Follow the instructions in the Control Panel section.
~ Recommended Block Heater Kit for protection in tempera-
tures below 32° F.
• Scheduled Maintenance Kit
~ Kit includes the recommended parts to maintain the genera-
tor. Refer to the Service Schedule for regular maintenance
intervals.
Serious injury, including death, or damage
will occur if not configured properly. Please
consult an Authorized Dealer with any ques-
tions.
For additional information, or to order any of these kits, please
contact an Authorized Service Dealer or Customer Service
Representative.
Figure 6.1 — Reconfigure the Fuel System
RECONFIGURING THE FUEL
SYSTEM
NOTE:
All models are configured to run on natural gas from the fac-
tory.
Before the generator can be operated using a LP fuel source, the
fuel system and control panel (refer to the installation drawing for
location) must be reconfigured. The steps to reconfigure the gen-
erator from a natural gas (NG) to a liquidified petroleum (LP) fuel
source are as follows:
FUEL SYSTEM
1. Turn the main gas supply off and disconnect the battery.
2. Remove the carburetor fuel hose from the outlet port of the
demand regulator (see Figure 6.1).
3. Disconnect the power wires from the fuel solenoid located
on top of the regulator assembly by removing the screw on
the front of the connector and pulling the connector forward,
away from the solenoid body.
CONTROL PANEL
The FUEL TYPE must be reconfigured in the control panel to final-
ize the conversion process. This generator is configured at the
factory to operate on natural gas. If conversion to LP is required,
please complete the mechanical conversion process and then call
888-9ACTIVATE for the control panel password. This fuel selection
conversion is required to be password protected by Environmental
Protection Agency [EPA] regulations.
4. Loosen the spring clamp on the small fuel enrichment line and
remove the hose from the hose barb.
5. Remove the black pipe assembly from the outlet port of the
demand regulator. The solenoid assembly may need to be
removed before performing this operation (Figure 6.1).
6. Remove the NG fuel jet (loosen counter clockwise) from the
outlet port.
7. Remove the LP fuel jet (loosen counter clockwise) from the jet
keeper port on the side of the regulator housing. Install this jet
into the outlet port in the regulator casting.
Whenever the Generator’s Fuel Regulator is
converted from one Fuel type to the other,
the Control Panel must be reconfigured for
the correct fuel type. Failure to convert both
the Regulator and Control Panel will result in
decreased performance and an increase in
emissions, and is a violation of EPA regula-
tions.
NOTE:
The jet sizes are stamped on the individual jets. The larger jet
size is used for running on NG.
8. Install the previously removed NG jet into the jet keeper port
on the side of the regulator housing.
. C v e 1 2 / 1 1
G e n S p e c 0 8 2 R
6-2
Download from Www.Somanuals.com. All Manuals Search And Download.
General Information
ALTERNATOR AC LEAD
ALTERNATOR POWER WINDING
CONNECTIONS
CONNECTIONS
The electrical wires in the unit’s AC connection (lower) panel
should be installed according to the number of leads and the
voltage/phase required for the application. The voltage and phase
are described on the generator data label. The number of lead
wires can be identified using the Specifications section and the
power output rating on the generator data label. For example, if
the generator produces 130kW, 277/480 Volt, 3-phase power, the
generator has 12 alternator output leads. Figure 7.3 describes the
stator power winding connection for the generator.
3-PHASE ALTERNATORS ("Y" CONFIGURATION)
The Stationary Emergency Generator is designed to supply
3-phase electrical loads. Electric power is produced in the alterna-
tor power windings. These windings were connected at the factory
to the main circuit breaker with a “Y” configuration as shown in
Figures 7.2 through 7.6.
The rated voltage between circuit breaker terminals E1-E2, E1-E3
and E2-E3 is 480V, 208V or 600V depending on the model.
The rated voltage between each circuit breaker terminal and the
neutral point 00 is 277V, 120V, or 346V depending on the model.
FOUR-LEAD, SINGLE-PHASE STATOR
Four-lead alternators (see Figure 7.1) are designed to supply elec-
trical loads with voltage code “A” (240V, 1-phase, 60 Hz). Electrical
power is produced in the stator power windings. These windings
were connected at the factory to the main circuit breaker as shown
in Figure 7.1.
Figure 7.2 — Stator Power Winding
Connections - 3-phase, 277/480V (6 Lead)
E1
The rated voltage between each circuit breaker terminal is 240V.
The rated voltage between each circuit breaker terminal and the
neutral point 00 is 120V.
S1
INTERNAL
CONNECTIONS
Figure 7.1 — Four-lead, Single-phase Stator
L - L
S4
S6
00 (NEUTRAL)
S5
S2
S3
E3
E2
L - N
Figure 7.3 — Stator Power Winding
Connections - 3-phase, 277/480V (12 Lead)
E1
S1
S4
S7
L - L
S12
S10
S9
S8
S11
S6
S5
S2
S3
E3
E2
L - N
. B v e 0 5 / 1 0
A C C o n n 0 0 7 R
7-1
Download from Www.Somanuals.com. All Manuals Search And Download.
General Information
Figure 7.4 — Stator Power Winding
Connections - 3-phase, 120/208V (6 Lead)
3-PHASE ALTERNATORS ("DELTA" CONFIGURATION)
The Stationary Emergency Generator is designed to supply
3-phase electrical loads. Electric power is produced in the alterna-
tor power windings. These windings were connected at the factory
to the main circuit breaker with a “Delta” configuration as shown
in Figures 7.7 and 7.8.
INTERNAL CONNECTIONS
E1
S1
S1
The rated voltage between circuit breaker terminals E1-E2, E1-E3
and E2-E3 is 240V.
The rated voltage between E1 or E3 and the neutral point 00 is
120V.
L-L
S4
S6
S4
00 (NEUTRAL)
S5
Figure 7.7 — Stator Power Winding
Connections - 3-phase, 120/240V (6 Lead)
S3
S2
S6 S5
E2
E3
E2
S3
S2
S6
S2
L-N
INTERNAL
CONNECTIONS
Figure 7.5 — Stator Power Winding
Connections - 3-phase, 120/208V (12 Lead)
L - L
E1
S7
S1
S3
S5
E1
E3
S4
S1
L-L
S10
S12
S4
L - N
S5
00 (NEUTRAL)
S9
S2
S6 S11
Figure 7.8 — Stator Power Winding
Connections - 3-phase, 120/240V (12 Lead)
E3
E2
S3
S8
L-N
E2
S12
S2
Figure 7.6 — Stator Power Winding
Connections - 3-phase, 346/600V (6 Lead)
E1
S5
S9
S1
INTERNAL
L - L
CONNECTIONS
S8
S6
L - L
S3
S11
S4
S6
00 (NEUTRAL)
E1
E3
S10
S1
S5
L - N
00 (NEUTRAL)
S2
E2
S3
E3
L - N
. B v e 0 5 / 1 0
A C C o n n 0 0 7 R
7-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
Upon power up, this controller will go through a system self test
CONTROL PANEL INTERFACE
which will check for the presence of utility voltage on the DC
circuits. This is done to prevent damage if the installer mistakenly
connects AC utility power sense wires into the DC terminal block.
If utility voltage is detected, the controller will display a warning
message and lock out the generator, preventing damage to the
controller. Power to the controller must be removed to clear this
warning.
USING THE AUTO/OFF/MANUAL SWITCH
With the switch set to AUTO, the engine may
crank and start at any time without warning.
Such automatic starting occurs when utility
power source voltage drops below a preset
level or during the normal exercise cycle. To
prevent possible injury that might be caused
by such sudden starts, always set the switch
to OFF and remove the fuse before work-
ing on or around the generator or transfer
switch. Then, place a “DO NOT OPERATE”
tag on the generator panel and on the trans-
fer switch.
Utility voltage must be turned on and present at the N1 and N2
terminals inside the generator control panel for this test to be
performed and pass.
NOTE:
DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT
WIRES IS NOT WARRANTABLE!
This test will be performed each time the controller is powered
up.
Next, the user must enter the minimum settings to operate. These
settings are current date and time and exercise day and time. The
maintenance intervals will be initialized (i.e. started) the first time
the clock is set. If the clock is never set at power up, the mainte-
nance intervals will be reset every time power is applied.
1. “AUTO” Position – Selecting this switch activates fully auto-
matic system operation. It also allows the unit to automati-
cally start and exercise the engine every seven days with the
setting of the exercise timer (see the Setting the Exercise
Timer section).
2. “OFF” Position – This switch position shuts down the engine.
If a subsequent power loss (loss of battery power) occurs the
Installation assistant will operate upon power restoration. The self
test routine will be run and then the customer will be required to
re-enter the time and date, as this is not retained during a power
loss. The unit will not require re-activation.
This position also prevents automatic operation.
3. “MANUAL” Position – Set the switch to MANUAL to crank
and start the engine. Transfer to standby power will not occur
unless there is a utility failure.
ACTIVATE THE GENERATOR
When battery power is applied to the generator during the instal-
lation process, the controller will turn ON and the LCD screen will
illuminate. However, the generator still needs to be activated before
it will automatically run in the event of a power outage.
DISPLAY INTERFACE MENUS
The LCD display is organized as detailed below:
• The “Home” page, this page is the default page which will be
displayed if no keys are pressed for 30 seconds. This page
normally shows the current Status message and the current
date and time. The highest priority active Alarm and/or Warning
will be automatically posted on this page as well as flashing
the backlight when such an event is detected. In the case of
multiple Alarms or Warnings, only the first message will be
displayed. To clear an Alarm or Warning, see the Protection
Systems section - Clear Alarm.
• The display backlight is normally off. If the user presses any
key, the backlight will come on automatically and remain on for
30 seconds after the last key was pressed.
• The “Main Menu” page will allow the user to navigate to all other
pages or sub-menus by using the Left/Right and Enter keys.
This page can be accessed at any time with several presses of
the dedicated Escape key. Each press of the Escape key takes
you back to the previous menu until the main menu is reached.
This page displays the following options: HISTORY; STATUS;
EDIT; AND DEBUG. (See the Appendix - "Menu System".)
Activating the generator is a simple one time process that is guided
by the controller screen prompts. Once the product is activated,
the controller screen will not prompt you again, even if you discon-
nect the generator battery.
To obtain the activation code, record the generator serial number
and log onto www.activategen.com or call 1-888-9ACTIVATE and
follow the steps to retrieve the activation code.
After obtaining your activation code, please complete the following
steps at the generator’s control panel in the Activation Chart on the
following page.
NOTE:
The generator will only run in manual until the passcode has
been entered.
. E v e 1 2 / 1 1
C n t r l N e x u s u s 0
8-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
ACTIVATION CHART
CHOOSE LANGUAGE
TROUBLESHOOTING
Display Reads:
Use ARROW keys to scroll to desired lan-
guage. Press ENTER to select.
If the wrong language is chosen, it can be
changed later using the “edit” menu.
