Generac Power Systems Portable Generator 10 kW LP User Manual

diagnostic  
repair  
manual  
air-cooled Product  
MODELS:  
7 kW NG, 8 kW LP  
9 kW NG, 10 kW LP  
13 kW NG, 14 kW LP  
16 kW NG, 17 kW LP  
18 kW NG, 20 kW LP  
a u t o m a t i c s ta n d b y g e n e r a t o r s  
Download from Www.Somanuals.com. All Manuals Search And Download.  
contents  
1.6 Engine-Generator Protective Devices ............. 25  
General ............................................................25  
Low Battery......................................................25  
Low Oil Pressure Shutdown.............................25  
High Temperature Switch.................................25  
Overspeed Shutdown ......................................25  
Rpm Sensor Failure.........................................25  
Overcrank Shutdown .......................................26  
1.7 Operating Instructions ..................................... 27  
Control Panel ...................................................27  
To Select Automatic Operation ........................28  
specifications .......................................................... 4  
Generator ................................................................ 4  
Engine ..................................................................... 5  
Fuel Consumption ................................................... 5  
Mounting Dimensions.............................................. 6  
Mounting Dimensions.............................................. 7  
Major Features ........................................................ 8  
Part 1 - GENEral iNformatioN ....................... 9  
1.1 Generator Identification................................... 10  
Introduction......................................................10  
1.2 Installation Basics............................................ 11  
Introduction......................................................11  
Selecting A Location........................................11  
Grounding The Generator................................11  
The Fuel Supply...............................................11  
The Transfer Switch / Load Center...................11  
Power Source And Load Lines.........................13  
System Control Interconnections.....................13  
Natural Gas Fuel Interconnections ..................13  
1.3 Non-prepackaged Interconnections ................ 14  
Manual Transfer To Standby”  
and Manual Startup.....................................28  
Manual Shutdown And  
Retransfer Back To Utility” ..........................28  
1.8 Automatic Operating Parameters .................... 29  
Introduction......................................................29  
Automatic Operating Sequences .....................29  
Part 2 - ac GENErators.................................. 31  
2.1 Description and Components.......................... 32  
Introduction......................................................32  
Engine-Generator Drive System......................32  
The AC Generator............................................32  
Rotor Assembly................................................32  
Stator Assembly...............................................33  
Brush Holder And Brushes (12-20 kW) ...........34  
Other AC Generator Components ...................34  
2.2 Operational Analysis ....................................... 35  
Rotor Residual Magnetism...............................35  
Field Boost (12-20 kW)....................................35  
Operation (8/10 kW).........................................36  
Operation (12-20 kW) ......................................36  
2.3 Troubleshooting Flowcharts............................. 37  
Connect a Pre-2008 Load Center Switch  
To a Current or Future  
Air-Cooled Generator...................................14  
Connect a 2008 And Later Load Center  
Switch to a Pre-2008  
Air-Cooled Generator...................................15  
1.4 Preparation Before Use................................... 16  
General ............................................................16  
Fuel Requirements...........................................16  
Fuel Consumption............................................16  
Reconfiguring The Fuel System.......................16  
Engine Oil Recommendations .........................18  
1.5 Testing, Cleaning and Drying........................... 19  
Meters ............................................................19  
The Vom...........................................................19  
Measuring AC Voltage .....................................19  
Measuring DC Voltage.....................................19  
Measuring AC Frequency ................................19  
Measuring Current...........................................20  
Measuring Resistance .....................................20  
Electrical Units.................................................21  
Ohm’s Law .......................................................21  
Visual Inspection..............................................22  
Insulation Resistance.......................................22  
The Megohmmeter...........................................22  
Stator Insulation Resistance Test (12-20 kW) .....23  
Stator Insulation Resistance Test (8-10 kW) .......23  
Rotor Insulation Resistance Test (8-10 kW) ........24  
Rotor Insulation Resistance Test (12-20 kW) ......24  
Cleaning The Generator...................................24  
Drying The Generator ......................................24  
Problem 1 – Generator Produces Zero  
Voltage or Residual Voltage (12-20 kW)...37-38  
Problem 2 – Generator Produces Zero  
Voltage or Residual Voltage (8/10 kW) ........38  
Problem 3 – Generator Produces  
Low Voltage at No-Load...............................39  
Problem 4 – Generator Produces  
High Voltage at No-Load..............................39  
Problem 5 – Voltage and Frequency Drop  
Excessively When Loads are Applied..........40  
2.4 Diagnostic Tests .............................................. 41  
Introduction......................................................41  
Safety ............................................................41  
Test 1 – Check Main Circuit Breaker................41  
Test 2 – Check AC Output Voltage...................41  
Test 4 – Fixed Excitation Test/Rotor  
Amp Draw Test ....................................42  
Test 5 – Wire Continuity (12-20 kW) ................43  
Test 6 – Check Field Boost (12-20 kW) ...........44  
Page 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Test 7 – Testing The Stator With A Vom  
(12-20 kW)...........................................44  
Problem 11 – No Battery Charge  
(Pre-Packed Load Center)...........................73  
Test 8 – Test Brushless Stator..........................45  
Test 9 – Check Capacitor.................................46  
Problem 12 – No Battery Charge  
(RTSN & RTSE Transfer Switch) .................73  
Problem 13 – No Battery Charge  
(Gen-Ready Load Center)...........................73  
Test 10 – Test DPE Winding on  
Brushless units....................................47  
Problem 14 – No Battery Charge  
(Load Shed Transfer Switch)........................73  
Test 11 – Resistance Check Of Rotor Circuit  
(12-20 kW)...........................................48  
3.4 Diagnostic Tests .............................................. 74  
General ............................................................74  
Test 12 – Check Brushes And Slip Rings  
(12-20 kW)...........................................48  
Test 26 – Check Voltage at  
Test 13 – Test Rotor Assembly(12-20 kW).......49  
Test 14 – Check AC Output Frequency............49  
Terminal Lugs E1, E2..........................74  
Test 27 – Check Manual Transfer Switch  
Operation.............................................75  
Test 15 – Check and Adjust Engine Governor  
(Single Cylinder Units).........................49  
Test 28 – Check 23 And 15B  
Test 16 – Check Stepper Motor Control  
(V-twin Engine Units)...........................50  
Wiring/Connections.............................76  
Test 29 – Test Transfer Relay TR......................77  
Test 30 – Standby Control Circuit ....................78  
Test 31 – Check Wire 23..................................78  
Test 32 – Utility Control Circuit.........................80  
Test 33 – Test Limit Switch SW2 and SW3 ......82  
Test 34 – Check Fuses F1 and F2...................82  
Test 35 – Check N1 and N2 Wiring..................83  
Test 36 – Check N1 and N2 Voltage ................83  
Test 17 – Check And Adjust Voltage  
Regulator (12-20 kW)..........................51  
Test 18 – Check Voltage And Frequency  
Under Load..........................................52  
Test 19 – Check For Overload Condition...........52  
Test 20 – Check Engine Condition...................52  
Test 21 – Field Flash Alternator (8-10 kW) ......52  
Part 3 - traNsfEr sWitcH............................... 55  
3.1 Description and Components.......................... 56  
General ............................................................56  
Enclosure.........................................................56  
Transfer Mechanism.........................................57  
Transfer Relay..................................................57  
Neutral Lug ......................................................58  
Manual Transfer Handle ..................................58  
Terminal Block .................................................58  
Fuse Holder .....................................................59  
3.2 Operational Analysis ....................................... 60  
Operational Analysis........................................60  
Utility Source Voltage Available .......................62  
Utility Source Voltage Failure ..........................63  
Transfer To Standby .........................................64  
Transfer To Standby .........................................65  
Utility Restored.................................................66  
Utility Restored, Transfer Switch De-energized ...67  
Utility Restored, Retransfer Back To Utility.......68  
Transfer Switch In Utility...................................69  
3.3 – Troubleshooting Flowcharts.......................... 70  
Introduction To Troubleshooting .......................70  
Test 37 – Check Utility Sensing Voltage  
at the Circuit Board..............................84  
Test 38 – Check Utility Sense Voltage .............84  
Test 39 – Check Voltage at  
Terminal Lugs N1, N2..........................84  
Test 40 – Check Battery Charger Supply  
Voltage “Pre-Wire Load Center..........86  
Test 41 – Check Battery Charger Output  
Voltage “Pre-Wire Load Center..........86  
Test 42 – Check Wire 0 and Wire15B  
“Pre-Wire Load Center.......................86  
Test 43 – Check Battery Charger  
Supply Voltage  
“RTSN & RTSE Transfer Switch.........87  
Test 44 – Check Battery Charger  
Output Voltage  
“RTSN & RTSE Transfer Switch.........87  
Test 45 – Check Wire 0/  
“RTSN & RTSE Transfer Switch” ........87  
Test 46 – Check Battery Charger  
Supply Voltage  
“GenReady Load Center....................90  
Test 47 – Check Battery Charger  
Output Voltage  
“GenReady Load Center....................90  
Test 48 – Check Wire 0/15B  
Problem 7 – In Automatic Mode,  
No Transfer to Standby ................................70  
“GenReady Load Center....................90  
Test 49 – Check Battery Charger  
Supply Voltage  
Problem 8 – In Automatic Mode, Generator  
Starts When Loss of Utility Occurs,  
“Load Shed Transfer Switch” ...............92  
Generator Shuts Down When Utility  
Test 50 – Check Battery Charger  
Output Voltage  
Returns But There Is No Retransfer To Utility  
Power / or Generator Transfers to Standby  
During Exercise Or In Manual Mode............71  
“Load Shed Transfer Switch” ...............92  
Test 51 – Check Wire 0 and Wire 15B  
“Load Shed Transfer Switch” ...............94  
Problem 9 – Blown F1 or F2 Fuse...............71  
Problem 10 – Units Starts And Transfer  
Occurs When Utility Power Is On.................72  
Page 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Part 4 - Dc coNtrol......................................... 95  
4.1 Description and Components.......................... 96  
General ............................................................96  
Terminal Strip / Interconnection Terminal.........96  
Circuit Board....................................................96  
Auto-Off-Manual Switch...................................96  
7.5 Amp Fuse...................................................96  
Menu System Navigation...............................102  
4.2 Operational Analysis ..................................... 104  
Introduction....................................................104  
Utility Source Voltage Available......................104  
Initial Dropout of Utility Source Voltage..........106  
Test 68 – Check Fuel Solenoid ......................132  
Test 69 – Check Choke Solenoid...................132  
Test 70 – Check for Ignition Spark.................134  
Test 71 – Check Spark Plugs.........................136  
Test 72 – Check Engine / Cylinder Leak  
Down Test / Compression Test ..........136  
Test 73 – Check Shutdown Wire....................137  
Test 74 – Check and Adjust  
Ignition Magnetos..............................138  
Test 75 – Check Oil Pressure Switch  
and Wire 86.......................................141  
Test 76 – Check High Oil  
Temperature Switch...........................142  
Test 77 – Check and Adjust Valves................142  
Test 78 – Check Wire 18 Continuity...............143  
Test 79 – Test Exercise Function ...................144  
Utility Voltage Dropout and  
Engine Cranking................................108  
Engine Startup and Running..........................110  
Initial Transfer to the “Standby” Source ..........112  
Test 80 – Check Cranking and  
Running Circuits................................144  
Utility Voltage Restored /  
Re-transfer to Utility...........................114  
Test 81 – Check to see if Low Speed  
Function is enabled ...........................146  
Engine Shutdown...........................................116  
4.3 Troubleshooting Flowcharts........................... 118  
Test 82 – Check operation of the  
Choke Solenoid.................................146  
Problem 15 – Engine Will Not Crank  
When Utility Power Source Fails................118  
Part 5 - oPEratioNal tEsts ........................ 147  
5.1 System Functional Tests................................ 148  
Introduction....................................................148  
Manual Transfer Switch Operation .................148  
Electrical Checks ...........................................148  
Generator Tests Under Load..........................149  
Checking Automatic Operation ......................150  
Setting The Exercise Timer............................150  
Part 6 - DisassEmBlY ..................................... 151  
6.1 Major Disassembly........................................ 152  
Front Engine Access......................................152  
Major Disassembly.........................................156  
Problem 16 – Engine Will Not Crank When  
AUTO-OFF-MANUAL Switch  
is Set to “MANUAL.....................................118  
Problem 17 – Engine Cranks  
but Won’t Start...........................................119  
Problem 18 – Engine Starts Hard and  
Runs Rough / Lacks Power / Backfires......120  
Problem 19 – Shutdown Alarm /  
Fault Occurred...........................................121  
Problem 20 – 7.5 Amp Fuse (F1) Blown ..... 122  
Problem 21 – Generator Will Not Exercise... 122  
Problem 22 – No Low Speed Exercise........ 122  
4.4 Diagnostic Tests ............................................ 123  
Introduction ...................................................123  
Torque Requirements  
(Unless Otherwise Specified)............162  
Test 56 – Check Position Of  
Part 7 - ElEctrical Data.............................. 163  
Wiring Diagram, 8 kW Home Standby................. 164  
Schematic, 8 kW Home Standby......................... 166  
Wiring Diagram, 10 kW Home Standby............... 168  
Schematic, 10 kW Home Standby....................... 170  
Wiring Diagram, 14 kW Home Standby............... 172  
Schematic, 14 kW Home Standby....................... 174  
Wiring Diagram, 17 kW Home Standby............... 176  
Schematic, 17 kW Home Standby....................... 178  
Wiring Diagram, 20 kW Home Standby............... 180  
Schematic, 20 kW Home Standby....................... 182  
Auto-Off- Manual Switch ..................123  
Test 57 – Try a Manual Start .........................123  
Test 58 – Auto-Off-Manual Switch  
(V-Twin Only).....................................123  
Test 59 – Test Auto Operations......................124  
Test 60 – Check 7.5 Amp Fuse......................124  
Test 61 – Check Battery.................................124  
Test 62 – Check Wire 56 Voltage ...................126  
Test 63 – Test Starter Contactor Relay  
(V-twin Only)......................................126  
Test 64 – Test Starter Contactor  
(Single Cylinder Engine)....................127  
Wiring Diagram, Home Standby Transfer Switch,  
9/10/12/16 Circuit ................................................ 184  
Test 65 – Test Starter Motor...........................128  
Test 66 – Check Fuel Supply and Pressure...130  
Schematic, Home Standby Transfer Switch,  
9/10/12/16 Circuit ................................................ 186  
Test 67 – Check Circuit Board  
Wire 14 Output..................................131  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sPEcificatioNs  
Generator  
Unit  
8 kW  
10 kW  
12 kW  
14 kW  
16 kW  
17 kW  
20 kW  
Rated Max. Continuous  
Power Capacity (Watts*)  
7,000 NG  
8,000 LP  
9,000 NG  
10,000 LP  
12,000 NG  
12,000 LP  
13,000 NG  
14,000 LP  
16,000 NG  
16,000 LP  
16,000 NG  
17,000 LP  
18,000 NG  
20,000 LP  
Rated Voltage  
120/240  
Rated Voltage at No-Load  
(NG)  
220-235  
247-249  
Rated Max. Continuous Load  
Current (Amps)  
120 Volts** (NG/LP)  
240 Volts (NG/LP)  
58.3/66.6  
29.2/33.3  
75.0/83.3  
37.5/41.6  
100.0/100.0  
50.0/50.0  
108.3/116.6  
54.2/58.3  
133.3/133.3  
66.6/66.6  
133.3/141.6  
66.6/70.8  
150.0/166.6  
75.0/83.3  
Main Line Circuit Breaker  
Circuits*** 50A, 240V  
40A, 240V  
35 Amp  
45 Amp  
50 Amp  
60 Amp  
65 Amp  
65 Amp  
100 Amp  
-
-
-
-
-
1
1
-
1
1
1
-
1
1
-
-
-
-
-
-
-
1
30A, 240V  
1
-
1
1
3
3
-
20A, 240V  
1
1
5
5
1
5
5
20A, 120V  
1
5
3
5
4
15A, 120V  
4
Phase  
1
2
Number of Rotor Poles  
Rated AC Frequency  
Power Factor  
60 Hz  
1
Battery Requirement  
Group 26R, 12  
Volts and 350 CCA  
Minimum  
Group 26R, 12 Volts and 525 CCA Minimum  
Weight (unit only in lbs.)  