Language
-
English
+
Escape
Enter
Display Reads:
Press ENTER to begin the activation pro-
cess.
If ESCAPE is pressed instead of ENTER,
your generator will only run in manual mode
(for test purposes) and NOT ACTIVATED will
be displayed. You will need to remove the
generator control panel fuse AND disconnect
the T1, N1 and N2 connector in the external
connection box (if equipped); or disconnect
utility input (main breaker) to the transfer
switch for 3-5 seconds and reconnect, then
begin with Step 1.
Activate me (ENT) or
ESC to run in manual
Escape
Enter
Display Reads:
If you do not have your activation code,
go to www.activategen.com or call
1-888-9ACTIVATE (922-8482).
To Activate go to
www.activategen.com
If you already have your activation code,
wait 3-5 seconds for the next display.
Escape
Enter
ENTER ACTIVATION CODE (Passcode)
TROUBLESHOOTING
Display Reads:
Use ARROW keys to scroll and find the first
number of your Activation Code.
Serial 123456789
Passcode XXXXX +/-
Press ENTER to select.
Repeat this step until all digits have been
entered.
Escape
Enter
Use ESCAPE to correct previous digits.
Display Reads:
Activation is complete when all digits are
entered above and your screen shows this
display.
What happens if “Wrong Passcode Try
Again” appears?
“SELECT HOUR (0-23)”
“-
Re-enter the activation code. If a second
attempt is unsuccessful, check the number
against the code given on activategen.com.
If it is correct and the generator will not
accept it, contact 1-888-9ACTIVATE (922-
8482).
6
+”
Follow the controller prompts to continue
setting the time function. Refer to your
Owner’s Manual with questions.
Escape
Enter
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1 R
8-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
• If utility is still lost after the “line interrupt period”, run the engine
INSTALLATION ASSISTANT
Interconnect System Self Test Feature (follow the on-screen
prompts).
up to normal RPM and transfer the load. At this time the con-
troller will exit the exercise routine and assume full automatic
operation.
Upon power up, this controller will go through a system self test
which will check for the presence of utility voltage on the DC
circuits. This is done to prevent damage if the installer mistakenly
connects AC utility power sense wires into the DC terminal block.
If utility voltage is detected, the controller will display a warning
message and lock out the generator, preventing damage to the
controller. Power to the controller must be removed to clear this
warning.
USER ADJUSTABLE SETTINGS
Factory
Default
Minimum
Setting
Maximum
Setting
Setting
Increment
1 min
Exercise
time
23:59
(11:59 pm)
2 pm
Wed
00:00 (12 am)
Sun
Exercise
day
Utility voltage must be turned on and present at the N1 and N2
terminals inside the generator control panel for this test to be
performed and pass.
Sat
1 day
Current
Time
23:59
(11:59 pm)
12 am 00:00 (12 am)
1 min
NOTE:
Current
Day
Sun
Jan
Sun
Jan
Sat
Dec
1 day
DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT
WIRES IS NOT WARRANTABLE!
Current
Month
1 month
1 year
This test will be performed each time the controller is powered
up.
Current
Year
2008
2008
2100
Upon first power up of the generator, the display interface will
begin an installation assistant. The assistant will prompt the user
to set the minimum settings to operate. These settings are simply:
Current Date/Time and Exercise Day/Time. The maintenance inter-
vals will be initialized when the exercise time is entered.
Language
Contrast
English
80%
French
0%
Spanish
100%
N/A
1%
The exercise settings can be changed at any time via the "EDIT"
menu (see Appendix, "Menu System").
FUEL CONVERSION
For fuel conversion steps, refer to the GenSpec section,
RECONFIGURING THE FUEL SYSTEM.
If the 12 volt battery is disconnected or the fuse removed, the
Installation Assistant will operate upon power restoration. The
only difference is the display will only prompt the customer for the
current Time and Date.
OPERATION
IF THE INSTALLER TESTS THE GENERATOR PRIOR TO
INSTALLATION, PRESS THE “ENTER” KEY TO AVOID SETTING
UP THE EXERCISE TIME. THIS WILL ENSURE THAT WHEN
THE CUSTOMER POWERS UP THE UNIT, HE WILL STILL BE
PROMPTED TO ENTER AN EXERCISE TIME.
This system is intended to supply standby power in the event of a
utility failure. The control system will monitor the utility voltage to
determine if stand-by power is required. Should the utility voltage
fail, the generator will start and run normally, detaching from the
utility and supplying the customer load from the generator. When
utility power returns, the controller will re-transfer the customer
load back to utility and shut down the generator.
SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer. Once it is set,
the generator will start and exercise every seven days, on the day
of the week and at the time of day specified. During this exercise
period, the unit runs for approximately 12 minutes and then shuts
down. Transfer of loads to the generator output does not occur
during the exercise cycle unless utility power is lost.
AUTOMATIC TRANSFER OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set to their
UTILITY position, i.e., loads connected to the utility power
source.
2. Be sure that normal UTILITY power source voltage is avail-
able to transfer switch terminal lugs N1 and N2 (Refer to the
Electrical Data section).
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO.
4. Set the generator’s main circuit breaker to its ON (or CLOSED)
position.
With the preceding steps complete, the generator will start auto-
matically when utility source voltage drops below a preset level.
After the unit starts, loads are transferred to the standby power
source. Refer to the Sequence of Automatic Operation section.
LOW SPEED EXERCISE
The standard start sequence will be initiated.
• All 1800 rpm units will exercise at 1400 RPM
• All 3600 rpm units will exercise at 1800 RPM
If utility is lost during exercise the controller will do the following:
• Wait for the “line interrupt period” for utility to return. If utility
returns within the “line interrupt period”, continue to exercise
at low RPM.
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1
8-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
SEQUENCE OF AUTOMATIC OPERATION
Initial Conditions: Generator in Auto ready to run, load being sup-
plied by the Utility Source through the transfer switch.
MANUAL START
Allows the user to start and run the generator manually.
Transfer of the load to the generator will occur if utility is lost while
the unit is running in the manual mode (only if activated).
1. When the utility voltage fails (falls below 60% of nominal), a
10-30 second (programmable) “line interrupt” delay timer is
started. The factory set time delay is 10 seconds. If at the
end of the line interrupt time the utility voltage is above 60%
the engine will not crank. If the utility voltage is still below
the 60% of nominal at the end of the line interrupt time, the
unit will crank and start. If the unit cranks for more than 10
seconds and the utility voltage rises above 80% of nominal
(programmed pickup voltage) and the unit has not started, the
crank cycle will abort.
2. As soon as the unit starts a 5 second “warm-up” timer is initi-
ated. When the warm-up timer expires the control will transfer
the load to the generator (through the RTS switch) if the utility
voltage is less than 80% of nominal. If the utility voltage is
greater than the 80% of nominal at the end of the warm-up
time the load will not be transferred to the generator and a one
minute low-speed cool down period will start. At the end of
the one minute cool down period the generator will stop.
3. Once the unit is running and the switch has transferred the
load to the generator the unit will monitor utility voltage.
When utility voltage returns (above the programmable pickup
voltage, normally 80% of nominal), a 15 second “Return to
Utility” timer will start. At the end of the return to utility time,
if the utility voltage is still above the pickup voltage, the unit
will transfer the load back to the utility source and run the unit
through a one minute cool down period. When the cool down
period is over the unit will shut down and be ready for the next
outage.
ALARM AND WARNING MESSAGES
Alarms are defined as “Latching” which means they must be
cleared before the alarm message on the screen will clear. They
can be of type “Shutdown” or not and are logged in the alarm log.
Alarms are all annunciated on the display).
Warnings are “Non Latching” meaning the message automati-
cally clears when the warning condition goes away. Warnings can
not be of type “Shutdown” but they are logged in the alarm log.
Warnings are all annunciated on the display.
LOW OIL PRESSURE SHUTDOWN ALARM
There is a 10 second delay before oil pressure is monitored.
HIGH COOLANT TEMPERATURE SHUTDOWN ALARM
There is a 10 second delay before engine temperature is moni-
tored.
Once running there is a 1/4 second delay before shut down. The
limit is set at 125° C or 257° F.
OVERCRANK SHUTDOWN ALARM
Occurs if the engine has not started within the specified crank
cycle.
4. If during the cool down period utility voltage should fall below
60% of nominal the 5 second warm-up timer is initiated and
the unit will transfer the load back to the generator and con-
tinue to monitor the utility.
OVERSPEED SHUTDOWN ALARM
Warning indicator is measured and calculated by the microproces-
sor. Overspeed is defined as +20% of nominal engine speed for 3
seconds, or +25% immediate.
CRANK CYCLES AND OVERCRANK SHUTDOWN
If the unit fails to start during a cranking period it will display the
Overcrank Shutdown Alarm. The system will control the cranking
cycles as follows:
Nominal engine speed = 60.0 Hz
RPM SENSOR FAILURE SHUTDOWN ALARM
During cranking: If the board does not see a valid RPM signal
within four (4) seconds of cranking it will shut down and lock out
on RPM sensor loss.
The first crank cycle is a 16 second crank time followed by a 7
second rest. The next 5 cycles will be 7 seconds of cranking time
each followed by a 7 second rest time.
If the unit fails to start by the end of the 6 crank/rest cycles
the Overcrank Shutdown Alarm will display and the unit will not
attempt to crank until the alarm is reset.
During running: If the RPM signal is lost for one full second the
board will shut the engine down, wait 15 seconds, then re-crank
the engine if in AUTO, it will not re-crank in MANUAL.
If no RPM signal is detected within the first four (4) seconds of
cranking, the control board will shut the engine down and latch out
on RPM sensor loss.
AUTO START
This unit is designed to automatically start in the event of a util-
ity failure or brown out condition. Brown out is defined as utility
voltage less than 60% nominal, while utility is considered good
when it is restored to at least the pickup value, 80% of nominal.
These levels are fixed. The “Line Interrupt period” is an adjustable
parameter by the dealer. If 2-wire start mode is activated, the unit
will start when 2-wire start is active.
If the RPM signal is detected the engine will start and run normally.
If the RPM signal is subsequently lost the control board will try
two more re-cranks before latching out and flashing the RPM
Sensor Failure message (if it is in AUTO).
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1 R
8-4
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
Figure 1 – Generator Control Panel
CHECK ENGINE MESSAGE
MISSING CAM PULSE ALARM
The control system has detected an emissions related fault. This
fault cannot be cleared using the control panel interface. The unit
will continue to operate in automatic mode. Contact your local
servicing dealer.
This is a shutdown alarm. The alarm will activate after five (5)
seconds of continuously missing cam pulses.
MISSING CRANK PULSE ALARM
This is a shutdown alarm. The alarm will activate after 12 con-
secutive revs where crank pulses are missing.
UNDER-FREQUENCY SHUTDOWN ALARM
After starting, if the generator stays under frequency for more than
30 seconds, it will shutdown.
LOW FUEL PRESSURE WARNING
Fuel pressure is monitored by a digital sensor with a fixed setpoint
of below five (5) inches water column.
LOW BATTERY ALARM
While running, if the average battery voltage falls below 11.9 volts
for one (1) minute, the low battery alarm will be displayed.
GOVERNOR SENSOR FAULT ALARM
The governor position is monitored by an analog feedback signal. If
the throttle position is seen outside of the normal operating range,
a shutdown alarm is displayed. If the throttle is commanded to
move, and no movement is seen, a shutdown alarm is displayed.
LOW BATTERY WARNING
The microprocessor will continually monitor the battery voltage
and display the Low Battery Voltage message if the battery voltage
falls below 12.2 Volts for one (1) minute.
WIRING ERROR ALARM
No other action is taken on a low battery warning condition. The
warning will automatically clear if the battery voltage rises above
12.2 volts.
When power is first apllied to the contoller, the software will per-
form a check on the wiring of the transfer output, and ensure it
does not have high voltage on the wire. If this is the case, it will
signal a miswire alarm and will not run. The test can be skipped
by use of the escape key.
NOTE:
The battery sentinel is a separate feature that monitors battery
condition.
UNDERVOLTAGE ALARM
If the generator voltage falls below 60% for >5 seconds, an alarm
will be issued.
LOW COOLANT LEVEL ALARM
This is a shutdown alarm. The sensor will be continuously moni-
tored. If an error condition is seen for five (5) consecutive sec-
onds, the alarm will be displayed.
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1
8-5
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
OVERVOLTAGE ALARM
ALARM CANCEL
If the generator voltage rises above 110% for >3 seconds, an
alarm will be issued.
When the generator is shut down due to a latching alarm, the Auto
/Off/ Manual switch must be set to the off position and the ENTER
key pressed to unlatch any active fault and clear the corresponding
fault alarm message.
If the generator voltage rises above 130% for >0.2 seconds, an
alarm will be issued.
INTERNAL FAILURE SHUTDOWN ALARM
Any internal failure that can be detected such as corrupted
firmware will cause this shutdown alarm. This alarm cannot be
cleared.
COMMON ALARM RELAY
The common alarm relay will be activated if there is a shutdown
alarm. It will not activate on warnings or indicate that the Auto/Off/
Manual switch is in the OFF position. The OFF position will clear
the alarms and the relay. The relay will not be used to indicate a
generator is not activated.
CANBUS ALARM
The common alarm connections are wired to a set of potential-
free (dry) contacts on the Nexus controller board. These Normally
Open (N.O.) contacts close when an alarm condition occurs and
are used to activate a remote signaling device. The circuit is rated
for a maximum of 130mA at 24 VDC. The connections are a short
set of free hanging wires that exit the engine harness loom directly
behind the Nexus Control Panel and are labeled numbers 209 and
210.
Where applicable, if the Canbus communications link fails to com-
municate, a “Canbus Alarm” will be generated. This only applies
to systems with external ignition modules. The alarm may be
generated if:
1. The physical link is broken.
2. The Ignition Module fails or resets.
3. The Nexus Controller fails or resets.
4. Having the Battery Chargers 120 VAC connected without a
battery installed.
MAINTENANCE ALERTS
Maintenance alerts will be provided for these conditions.
5. A blown 10 amp Ignition Module fuse (approximately 12
inches away from the starter).
6. A blown 25 amp system fuse (located approximately 12
inches away from the DC alternator).
NOTE:
SERVICE SCHEDULE ‘A’
Inspect Accessory Drive Alert
Coolant Change & Flush
1yr / 100hrs*
1yr / 100hrs
1yr / 100hrs
1yr / 100hrs*
1yr / 100hrs
1yr / 100hrs
6mo / 50hrs*
The “Canbus Alarm” will not clear on its own. To clear the
alarm, press the “enter” key to acknowledge the alarm. The
alarm will clear and if the fault is still present, the alarm will
reoccur.
Inspect Spark Plugs Alert
Change Oil & Filter Alert
IGNITION ALARM
When an ignition alarm occurs, a generic message “Ignition Fault”
will be displayed as the fault code.
Inspect Battery Alert
Change / Inspect Air Filter Alert
Clean/Inspect Air Inlet & Exhaust
* Items require a 3 month / 30 hour break-in change or check.
MAINTENANCE WARNING
When a maintenance period expires, a warning message will be
posted. The warning can be reset by hitting the Enter key. Resetting
will clear the warning and reset the maintenance counters for the
condition annunciated. The history log will reflect the maintenance
warning.
SERVICE SCHEDULE ‘B’
Change / Inspect spark plugs alert
2yr/ 250hr
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1 R
8-6
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
. E v e 1 2 / 1 1
C n t r l N e x u s 0 0 1
8-7
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
STATIONARY EMERGENCY
GENERATOR CONTROL AND
OPERATION
Do not crank the engine continuously for lon-
ger than 30 seconds, or the heat may
damage the starter motor.
n
Refer to the appropriate control panel operator’s manual for this
unit.
• Let engine stabilize and warm up.
• Check all applicable instrument and gauge readings. When
certain that all readings are correct, move the transfer switch
manual handle to the STANDBY (or EMERGENCY STANDBY)
position, i.e., load circuits supplied by the generator.
• Set the generator’s main line circuit breaker to its ON (or
CLOSED) position.
OPERATING UNIT WITH MANUAL
TRANSFER SWITCH
If the Stationary Emergency Generator was installed in conjunction
with a transfer switch capable of manual operation only, the fol-
lowing procedure applies. A manually operated transfer switch is
one that will not provide automatic start-up and does not include
an intelligence circuit.
• Load circuits are now powered by the generator.
RETRANSFER AND SHUTDOWN
For additional information, refer to the applicable control panel
manual for this unit, as well as any literature pertaining to the
specific transfer switch.
ENGINE START-UP AND TRANSFER
For additional information, refer to the applicable control panel
manual for this unit, as well as any literature pertaining to the
specific transfer switch.
To transfer the load back to the utility power source and shut down
the generator, follow these directions:
• Set the generator’s main line circuit breaker to its OFF (or OPEN)
position.
• Manually move the transfer switch handle to its UTILITY
(NORMAL) position, i.e., load circuits connected to the utility.
• Turn ON the utility power supply to the transfer switch, using
the means provided (such as the utility power source main line
circuit breaker).
• Let the generator run at no-load for a few minutes to stabilize
internal temperatures.
• Shut down the generator.
nThe Maintenance Disconnect Switch and the
AUTO/OFF/MANUAL switches (if so equipped)
must be set properly, or the generator will
crank and start as soon as the utility power to
the transfer switch is turned off. Refer to appli-
cable control panel and transfer switch manuals
for more information.
nDo not proceed until certain that utility source
voltage is available to the transfer switch and
OPERATING UNIT WITH AUTOMATIC
the transfer switch main contacts are set to
UTILITY.
TRANSFER SWITCH
Do not attempt manual operation until all
power supplies to the transfer switch have been
If the Stationary Emergency Generator has been installed with an
automatic transfer switch, the engine may be started and stopped
automatically or manually.
positively turned off, or extremely dangerous -
possibly lethal - electrical shock will result.
NOTE:
Transfer switch enclosure doors should be kept
closed and locked. Only authorized personnel
Refer to the applicable manual for your transfer switch and to
“Transfer Switch Start Signal Connections”. In addition, please
note the dangers under “Engine Start-up and Transfer.”
should be allowed access to the transfer switch
interior. Extremely high and dangerous voltages
are present in the transfer switch.
In order to transfer load from the utility source to the generator,
follow these directions:
• Turn OFF or disconnect the utility power circuit to the transfer
switch, using the means provided (such as the utility source
main line circuit breaker).
• Set the transfer handle to its UTILITY (NORMAL) position with
load circuits connected to the utility power supply.
• Set the generator’s main line circuit breaker to its OFF (or OPEN)
position.
• Start the generator.
. D v e 0 5 / 1 0
O p e r 0 0 1 R
9-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Refer to the Service Schedule for engine oil and filter change fre-
quencies.
GENERAL MAINTENANCE
Drain the oil while the engine is still warm from running. This
means warm up the engine, shut it down and drain immediately
as follows:
Before working on the Stationary Emergency
Generator, ensure the following:
• The AUTO/OFF/MANUAL switch is in the OFF position.
• The control panel fuse has been removed from the control
box.
1. Remove the drain hose from its retaining clip or cut the zip-tie
securing the oil drain hose.
2. Loosen and remove OIL DRAIN HOSE CAP. Drain oil com-
• The 120VAC supply to the battery charger is switched OFF.
• The negative battery cable has been removed.
pletely into suitable container.
3. When all oil has drained, install and tighten OIL DRAIN HOSE
CAP and secure drain hose with a new zip-tie, or place the
hose in its retaining clip.
CHECK ENGINE OIL
Check engine crankcase oil level (Figure 10.1) according to the
Service Schedule and SIB10-10-L24G.
4. Turn OIL FILTER (Figure 10.1) counterclockwise and remove.
Properly dispose of old filter.
5. Apply light coating of new engine oil to seal of new oil fil-
ter. Install FILTER and tighten by hand only. DO NOT OVER
TIGHTEN.
• Remove oil dipstick and wipe dry with a clean, lint-free cloth.
• Install oil dipstick, then remove again.
• Oil should be between FULL and ADD marks.
• If oil level is below the dipstick ADD mark, remove oil fill cap-.
Add the recommended oil to bring oil level up to the FULL
mark. DO NOT FILL ABOVE THE “FULL” MARK. See “Engine Oil
Recommendations” for recommended oils.
6. Remove OIL FILL CAP and add recommended oil. Crankcase
oil capacity is listed in the "Specifications" section.
After refilling the crankcase with oil, always
check oil level on dipstick. NEVER OPERATE
ENGINE WITH OIL BELOW THE DIPSTICK “ADD”
MARK.
n
Figure 10.1 - Oil Dipstick and Oil Fill Cap
OIL FILL CAP
7. Start engine and check for oil leaks.
8. Shut OFF engine and wait 10 minutes for the oil to settle down
into the oil pan. Recheck oil level on dipstick. DO NOT fill
above the dipstick "FULL" mark.
9. Dispose of used oil at a proper collection center.
COOLING INTAKE/OUTLET
Air intake and outlet openings in the generator compartment must
be open and unobstructed for continued proper operation. This
includes such obstructions as high grass, weeds, brush, leaves
and snow.
OIL
Without sufficient cooling and ventilating air flow, the engine/gen-
erator quickly overheats, which causes it to shut down. (See the
installation diagram.)
DIPSTICK
The exhaust system parts from this product get
extremely hot and remains hot after shutdown.
High grass, weeds, brush, leaves, etc. must
remain clear of the exhaust. Such materials may
ignite and burn from the heat of the exhaust
system.