Enclosure  
340  
387  
439  
439  
Steel  
455  
455/421  
450  
Steel  
Steel  
Steel  
Steel  
Steel/Aluminum  
Aluminum  
Normal Operating Range  
-20° F (-28.8° C) to 77° F (25° C)  
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.  
Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6 C (10 F) above 16 C (60 F)  
ambient temperature.  
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the value  
stated for the 240 volts.  
*** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer switch.  
Stator WindinG reSiStance ValueS / rotor reSiStance  
8 kW  
10 kW  
12 kW  
14 kW  
16 kW  
17 kW  
20 kW  
Power Winding: Across 11 & 22  
Power Winding: Across 33 & 44  
Excitation Winding: Across 2 & 6  
Rotor Resistance  
0.123-0.1439  
0.090-0.105  
0.100-0.116  
0.100-0.116  
0.074-0.086  
0.074-0.086  
0.0415-0.0483  
0.123-0.1439  
0.776-0.902  
3.01-3.49  
0.090-0.105  
0.511-0.594  
3.22-3.74  
0.100-0.116  
0.876-1.018  
7.96-9.25  
0.100-0.116  
0.876-1.018  
7.96-9.25  
0.074-0.086  
0.780-0.906  
8.79-10.21  
0.074-0.086  
0.780-0.906  
8.79-10.21  
0.0415-0.0483  
0.731-0.850  
10.02-11.65  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SpecificationS  
engine  
Model  
8 kW  
GH-410  
1
10 kW  
12/14/16/17 kW  
20 kW  
GT-999  
2
Type of Engine  
GT-530  
2
GT-990  
2
Number of Cylinders  
Rated Horsepower @ 3,600 rpm  
Displacement  
14.8  
18  
32  
34  
407cc  
530cc  
992cc  
999cc  
Cylinder Block  
Aluminum w/Cast Iron Sleeve  
Valve Arrangement  
Ignition System  
Overhead Valves  
Solid-state w/Magneto  
Recommended Spark Plug  
Spark Plug Gap  
RC14YC  
0.76 mm (0.030 inch)  
9.4:1  
BPR6HS  
RC14YCA  
1.02 mm (0.040 inch)  
9.5:1  
RC12YC  
1.02 mm (0.040 inch)  
9.5:1  
0.76 mm (0.030 inch)  
9.5:1  
Compression Ratio  
Starter  
12 VDC  
Part # 070185F  
3,600  
Oil Capacity Including Filter  
Recommended Oil Filter  
Recommended Air Filter  
Operating RPM  
Approx. 1.5 Qts  
Part # 0G3332  
Approx. 1.8 Qts  
Part # 0E9581  
Approx. 1.9 Qts  
Part # 0C8127  
Approx. 1.9 Qts  
Part # 0G5894  
Fuel Consumption  
Model #  
Natural Gas*  
Full Load  
140  
LP Vapor**  
Full Load  
1.68/62  
1.93/70  
2.08/76  
2.30/84  
2.51/91  
2.57/94  
2.90/106  
1/2 Load  
77  
1/2 Load  
0.94/34  
1.25/46  
1.53/56  
1.56/58  
1.59/58  
1.61/59  
1.89/69  
7/8 kW  
9/10 kW  
12/12 kW  
13/14 kW  
16/16 kW  
16/17 kW  
18/20 kW  
102  
156  
152  
215  
156  
220  
183  
261  
183  
261  
206  
294  
* Natural gas is in cubic feet per hour.  
**LP is in gallons per hour/cubic feet per hour.  
Values given are approximate.  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sPEcificatioNs  
mountinG dimenSionS  
299  
[11.8]  
1079.5  
[42.5]  
698  
[27.5]  
997  
[39.3]  
747  
[29.4]  
207  
[8.2]  
454  
[17.9]  
508  
[20.0]  
TRANSFER  
SWITCH  
8KW - 17KW  
(IF SUPPLIED)  
Ø30.2 [Ø1.2]  
LIFTING HOLES 4 CORNERS  
TRANSFER  
SWITCH  
20KW  
(IF SUPPLIED)  
"DO NOT LIFT BY ROOF"  
637.6  
[25.1]  
1218  
[47.9]  
731.9  
[28.8]  
642  
[25.3]  
76.2 [3.0]  
PEA GRAVEL  
MINIMUM  
1226  
[48.3]  
FRONT VIEW  
LEFT SIDE VIEW  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sPEcificatioNs  
mountinG dimenSionS  
AIR INTAKE  
457.2  
[18.0]  
MINIMUM DISTANCE  
914 [36.0]  
MINIMUM OPEN AREA  
ON SIDES AND FRONT  
AIR OUTLET  
AIR INTAKE  
250.0  
[9.8]  
575.3  
[22.7]  
530.0  
[20.9]  
HOLE LOCATIONS FOR  
OPTIONAL MOUNTING TO  
A CONCRETE PAD  
446.6  
[17.6]  
378.7  
[14.9]  
44.8  
[1.8]  
FRONT OF UNIT  
FUEL INLET - 12-20KW (1/2" NPT)  
8 & 10KW (3/4" NPT) - USE SUPPLIED ADAPTER  
REQUIRED FUEL PRESSURE: NATURAL GAS = 5-7" WATER COLUMN  
LIQUID PROPANE (VAPOR) = 10-12" WATER COLUMN  
CABLE ACCESS HOLE  
178.9  
[7.0]  
244.4  
[9.6]  
GROUNDING LUG  
REAR VIEW  
RIGHT SIDE VIEW  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sPEcificatioNs  
major FeatureS  
8kW, Single Cylinder, GH-410 Engine  
10kW, V-twin, GT-530 Engine  
(door removed)  
(door removed)  
Circuit  
Breaker  
Oil  
Dipstick  
Data Label  
(see sample)  
Control  
Panel  
Oil  
Dipstick  
Data Label  
(see sample)  
Control  
Panel  
Circuit  
Breaker  
Exhaust  
Enclosure  
Exhaust  
Enclosure  
Air  
Filter  
Air Filter  
Fuel Inlet  
(back)  
Fuel Inlet  
(back)  
Fuel  
Regulator  
Fuel  
Regulator  
Composite Base  
Oil Filter  
Battery Compartment  
Composite Base  
Oil Filter  
Battery Compartment  
Figure 1.3 – 12, 14, 16, 17 and 20kW, V-twin,  
GT-990/GT-999 Engine (door removed)  
Data Label  
(see sample)  
Oil  
Dipstick  
Control  
Panel  
Circuit Breakers  
GFCI Outlet  
(All 17 & 20kW)  
Air Filter  
Exhaust  
Enclosure  
Fuel Inlet  
(back)  
Fuel  
Regulator  
Composite Base  
Oil Filter  
Battery Compartment  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
taBlE of coNtENts  
Part  
titlE  
PaGE  
10  
1.1  
1.2  
1.3  
Generator identification  
installation Basics  
Non-Prepackaged  
interconnections  
11  
Part 1  
GENEral  
iNformatioN  
14  
1.3  
1.4  
1.5  
Preparation Before use  
testing, cleaning and Drying  
Engine-Generator Protective  
Devices  
16  
18  
25  
1.6  
1.7  
operating instructions  
automatic operating  
Parameters  
27  
29  
air-cooled, automatic  
standby Generators  
1.1 Generator Identification................................... 10  
Introduction......................................................10  
1.2 Installation Basics............................................ 11  
Introduction......................................................11  
Selecting A Location........................................11  
Grounding The Generator................................11  
The Fuel Supply...............................................11  
The Transfer Switch / Load Center...................11  
Power Source And Load Lines.........................13  
System Control Interconnections.....................13  
Natural Gas Fuel Interconnections ..................13  
1.3 Non-prepackaged Interconnections ................ 14  
Measuring Resistance .....................................20  
Electrical Units.................................................21  
Ohm’s Law .......................................................21  
Visual Inspection..............................................22  
Insulation Resistance.......................................22  
The Megohmmeter...........................................22  
Stator Insulation Resistance Test (12-20kW)...23  
Stator Insulation Resistance Test (8-10kW).....23  
Rotor Insulation Resistance Test (8-10kW)......24  
Rotor Insulation Resistance Test (12-20kW)....24  
Cleaning The Generator...................................24  
Drying The Generator ......................................24  
1.6 Engine-Generator Protective Devices ............. 25  
General ............................................................25  
Low Battery......................................................25  
Low Oil Pressure Shutdown.............................25  
High Temperature Switch.................................25  
Overspeed Shutdown ......................................25  
Rpm Sensor Failure.........................................25  
Overcrank Shutdown .......................................26  
1.7 Operating Instructions ..................................... 27  
Control Panel ...................................................27  
To Select Automatic Operation ........................28  
Connect a Pre-2008 Load Center Switch  
To a Current or Future  
Air-Cooled Generator...................................14  
Connect a 2008 And Later Load Center  
Switch to a Pre-2008  
Air-Cooled Generator...................................15  
1.4 Preparation Before Use................................... 16  
General ............................................................16  
Fuel Requirements...........................................16  
Fuel Consumption............................................16  
Reconfiguring The Fuel System.......................16  
Engine Oil Recommendations .........................18  
1.5 Testing, Cleaning and Drying........................... 19  
Meters ............................................................19  
The Vom...........................................................19  
Measuring AC Voltage .....................................19  
Measuring DC Voltage.....................................19  
Measuring AC Frequency ................................19  
Measuring Current...........................................20  
Manual Transfer To Standby”  
and Manual Startup.....................................28  
Manual Shutdown And  
Retransfer Back To Utility” ..........................28  
1.8 Automatic Operating Parameters .................... 29  
Introduction......................................................29  
Automatic Operating Sequences .....................29  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.1  
GENErator iDENtificatioN  
GENERAL INFORMATION  
Part 1  
It is not our intent to provide detailed disassembly and  
reassemble instructions in this manual. It is our intent  
to (a) provide the service technician with an under-  
standing of how the various assemblies and systems  
work, (b) assist the technician in finding the cause of  
malfunctions, and (c) effect the expeditious repair of  
the equipment.  
introduction  
This Diagnostic Repair Manual has been prepared  
especially for the purpose of familiarizing service per-  
sonnel with the testing, troubleshooting and repair of  
air-cooled, automatic standby generators. Every effort  
has been expended to ensure that information and  
instructions in the manual are both accurate and cur-  
rent. However, changes, alterations or other improve-  
ments may be made to the product at any time with-  
out prior notification.  