OIL
FILTER
CHANGING ENGINE OIL
INSPECT COOLING SYSTEM
• Inspect engine cooling system. See the Service Schedule.
• Check hoses for damage, deterioration, leaks, etc. Correct any
discrepancies found.
Hot oil may cause burns. Allow engine to cool
before draining oil. Avoid prolonged or repeat-
n
ed skin exposure with used oil. Thoroughly
wash exposed areas with soap.
• Check hose clamps for tightness.
. A v e 0 5 / 1 0
M a i n t 0 2 7 R
10-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
ENGINE COOLANT
CHECK FAN BELT
Checkcoolantlevelincoolantrecoverybottle.See theSpecifications
and Service Schedule sections.
• Inspect fan belts every year. Replace any damaged, deterio-
rated, worn or otherwise defective belt.
• Check fan belt tension. Thumb pressure, exerted midway
between pulleys, should deflect about 3/8 to 5/8 of an inch.
Adjust belt tension as required.
• Add recommended coolant mixture as necessary.
• Periodically remove radiator pressure cap (only when engine
has cooled down) to make sure the coolant recovery system
is functioning properly. Coolant should be at bottom of radia-
tor filler neck. If coolant level is low, inspect gasket in radiator
pressure cap. Replace cap, if necessary. To have pressure cap
tested, contact a Service Facility. Inspect cooling system and
coolant recovery system for leaks.
• Check fan belt alignment (see Figure 10.2).
Figure 10.2 – Fan Belt
COOLANT CHANGE
Every year, have a service facility drain, flush and refill the cooling
system. See the Specifications and Service Schedule for cooling
system recommendations.
OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL
SYSTEM
Engine cranking, start up and running are controlled by a solid
state Engine Controller circuit board. Battery voltage is delivered
to that circuit board via the control panel fuse. This overcurrent
protection device will open if the circuit is overloaded.
INSPECT ENGINE GOVERNOR
Visually inspect electronic governor.
If a circuit breaker opens or a fuse element
melts, find the cause of the overload before
n
resetting the circuit breaker or replacing the
fuse.
Do not attempt to adjust the governor. Only
EXERCISE SYSTEM
Starts the Stationary Emergency Generator engine once every
seven days and lets it run for 12 minutes.
qualified service facilities should adjust the
n
governor. Excessively high operating speeds
are dangerous and increase the risk of personal
injury. Low speeds impose a heavy load on the
engine when adequate engine power is not
available and may shorten engine life. Correct
rated frequency and voltage are supplied only
at the proper governed speed. Some connected
electrical load devices may be damaged by
incorrect frequency and/or voltage. Only quali-
fied service technicians should adjust the gov-
erned speed.
PERFORM VISUAL INSPECTION
Complete a thorough visual inspection of the entire engine-genera-
tor monthly. Look for obvious damage, loose, missing or corroded
nuts, bolts and other fasteners. Look for fuel, oil or coolant leaks.
INSPECT EXHAUST SYSTEM
Inspect the exhaust system at least once every year. Check all
exhaust system pipes, mufflers, clamps, etc. for condition, tight-
ness, leaks, security, damage.
CHANGING THE ENGINE AIR FILTER
To replace the engine air filter, remove the air filter cover and
replace the air filter making sure it is positioned properly before
reattaching the cover (Figure 10.3).
See the Service Schedule for air filter maintenance.
. A v e 0 5 / 1 0
M a i n t 0 2 7 R
10-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
nBattery electrolyte fluid is an extremely corro-
sive sulfuric acid solution that can cause severe
Figure 10.3 – Engine Air Filter
burns. Do not permit fluid to contact eyes, skin,
clothing, painted surfaces, etc. Wear protective
goggles, protective clothing and gloves when
handling a battery. If fluid is spilled, flush the
affected area immediately with clear water.
Do not use any jumper cables or booster bat-
tery to crank and start the generator engine. If
the battery has completely discharged, remove
it from the generator for recharging.
n
AIR
FILTER
Be sure the AUTO/OFF/MANUAL switch is set
to the OFF position, before connecting the
battery cables. If the switch is set to AUTO or
MANUAL, the generator can crank and start as
soon as the battery cables are connected.
n
Be sure the 120VAC power supply to the battery
is turned OFF, or sparking may occur at the bat-
tery posts as the cables are attached and cause
an explosion.
SPARK PLUGS
Reset the spark plug gap or replace the spark plugs as neces-
sary.
1. Clean the area around the base of the spark plugs to keep dirt
and debris out of the engine. Clean by scraping or washing
using a wire brush and commercial solvent. Do not blast the
spark plugs to clean.
2. Remove the spark plugs and check the condition. Replace
the spark plugs if worn or if reuse is questionable. See the
“Service Schedule” section for recommended inspection.
3. Check the spark plug gap using a wire feeler gauge. See the
Specifications section for the required spark plug gap.
BATTERY REPLACEMENT
NOTE:
Unit DOES NOT include battery.
When supplying or replacing the battery, the recommended num-
ber and type of battery is listed in the Specifications Section.
NOTE:
The BCI number should be located directly on the battery.
BATTERY MAINTENANCE
The battery should be inspected per the Service Schedule section.
The following procedure should be followed for inspection:
BATTERY FLUID
Check battery electrolyte fluid based on the Service Schedule.
Fluid should cover separators in all battery cells. If fluid level is
low, add distilled water to cover tops of separators. DO NOT USE
TAP WATER IN BATTERY.
1. Inspect the battery posts and cables for tightness and corro-
sion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries and, if
necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP
WATER IN BATTERIES.
CLEANING THE STATIONARY EMERGENCY GENERATOR
Keep the generator as clean and as dry as possible. Dirt and
moisture that accumulates on internal generator windings have an
adverse effect on insulation resistance.
3. Have the state of charge and condition checked. This should
be done with an automotive-type battery hydrometer.
Periodically clean generator exterior surfaces. A soft brush may be
used to loosen caked on dirt. Use a vacuum system or dry, low
pressure air to remove any accumulations of dirt. The generator is
housed inside an all-weather enclosure, clean the enclosure with a
soft, damp cloth or sponge and water.
Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture
around the battery for several hours after
charging. The slightest spark can ignite the gas
and cause an explosion. Such an explosion can
shatter the battery and cause blindness or other
injury. Any area that houses a storage battery
must be properly ventilated. Do not allow smok-
ing, open flame, sparks or any spark producing
tools or equipment near the battery.
Once each year have the generator cleaned and inspected by a
Service Dealer. That dealer will use dry, low pressure air to clean
internal windings.
Finally, have the insulation resistance of stator and rotor windings
checked. If insulation resistances are excessively low, the genera-
tor may require drying.
. A v e 0 5 / 1 0
M a i n t 0 2 7 R
10-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Schedule
SERVICE SCHEDULE
System / Component
Frequency
Procedure
Weekly - W
Monthly - M
Yearly - Y
Inspect
Change
Clean
Fuel
Fuel Lines & Connections
Lubrication
M
X
Oil Level
M
Y
X*
Oil
X**
X**
Oil Filter
Y
Cooling
Engine Coolant Lines & Connections
Engine Coolant Level
Engine Coolant
M
M
Y
X
X
X
Enclosure Louvers
Engine
W
X
X
Air Cleaner
Y
Y
X
X
X***
X***
Spark Plugs
Battery
Remove Corrosion, Ensure Dryness
Clean & Tighten Battery Terminals
Check Charge State
Check Electrolyte Level
General Condition
Vibration, Noise, Leakage, Temperature
Generator System
Complete Tune-up and System Inspection
Footnotes
M
M
M
M
X
X
X
X
X
X
X***
X***
M
Y
X
To be completed by an Authorized Service Dealer.
* Inspect the oil level monthly or every 12 hours during continuous operation.
** Change oil and oil filter after the first 30 hours of operation and then every 100 hours or annually thereafter, whichever occurs first.
Change sooner when operating under heavy load or in a dusty or dirty environment or in high ambient temperatures.
*** Replace as necessary.
. B v e 0 5 / 1 0
v S S c r h d 0 0 4 R
11-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
TROUBLESHOOTING GUIDE
PROBLEM
Engine won’t crank.
CAUSE
CORRECTION
1. Control panel 7.5 amp fuse blown.
2. Loose or corroded or defective
battery cables.
1. Replace fuse.*
2. Tighten, clean or replace
battery cables as necessary.*
3. Replace contactor.*
4. Replace starter motor.*
5. Remove, change or replace battery.*
3. Defective starter contactor.
4. Defective starter motor.
5. Dead or Defective Battery.
Engine cranks but won't start.
Engine starts hard, runs rough.
1. Out of fuel.
2. Fuel solenoid (FS) is defective
3. Spark plugs defective.
1. Replenish fuel/turn on fuel valve.
2. Replace solenoid.*
3. Clean, regap or replace plugs.
1. Air cleaner plugged or damaged.
2. Defective spark plugs.
3. Fuel pressure incorrect.
1. Clean or replace as needed.
2. Clean, regap or replace plugs.
3. Confirm fuel pressure to regulator is as
recommended in SPECIFICATIONS.*
4. Confirm fuel pressure to regualtor is as
recommended in SPECIFICATIONS.*
5. Reconfigure the fuel system. (See
RECONFIGURING THE FUEL SYSTEM in
manual.*
4. Insufficient fuel supply.
5. Fuel system set to wrong fuel type.
Engine starts then shuts down.
1. Engine oil level is low.
2. Engine is overheated.
3. Defective Low Oil Pressure Switch
4. Defective Coolant Temperature Switch
5. Defective Control Module circuit board.
6. Coolant Level is Low.
1. Check oil and add oil as needed.
2. Check cooling system for leaks.
3. Replace switch.*
4. Replace switch.*
5. Replace board.*
6. Repair leak - Add coolant.
7. Replace Switch.*
7. Defective Low Coolant Level Switch
AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch
1. Replace board.*
2. Replace board.*
engine continues to run.
2. Defective Control Module circuit board
No AC output from generator.
1. Main line circuit breaker is tripped/open.
2. Generator internal failure.
1. Reset to ON/CLOSED.
2. *
3. Thermal circuit breaker open.
3. Auto-reset - Wait 5 min. and attempt restart.
*Contact the nearest Dealer for assistance.
. B v e 0 5 / 1 0
r b T l s h t 0 0 3 R
12-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty
United States Environmental Protection Agency Warranty Statement
(Stationary Emergency Spark-Ignited Generators)
Warranty Rights, Obligations and Coverage
The United States Environmental Protection Agency (EPA) and Generac Power Systems, Inc. (Generac) are pleased to explain the
Emission Control System Warranty on your new stationary emergency engine. If during the warranty period, any emission control system
or component on your engine is found defective in materials or workmanship, Generac will repair your engine at no cost to you for diag-
nosis, replacement parts and labor provided it be done by a Generac Authorized Warranty Service Facility. Your emission control system
may include parts such as the fuel metering, ignition, and exhaust systems and other related emission related components listed below.