ITEM NUMBER:  
Many home standby generators are manufactured  
to the unique specifications of the buyer. The Model  
Number identifies the specific generator set and its  
unique design specifications.  
The manual has been divided into PARTS. Each PART  
has been divided into SECTIONS. Each SECTION  
consists of two or more SUBSECTIONS.  
SERIAL NUMBER:  
Used for warranty tracking purposes.  
Item # 0055555  
Serial  
Volts  
1234567  
120/240 AC  
108.3/108.3  
13000  
Amps  
Watts  
MODEL #  
SERIAL #  
WATTS  
VOLTS  
AMPS  
13000  
0055555  
1234567  
120/240 AC  
108.3/108.3  
1 PH, 60 HZ, RPM 3600  
1PH, 60Hz, 3600 RPM, CLASS F INSULATION  
RAINPROOF ENCLOSURE FITTED  
RATED AMBIENT TEMP - 40°C  
CLASS F INSULATION  
MAX OPERATING AMBIENT  
TEMP - 120F/49C  
FOR STANDBY SERVICE, NEUTRAL FLOATING  
FOR STANDBY SERVICE  
NEUTRAL FLOATING  
Model Number -  
Serial Number -  
MAX LOAD UNBALANCED - 50%  
Figure 1. Typical Data Plates  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.2  
iNstallatioN Basics  
GENERAL INFORMATION  
Part 1  
LP (propane) gas is usually supplied as a liquid in  
pressure tanks. Both the air-cooled and the liquid  
cooled units require a “vapor withdrawal” type of fuel  
supply system when LP (propane) gas is used. The  
vapor withdrawal system utilizes the gaseous fuel  
vapors that form at the top of the supply tank.  
introduction  
Information in this section is provided so that the  
service technician will have a basic knowledge of  
installation requirements for home standby systems.  
Problems that arise are often related to poor or unau-  
thorized installation practices.  
The pressure at which LP gas is delivered to the  
generator fuel solenoid valve may vary considerably,  
depending on ambient temperatures. In cold weather,  
supply pressures may drop to “zero”. In warm weath-  
er, extremely high gas pressures may be encountered.  
A primary regulator is required to maintain correct gas  
supply pressures.  
A typical home standby electric system is shown in  
Figure 1 (next page). Installation of such a system  
includes the following:  
• Selecting a Location  
• Grounding the generator.  
• Providing a fuel supply.  
Current recommended gaseous fuel pressure at the inlet  
side of the generator fuel solenoid valve is as follows:  
• Mounting the load center.  
• Connecting power source and load lines.  
• Connecting system control wiring.  
• Post installation tests and adjustments.  
lP  
NG  
Minimum water column  
Maximum water column  
10 inches 5 inches  
12 inches 7 inches  
SelectinG a location  
A primary regulator is required to ensure that proper  
fuel supply pressures are maintained.  
Install the generator set as close as possible to the  
electrical load distribution panel(s) that will be pow-  
ered by the unit, ensuring that there is proper ventila-  
tion for cooling air and exhaust gases. This will reduce  
wiring and conduit lengths. Wiring and conduit not  
only add to the cost of the installation, but excessively  
long wiring runs can result in a voltage drop.  
DaNGEr: lP aND Natural Gas arE BotH  
HiGHlY EXPlosiVE. GasEous fuEl liNEs  
must BE ProPErlY PurGED aNDtEstED  
for lEaKs BEforEtHis EQuiPmENt is  
PlacED iNto sErVicE aND PErioDicallY  
tHErEaftEr. ProcEDurEs usED iN  
*
Control system interconnections between the transfer  
switch and generator consist of N1 and N2, and leads  
23, 15B and 0. Control system interconnection leads  
must be run in a conduit that is separate from the AC  
power leads. Recommended wire gauge size depends  
on the length of the wire:  
GasEous fuEl lEaKaGEtEsts must  
comPlY strictlY WitH aPPlicaBlE fuEl  
Gas coDEs. Do Not usE flamE or aNY  
sourcE of HEattotEst for Gas lEaKs.  
No Gas lEaKaGE is PErmittED. lP Gas is  
HEaViErtHaN air aNDtENDsto sEttlE iN  
loW arEas. Natural Gas is liGHtErtHaN  
air aNDtENDsto sEttlE iN HiGH PlacEs.  
EVENtHE sliGHtEst sParK caN iGNitE  
tHEsE fuEls aND causE aN EXPlosioN.  
max. cable length  
35 feet (10.67m)  
recommended Wire size  
No. 16 AWG.  
60 feet (I8.29m)  
No. 14 AWG.  
90 feet (27.43m)  
No. 12 AWG.  
Use of a flexible length of hose between the genera-  
tor fuel line connection and rigid fuel lines is required.  
This will help prevent line breakage that might be  
caused by vibration or if the generator shifts or settles.  
The flexible fuel line must be approved for use with  
gaseous fuels.  
GroundinG the Generator  
The National Electric Code requires that the frame  
and external electrically conductive parts of the gen-  
erator be property connected to an approved earth  
ground. Local electrical codes may also require prop-  
er grounding of the unit. For that purpose, a ground-  
ing lug is attached to the unit. Grounding may be  
accomplished by attaching a stranded copper wire of  
the proper size to the generator grounding lug and to  
an earth-driven copper or brass grounding-rod (elec-  
trode). Consult with a local electrician for grounding  
requirements in your area.  
Flexible fuel line should be kept as straight as possi-  
ble between connections. The bend radius for flexible  
fuel line is nine (9) inches. Exceeding the bend radius  
can cause the fittings to crack.  
the tranSFer SWitch / load center  
A transfer switch is required by electrical code, to pre-  
vent electrical feedback between the utility and stand-  
by power sources, and to transfer electrical loads from  
one power supply to another safely.  
the Fuel Supply  
Units with air-cooled engines were operated, tested  
and adjusted at the factory using natural gas as a  
fuel. These air-cooled engine units can be converted  
to use LP (propane) gas by making a few adjustments  
for best operation and power.  
TRANSFER SWITCHES:  
Instructions and information on transfer switches may  
be found in Part 3 of this manual.  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.2  
iNstallatioN Basics  
GENERAL INFORMATION  
Part 1  
Figure 1. Typical Installation  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.2  
iNstallatioN Basics  
GENERAL INFORMATION  
Part 1  
poWer Source and load lineS  
SyStem control interconnectionS  
The utility power supply lines, the standby (genera-  
tor) supply lines, and electrical load lines must all be  
connected to the proper terminal lugs in the transfer  
switch. The following rules apply: In 1-phase systems  
with a 2-pole transfer switch, connect the two utility  
source hot lines to Transfer Switch Terminal Lugs N1  
and N2. Connect the standby source hot lines (E1,  
E2) to Transfer Switch Terminal Lugs E1 and E2.  
Connect the load lines from Transfer Switch Terminal  
Lugs T1 and T2 to the electrical load circuit. Connect  
UTILITY, STANDBY and LOAD neutral lines to the  
neutral block in the transfer switch.  
Home standby generators are equipped with a termi-  
nal board identified with the following terminals: (a)  
UTILITY 1, (b) UTILITY 2, (c) 23, and (d) 15B. Load  
centers house an identically marked terminal board.  
When these four terminals are properly interconnect-  
ed, dropout of utility source voltage below a preset  
value will result in automatic generator startup and  
transfer of electrical loads to the “Standby” source.  
On restoration of utility source voltage above a preset  
value will result in retransfer back to that source and  
generator shutdown.  
natural GaS Fuel interconnectionS  
5-7” WC REGULATOR  
TO HOUSEHOLD  
GAS METER CAPABLE  
OF PROVIDING NATURAL GAS  
FUEL FLOW OF:  
140,000 (7 kW)  
156,000 (9 kW)  
215,000 (12 kW)  
220,000 (13 kW)  
261,000 (16 kW)  
294,000 (18 kW)  
BTU/HOUR  
SAFETY  
SHUT OFF  
VALVE  
0000001  
+HOUSEHOLD APPLIANCES  
(BASED ON 1000 BTU/CU FT)  
GAS MAIN  
2-5 PSI  
Figure 2. Proper Fuel Installation  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1.3  
non-PrePackaged interconnectionS  
General information  
Part 1  
Discussion:  
3. Using the following diagram and UL approved wire nuts  
connect the following wires together. Wire 0 will not be  
utilized for this setup.  
on the current model air-cooled generators Wire 194  
was changed to 15B. Wire 15B is still utilized for posi-  
tive voltage for the transfer relay and Wire 23 is still the  
control ground for transferring the generator. By follow-  
ing the procedures below it is possible to connect new  
product with Wire 15B to old or current product that  
still utilize Wire 194, such as an rts switch.  
CONTROL WIRES FROM  
TRANSFER SWITCH  
N1 (BLU)  
N2 (YEL)  
23 (BRN)  
194 (ORG)  
N1 (YEL)  
N2 (YEL)  
23 (WHT)  
15B (RED)  
0 (BLK)  
ConneCt a pre-2008 load Center switCh to a  
Current or Future air-Cooled generator.  
ProceDure:  
1. Follow all instructions located in the Installation Manual  
that was supplied with the unit regarding mounting of the  
switch, junction box, and generator.  
note: when installing a standalone 5500 series  
generator, the battery charger will be located in the  
generator on the side of the control assembly.  
WIRE NUTS  
CONTROL WIRES FROM  
ENGINE GENERATOR  
2. Inside the Junction box between the generator and the  
transfer switch there will be 5 wires coming from the  
generator and 4 wires from the transfer switch.  
Figure 1. Wire Connections  
“08” & LATER HSB AIR-COOLED GENERATORS  
SINGLE & V-TWIN ENGINES  
PRE “08” LOAD CENTER  
TRANSFER SWITCH  
WIRE  
NUTS  
CONTROL WIRES FROM ENGINE GENERATOR  
CONTROL WIRES FROM TRANSFER SWITCH  
N1 (YEL)  
N2 (YEL)  
23 (WHT)  
15B (RED)  
0 (BLK)  
N1 (BLU)  
N2 (YEL)  
23 (BRN)  
194 (ORG)  
EXTERNAL CUSTOMER  
CONNECTION BOX  
INSTALL BATTERY CHARGER GENERAC P/N 0G8023  
Figure 2. Post 2008 HSB Interconnections  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.3  
NoN-PrEPacKaGED iNtErcoNNEctioNs  
GENERAL INFORMATION  
Part 1  
connect a 2008 and later load center SWitch  
to a pre-2008 air-cooled Generator.  
CONTROL WIRES FROM  
ENGINE GENERATOR  
PROCEDURE:  
N1 (BLU)  
N2 (YEL)  
23 (BRN)  
194 (ORG)  
N1 (YEL)  
N2 (YEL)  
23 (WHT)  
15B (RED)  
0 (BLK)  
1. Follow all instructions located in the Installation Manual  
that was supplied with the unit regarding mounting of the  
switch, junction box, and generator.  
note: When installing a standalone pre-2008 gen-  
erator, the battery charger will be located in the  
generator utilizing the 12 Vdc trickle charger.  
2. Inside the Junction box between the generator and the  
transfer switch there will be 4 wires coming from the  
generator and 5 wires from the transfer switch.  
3. Using the following diagram and UL approved wire nuts  
connect the following wires together. Wire 0 will not be  
utilized for this setup.  
CONTROL WIRES FROM  
TRANSFER SWITCH  
WIRE NUTS  
note: remove the battery charger from the trans-  
fer switch; it will not be utilized in the operation of  
the generator.  
Figure 3. Wire Connections  
PRE “08” HSB AIR-COOLED GENERATORS  
SINGLE & V-TWIN ENGINES  
“08” & LATER LOAD CENTER  
TRANSFER SWITCH  
WIRE  
NUTS  
CONTROL WIRES FROM ENGINE GENERATOR  
CONTROL WIRES FROM TRANSFER SWITCH  
N1 (YEL)  
N2 (YEL)  
23 (WHT)  
15B (RED)  
0 (BLK)  
N1 (BLU)  
N2 (YEL)  
23 (BRN)  
194 (ORG)  
EXTERNAL CUSTOMER  
CONNECTION BOX  
Figure 4. Pre-2008 HSB Interconnections  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.4  
PrEParatioN BEforE usE  
GENERAL INFORMATION  
Part 1  
All installed gaseous fuel piping must be purged and  
leak tested prior to initial start-up in accordance with  
local codes, standards and regulations.  
General  
The installer must ensure that the home standby gen-  
erator has been properly installed. The system must  
be inspected carefully following installation. All appli-  
cable codes, standards and regulations pertaining to  
such installations must be strictly complied with. In  
addition, regulations established by the Occupational  
Safety and Health Administration (OSHA) must be  
complied with.  
Fuel conSumption  
The fuel consumption rates are listed in the  
SPECIFICATIONS section at the front of this manual.  
BTU FLOW REqUIREMENTS - NATURAL GAS:  
Prior to initial startup of the unit, the installer must  
ensure that the engine-generator has been properly  
prepared for use. This includes the following:  
BTU flow required for each unit based on 1000 BTU  
per cubic foot.  
• An adequate supply of the correct fuel must be  
7 kW -  
9 kW -  
12 kW -  
13 kW -  
16 kW -  
18 kW -  
140,000 BTU/Hour  
156,000 BTU/Hour  
215,000 BTU/Hour  
220,000 BTU/Hour  
261,000 BTU/Hour  
294,000 BTU/Hour  
available for generator operation.  
• The engine must be properly serviced with the rec-  
ommended oil.  
Fuel requirementS  
With LP gas, use only the vapor withdrawal system.  
This type of system uses the vapors formed above  
the liquid fuel in the storage tank.  
DANGER  
The engine has been fitted with a fuel carburetion  
system that meets the specifications of the 1997  
California Air Resources Board for tamper-proof dual  
fuel systems. The unit will run on natural gas or LP  
gas, but it has been factory set to run on natural gas.  
Should the primary fuel need to be changed to LP  
gas, the fuel system needs to be reconfigured. See  
the Reconfiguring the Fuel System section for instruc-  
tions on reconfiguration of the fuel system.  
Gaseous fuels such as natural gas and liquid  
propane (lP) gas are highly explosive. Even  
the slightest spark can ignite such fuels and  
cause an explosion. No leakage of fuel is per-  
mitted. Natural gas, which is lighter than air,  
tends to collect in high areas. lP gas is heavi-  
er than air and tends to settle in low areas.  
$
Recommended fuels should have a Btu content of  
at least 1,000 Btus per cubic foot for natural gas; or  
at least 2,520 Btus per cubic foot for LP gas. Ask the  
fuel supplier for the Btu content of the fuel.  
note: a minimum of one approved manual shut-  
off valve must be installed in the gaseous fuel  
supply line. the valve must be easily accessible.  
local codes determine the proper location.  
Required fuel pressure for natural gas is 5 inches to  
7 inches water column (0.18 to 0.25 psi); and for liq-  
uid propane, 10 inches to 12 inches of water column  
(0.36 to 0.43 psi).  
reconFiGurinG the Fuel SyStem  
note: all pipe sizing, construction and layout  
must comply with nFpa 54 for natural gas applica-  
tions and nFpa 58 for liquid propane applications.  
once the generator is installed, verify that the  
fuel pressure neVer drops below four (4) inches  
water column for natural gas or 10 inches water  
column for liquid propane.  
8 kW, 410CC ENGINE:  
To reconfigure the fuel system from NG to LP, follow  
these steps (Figure 1):  
note: the primary regulator for the propane sup-  
ply is not included with the generator. a fuel  
pressure of 10 to 12 inches of water column (0.36  
to 0.43 psi) to the fuel inlet of the generator must  
be supplied.  
Prior to installation of the generator, the installer  
should consult local fuel suppliers or the fire marshal  
to check codes and regulations for proper installation.  
Local codes will mandate correct routing of gaseous  
fuel line piping around gardens, shrubs and other  
landscaping to prevent any damage.  
1. Turn off the main gas supply (if connected).  
2. Open the roof and remove the door.  
3. Remove the battery (if installed).  
Special considerations should be given when install-  
ing the unit where local conditions include flood-  
ing, tornados, hurricanes, earthquakes and unstable  
ground for the flexibility and strength of piping and  
their connections.  
4. Locate the plastic T-handle fuel selector in the poly bag  
supplied with the generator.  
Use an approved pipe sealant or joint compound on  
all threaded fitting.  
5. Locate the selector knob on the air box cover, behind  
the yellow air filter door and power bulge. The unit  
comes from the factory in the NG (Natural Gas) position.  
Grasping the T-handle, insert the pin end into the hole  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.4  
PrEParatioN BEforE usE  
GENERAL INFORMATION  
Part 1  
in the selector knob and pull out to overcome spring  
pressure and then twist clockwise 90 degrees and allow  
the selector to return in once aligned with the LP (Liquid  
Propane) position.  
FUEL SELECTION  
LEVER -  
6. Save this tool with the Owner's Manual.  
“OUT” POSITION FOR  
LIQUID PROPANE  
(VAPOR) FUEL  
7. Install the battery, door and close the roof.  
8. Reverse the procedure to convert back to natural gas.  
Figure 3. 10 kW, GT-530 (Inlet Hose Slid Back)  
1. Open the roof.  
2. for 10 kW units: Loosen clamp and slide back the  
air inlet hose.  
• Slide fuel selector on carburetor out towards the  
back of the enclosure (Figures 2 and 3).  
• Return the inlet hose and tighten clamp securely.  
for 12, 14, 16, 17 and 20 kW units: remove the air  
cleaner cover.  
• Slide the selector lever out towards the back of the  
enclosure (Figures 4 and 5).  
Figure 1. Demand Regulator  
10, 12, 14, 16, 17 AND 20 kW, V-TWIN ENGINES:  
• Return the air cleaner cover and tighten the two  
thumb screws.  
To reconfigure the fuel system from NG to LP, follow  
these steps:  
3. Close the roof.  
note: the primary regulator for the propane sup-  
ply is not included with the generator. a fuel  
pressure of 10 to 12 inches of water column (0.36  
to 0.43 psi) to the fuel inlet of the generator muSt  
Be Supplied.  
4. Reverse the procedure to convert back to natural gas.  
FUEL SELECTION  
LEVER -  
“IN” POSITION FOR  
NATURAL GAS  
FUEL SELECTION  
LEVER -  
“IN” POSITION FOR  
NATURAL GAS  
Figure 4. 12/14/16/17/20 kW, GT-990/GT-999  
(Airbox Cover Removed)  
Figure 2. 10 kW, GT-530 (Inlet Hose Slid Back)  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.4  
PrEParatioN BEforE usE  
GENERAL INFORMATION  
Part 1  
enGine oil recommendationS  
All oil should meet minimum American Petroleum  
Institute (API) Service Class SJ, SL or better. Use  
no special additives. Select the oil's viscosity grade  
according to the expected operating temperature.  
FUEL SELECTION  
LEVER -  
“OUT” POSITION FOR  
LIQUID PROPANE  
(VAPOR) FUEL  
• SAE 30 è Above 32° F  
• 10W-30 è Between 40° F and -10° F  
• Synthetic 5W-30 è 10° F and below  
Engine crankcase oil capacities for the engines cov-  
ered in this manual can be found in the specifications  
section at the beginning of the book.  
any attempt to crank or start the engine  
before it has been properly serviced with  
the recommended oil may result in an  
*
engine failure.  
Figure 5. 12/14/16/17/20 kW, GT-990/GT-999  
(Airbox Cover Removed)  
SAE 30  
10W-30  
Synthetic 5W-30  
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.5  
tEstiNG, clEaNiNG aND DrYiNG  
GENERAL INFORMATION  
Part 1  
meterS  
meaSurinG ac VoltaGe  
Devices used to measure electrical properties are  
called meters. Meters are available that allow one  
to measure (a) AC voltage, (b) DC voltage, (c) AC  
frequency, and (d) resistance In ohms. The following  
apply:  
An accurate AC voltmeter or a VOM may be used to read  
the generator’s AC output voltage. The following apply:  
1. Always read the generator’s AC output voltage only at  
the unit’s rated operating speed and AC frequency.  
To measure AC voltage, use an AC voltmeter.  
To measure DC voltage, use a DC voltmeter.  
• Use a frequency meter to measure AC frequency In  
“Hertz” or “cycles per second”.  
2. The generator’s Voltage Regulator can be adjusted for  
correct output voltage only while the unit is operating at  
its correct rated speed and frequency.  
3. Only an AC voltmeter may be used to measure AC  
voltage. DO NOT USE A DC VOLTMETER FOR THIS  
PURPOSE.  
• Use an ohmmeter to read circuit resistance, in “ohms”.  
the Vom  
DaNGEr!: GENErators ProDucE HiGH  
aND DaNGErous VoltaGEs. coNtact  
WitH HiGH VoltaGE tErmiNals Will  
rEsult iN DaNGErous aND PossiBlY  
lEtHal ElEctrical sHocK.  
A meter that will permit both voltage and resistance to  
be read is the “volt-ohm-milliammeter” or “VOM”.  
*
Some VOMs are of the “analog” type (not shown).  
These meters display the value being measured by  
physically deflecting a needle across a graduated  
scale. The scale used must be Interpreted by the user.  
“Digital” VOM’s (Figure 1) are also available and are  
generally very accurate. Digital meters display the  
measured values directly by converting the values to  
numbers.  
meaSurinG dc VoltaGe  
A DC voltmeter or a VOM may be used to measure  
DC voltages. Always observe the following rules:  
note: Standard ac voltmeters react to the  
aVeraGe value of alternating current. When  
working with ac, the effective value is used. For  
that reason a different scale is used on an ac  
voltmeter.the scale is marked with the effective or  
rms” value even though the meter actually reacts  
to the average value. that is why the ac voltmeter  
will give an incorrect reading if used to measure  
direct current (dc).  
1. Always observe correct DC polarity.  
a. Some VOM’s may be equipped with a polarity  
switch.  
b. On meters that do not have a polarity switch,  
DC polarity must be reversed by reversing the  
test leads.  
2. Before reading a DC voltage, always set the meter to a  
higher voltage scale than the anticipated reading. If in  
doubt, start at the highest scale and adjust the scale  
downward until correct readings are obtained.  
3. The design of some meters is based on the “current  
flow” theory while others are based on the “electron  
flow” theory.  
a. The “current flow” theory assumes that direct  
current flows from the positive (+) to the nega-  
tive (-).  
b. The “electron flow” theory assumes that current  
flows from negative (-) to positive (+).  
note: When testing generators, the current flow”  
theory is applied. that is, current is assumed to  
flow from positive (+) to negative (-).  
meaSurinG ac Frequency  
The generator’s AC output frequency is proportional  
to Rotor speed. Generators equipped with a 2-pole  
Rotor must operate at 3600 rpm to supply a frequency  
of 60 Hertz. Units with 4-pole Rotor must run at 1800  
rpm to deliver 60 Hertz.  
Figure 1. Digital VOM  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.5  
tEstiNG, clEaNiNG aND DrYiNG  
GENERAL INFORMATION  
Part 1  
IN-LINE:  
meaSurinG current  
Alternatively, to read the current flow in AMPERES, an  
in-line ammeter may be used. Most Digital Volt Ohm  
Meters (VOM) will have the capability to measure  
amperes.  
CLAMP-ON:  
To read the current flow, in AMPERES, a clamp-on  
ammeter may be used. This type of meter indicates  
current flow through a conductor by measuring the  
strength of the magnetic field around that conductor.  
The meter consists essentially of a current trans-  
former with a split core and a rectifier type instrument  
connected to the secondary. The primary of the cur-  
rent transformer is the conductor through which the  
current to be measured flows. The split core allows  
the Instrument to be clamped around the conductor  
without disconnecting it.  
This usually requires the positive meter test lead to be  
connected to the correct amperes plug, and the meter  
to be set to the amperes position. Once the meter is  
properly set up to measure amperes the circuit being  
measured must be physically broken. The meter will be  
in-line or in series with the component being measured.  
In Figure 4 the control wire to a relay has been  
removed. The meter is used to connect and supply  
voltage to the relay to energize it and measure the  
amperes going to it.  
Current flowing through a conductor may be mea-  
sured safely and easily. A line-splitter can be used  
to measure current in a cord without separating the  
conductors.  
1.00  
A
BATTERY  
-
+
RELAY  
Figure 4. A VOM as an In-line meter  
Figure 2. Clamp-On Ammeter  
meaSurinG reSiStance  
The volt-ohm-milliammeter may be used to measure  
the resistance in a circuit. Resistance values can be  
very valuable when testing coils or windings, such as  
the Stator and Rotor windings.  
When testing Stator windings, keep in mind that the  
resistance of these windings is very low. Some meters  
are not capable of reading such a low resistance and  
will simply read CONTINUITY.  
If proper procedures are used, the following condi-  
tions can be detected using a VOM:  
• A “short-to-ground” condition in any Stator or Rotor  
winding.  
Figure 3. A Line-Splitter  
• Shorting together of any two parallel Stator windings.  
• Shorting together of any two isolated Stator windings.  
• An open condition in any Stator or Rotor winding.  
note: if the physical size of the conductor or  
ammeter capacity does not permit all lines to be  
measured simultaneously, measure current flow  
in each individual line. then, add the individual  
readings.  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.5  
tEstiNG, clEaNiNG aND DrYiNG  
GENERAL INFORMATION  
Part 1  
Component testing may require a specific resis-  
tance value or a test for INFINITY or CONTINUITY.  
Infinity is an OPEN condition between two electrical  
points, which would read as no resistance on a VOM.  
Continuity is a closed condition between two electrical  
points, which would be indicated as very low resis-  
tance or “ZERO” on a VOM.  