Generac will warrant the emissions control systems on your 2009 and later model year engines provided there has been no abuse,
neglect, unapproved modification or improper maintenance of your engine. For engines less than 130 HP the warranty period is two years
from the date of sale to the ultimate purchaser. For engines greater than or equal to 130 HP the warranty period is three years from the
date of the engine being placed into service.
Purchaser's/Owner's Warranty Responsibilities
As the engine purchaser/owner you are responsible for the following. 1.) The engine must be installed and configured in accordance
to the Generac's installation specifications. 2.) The completion of all maintenance requirements listed in your Owner’s Manual. 3.) Any
engine setting adjustment must be done in accordance and consistent with the instructions in the Owner’s Manual. 4.) Any emission con-
trol system or component must be maintained and operated appropriately in order to ensure proper operation of the engine and control
system to minimize emissions at all times.
Generac may deny any/or all Emission Control System Warranty coverage or responsibility of the engine, or an emission control system
or component on your engine thereof, if it has failed due to abuse, neglect, unapproved modification or improper maintenance, or the use
of counterfeit and/or 'gray market' parts not made, supplied or approved by Generac. Warranty service can be arranged by contacting
either your selling dealer or a Generac Authorized Warranty Service dealer, 1-800-333-1322 for the dealer nearest you. The purchaser/
owner shall be responsible for any expenses or other charges incurred for service calls and/or transportation of the product to/from the
inspection or repair facilities. The purchaser/owner shall be responsible for any and/or all damages or losses incurred while the engine
is being transported/shipped for inspection or warranty repairs. Contact Generac Power Systems Inc. for additional Emission Control
System Warranty related information, Generac Power Systems, Inc. P.O. Box 8, Waukesha, WI 53187, or call 1-800-333-1322 or www.
generac.com.
Important Note
This warranty statement explains your rights and obligations under the Emission Control System Warranty, which is provided to you by
Generac pursuant to federal law. Note that this warranty shall not apply to any incidental, consequential or indirect damages caused by
defects in materials or workmanship or any delay in repair or replacement of the defective part(s). This warranty is in place of all other
warranties, expressed or implied. Specifically, Generac makes no other warranties as to the merchantability or fitness for a particular pur-
pose. Any implied warranties which are allowed by law, shall be limited in duration to the terms of the express warranty provided herein.
Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
Emission Related Parts Include the Following (if so equipped)
1) Fuel Metering System
3)
4)
5)
Ignition System Including
1.1) Gasoline Carburetor Assembly And Internal
Components A) Fuel Filter, B) Carburetor, C) Fuel
Pump
1.2) Carburetion Assembly And Its Components
A) Fuel Controller, B) Carburetor And Its Gaskets, C)
Mixer And It Gaskets, D) Primary Gas Regulator E)
Liquid Vaporizer
1.3) Fuel Regulator
2) Air Induction System Including
A) Intake Pipe/Manifold,
A) Spark Plug, B) Ignition Module,
C) Ignition Coil, D) Spark Plug Wires
Exhaust System
A) Catalyst Assembly, B) Exhaust Manifold,
C) Muffler, D) Exhaust Pipe, E) Muffler Gasket
Crankcase Breather Assembly Including
A) Breather Connection Tube, B) Pcv Valve
Oxygen Sensor
6)
7)
Diagnostic Emission-Control System
B) Air Cleaner
. D v e 0 9 / 1 1 n t y 0 0 1 R E m s n W r
13-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty
United States Environmental Protection Agency Compliance Requirements
(Stationary Emergency Spark-Ignited Generators)
Purchaser's/Owner's Recordkeeping Responsibilities
The United States Environmental Protection Agency (EPA) and Generac Power Systems, Inc. (Generac) are pleased to explain your record-
keeping requirements for compliance with Subpart JJJJ- Standards of Performance for Stationary Spark Ignition Internal Combustion Engines
as listed in the Electronic Code of Federal Regulations Title 40 Part 60. As the engine purchaser/owner who operates and maintains their
certified emergency stationary engine and emission control system according to applicable emission related guidelines as specified in this
Owner's Manual, you are required to meet the following notification and recordkeeping requirements to demonstrate compliance. 1.) Maintain
documentation that the engine is certified to meet emission standards. 2.) Recordkeeping of maintenance conducted. 3.) Recordkeeping of
the provision allowing natural gas engines to operate using propane for a maximum of 100 hours per year as an alternate fuel solely dur-
ing emergency operations provided the engine is not certified to operate on propane. 4.) Meet all compliance notifications submitted to the
purchaser/owner and maintain all supporting documentation. 5.) Recordkeeping of hours of operation, including what classified the operation
as emergency and how many hours are spent for non-emergency operation. For emergency engines greater than or equal to 130 HP, record-
keeping of hours of operation begins January 1, 2011. For emergency engines less than 130 HP, recordkeeping of hours of operation begins
January 1, 2009; Engines are equipped with non-resettable hour meters to facilitate recordkeeping.
Specific Air Quality Management or Air Pollution Control Districts may have different and additional record keeping/reporting requirements.
Your permit to construct and/or operate the engine may be contingent upon compliance with those requirements. Check with your local Air
Quality Management or Air Pollution Control District for specific requirements.
Emergency stationary internal combustion engines (ICE) may be operated for the purpose of maintenance checks and readiness testing,
provided that the tests are recommended by Federal, State or local government, Generac, or the insurance company associated with the en-
gine. Maintenance checks and readiness testing of such units is limited to 100 hours per year. There is no time limit on the use of emergency
stationary ICE in emergency situations. The purchaser/owner may petition the Administrator for approval of additional hours to be used for
maintenance checks and readiness testing, but a petition is not required if the owner maintains records indicating that Federal, State, or local
standards require maintenance and testing of emergency ICE beyond 100 hours per year. Emergency stationary ICE may operate up to 50
hours per year in non emergency situations, but those 50 hours are counted towards the 100 hours per year provided for maintenance and
testing.
The 50 hours per year for non-emergency situations cannot be used for peak shaving or to generate income for a facility to supply power to
an electric grid or otherwise supply power as part of a financial arrangement with another entity. For purchaser/owner of emergency engines,
any operation other than emergency operation, maintenance and testing, and operation in non-emergency situations for 50 hours per year, as
permitted in this section is prohibited.
If you operate and maintain your certified emergency stationary SI internal combustion engine and emissions control systems in accordance
to the specifications and guidelines in this Owner’s Manual EPA will not require engine performance testing. If not, your engine will be consid-
ered non-certified and you must demonstrate compliance according to Subpart JJJJ - Standards of Performance for Stationary Spark Ignition
Internal Combustion Engines as listed in the Electronic Code of Federal Regulations Title 40 Part 60.
Emission-Related Installation Instructions
Your certified emergency stationary engine has pre-set emission control systems or components that require no adjustment. Inspection and
replacement of an emissions related component is required to be done so in accordance with the requirements cited in the United States
Environmental Protection Agency Warranty Statement or can be arranged by contacting either your selling dealer or a Generac Authorized
Warranty Service dealer, 1-800-333-1322 for the dealer nearest you. Failing to follow these instructions when installing a certified engine in a
piece of nonroad equipment violates federal law 40 CFR 1068.105 (b), subject to fines or penalties as described in the Clean Air Act.
. D v e 0 9 / 1 1 n t y 0 0 1 R E m s n W r
13-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Notes
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
1
0G4827
0G2927
0G2827
0G3451
0G0820A
0G4452
020746
049226
051713
022129
0G4825
0G4826
0G2926
0G3682
0G5584
0G3685
0G2826
0G3683
0G6573
0G3686
0G3684
0G3687
0G5909
0G6103
0A5382A
075591
051787
0A5601A
0G8827
0G8827A
0A9375
022152
0G4196
042558
051756
0G0965B
053607
051769
023365
0F3353
072578
0G3787
0A8830
077043E
0G2070
0G2070A
045771
1
1
1
1
1
1
4
4
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
4
4
4
4
1
1
4
1
1
1
4
6
1
10
4
1
1
1
4
ASSY RTR 104 KD1 HI EFF (18KW)
RTR-102-20.0AD1 CPL (2006) (20KW)
ASSY RTR 25KW 2P (2006) (25KW)
ASSY RTR 30KW 2P 10"(2006)
HOUSINGBLOWER L GPILOT
BLOWER HOUSINGSCREEN
SCREW PPHM M5-0.8 X 8 ZINC
WASHER LOCK M5
WASHER FLAT M5
2
3
4
5
6
7
8
WASHER LOCK M8-5/16
ASSY STR 104-18AD1 HI EFF (18KW)
ASSY STR 104 18GD1 HI EFF (18KW)
STR-102-20.0AD1 CPL (2006) (20KW)
STR-102-20.0GD1 CPL (2006) (20KW)
STR-102-20.0JD1 CPL (2006) (20KW)
STR-102-20.0KD1 CPL (2006) (20KW)
ASSY STR 102 25AD1 (2006) (25KW)
STR-102-25.0GD1 CPL (2006) (25KW)
STR-102-25.0-JD1 CPL (2006) (25KW)
STR-102-25.0KD1 CPL (2006) (25KW)
STR-102-30.0GD2 CPL (30KW)
STR-102-30.0KD2 CPL (30KW)
ASSY STR 102 30AD2 10" (30KW)
STR-102-30.0JD2
BEARING CARRIER REAR L G PILOT
ASSY HOLDER BRUSH
SCREW HHC M4-0.7 X 16 G8.8
COVER REAR BEARING
STUD M8-1.25 475 LONG
STUD M8-1.25 418 LONG
SCREW RHM #10-24 X 2
WASHER LOCK #10
FLYWHEEL & RINGGEAR ASSY 1.6L
KEY SQ 3/8 X 1 STEEL
SCREW HHC M10-1.5 X 20 C8.8
PLATE FLEX 1.6L R12.7
SCREW HHC M12-1.75 X 35 G8.8
WASHER LOCK M12
WASHER SHAKEPROOF INT #8
SCREW HHC M10-1.0 X 20 G10.9
SPACER ROTOR SHAFT
WASHER .41 ID .94 OD .12 THK
WASHER FLAT .34 ID X .75 O D
FLEX CONDUIT 1" BLACK (NOT SHOWN)
PLATE SPACER 14GA 1.6L (TO BE USED WITH ENGINE PLATE P/N 0G0834.)
PLATE SPACER 16GA 1.6L (TO BE USED WITH ENGINE PLATE P/N 0G0834A.)
NUT HEX M8-1.25 G8 CLEAR ZINC
9
10
11
12
13
14
15
16
17
18
19
20
21
22
(1) 23
24
25
26
27
28
29
(1) APPLY LOCTITE 242 BEFORE THREADING SCREW INTO CRANKSHAFT.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: CONNECTION BOX C1 CPL
DRAWING #: 0H7234
APPLICABLE TO:
GROUP A
ITEM
PART#
QTY.