OHM:  
The OHM is the unit of RESISTANCE. In every circuit  
there is a natural resistance or opposition to the flow  
of electrons. When an EMF is applied to a complete  
circuit, the electrons are forced to flow in a single  
direction rather than their free or orbiting pattern. The  
resistance of a conductor depends on (a) its physical  
makeup, (b) its cross-sectional area, (c) its length,  
and (d) its temperature. As the conductor’s tempera-  
ture increases, its resistance increases in direct pro-  
portion. One (1) ohm of resistance will permit one (1)  
ampere of current to flow when one (1) volt of electro-  
motive force (EMF) is applied.  
electrical unitS  
AMPERE:  
The rate of electron flow in a circuit is represented  
by the AMPERE. The ampere is the number of elec-  
trons flowing past a given point at a given time. One  
AMPERE is equal to just slightly more than six thou-  
sand million billion electrons per second.  
ohm’S laW  
A definite and exact relationship exists between  
VOLTS, OHMS and AMPERES. The value of one can  
be calculated when the value of the other two are  
known. Ohm’s Law states that in any circuit the current  
will increase when voltage increases but resistance  
remains the same, and current will decrease when  
resistance Increases and voltage remains the same.  
With alternating current (AC), the electrons flow first  
in one direction, then reverse and move in the oppo-  
site direction. They will repeat this cycle at regular  
intervals. A wave diagram, called a “sine wave” shows  
that current goes from zero to maximum positive  
value, then reverses and goes from zero to maximum  
negative value. Two reversals of current flow is called  
a cycle. The number of cycles per second is called  
frequency and is usually stated in “Hertz”.  
VOLT:  
VOLTS  
(E)  
The VOLT is the unit used to measure electrical  
PRESSURE, or the difference in electrical potential  
that causes electrons to flow. Very few electrons will  
flow when voltage is weak. More electrons will flow as  
voltage becomes stronger. VOLTAGE may be consid-  
ered to be a state of unbalance and current flow as  
an attempt to regain balance. One volt is the amount  
of EMF that will cause a current of 1 ampere to flow  
through 1 ohm of resistance.  
AMPS  
(I)  
OHMS  
(R)  
Conductor of a  
Circuit  
Figure 6. Ohm’s Law  
oHm - Unit measuring resistance  
or opposition to flow  
If AMPERES is unknown while VOLTS and OHMS are  
known, use the following formula:  
VoltS  
+
ampereS =  
-
ohmS  
amPErE - Unit measuring rate of  
current flow (number of electrons  
past a given point)  
If VOLTS is unknown while AMPERES and OHMS are  
known, use the following formula:  
VoltS = ampereS x ohmS  
Volt - Unit measuring force or  
difference in potential  
If OHMS is unknown but VOLTS and AMPERES are  
known, use the following:  
causing current flow  
VoltS  
ampereS  
=
ohmS  
Figure 5. Electrical Units  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.5  
tEstiNG, clEaNiNG aND DrYiNG  
GENERAL INFORMATION  
Part 1  
The MINIMUM acceptable megger reading for stators  
may be calculated using the following formula:  
ViSual inSpection  
When it becomes necessary to test or troubleshoot a  
generator, it is a good practice to complete a thorough  
visual inspection. Remove the access covers and look  
closely for any obvious problems. Look for the following:  
MINIMUM INSULATION  
RESISTANCE  
(in “Megohms”)  
GENERATOR RATED VOLTS  
__________________________  
=
+1  
1000  
• Burned or broken wires, broken wire connectors,  
eXample: Generator is rated at 120 volts ac.  
divide “120” by “1000” to obtain “0.12”. then add  
“1” to obtain “1.12” megohms. minimum insulation  
resistance for a 120 Vac stator is 1.12 megohms.  
damaged mounting brackets, etc.  
• Loose or frayed wiring insulation, loose or dirty  
connections.  
• Check that all wiring is well clear of rotating parts.  
• Verify that the Generator properly connected for the  
correct rated voltage. This is especially important on  
new installations. See Section 1.2, “AC Connection  
Systems”.  
• Look for foreign objects, loose nuts, bolts and other  
fasteners.  
• Clean the area around the Generator. Clear away  
paper, leaves, snow, and other objects that might  
blow against the generator and obstruct its air  
openings.  
If the stator insulation resistance is less than the cal-  
culated minimum resistance, clean and dry the stator.  
Then, repeat the test. If resistance is still low, replace  
the stator.  
Use the Megger to test for shorts between isolated  
windings as outlined “Stator Insulation Tests”.  
Also test between parallel windings. See “Test  
Between Windings” on next page.  
TESTING ROTOR INSULATION (12-20kW):  
Apply a voltage of 500 volts across the rotor posi-  
tive (+) slip ring (nearest the rotor bearing), and  
a clean frame ground (i.e. the rotor shaft). DO  
NOT EXCEED 500 VOLTS AND DO NOT APPLY  
VOLTAGE LONGER THAN 1 SECOND. FOLLOW  
THE MEGGER MANUFACTURER’S INSTRUCTIONS  
CAREFULLY.  
inSulation reSiStance  
The insulation resistance of stator and rotor windings  
is a measurement of the integrity of the insulating  
materials that separate the electrical windings from  
the generator steel core. This resistance can degrade  
over time or due to such contaminants as dust, dirt,  
oil, grease and especially moisture. In most cases,  
failures of stator and rotor windings is due to a break-  
down in the insulation. And, in many cases, a low insu-  
lation resistance is caused by moisture that collects  
while the generator is shut down. When problems are  
caused by moisture buildup on the windings, they can  
usually be corrected by drying the windings. Cleaning  
and drying the windings can usually eliminate dirt and  
moisture built up in the generator windings.  
rotor miNimum iNsulatioN rEsistaNcE:  
1.5 megohms  
TESTING ROTOR INSULATION (8-10kW):  
No test available.  
cautioN: Before attempting to measure insu-  
lation resistance, first disconnect and isolate  
all leads of the winding to be tested. Electronic  
components, diodes, surge protectors, relays,  
voltage regulators, etc., can be destroyed if  
subjected to high megger voltages.  
*
the meGohmmeter  
GENERAL:  
A megohmmeter, often called a “megger”, consists of  
a meter calibrated in megohms and a power supply.  
Use a power supply of 500 volts when testing stators  
or rotors. DO NOT APPLY VOLTAGE LONGER THAN  
ONE (1) SECOND.  
TESTING STATOR INSULATION:  
All parts that might be damaged by the high meg-  
ger voltages must be disconnected before testing.  
Isolate all stator leads (Figure 8) and connect all of  
the stator leads together. FOLLOW THE MEGGER  
MANUFACTURER’S INSTRUCTIONS CAREFULLY.  
Use a megger power setting of 500 volts. Connect  
one megger test lead to the junction of all stator  
leads, the other test lead to frame ground on the sta-  
tor can. Read the number of megohms on the meter.  
Figure 7. One Type of Hi-Pot Tester  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.5  
tEstiNG, clEaNiNG aND DrYiNG  
GENERAL INFORMATION  
Part 1  
HI-POT TESTER:  
b. Plug the tester cord into a 120 volt AC wall  
socket and set its voltage selector switch to  
“1500 volts”.  
A “Hi-Pot” tester is shown in Figure 7. The model  
shown is only one of many that are commercially  
available. The tester shown is equipped with a voltage  
selector switch that permits the power supply voltage  
to be selected. It also mounts a breakdown lamp that  
will illuminate to indicate an insulation breakdown dur-  
ing the test.  
c. Turn the tester switch ON and observe the  
breakdown lamp on tester. DO NOT APPLY  
VOLTAGE LONGER THAN 1 SECOND. After  
one (1) second, turn the tester switch OFF.  
If the breakdown lamp comes on during the one-sec-  
ond test, the stator should be cleaned and dried. After  
cleaning and drying, repeat the insulation test. If, after  
cleaning and drying, the stator fails the second test,  
the stator assembly should be replaced.  
Stator inSulation reSiStance teSt  
(12-20 kW)  
6. Proceed to the Voltage Regulator. Each winding will be  
individually tested for a short to ground. Refer to Steps  
5a-5c and perform the same test on the following wires:  
GENERAL:  
Units with air-cooled engine are equipped with (a)  
dual stator AC power windings, and (b) excitation or  
DPE winding. Insulation tests of the stator consist of  
(a) testing all windings to ground, (b) testing between  
isolated windings, and (c) testing between parallel  
windings. Figure 8 is a pictorial representation of the  
various stator leads on units with air-cooled engines.  
Wire  
Number  
Winding  
22S  
11S  
6
Sense Lead Power  
Sense Lead Power  
Excitation  
TESTING ALL STATOR WINDINGS TO GROUND:  
2
Excitation  
1. Disconnect stator output leads 11 and 44 from the gen-  
erator main line circuit breaker.  
0
Ground  
4
Positive to Brush Ground  
2. Remove stator output leads 22 and 33 from the neutral  
connection and separate the two leads.  
TEST BETWEEN WINDINGS:  
3. Disconnect Wires 11 and 22 from Voltage Regulator.  
Ensure these wires are not touching any other compo-  
nents on the generator.  
1. Disconnect Stator Output Leads 11 and 44 from the  
generator main line circuit breaker.  
2. Remove Stator Output Leads 22 and 33 from the neutral  
connection and separate the two leads.  
2
6
3. Disconnect Wires 11, 22, 2, and 6 from Voltage  
Regulator. Ensure these wires are not touching any  
other components on the generator.  
11P  
11S (12-20 kW)  
22P  
4. Connect the red tester probe to Wire 2. Connect the  
black tester probe to Stator Lead 11. Refer to Steps 5a  
through 5c of “TESTING ALL STATOR WINDINGS TO  
GROUND” on previous page.  
22S (12-20 kW)  
33  
5. Repeat Step 4 between Wire 2 and Stator Lead 33.  
6. Repeat Step 4 between Stator Lead 11 and Stator Lead 33.  
44  
Figure 8. Stator Winding Leads  
Stator inSulation reSiStance teSt  
4. Connect the terminal ends of Wires 11, 22, 33 and 44  
together. Make sure the wire ends are not touching any  
part of the generator frame or any terminal.  
(8-10 kW)  
GENERAL:  
Units with air-cooled engine are equipped with (a)  
dual stator AC power windings, and (b) excitation or  
DPE winding. Insulation tests of the stator consist of  
(a) testing all windings to ground, (b) testing between  
isolated windings, and (c) testing between parallel  
windings. Figure 8 is a pictorial representation of the  
various stator leads on units with air-cooled engines.  
5. Connect the red test probe of the Hi-Pot tester to the  
joined terminal ends of stator leads 11, 22, 33 and 44.  
Connect the black tester lead to a clean frame ground  
on the stator can. With tester leads connected in this  
manner, proceed as follows:  
a. Turn the Hi-Pot tester switch OFF.  
Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.5  
tEstiNG, clEaNiNG aND DrYiNG  
GENERAL INFORMATION  
Part 1  
TESTING ALL STATOR WINDINGS TO GROUND:  
4. Plug the tester into a 120 volts AC wall socket and set  
the voltage switch to “1500 volts”.  
1. Disconnect Stator Output Leads 11 and 44 from the  
generator main line circuit breaker.  
5. Turn the tester switch “On” and make sure the pilot light  
has turned on.  
2. Disconnect Stator Output Leads 2 and 6 from the  
capacitor located on the end of the stator assembly.  
6. Observe the breakdown lamp, then turn the tester switch  
OFF. DO NOT APPLY VOLTAGE LONGER THAN ONE  
(1) SECOND.  
3. Remove Stator Output Leads 22 and 33 from the neutral  
connection and separate the two leads.  
If the breakdown lamp came on during the one (1)  
second test, cleaning and drying of the rotor may be  
necessary. After cleaning and drying, repeat the insu-  
lation breakdown test. If breakdown lamp comes on  
during the second test, replace the rotor assembly.  
4. Connect the terminal ends of Wires 11, 22, 33, and 44  
together. Make sure the wire ends are not touching any  
part of the generator frame or any terminal.  
5. Connect the red test probe of the Hi-Pot tester to the  
joined terminal ends of Stator Leads 11, 22, 33, and 44.  
Connect the black tester lead to a clean frame ground  
on the stator can. With tester leads connected in this  
manner, proceed as follows:  
a. Turn the Hi-Pot tester switch OFF.  
b. Plug the tester cord into a 120 volt AC wall  
socket and set its voltage selector switch to  
“1500 volts”.  
c. Turn the tester switch ON and observe the  
breakdown lamp on tester. DO NOT APPLY  
VOLTAGE LONGER THAN 1 SECOND. After  
one (1) second, turn the tester switch OFF.  
POSITIVE (+)  
TEST LEAD  
6. Connect the terminal ends of Wires 2 and 6 together.  
Make sure the wire ends are not touching any part of  
the generator frame or any terminal.  
Figure 9. Testing Rotor Insulation (12-20kW)  
7. Repeat Step 5.  
cleaninG the Generator  
If the breakdown lamp came on during the one (1)  
second test, cleaning and drying of the rotor may be  
necessary. After cleaning and drying, repeat the insu-  
lation breakdown test. If breakdown lamp comes on  
during the second test, replace the rotor assembly.  