DESCRIPTION
1
2
(4)3
4
0H6795
0H6796
0H67330ST0R
0H7115
022097
1
1
1
2
2
CONBOX BACK/SIDES C1 CPL
CONBOX TOP C1 CPL
BRACKET GIMBAL CONTROL PNL RAW
KNOB M6-1.0 CONTROL PANEL
WASHER LOCK M6-1/4
5
6
(3)7
8
022473
SEE CHART
052777
4
1
3
WASHER FLAT 1/4-M6 ZINC
CIRCUIT BREAKER
WASHER FLAT M3
9
043182
3
WASHER LOCK M3
10
(4)11
12
051714
0H81040AS0R
045764
3
1
2
3
NUT HEX M3-0.5 G8 CLEAR ZINC
COVER DPE BREAKER NEXUS
SCREW HHTT M4-0.7 X 8 ZP
WASHER LOCK #8-M4
13
022264
14
0A9457
1
DECAL NEUTRAL
15
16
(2)17
18
(4)19
20
21
22
23
24
REF
1
18
1
6
1
1
12
2
2
2
ASSY CTRL PROGRAMMED
SCREW HWHT M6-1 X 16 N WA Z/JS
REGULATOR - DC ALT
NUT FLANGE M6-1.0 NYLOK
SHIELD HIGH/LOW C1 RAW
RELAY SOLENOID 12VDC PNL MNT
SCREW HHSP #10 X 3/8 HI-LOW
SCREW HHC M6-1.0 X 20 C8.8
NUT HEX M5-0.8 G8 CLEAR ZINC
WASHER LOCK M5
0C2454
0A1354A
0D3700
0H88380ST0R
056739
0F5458
042568
051716
049226
25
051713
2
WASHER FLAT M5
26
27
28
29
0D7177V
0F5752F
0H6267
056326
0G3524
0D7393T
0D7393U
0F5376S0AR
0F5396S0AR
057073
2
1
1
1
DIODE BRIDGE 1P 35A 1000V
RES WW 15R 5% 25W QK CONN
COVER VOLTAGE SHIELD
TRIM VINYL BLACK 1/8GP (3”LG)
COVER BELL HOUSING CONBOX
TERM BLOCK 3P UL 12-20AWG
TERM BLOCK 4P UL 12-20AWG
MX150L SLRRMNT 22-18 8P W/O GA
MX150L SLRRMNT 22-18 12P W/OGA
JUNCTION BLOCK 3/8-16
30
1
(1)31
(1)32
(1)33
(1)34
35
REF
REF
REF
REF
1
36
37
38
0C2265
057329
022237
3
1
1
SCREW PHTT M4-0.7 X 12 ZP
LUG SLDLSS 350-#6X13/32 AL/CU
WASHER LOCK 3/8
39
022241
1
NUT HEX 3/8-16 STEEL
40
41
42
43
44
45
46
025433
023762
0H7292
0H7293
029289
1
1
1
1
1
1
2
LUG SLDLSS #6-14 X 13/64 CU
WASHER LOCK EXT #10 STL
DECAL CUSTOMER CONTROL CONNECT
DECAL CONBOX TB1 CONNECTIONS
TAPE ELEC 1/2 FOAM (62” LG)
DECAL CUSTOMER POWER CONNECT
WASHER NYLON .257
0J0489
0A2115
47
48
49
50
51
52
0F6146
1
1
REF
1
1
HANG TAG 2 WIRE START (NOT SHOWN)
HARN CONBOX NEXUS (NOT SHOWN)
FUSE ATO TYPE 7.5AMP (BROWN)
DECAL GROUND LUG
GASKET WIRE ENTRY COVER
DECAL CAUTION ELEC SHOCK SM
0H6692
0D7178T
067210A
0J6701
0H8006
1
UL CIRCUIT BREAKER (225AF)
A
B
C
D
E
F
G
H
J
0G5249
REF
1
1
1
2
2
2
10
2
2
CB 150A 2 POLE 240V 225AF
COVER CB G 225AF C1 CONBOX
INSULATOR CB 2P 225AF
SPRT CIRCUIT BREAKER G 225AF
WASHER FLAT #8 ZINC
WASHER LOCK #8-M4
NUT HEX #8-32 STEEL
SCREW HWHT M6-1 X 16 N WA Z/JS
SCREW RHM #8-32 X 3-1/4
BUS BAR 200A LUG ADAPTOR
SCREW SHC M8-1.25 X 20 G8
0H6846
0F8432A
0G5734
038150
022264
022471
0C2454
053640
0F8843
049897
K
L
4
REVISION: J-6101-L
DATE: 8/12/13
Page 4 of 8
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: CONNECTION BOX C1 CPL
DRAWING #: 0H7234
APPLICABLE TO:
GROUP A
ITEM
PART#
QTY.
DESCRIPTION
M
N
P
R
S
T
U
V
W
X
022129
022145
045771
058306
0F8451
6
4
2
2
2
1
1
1
4
1
WASHER LOCK M8-5/16
WASHER FLAT 5/16-M8 ZINC
NUT HEX M8-1.25 G8 CLEAR ZINC
SCREW SHC M8-1.25 X 25 C12.9
LUG SLDLSS 300 MCM-6 AL/CU
DECAL TERMINAL SHOCK HZD BI
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
0G3259
0J78230AS0R
029289
036261
0K4772
RIVET POP .125 X .275 SS
DECAL SERVICE DISCONNECT
(1) ITEMS INCLUDED WITH HARNESS P/N 0H6692.
(2) ITEMS USED ON 1.6L MODELS ONLY.
(3) SEE “C1 DPE BREAKER SELECTION” TABLE.
(4) SHEET METAL PARTS LISTED IN THE BOM TABLE ARE REPRESENTING GENERIC PARTS (NO COLOR)
•
•
MANUFACTURING: FOR CORRECT MATERIAL AND COLOR REFER TO AS400 BOM.
CUSTOMER: WHEN ORDERING REPLACEMENT PARTS ENTER BASE NUMBER (FIRST 6 DIGITS ONLY) IN THE
SYSTEM FOR CORRECT MATERIAL AND COLOR (FOR REFERENCE SEE GUIDELINE 0H7169).
REVISION: J-6101-L
DATE: 8/12/13
Page 5 of 8
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: CONNECTION BOX C1 CPL
DRAWING #: 0H7234
APPLICABLE TO:
GROUP A
ITEM
PART#
QTY.
DESCRIPTION
UL CIRCUIT BREAKER (CC 2P)
A
0H4745
REF
CB 0100A 2P 240V E CC LL
CB 0125A 2P 240V E CC LL
CB 0150A 2P 240V E CC LL
COVER CB E CC 2P C1 CONBOX
NUT HEX M5-0.8 G8 CLEAR ZINC
CIRCUIT BREAKER SUPPORT (CC)
WASHER FLAT #8 ZINC
WASHER LOCK #8-M4
NUT HEX #8-32 STEEL
SCREW HWHT M6-1 X 16 N WA Z/JS
SCREW RHM #8-32 X 3-1/4
SCREW PPHM M5-0.8 X 12 ZNC
WASHER FLAT #10 ZINC
0H4746
0H4747
0H6847
051716
0H4656
038150
022264
022471
0C2454
053640
091526
023897
049226
0H4698
0J78230AS0R
029289
036261
0K4772
REF
REF
1
2
1
2
2
2
10
2
2
4
2
1
1
1
4
1
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
S
WASHER LOCK M5
INSULATOR CB 2P E TYPE CC
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
RIVET POP .125 X .275 SS
DECAL SERVICE DISCONNECT
UL CIRCUIT BREAKER (CC/FG (3P) )
A
0H4913
REF
CB 0100 3P 240V E CC LL
0H4914
0H5488
0H5489
0H7294
0H4698A
0H4656
0H5604
038150
022264
022471
0C2454
053640
0H5721
091526
023897
049226
051716
0J78230AS0R
029289
036261
0K4772
REF
REF
REF
1
1
REF
REF
4
4
4
10
4
4
3
6
3
3
1
1
CB 0125 3P 240V E CC LL
CB 0080 3P 600V E FG LL
CB 0090 3P 600V E FG LL
CB COVER E CC/FG 3P C1 CONBOX
INSULATOR CB 3P E TYPE CC/FG
CIRCUIT BREAKER SUPPORT (CC)
CIRCUIT BREAKER SUPPORT (FG)
WASHER FLAT #8 ZINC
B
C
D
E
F
G
H
J
WASHER LOCK #8-M4
NUT HEX #8-32 STEEL
SCREW HWHT M6-1 X 16 N WA Z/JS
SCREW RHM #8-32 X 3-1/4 (CC)
SCREW PPHM #8-32 X 1-3/4 ZINC (FG)
SCREW PPHM M5-0.8 X 12 ZNC
WASHER FLAT #10 ZINC
K
L
M
N
P
Q
R
S
WASHER LOCK M5
NUT HEX M5-0.8 G8 CLEAR ZINC
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
RIVET POP .125 X .275 SS
DECAL SERVICE DISCONNECT
4
1
REVISION: J-6101-L
DATE: 8/12/13
Page 6 of 8
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: CONNECTION BOX C1 CPL
DRAWING #: 0H7234
APPLICABLE TO:
GROUP A
ITEM
PART#
QTY.