Caked or greasy dirt may be loosened with a soft  
brush or a damp cloth. A vacuum system may be used  
to clean up loosened dirt. Dust and dirt may also be  
removed using dry, low-pressure air (25 psi maximum).  
cautioN: Do not use sprayed water to clean  
rotor inSulation reSiStance teSt  
the generator. some of the water will be  
retained on generator windings and terminals,  
and may cause very serious problems.  
*
(8-10 kW)  
No test available.  
dryinG the Generator  
rotor inSulation reSiStance teSt  
(12-20 kW)  
To dry a generator, proceed as follows:  
1. Open the generator main circuit breaker. NO  
ELECTRICAL LOADS MUST BE APPLIED TO THE  
GENERATOR WHILE DRYING.  
Before attempting to test rotor insulation, the brush  
holder must be completely removed. The rotor must  
be completely isolated from other components before  
starting the test. Attach all leads of all stator windings  
to ground.  
2. Disconnect all Wires 6 from the voltage regulator.  
1. Connect the red tester lead to the positive (+) slip ring  
(nearest the rotor bearing).  
3. Provide an external source to blow warm, dry air through  
the generator interior (around the rotor and stator wind-  
ings. DO NOT EXCEED 185° F. (85° C.).  
2. Connect the black tester probe to a clean frame ground,  
such as a clean metal part of the rotor shaft.  
4. Start the generator and let it run for 2 or 3 hours.  
3. Turn the tester switch OFF.  
5. Shut the generator down and repeat the stator and rotor  
insulation resistance tests.  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.6  
ENGiNE-GENErator ProtEctiVE DEVicEs  
GENERAL INFORMATION  
Part 1  
General  
oVerSpeed ShutdoWn  
Standby electric power generators will often run  
unattended for long periods of time. Such operating  
parameters as (a) battery voltage, (b) engine oil pres-  
sure, (c) engine temperature, (d) engine operating  
speed, and (e) engine cranking and startup are not  
monitored by an operator during automatic operation.  
Because engine operation will not be monitored, the  
use of engine protective safety devices is required to  
prevent engine damage in the event of a problem.  
During engine cranking and operation, the circuit  
board receives AC voltage and frequency signals  
from the ignition magneto, via Wire 18. Should the  
speed exceed approximately 72 Hz (4320 rpm),  
circuit board action will de-energize a “run relay”  
(mounted on the circuit board). The relay’s contacts  
will open, to terminate engine ignition and close a  
fuel shutoff solenoid. The engine will then shut down.  
This feature protects the engine-generator against  
damaging overspeeds.  
Generator engines mount several engine protec-  
tive devices. These devices work in conjunction with  
a circuit board, to protect the engine against such  
operating faults as (a) low battery, (b) low engine oil  
pressure, (c) high temperature, (d) overspeed, and  
(e) overcrank. On occurrence of any one or more of  
those operating faults, circuit board action will effect  
an engine shutdown.  
note: the circuit board also uses rpm sensing to  
terminate engine cranking.  
rpm SenSor Failure  
During cranking, if the board does not see a valid  
RPM signal within three (3) seconds, it will shut down  
and latch out on RPM sensor loss.  
loW Battery  
During running, if the RPM signal is lost for one full  
second the board will shut down the engine, wait 15  
seconds, then re-crank the engine.  
• If an RPM signal is not detected within the first three  
(3) seconds of cranking, the control board will shut  
the engine down and latch out on RPM sensor loss.  
• If the RPM signal is detected the engine will start  
and run normally. If the RPM signal is subsequently  
lost again, the control board will try one more re-  
crank attempt before latching out and flashing the  
overspeed LED or RPM Sensor Failure.  
The microprocessor will continually monitor the bat-  
tery voltage and turn on the Low Battery Warning  
if the battery voltage falls below 10.8 volts for one  
(1) minute. No other action is taken on a low battery  
condition. Low battery voltage is a non-latching alarm  
which will automatically clear if the battery voltage  
rises above 11.0 volts. Battery voltage is NOT moni-  
tored during the crank cycle.  
loW oil preSSure ShutdoWn  
See Figure 1. An oil pressure switch is mounted on  
the engine oil filter adapter. This switch has normally  
closed contacts that are held open by engine oil pres-  
sure during cranking and startup. Should oil pressure  
drop below approximately 5 psi, the switch contacts  
will close. On closure of the switch contacts, a Wire  
86 circuit from the circuit board will be connected to  
ground. Circuit board action will then de-energize  
a “run relay” (on the circuit board). The run relay’s  
normally open contacts will then open and a 12 volts  
DC power supply to a Wire 14 circuit will then be  
terminated. This will result in closure of a fuel shutoff  
solenoid and loss of engine ignition.  
LOW OIL SWITCH  
HIGH TEMP SWITCH  
OIL FILTER  
OIL  
DRAIN  
HOSE  
hiGh temperature SWitch  
This switch’s contacts (Figure 1) close if the tempera-  
ture should exceed approximately 144° C (293° F),  
initiating an engine shutdown. The generator will auto-  
matically restart and the fault on the generator control  
panel will reset once the temperature has returned to  
a safe operating level.  
Figure 1. Engine Protective Switches on an  
Air-Cooled Engine  
Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.6  
ENGiNE-GENErator ProtEctiVE DEVicEs  
GENERAL INFORMATION  
Part 1  
CRANkING CONDITIONS:  
oVercrank ShutdoWn  
The following notes apply during cranking cycle.  
This feature prevents the generator from damaging  
itself when it continually attempts to start and another  
problem, such as no fuel supply, prevents it from start-  
ing. The unit will crank and rest for a preset time limit.  
Then, it will stop cranking, and the LCD screen or the  
LED on the generator control panel will light indicating  
an overcrank failure. The AUTO-OFF-MANUAL switch  
will need to be set to OFF and then back to AUTO to  
reset the generator control board.  
1. Starter motor will not engage within five (5) seconds of  
the engine shutting down.  
2. The fuel output will not be energized with the starter.  
3. The starter and magneto outputs will be energized  
together.  
4. Once the starter is energized the control board will begin  
looking for engine rotation. If it does not see an RPM  
signal within three (3) seconds it will shut down and  
latch out on RPM sensor loss.  
note: if the fault is not repaired, the overcrank  
feature will continue to activate.  
The system will control the cyclic cranking as follows:  
16 second crank, seven (7) second rest, 16 second  
crank, seven (7) second rest followed by three (3)  
additional cycles of seven (7) second cranks followed  
by seven (7) second rests.  
5. Once the control board sees an RPM signal it will  
energize the fuel solenoid, drive the throttle open and  
continue the crank sequence.  
CHOkE OPERATION:  
6. Starter motor will disengage when speed reaches  
starter dropout.  
1. The 990/999cc engines have an electric choke in the  
air box that is automatically controlled by the electronic  
control board.  
7. If the generator does not reach 2200 RPM within 15  
seconds, re-crank cycle will occur.  
2. The 530cc engines have an electric choke on the divider  
panel air inlet hose that is automatically controlled by  
the electronic control board.  
8. If engine stops turning between starter dropout and 2200  
RPM, the board will go into a rest cycle for seven (7)  
seconds then re-crank (if additional crank cycles exist).  
3. The 410cc engines have a choke behind the air box that  
is automatically controlled by the electronic control board.  
9. Once started, the generator will wait for a hold-off  
period before starting to monitor oil pressure and oil  
temperature (refer to the Alarm Messages section for  
hold-off times).  
FAILURE TO START:  
This is defined as any of the following occurrences  
during cranking.  
10.During Manual start cranking, if the Mode switch is  
moved from the Manual position, the cranking stops  
immediately.  
1. Not reaching starter dropout within the specified crank  
cycle. Starter dropout is defined as four (4) cycles at  
1,500 RPM (1,800 RPM for 8 kW units).  
11.During Auto mode cranking, if the Utility returns, the  
cranking cycle does NOT abort but continues until  
complete. Once the engine starts, it will run for one (1)  
minute, then shut down.  
2. Reaching starter dropout, but then not reaching 2200  
RPM within 15 seconds. In this case the control board  
will go into a rest cycle for seven (7) seconds, then con-  
tinue the rest of the crank cycle.  
During a rest cycle the start and fuel outputs are de-  
energized and the magneto output is shorted to ground.  
Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.7  
oPEratiNG iNstructioNs  
GENERAL INFORMATION  
Part 1  
control panel  
DaNGEr:WHEN tHE GENErator is  
iNstallED iN coNJuNctioN WitH aN  
automatic traNsfEr sWitcH, ENGiNE  
craNKiNG aND startuP caN occur at  
aNY timE WitHout WarNiNG (ProViDiNG  
tHE auto-off-maNual sWitcH is sEt to  
auto).to PrEVENt automatic startuP  
aND PossiBlE iNJurY tHat miGHt BE  
causED BY sucH startuP, alWaYs sEt  
tHE auto-off-maNual sWitcH to its  
off PositioN BEforE WorKiNG oN or  
arouND tHis EQuiPmENt.  
*
SYSTEM READY  
LOW BATTERY  
LOW OIL PRESSURE  
HIGH OIL TEMPERATURE  
OVERSPEED  
SET  
EXERCISE  
ECS  
ENTER  
RPM SENSOR LOSS  
OVERCRANK  
7.5 AMP FUSE:  
This fuse protects the DC control circuit (including the  
circuit board) against overload. If the fuse element  
has melted open due to an overload, engine cranking  
or running will not be possible. Should fuse replace-  
ment become necessary, use only an identical 7.5  
amp replacement fuse.  
8 kW UNITS  
10-20 kW UNITS  
Figure 1. Generator Control Panel  
SETTING THE EXERCISE TIMER:  
AUTO-OFF-MANUAL SWITCH:  
This generator is equipped with an exercise timer.  
Once it is set, the generator will start and exercise  
every seven days, on the day of the week and at the  
time of day specified. During this exercise period,  
the unit runs for approximately 12 minutes and then  
shuts down. Transfer of loads to the generator output  
does not occur during the exercise cycle unless utility  
power is lost.  
Use this switch to (a) select fully automatic operation,  
(b) to crank and start the engine manually, and (c) to  
shut the unit down or to prevent automatic startup.  
1. AUTO position:  
a. Select AUTO for fully automatic operation.  
b. When AUTO is selected, circuit board will moni-  
tor utility power source voltage.  
8kW:  
c. Should utility voltage drop below a preset level  
and remain at such a low level for a preset time,  
circuit board action will initiate engine cranking  
and startup.  
A switch on the control panel (see Figure1) permits  
selection of the day and time for the system to exercise.  
At the chosen time, perform the following sequence to  
select the desired day and time of day the system will  
exercise. Remember seasonal time changes affect the  
exercise settings.  
d. Following engine startup, circuit board action  
will initiate transfer of electrical loads to the  
“Standby” source side.  
1. Verify that the AUTO-OFF-MANUAL switch is set to AUTO.  
e. On restoration of utility source voltage above  
a preset level, circuit board action will initiate  
retransfer back to the “Utility Source” side.  
2. Press and hold the “Set Exercise” switch for several  
seconds. All the red LED’s will stop flashing immediately  
and the generator will start.  
f. Following retransfer, circuit board will shut the  
engine down and will then continue to monitor  
utility source voltage.  
3. The generator will start and run for approximately 12  
minutes and then shut down. The exerciser is now set to  
run at this time of day each week.  
2. OFF Position:  
a. Set the switch to OFF to stop an operating engine.  
Example: If the “Set Exercise” pressed on Saturday  
afternoon at 2:00 p.m., the generator will start and  
exercise for approximately 12 minutes every Saturday  
at 2:00 p.m.  
b. To prevent an automatic startup from occurring,  
set the switch to OFF.  
3. MANUAL Position:  
note: the exerciser will only work in the auto  
mode and will not work unless this procedure  
is performed. the exerciser will need to be reset  
every time the 12 Volt battery is disconnected and  
then reconnected, and when the fuse is removed  
and/or replaced.  
a. Set switch to MANUAL to crank and start unit  
manually.  
b. Engine will crank cyclically and start (same as  
automatic startup, but without transfer). The unit  
will transfer if utility voltage is not available.  
Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.7  
oPEratiNG iNstructioNs  
GENERAL INFORMATION  
Part 1  
10-20 kW – INSTALLATION ASSISTANT:  
manual tranSFer to “StandBy” and  
manual Startup  
Upon first power up of the generator, the display inter-  
face will begin an installation assistant. The assistant  
will prompt the user to set the minimum settings to  
operate. These settings are simply: Current Date/Time  
and Exercise Day/Time. The maintenance intervals  
will be initialized when the exercise time is entered for  
the first time (Figure 3.2).  
To transfer electrical loads to the “Standby” (generator)  
source and start the generator manually, proceed as  
follows:  
1. On the generator panel, set the AUTO-OFF-MANUAL  
switch to OFF.  
The exercise settings can be changed at any time via  
the "EDIT" menu (see Appendix, "Menu System").  
2. On the generator, set the main line circuit breaker to it’s  
OFF or “Open” position.  
If the 12 Volt battery is disconnected or the fuse  
removed, the Installation Assistant will operate upon  
power restoration. The only difference is the display  
will only prompt the customer for the current Time  
and Date.  