DESCRIPTION
UL CIRCUIT BREAKER (BQ 2P)
A
0D5543
REF
CB 0090A 2P 240V S BQ2 LL
CB 0100A 2P 240V S BQ2 LL
CB 0125A 2P 240V S BQ2 LL
COVER CB S BQ2 C1 CONBOX
BRKT CB MTG BACK
CIRCUIT BREAKER SUPPORT (BQ)
SCREW HHC M5-0.8 X 20 G8.8
WASHER FLAT #10 ZINC
0D5544
0A2077
0H6842
0E7890
0G4497
052619
REF
REF
1
1
1
B
C
D
E
F
2
4
023897
G
H
J
K
L
049226
0C2454
051716
0G9708
022264
2
10
2
2
2
WASHER LOCK M5
SCREW HWHT M6-1 X 16 N WA Z/JS
NUT HEX M5-0.8 G8 CLEAR ZINC
SCREW PHTT M4-0.7 X 8 ZP
WASHER LOCK #8-M4
M
N
P
R
0J78230AS0R
029289
1
1
4
1
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
RIVET POP .125 X .275 SS
DECAL SERVICE DISCONNECT
036261
0K4772
UL CIRCUIT BREAKER (BQ 3P)
A
062812
053691
040532
0H6843
0E6002
0G4497
052619
REF
CB 0080A 3P 240V S BQ3 LL
CIRCT BRK 90 X 3 ITE BQ3-B090
CB 0100A 3P 240V S BQ3 LL
COVER CB S BQ3 C1 CONBOX
MTG TRACK BQ SIEMENS CB 3P
CIRCUIT BREAKER SUPPORT (BQ)
SCREW HHC M5-0.8 X 20 G8.8
WASHER FLAT #10 ZINC
REF
REF
1
1
1
B
C
D
E
F
3
6
023897
G
H
J
K
L
049226
0C2454
051716
0G9708
022264
3
10
3
2
2
WASHER LOCK M5
SCREW HWHT M6-1 X 16 N WA Z/JS
NUT HEX M5-0.8 G8 CLEAR ZINC
SCREW PHTT M4-0.7 X 8 ZP
WASHER LOCK #8-M4
M
N
P
R
0J78230AS0R
029289
1
1
4
1
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
RIVET POP .125 X .275 SS
036261
0K4772
DECAL SERVICE DISCONNECT
UL CIRCUIT BREAKER (ED 3P)
A
0D5552
REF
REF
REF
REF
1
1
4
4
4
CB 0050A 3P 480V S ED4 LL
CB 0090A 3P 480V S ED4 LL
CB 0100A 3P 480V S ED4 LL
CB 0125A 3P 480V S ED4 LL
COVER CB S ED3 C1 CONBOX
CIRCUIT BREAKER SUPPORT (ED)
WASHER FLAT #8 ZINC
0D5556
0D5557
0D9693
0H6844
0G4498
038150
B
C
D
E
F
022264
022471
WASHER LOCK #8-M4
NUT HEX #8-32 STEEL
G
H
J
K
L
M
N
P
R
0A8278
0C2454
066715
3
10
4
3
3
1
1
4
1
SCREW SHC 1/4-28 X 3/4 G8.8 NZ
SCREW HWHT M6-1 X 16 N WA Z/JS
SCREW RHM #8-32 X 4-1/2
WASHER LOCK M6-1/4
WASHER-STEP 1/2ODX9/32ID BRASS
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
022097
0D5621
0J78230AS0R
029289
036261
0K4772
RIVET POP .125 X .275 SS
DECAL SERVICE DISCONNECT
UL CIRCUIT BREAKER (QN2 2P)
A
B
C
D
E
F
0E7283
REF
1
1
1
2
CB 0150A 2P 240V S QN2 LL
0H6845
0E3664
0G4112
074908
0C2454
COVER CB S QN2 C1 CONBOX
BASE, QN CIRCUIT BREAKER
BREAKER SUPPORT BRACKET 30KW
SCREW HHTT M5-0.8 X 10 BP
SCREW HWHT M6-1 X 16 N WA Z/JS
10
REVISION: J-6101-L
DATE: 8/12/13
Page 7 of 8
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: CONNECTION BOX C1 CPL
DRAWING #: 0H7234
APPLICABLE TO:
GROUP A
ITEM
PART#
QTY.
DESCRIPTION
G
H
J
0J78230AS0R
029289
1
1
4
1
SHIELD CB HANDLE CONBOX
TAPE ELEC 1/2 FOAM
RIVET POP .125 X .2
036261
0K4772
K
DECAL SERVICE DISCONNECT
REVISION: J-6101-L
DATE: 8/12/13
Page 8 of 8
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
1
2
3
4
5
6
7
8
0G3418
0G3421
0G3419
0E9837B
0G3553
0E3257
0G4080
099502
0G4070
0G4072
0G4071
046627
052250
022473
022097
0C8566
045771
0C2454A
042568
0G3573
0G3574
0G3420
080713
076749
048031C
029032
0G4451
055934N
0F9504
0G0568
0G3433
0E2507
0H1827
0A2628
029333A
042907
027482
022129
039253
0H1851
1
1
1
1
1
2
1
6
1
1
1
1
2
8
8
4
4
28
4
1
1
1
1
1
2
1
REF
2
1
1
1
1
1
1
10
4
RADIATOR SUPPORT LH SIDE 1.6L
VENTURI 1.6L
RADIATOR SUPPORT RH SIDE 1.6L
RADIATOR 1.6L CHY
FAN COOL 450MM DIA 7 BLADE
SCREW HWHTF M6-1.0 X 16
HOSE LOWER RADIATOR 1.6L
CLAMP HOSE #24 B1.06-2.00
HOSE REAR COOLANT 1.6L
TUBE ENGINE COOLANT 1.6L
HOSE UPPER RADIATOR 1.6L
CAP RADIATOR
TAPE FOAM 1 X 1 (24” LG)
WASHER FLAT 1/4-M6 ZINC
WASHER LOCK M6-1/4
SCREW HHFC M6-1.0 X 20 G8.8
NUT HEX M8-1.25 G8 CLEAR ZINC
SCREW THF M6-1 X 12 N WA Z/JS
SCREW HHC M6-1.0 X 20 G8.8
GUARD FAN LH C1
GUARD FAN RH C1
RADIATOR BLOCK-OFF
BRACKET COOLANT TANK
TANK COOLANT RECOVERY
CLAMP HOSE BAND 1/4
HOSE 9/32 ID (43” LG)
BRACKET STEPPER MOTOR COOLANT
CLAMP VINYL 1.31 X .281 Z
GROMMET 5/8"X 1 1/8"X 5/16"
ASSY FAN BEARING SUPPORT
BRACKET FAN ALT ADAPTER 1.6L
PROBE COOLANT LEVEL 3/8NPTF
PROBE COOLANT LEVEL 3/8-18NPTF (USE WITH I/N 40, P/N 0H1851)
PULLEY - FAN 95 DIA
TIE WRAP UL 7.4" X .19" BLK (NOT SHOWN)
SCREW HHC M8-1.25 X 16 G8.8
WASHER SHAKEPROOF EXT 5/16 STL
WASHER LOCK M8-5/16
9
10
11
12
13
14
15
16
17
18
19
20
21
23
24
25
26
27
28
29
30
31
32
33
34
35
(1) 36
37
38
39
4
4
4
1
SCREW HHC M8-1.25 X 20 G8.8
ASSY PCB LCL SENSOR (USE WITH I/N 33, P/N 0H1827 ONLY)
(2) 40
(1) APPLY LOCTITE 242 TO I/N 36 BEFORE THREADING INTO I/N 31.
(2) USE WITH R-200 CONTROL PANEL ONLY.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: MOUNTING BASE 1.6L
DRAWING #: 0G3531
APPLICABLE TO:
GROUP C
ITEM
PART#
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
13
14
15
16
17
18
19
0G3343
027482
070936
070936C
039253
022145
022129
045771
071956
051730
021991
026850
0G3461
055414
047411
022097
022473
025507
1
1
2
MOUNTING BASE 1.6L 2007 C1
WASHER SHAKEPROOF EXT 5/16 STL
DAMPENER VIBRATION
VIB. ISO. 70-75 DURO
SCREW HHC M8-1.25 X 20 G8.8
WASHER FLAT 5/16 ZINC
WASHER LOCK M8-5/16
NUT HEX M8-1.25 G8 YEL CHR
WASHER FLAT M8
SCREW HHC M8-1.25 X 60 G8.8
EARTH STRAP
WASHER SHAKEPROOF EXT 1/4 STL
ALTERNATOR SUPPORT BLOCK OFF
LUG SLDLSS #2-#8 X 17/64 CU
SCREW HHC M6-1.0 X 16 G8.8
WASHER LOCK M6-1/4
2
12
16
16
4
4
4
1
1
2
1
1
1
5
1
WASHER FLAT 1/4-M6 ZINC
WASHER LOCK EXT 7/16 STL
REVISION: H-5975-B
DATE: 2/5/10
Page 2 of 2
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
0F3408C
0F3411
025507
059980
046526
077483
050331A
050331
038805J
038804M
045771
022131
027482
0F3976
0C2454
022145
1
1
1
1
1
REF
REF
REF
1
1
REF
1
BATTERY TRAY, C1 & C2
STRAP BATTERY RETAINMENT
WASHER SHAKEPROOF EXT 7/16 STL
SCREW HHC M10-1.5 X 25 G10.9
WASHER LOCK M10
BATTERY 12VDC 75-AH 26
BATTERY POST COVER RED +
BATTERY POST COVER BLK -
CABLE BATTERY BLACK #1 X 30.00
CABLE BATTERY RED #1 X 21.00
NUT HEX M8-1.25 G8 YEL CHR
WASHER FLAT 3/8-M10 ZINC
WASHER SHAKEPROOF EXT 5/16 STL
BOOT CONTACTOR CABLES
SCREW THF M6-1 X 16 N WA Z/JS
WASHER FLAT 5/16-M8 ZINC
1
1
4
REF
NOTE: WHEN INSTALLING BATTERY, TUCK BATTERY’S LIFTING STRAP ALONG
THE LEFT SIDE OF BATTERY ( SIDE OPPOSITE RADIATOR) BEFORE
CONNECTING THE BATTERY CABLES.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: ENGINE COMMON PARTS 1.6L
DRAWING #: 0H7219
APPLICABLE TO:
GROUP D
ITEM
PART#
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
0H1734
0G0834A
0G0820A
0G7461
0G0839
0G0781
0G0722
0G4059
0G4604
0G3424
0G0786
0G4605
0F9617A
0A1354B
0G0823
0G3900
0D2244M
036710
REF
1
REF
1
2
1
1
1
1
1
1
1
1
1
1
1
1
2
ENGINE GENERAC 1.6L G11 CERT
ENGINE PLATE 1.6L 6MM (TO BE USED WITH PLATE SPACER P/N 0G2070A.)