3. Turn OFF the power supply to the transfer switch, using  
whatever means provided (such as a utility source line  
circuit breaker).  
if the installer tests the generator prior to instal-  
lation, press the “enter” key to avoid setting  
up the exercise time. this will ensure that when  
the customer powers up the unit, he will still be  
prompted to enter an exercise time.  
4. Manually actuate the transfer switch main contacts to  
their “Standby” position, i.e., loads connected to the  
“Standby” power source side.  
note: For instructions on manual operation of  
transfer switches, see part 3.  
note:the exerciser will only work in the auto mode  
and will not work unless this procedure is performed.  
the current date/time will need to be reset every time  
the 12 Volt battery is disconnected and then recon-  
nected, and/or when the fuse is removed.  
5. On the generator panel, set the AUTO-OFF-MANUAL  
switch to MANUAL. The engine should crank and start.  
6. Let the engine warm up and stabilize for a minute or two  
at no-load.  
to Select automatic operation  
7. Set the generator main line circuit breaker to its “On”  
or “Closed” position. The generator now powers the  
electrical loads.  
The following procedure applies only to those instal-  
lations in which the air-cooled, automatic standby  
generator is installed in conjunction with a transfer  
switch. Transfer switches do not have an intelligence  
circuit of their own. Automatic operation on transfer  
switch and generator combinations is controlled by  
circuit board action.  
manual ShutdoWn and retranSFer  
Back to “utility”  
To select automatic operation when a transfer switch  
is installed along with a home standby generator,  
proceed as follows:  
To shut the generator down and retransfer electrical  
loads back to the UTILITY position, proceed as follows:  
1. Set the generator main line circuit breaker to its OFF or  
“Open” position.  
1. Check that the transfer switch main contacts are at  
their UTILITY position, i.e., the load is connected to the  
power supply. If necessary, manually actuate the switch  
main contacts to their UTILITY source side. See Part 3  
of this manual, as appropriate, for instructions.  
2. Let the generator run at no-load for a few minutes, to cool.  
3. Set the generator AUTO-OFF-MANUAL switch to OFF.  
Wait for the engine to come to a complete stop.  
2. Check that utility source voltage is available to transfer  
switch terminal lugs N1 and N2 (2-pole, 1-phase transfer  
switches).  
4. Turn off the utility power supply to the transfer switch  
using whatever means provided (such as a utility source  
main line circuit breaker)  
3. Set the generator AUTO-OFF-MANUAL switch to its  
AUTO position.  
5. Manually actuate the transfer switch to its UTILITY  
source side, i.e., load connected to the utility source.  
4. Actuate the generator main line circuit breaker to its “On”  
or “Closed” position. With the preceding Steps 1 through  
4 completed, a dropout in utility supply voltage below a  
preset level will result in automatic generator cranking  
and start-up. Following startup, the transfer switch will be  
actuated to its “Standby” source side, i.e., loads powered  
6. Turn on the utility power supply to the transfer switch,  
using whatever means provided.  
7. Set the generator AUTO-OFF-MANUAL switch to AUTO.  
by the standby generator.  
Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.8  
automatic oPEratiNG ParamEtErs  
GENERAL INFORMATION  
Part 1  
FAILURE TO START:  
introduction  
This is defined as any of the following occurrences  
during cranking.  
When the generator is installed in conjunction with  
a transfer switch, either manual or automatic opera-  
tion is possible. Manual transfer and engine startup,  
as well as manual shutdown and re-transfer are  
covered in Section 1.7. Selection of fully automatic  
operation is also discussed in that section. This  
section will provide a step-by-step description of the  
sequence of events that will occur during automatic  
operation of the system.  
1. Not reaching starter dropout within the specified crank  
cycle. Starter dropout is defined as four (4) cycles at  
1,000 RPM.  
2. Reaching starter dropout, but then not reaching 2200  
RPM within 15 seconds. In this case the control board  
will go into a rest cycle for seven (7) seconds, then  
continue the rest of the crank cycle.  
utility Failure  
During a rest cycle the start and fuel outputs are  
de-energized and the magneto output is shorted to  
ground.  
Initial Conditions: Generator in Auto, ready to run,  
load being supplied by utility source. When utility  
fails (below 65% of nominal), a 10 second (optionally  
programmable on the 17 and 20 kW only) line inter-  
rupt delay time is started. If the utility is still gone  
when the timer expires, the engine will crank and  
start. Once started, a five (5) second engine warmup  
timer will be initiated.  
CRANkING CONDITIONS:  
The following notes apply during cranking cycle.  
1. Starter motor will not engage within five (5) seconds of  
the engine shutting down.  
When the warm-up timer expires, the control will  
transfer the load to the generator. If the utility power  
is restored (above 75% of nominal) at any time from  
the initiation of the engine start until the generator  
is ready to accept load (5 second warm-up time has  
not elapsed), the controller will complete the start  
cycle and run the generator through its normal cool  
down cycle; however, the load will remain on the utility  
source.  
2. The fuel output will not be energized with the starter.  
3. The starter and magneto outputs will be energized  
together.  
4. Once the starter is energized the control board will begin  
looking for engine rotation. If it does not see an RPM  
signal within three (3) seconds it will shut down and  
latch out on RPM sensor loss.  
5. Once the control board sees an RPM signal it will  
energize the fuel solenoid, drive the throttle open and  
continue the crank sequence.  
crankinG  
The system will control the cyclic cranking as follows:  
16 second crank, seven (7) second rest, 16 second  
crank, seven (7) second rest followed by three (3)  
additional cycles of seven (7) second cranks followed  
by seven (7) second rests.  
6. Starter motor will disengage when speed reaches starter  
dropout.  
7. If the generator does not reach 2200 RPM within 15  
seconds, re-crank cycle will occur.  
CHOkE OPERATION:  
8. If engine stops turning between starter dropout and  
2200 RPM, the board will go into a rest cycle for seven  
(7) seconds then re-crank (if additional crank cycles  
exist).  
1. The 990/999cc engines have an electric choke in the  
air box that is automatically controlled by the electronic  
control board.  
2. The 530cc engines have an electric choke on the divider  
panel air inlet hose that is automatically controlled by  
the electronic control board.  
9. Once started, the generator will wait for a holdoff period  
before starting to monitor oil pressure and oil temperature  
(refer to the Alarm Messages section for hold-off times).  
3. The 410cc engines have a choke behind the air box  
that is automatically controlled by the electronic control  
board.  
10.During Manual start cranking, if the Mode switch is  
moved from the Manual position, the cranking stops  
immediately.  
11.During Auto mode cranking, if the Utility returns, the  
cranking cycle does NOT abort but continues until  
complete. Once the engine starts, it will run for one (1)  
minute, then shut down.  
Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 1.8  
automatic oPEratiNG ParamEtErs  
GENERAL INFORMATION  
Part 1  
load tranSFer  
The transfer of load when the generator is running is  
dependent upon the operating mode as follows:  
1. Manual  
• Will not transfer to generator if utility is present.  
• Will transfer to generator if utility fails (below 65% of  
nominal for 10 consecutive seconds.  
• Will transfer back when utility returns for 15 consec-  
utive seconds. The engine will continue to run until  
removed from the Manual mode.  
2. Auto  
• Will start and run if Utility fails for 10 consecutive  
seconds.  
• Will start a five (5) second engine warm-up timer.  
• Will not transfer if utility subsequently returns.  
• Will transfer to generator if utility is still not present.  
• Will transfer back to utility once utility returns (above  
75% of nominal) for 15 seconds.  
• Will transfer back to utility if the generator is shut  
down for any reason (such as the switch is in the  
OFF position or a shutdown alarm.  
• After transfer, will shut down engine after one (1)  
minute cool-down time.  
3. Exercise  
• Will not exercise if generator is already running in  
either Auto or Manual mode.  
• During exercise, the controller will only transfer if  
utility fails during exercise for 10 seconds, and will  
switch to Auto mode.  
utility reStored  
Initial Condition: Generator supplying power to cus-  
tomer load. When the utility returns (above 75% of  
nominal), a 15 second return to utility timer will start.  
At the completion of this timer, if the utility supply is  
still present and acceptable, the control will transfer  
the load back to the utility and run the engine through  
a one (1) minute cool down period and then shut  
down. If utility fails for three (3) seconds during this  
cool down period, the control will transfer load back to  
the generator and continue to run while monitoring for  
utility to return.  
Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
taBlE of coNtENts  
Part  
titlE  
PaGE#  
30  
2.1. Description and components  
2.2 operational analysis  
2.3 troubleshooting flow charts  
33  
35  
Part 2  
2.4 Diagnostic tests  
39  
ac GENErators  
air-cooled, automatic  
standby Generators  
2.1 Description and Components.......................... 32  
Introduction......................................................32  
Engine-Generator Drive System......................32  
The AC Generator............................................32  
Rotor Assembly................................................32  
Stator Assembly...............................................33  
Brush Holder And Brushes (12-20 kW) ...........34  
Other AC Generator Components ...................34  
2.2 Operational Analysis ....................................... 35  
Rotor Residual Magnetism...............................35  
Field Boost (12-20 kW Units) ..........................35  
Operation (8/10 kW).........................................36  
Operation (12-20 kW) ......................................36  
2.3 Troubleshooting Flowcharts............................. 37  
Test 1 – Check Main Circuit Breaker................41  
Test 2 – Check AC Output Voltage...................41  
Test 4 – Fixed Excitation Test/Rotor  
Amp Draw Test ....................................42  
Test 5 – Wire Continuity (12-20 kW) ................43  
Test 6 – Check Field Boost (12-20 kW) ...........44  
Test 7 – Testing The Stator With A Vom  
(12-20 kW)...........................................44  
Test 8 – Test Brushless Stator..........................45  
Test 9 – Check Capacitor.................................46  
Test 10 – Test DPE Winding on  
Brushless units....................................47  
Test 11 – Resistance Check Of Rotor Circuit  
(12-20 kW)...........................................48  
Test 12 – Check Brushes And Slip Rings  
(12-20 kW)...........................................48  
Problem 1 – Generator Produces Zero  
Voltage or Residual Voltage 12-20 kW.... 37-38  
Test 13 – Test Rotor Assembly(12-20 kW).......49  
Test 14 – Check AC Output Frequency............49  
Problem 2 – Generator Produces Zero  
Voltage or Residual Voltage 8/10 kW ............38  
Test 15 – Check and Adjust Engine Governor  
(Single Cylinder Units).........................49  
Problem 3 – Generator Produces  
Low Voltage at No-Load ................................39  
Test 16 – Check Stepper Motor Control  
(V-twin Engine Units)...........................50  
Problem 4 – Generator Produces  
High Voltage at No-Load ...............................39  
Test 17 – Check And Adjust Voltage  
Regulator (12-20 kW)..........................51  
Problem 5 – Voltage and Frequency Drop  
Excessively When Loads are Applied ...........40  
Test 18 – Check Voltage And Frequency  
Under Load..........................................52  
2.4 Diagnostic Tests .............................................. 41  
Introduction......................................................41  
Safety ............................................................41  
Test 19 – Check For Overload Condition...........52  
Test 20 – Check Engine Condition...................52  
Test 21 – Field Flash Alternator (8-10 kW) ......52  
Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.1  
DEscriPtioN & comPoNENts  
AC GENERATORS  
Part 2  
1), and mounted in an enclosure. Both the engine and  
generator rotor are driven at approximately 3600 rpm,  
to provide a 60 Hz AC output.  
introduction  
The air-cooled, automatic standby system is an easy  
to install, fully enclosed and self-sufficient electric  
power system. It is designed especially for homeown-  
ers, but may be used in other applications as well.  
On occurrence of a utility power failure, this high  
performance system will (a) crank and start automati-  
cally, and (b) automatically transfer electrical loads to  
generator AC output.  
the ac Generator  
Figure 1 shows the major components of the AC  
generator.  
The generator revolving field (rotor) is driven by an  
air-cooled engine at about 3600 rpm.  
rotor aSSemBly  
The generator may be used to supply electrical power  
for the operation of 120 and/or 240 volts, 1-phase, 60  
Hz, AC loads.  
12-20 kW:  
The 2-pole rotor must be operated at 3600 rpm to  
supply a 60 Hertz AC frequency. The term “2-pole”  
means the rotor has a single north magnetic pole and  
a single south magnetic pole. As the rotor rotates, its  
lines of magnetic flux cut across the stator assem-  
bly windings and a voltage is induced into the stator  
windings. The rotor shaft mounts a positive (+) and  
a negative (-) slip ring, with the positive (+) slip ring  
nearest the rear bearing carrier. The rotor bearing is  
pressed onto the end of the rotor shaft. The tapered  
rotor shaft is mounted to a tapered crankshaft and is  
held in place with a single through bolt.  