HOUSING BLOWER LG PILOT
STARTER MOTOR 12V
ENGINE MOUNTING FOOT STAMPING
EXHAUST MANIFOLD 1.6L MACHINED
INTAKE MANIFOLD MACHINED 1.6L
SHIELD 1.6L EXHAUST HEAT
DC ALTERNATOR ADAPTER MACHINED
PULLEY CRANKSHAFT MACHINED
WASHER PULLEY
BRACKET TENSIONER DC ALT
SPACER ALTERNATOR
DC ALTERNATR HAN-KOK
V-BELT 3/8 X 30.6
CAP, 1.5" HOLE SHALLOW
ASSY MAGPICKUP (3/8-24 MALE)
PIN SPRING 1/4 X 3/4
SCREW HHC M12-1.5 X 40 G10.9
SCREW HHC M10-1.5 X 25 G10.9
WASHER LOCK M10
WASHER FLAT 3/8-M10 ZINC
NUT HEX M10-1.5 CLASS 10 ZINC
GASKET INTAKE MANIFOLD 1.6L
GASKET EXHAUST MANIFOLD 1.6L
NUT TOP LOCK FL M8-1.25
SCREW HHC M10-1.5 X 70 G8.8
SCREW HHC M10-1.5 X 110 G10.9
SCREW HHC M10-1.5 X 40 G10.9
SCREW HHC M8-1.25 X 35 G8.8
WASHER LOCK M8-5/16
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
46
47
48
49
50
51
52
53
54
55
56
57
58
59
61
62
63
64
65
0C5479
059980
046526
1
13
22
18
9
1
1
14
1
4
4
1
4
3
1
3
3
4
4
5
3
5
1
1
1
1
1
1
1
1
1
3
29
1
1
1
1
022131
0G3922
0G0464
0G0465
052858
051735
0G3920
0A7387
039414
022129
022145
029333A
057821
045771
022507
022097
WASHER FLAT 5/16-M8 ZINC
TIE WRAP UL 7.4" X .19" BLK
SCREW HHC M8-1.25 X 40 G8.8
NUT HEX M8-1.25 G8 CLEAR ZINC
SCREW HHC 1/4-20 X 1/2 G5
WASHER LOCK M6-1/4
022473
090388
WASHER FLAT 1/4-M6 ZINC
SCREW HHTT M6-1.0 X 12 ZINC
WASHER FLAT M10 HEAVY DUTY
TEMPERATURE SENDER, DELPHI
BSHG RDCR HEX 1/4 TO 1/8
HARN LOW OIL PRESS SWITCH ASSY
ADAPTER DRAIN OIL
0A5768
0E0502
035579
0H7435
0C1852
069860C
069811
HOSE OIL DRAIN ASSY 21"
CAP HEX 1/4 NPT BRASS
0G38580ST03
025065
STRUT LH 1.6L ENG ADAPT PLATE
NIPPLE PIPE 3/8 NPT X 1-1/2
PIPE TEE 3/8 NPT
SCREW HWHTF M6-1.0 X 16
WASHER FLAT .34 ID X .75 OD
HARN ENG G1.6L G11 NEXUS (NOT SHOWN)
OIL FILTER 1.6L
CONDUIT FLEX .25"ID (6” LG)
STRUT RH 1.6L ENG ADAPT PLATE
BARBED STR 3/8 NPT X 3/8
027738A
0E3257
0A8830
0H6690
0G02070100
077043H
0G38620ST03
055596
0C7649
0H2250
0G3433
049541
0G7311
0G4451
0F4001E
1
3
1
REF
1
REF
1
1
CLAMP HOSE .38-.87
HOSE COOLANT 3/8 ID 20R3 (11” LG)
BRACKET FAN ALT ADAPTER 1.6L
SCREW HHC M10-1.5 X 35 G8.8
DECAL EMISSION CTRL INFO 1.6L
BRACKET STEPPER MOTOR COOLANT
ANCHOR HARNESS
REVISION: H-8414-C
DATE: 3/1/11
Page 2 of 2
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: FUELSYS NG/LPV 1.6L CPL
DRAWING #: 0H6671
APPLICABLE TO:
GROUP E
ITEM
PART#
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
037561
0A5547
062522
022127
059402
091526
049226
0E0519A
048031J
0E6586
0G1397E
0F7790
0E7121
0G4573C
0E8286
047527
057823
035685
057753B
0E4395
022129
0A6344
048031L
0G1985
047290
047290
0F3994
0G3178
048031P
059057
045771
051767
022097
039253
0G9348
026812
076691
026490
075580
0D1509
075436
022145
026915
0E6586A
1
1
1
1
1
4
4
1
4
1
1
1
2
1
1
1
2
2
1
1
2
1
4
1
1
1
1
1
1
1
2
4
5
2
1
2
1
1
1
1
1
2
1
1
NUT WING 1/4-20 NYLK
COVER AIR CLEANER
STUD TH 1/4-20 X 3 G2 ZNC FULL
NUT HEX 1/4-20 STEEL
FILTER ELEMENT
SCREW PPHM M5-0.8 X 12 ZNC
WASHER LOCK M5
ADAPTER, CARBURETOR W/PVC CONN
CLAMP HOSE BAND .63
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
(1)36
(1)37
(1)38
(1)39
40
41
42
(1)43
44
GASKET BOSCH 32 & 40
FUEL REG. REWORK 1.6L
VENTURI THROTTLE 21MM
O-RING 47.625 ID X 2.38 WIDTH
MIXER ACTUATOR 32MM MACHINED
STREET EL 45D 1/2 NPT BRASS
BARBED STR 1/2 NPT X 3/4
CLAMP HOSE #10 .56-1.06
CLAMP HOSE #28 1.32-2.25
HOSE 1.5 ID X 2 LG 20R4
ACTUATOR BOSCH 32 GOVERNOR
WASHER LOCK M8-5/16
BARBED EL 90 1/8 NPT X 3/8
CLAMP HOSE BAND 1.0"
HOSE BARB REDUCR TEE 3/4"-3/8"
HOSE 3/8 ID SINGLE BRAID (11.5” LG)
HOSE 3/8 ID SINGLE BRAID (12” LG)
PCV VALVE 2.5L FORD
HOSE BREATHER 1.6L
CLAMP HOSE BAND .88"
HOSE 3/4 ID SAE-30R2 (16"LG)
NUT HEX M8-1.25 G8 YEL CHR
SCREW HHC M6-1.0 X 45 C8.8 FTH
WASHER LOCK M6-1/4
SCREW HHC M8-1.25 X 20 G8.8
ASSY REG INLET NPT FITTINGS
ELBOW 90D 3/4 NPT
NIPPLE PIPE 3/4NPTX4.5 BLK IRN
NIPPLE PIPE 3/4NPT X 2
FLANGE FUEL INLET
DECAL INLET PRESSURE
DECAL FUEL INLET
WASHER FLAT 5/16 ZINC
NIPPLE CLOSE 3/4 X 1.375
GASKET BOSCH 32
(1) INCLUDED IN ITEM 35 (ASSY REG INLET NPT FITTINGS)
REGULATOR NOTES:
REGULATOR (I/N 11) AS SHOWN IN ILLUSTRATION IS SET UP FOR NATURAL GAS APPLICATION.
TO CONFIGURE REGULATOR FOR LP VAPOR, REFER TO THE “RECONFIGURING THE FUEL SYSTEM” SECTION OF THIS
MANUAL.
REVISION: -A-
DATE: 1/21/10
Page 2 of 2
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLODED VIEW: EV ENCLOSURE C1 CPL
DRAWING #: 0G3534
GROUP F
ITEM
PART#
QTY.
DESCRIPTION
(2) 1
(2) 2
(1) 3
(2) 4
6
0G33370AL0R
0J14640AL0R
077992
0J14630AL0R
0F4487A
022127
1
1
10
2
1
ROOF 1.6L C1
REAR INTAKE WRAP C1
NUT HEX LOCK M6-1.0 SS NY INS
DOOR LEFT/RIGHT SIDE C1
ASSY ACCESS COVER
7
1
NUT HEX 1/4-20 STEEL
8
9
022097
022473
0C2454
0F5048D
0F5049B
0F8869D
089961
078115
0H7518
0H7518A
0E3257
0912970090
0H7518B
0C8566
1
10
8
2
2
1
1
8
2
1
6
2
1
10
10
8
WASHER LOCK M6-1/4
WASHER FLAT 1/4-M6 ZINC
SCREW THF M6-1 X 16 N WA Z/JS
VISE-ACTION LATCH, SLOTTED CIR
PULL TAB DOOR LOCK SS
KEY VISE-ACTION LATCH,SLOT CIR
FOAM STRIP 3/4"WIDE X 3/16"THK (294”LG)
WASHER SELF LOCKING DOME
INSULATION SIDE DOOR C1
INSULATION ROOF C1
SCREW HWHTF M6-1.0 X 16
ASSY WIRE 14AWG GRN/YEL (32.25”LG)
INSULATION REAR C1
SCREW HHFC M6-1.0 X 20 G8.8
NUT SPRINGCLIP M6-1.0
(1)10
11
12
13
14
15
16
17
(1)19
20
21
23
24
25
0H0412
022097
WASHER LOCK M6-1/4
(3) 26
27
0H7529
1
1
1
1
FOIL ALUMINUM WITH ADHESIVE
RF COVER PLATE-PLASTIC-BISQUE
RF COVER PLATE-PLASTIC-GREY
FRONT DISCHARGE WRAP 1.6L C1
WASHER LOCK SPECIAL 1/4"
0H1208A
0H1208B
0G33350AL0R
0A1658
(2) 28
(1)29
2
(1)ENCLOSURE NOTE: ALL PANELS THAT FASTEN TO THE ROOF MUST BE SECURED USING I/N 10 (THREAD FORMING FASTENER) AND I/N 3 (LOCK NUT) AND
TO INCLUDE AT LEAST ONE CONNECTION POINT USING I/N 19 (THREAD FORMING FASTENER) WITH I/N 3 (LOCK NUT) TO EACH PANEL. LOCK NUT IS TO BE
INSTALLED AFTER THREAD FORMING FASTENER HAS PENETRATED THROUGH EXTRUSION IN ENCLOSURE PANELS. ALL PANEL TO BASEFRAME
CONNECTIONS TO INCLUDE AT LEAST ONE CONNECTION POINT USING I/N 29 (WASHER SPECIAL).
(2) SHEET METAL PARTS LISTED IN THE BOM TABLE ARE REPRESENTING GENERIC PARTS (NO COLOR)
•
•
MANUFACTURING: FOR CORRECT MATERIAL AND COLOR REFER TO AS400 BOM.
CUSTOMER: WHEN ORDERING REPLACEMENT PARTS ENTER BASE NUMBER (FIRST 6 DIGITS ONLY) IN THE SYSTEM FOR CORRECT MATERIAL
AND COLOR (FOR REFERENCE SEE GUIDELINE 0H7169).
(3) USED ON 1.5L / 1.6L UNITS ONLY.1
REVISION: J-1720-K
DATE: 3/23/12
Page 2 of 2
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
0F7366
0F7647
0F8095
0G3576
0E3257
0F7644
0C6119
036434
036449
022129
022259
038750
0G3575
0F3794A
022097
049813
022473
1
1
1
1
4
2
1
3
3
6
6
1
1
1
1
1
6
MUFFLER C1
MUFFLER SADDLE
PIPE EXHAUST OUTLET
EXHAUST PIPE LOWER 1.6L
SCREW HWHTF M6-1.0 X 16
MUFFLER STRAP
BOLT U 5/16-18 X 2-1/4
BOLT U 5/16-18 X 2.09
SADDLE 2 INCH
WASHER LOCK M8-5/16
NUT HEX 5/16-18 STEEL
SCREW HHC M6-1.0 X 30 G8.8
EXHAUST PIPE UPPER 1.6L SS
EXHAUST BLANKET 500MM LONG
WASHER LOCK M6-1/4
NUT HEX M6 X 1.0 G8 YEL CHR
WASHER FLAT 1/4-M6 ZINC
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
. A v 0 4 / 0 7 k P g B 0 0 a 1 c R e
Download from Www.Somanuals.com. All Manuals Search And Download.
|