A 2-pole, “W/V-Type” transfer switch is offered (see  
Part 3). The transfer switch does not include an “intel-  
ligence circuit” of it’s own. Instead, automatic startup,  
transfer, running, retransfer and shutdown operations  
are controlled by a solid state circuit board in the  
generator control panel.  
enGine-Generator driVe SyStem  
The generator revolving field is driven by an air-  
cooled, horizontal crankshaft engine. The generator is  
directly coupled to the engine crankshaft (see Figure  
"8KW"  
"C"  
"D"  
0.8  
"12KW - 20KW"  
"D"  
ENGINE ADAPTOR  
"10KW"  
"8KW - 10KW"  
"C"  
"D"  
BRUSH HOLDER  
ASSEMBLY  
"B"  
"C"  
"D"  
STATOR  
9
"C"  
"B"  
"B"  
ROTOR  
ENGINE ADAPTOR  
"12KW - 20KW"  
BEARING CARRIER  
Figure 1. AC Generator Exploded View  
Page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.1  
DEscriPtioN & comPoNENts  
AC GENERATORS  
Part 2  
Stator aSSemBly  
SLIP RINGS  
The stator can houses and retains (a) dual AC power  
windings, and (b) excitation winding. A total of six (6)  
or eight (8) stator leads are brought out of the stator  
can as shown in Figure 4.  
The stator can is sandwiched between an engine  
adapter and a rear bearing carrier. It is retained in that  
position by four stator studs.  
2
BEARING  
6
11P  
11S (12-20 kW)  
22P  
Figure 2. The 2-Pole Rotor Assembly 12-20 kW  
8/10kW:  
Like the 12-20 kW rotor, the 8/10 kW 2-pole rotor must  
be operated at 3600 rpm to supply a 60 Hertz AC fre-  
quency. However, the 8/10kW rotor uses no slip rings.  
As the rotor rotates in the generator voltage is induced  
from the Excitation winding using a capacitor that is in  
turn excited by the rotor. A continuous loop of charging  
and discharging of the capacitor is maintained that  
acts as a voltage regulation system. The rotor bearing  
is pressed onto the end of the rotor shaft. The tapered  
rotor shaft is mounted to a tapered crankshaft and is  
held in place with a single through bolt.  
22S (12-20 kW)  
33  
44  
Figure 4. Stator Assembly Leads  
DIODE A  
COIL 1  
COIL 2  
BEARING  
DIODE B  
DIODE B  
DIODE A  
ANODE  
ANODE  
CATHODE  
CATHODE  
Figure 3. The 2-Pole Rotor Assembly 8/10kW  
Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.1  
DEscriPtioN & comPoNENts  
AC GENERATORS  
Part 2  
The regulator provides “over-voltage” protection, but  
does not protect against “under-voltage”. On occur-  
rence of an “over-voltage” condition, the regulator will  
“shut down” and complete loss Of excitation current  
to the rotor will occur. Without excitation current, the  
generator AC output voltage will drop to approximately  
one-half (or lower) of the unit’s rated voltage.  
BruSh holder and BruSheS  
(12-20 kW)  
The brush holder is retained to the rear bearing car-  
rier by means of two #10-32 x 9/16 Taptite screws. A  
positive (+) and a negative (-) brush are retained in  
the brush holder, with the positive (+) brush riding on  
the slip ring nearest the rotor bearing.  
Wire 4 connects to the positive (+) brush and Wire 0  
to the negative (-) brush. Wire 0 connects to frame  
ground. Rectified and regulated excitation current, as  
well as current from a field boost circuit, are delivered  
to the rotor windings via Wire 4, and the positive (+)  
brush and slip ring. The excitation and field boost cur-  
rent passes through the windings and to frame ground  
via the negative (-) slip ring and brush, and Wire 0.  
This current flow creates a magnetic field around the  
rotor having a flux concentration that is proportional to  
the amount of current flow.  
4
0
Figure 5. Typical Voltage Regulator  
A single red lamp (LED) glows during normal opera-  
tion. The lamp will become dim if excitation winding  
AC output diminishes. It will go out on occurrence of  
an open condition in the sensing AC output circuit.  
An adjustment potentiometer permits the stator AC  
power winding voltage to be adjusted. Perform this  
adjustment with the generator running at no-load, and  
with a frequency of 60 Hz  
+
-
At the stated no-load frequency, adjust to obtain a  
line-to-line AC voltage of 247-249 volts.  
MAIN LINE CIRCUIT BREAkER:  
Figure 4. Brush Holder and Brushes (12-20 kW)  
The main line circuit breaker protects the generator  
against electrical overload. See “Specifications” in  
front of manual for amp ratings.  
other ac Generator componentS  
Some AC generator components are housed in the  
generator control panel enclosure, and are not shown  
in Figure 1. These are (a) a voltage regulator, and (b)  
a main line circuit breaker.  
VOLTAGE REGULATOR (12-20 kW):  
A typical voltage regulator is shown in Figure 5.  
Unregulated AC output from the stator excitation  
winding is delivered to the regulator’s DPE terminals,  
via Wire 2 and Wire 6. The voltage regulator rectifies  
that current and, based on stator AC power winding  
sensing, regulates it. The rectified and regulated  
excitation current is then delivered to the rotor wind-  
ings from the positive (+) and negative (-) regulator  
terminals, via Wire 4 and Wire 0. Stator AC power  
winding “sensing” is delivered to the regulator “SEN”  
terminals via Wires 11 and 22.  
Page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.2  
oPEratioNal aNalYsis  
AC GENERATORS  
Part 2  
Field boost voltage is reduced from that of battery  
voltage by the resistor action and, when read with a  
DC voltmeter, will be approximately 9 or 10 volts DC.  
rotor reSidual maGnetiSm  
The generator revolving field (rotor) may be consid-  
ered to be a permanent magnet. Some “residual”  
magnetism is always present in the rotor. This residual  
magnetism is sufficient to induce a voltage into the  
stator AC power windings that is approximately 2-12  
volts AC.  
+12 VDC  
13  
PIN 5  
Field BooSt (12-20 kW)  
TO  
STARTER  
56  
FIELD  
BOOST  
RESISTOR  
FIELD BOOST CIRCUIT:  
DIODE  
When the engine is cranking, direct current flow is  
delivered from a circuit board to the generator rotor  
windings, via Wire 4.  
PIN 1  
STARTER  
CONTACTOR  
CRANk  
FIELD  
BOOST  
DIODE  
4
RELAY k1  
BASE  
TRANSISTOR  
The field boost system is shown schematically in  
Figure 2. Manual and automatic engine cranking  
is initiated by circuit board action, when that circuit  
board energizes a crank relay. Battery voltage is then  
delivered to field boost Wire 4 (and to the rotor), via  
a field boost resistor and diode. The crank relay, field  
boost resistor and diode are all located on the circuit  
board.  
FIELD  
BOOST  
TO  
CIRCUIT BOARD  
ROTOR  
Notice that field boost current is available only while  
the crank relay is energized, i.e., while the engine is  
cranking.  
Figure 2. Field Boost Circuit Schematic  
TO LOAD  
MLB = MAIN LINE  
MLB  
CIRCUIT BREAKER  
TO LOAD  
MLB  
MLB = MAIN LINE CIRCUIT BREAKER  
STATOR  
POWER  
STATOR  
POWER  
SENSING  
WINDING  
WINDING  
STATOR  
POWER  
WINDING  
STATOR  
POWER  
WINDING  
MAGNETIC  
FIELD  
FIELD BOOST FROM  
CONTROL LOGIC  
CIRCUIT BOARD  
ENGINE -  
DIRECT  
DRIVE  
MAGNETIC  
FIELD  
ROTOR  
ENGINE -  
DIRECT  
DRIVE  
MAGNETIC  
FIELD  
ROTOR  
VOLTAGE  
REGULATOR  
STATOR  
EXCITATION  
WINDING  
MAGNETIC  
FIELD  
STATOR  
EXCITATION  
WINDING  
CAPACITOR  
12-20 kW Units  
8/10 kW Units  
Figure 1. Operating Diagram of AC Generator  
Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.2  
oPEratioNal aNalYsis  
AC GENERATORS  
Part 2  
FIELD EXCITATION:  
operation (8/10 kW)  
An AC voltage is induced into the stator excitation  
(DPE) windings. The DPE winding circuit is complet-  
ed to the voltage regulator, via Wire 2 and Wire 6.  
Unregulated alternating current can flow from the wind-  
ing to the regulator.  
STARTUP:  
When the engine is started, residual magnetism from  
the rotor induces a voltage into (a) the stator AC  
power windings, and (b) the stator excitation or DPE  
windings. The capacitor on the DPE winding will be  
charged and then will discharge causing a voltage to  
be induced back into the rotor.  
The voltage regulator “senses” AC power winding out-  
put voltage and frequency via stator Wires 11 and 22.  
The regulator changes the AC from the excitation  
winding to DC. In addition, based on the Wires 11  
and 22 sensing signals, it regulates the flow of direct  
current to the rotor.  
FIELD EXCITATION:  
An AC voltage is induced into the stator excitation  
(DPE) windings. The DPE winding circuit is completed  
to the capacitor, via Wire 2 and Wire 6.  
The rectified and regulated current flow from the regu-  
lator is delivered to the rotor windings, via Wire 4, and  
the positive brush and slip ring. This excitation current  
flows through the rotor windings and is directed to  
ground through the negative (-) slip ring and brush,  
and Wire 0.  
The capacitor will charge at a rate that is dependant  
on the amount of voltage that is being induced into it.  
Once the capacitor is fully charged the voltage that  
it discharges is a constant voltage and will in-turn  
increase the size of the magnetic field of the rotor.  
The greater the current flow through the rotor windings,  
the more concentrated the lines of flux around the rotor  
become.  
The greater the current flow through the rotor windings,  
the more concentrated the lines of flux around the rotor  
become.  
The more concentrated the lines of flux around the  
rotor that cut across the stationary stator windings,  
the greater the voltage that is induced into the stator  
windings.  
The more concentrated the lines of flux around the  
rotor that cut across the stationary stator windings,  
the greater the voltage that is induced into the stator  
windings.  
Initially, the AC power winding voltage sensed by the  
regulator is low. The regulator reacts by increasing  
the flow of excitation current to the rotor until volt-  
age increases to a desired level. The regulator then  
maintains the desired voltage. For example, if voltage  
exceeds the desired level, the regulator will decrease  
the flow of excitation current. Conversely, if voltage  
drops below the desired level, the regulator responds  
by increasing the flow of excitation current.  
AC POWER WINDING OUTPUT:  
A regulated voltage is induced into the stator AC  
power windings. When electrical loads are connected  
across the AC power windings to complete the circuit,  
current can flow in the circuit.  
operation (12-20 kW)  
AC POWER WINDING OUTPUT:  
A regulated voltage is induced into the stator AC  
power windings. When electrical loads are connected  
across the AC power windings to complete the cir-  
cuit, current can flow in the circuit. The regulated  
AC power winding output voltage will be in direct  
proportion to the AC frequency. For example, on units  
rated 120/240 volts at 60 Hz, the regulator will try to  
maintain 240 volts (line-to-line) at 60 Hz. This type of  
regulation system provides greatly improved motor  
starting capability over other types of systems.  
STARTUP:  
When the engine is started, residual plus field boost  
magnetism from the rotor induces a voltage into  
(a) the stator AC power windings, and (b) the sta-  
tor excitation or DPE windings. In an “on-speed”  
condition, residual plus field boost magnetism are  
capable of creating approximately one-half the unit’s  
rated voltage.  
ON-SPEED OPERATION:  
As the engine accelerates, the voltage that is induced  
into the stator windings increases rapidly, due to the  
increasing speed at which the rotor operates.  
Page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.3  
trouBlEsHootiNG floWcHarts  
AC GENERATORS  
Part 2  
General  
Use the “Flow Charts” in conjunction with the detailed  
instructions in Section 2.4. Test numbers used in  
the flow charts correspond to the numbered tests in  
Section 2.4.  
The first step in using the flow charts is to correctly  
identify the problem. Once that has been done, locate  
the problem on the following pages. For best results,  
perform all tests in the exact sequence shown in the  
flow charts.  
Problem 1 - Generator Produces Zero Voltage or Residual Voltage  
(12-20 kW)  
TEST 1 - CHECK  
MAIN CIRCUIT  
BREAKER  
RESET TO  
“ON”  
OR REPLACE  
IF BAD  
RE-TEST  
TEST 4 - PERFORM  
FIXED EXCITATION /  
ROTOR AMP DRAW  
A
G
REPAIR  
OR REPLACE  
FUSES  
D
B
C
CHECK  
VOM  
FUSES  
GOOD  
TEST 11 -  
CHECK  
ROTOR  
TEST 7 - TEST  
STATOR  
GOOD  
RESISTANCE  
BAD  
PERFORM STATOR  
INSULATION  
RESISTANCE TEST  
-
BAD  
TEST 5 - WIRE  
CONTINUITY  
TEST 12 -  
CHECK  
BAD  
SECTION 1.4  
BRUSHES &  
SLIP RINGS  
BAD  
GOOD  
BAD  
GOOD  
REPAIR  
OR  
TEST 6 -  
FIELD BOOST  
REPLACE  
REPAIR  
OR  
REPLACE  
TEST 13 -  
TEST ROTOR  
ASSEMBLY  
BAD  
BAD  
REPAIR  
OR  
REPLACE  
THEN  
GOOD  
GOOD  
RETEST  
PERFORM ROTOR  
INSULATION  
RESISTANCE TEST  
-
BAD  
REPLACE  
VOLTAGE  
REGULATOR  
SECTION 1.4  
Page 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.3  
trouBlEsHootiNG floWcHarts  
AC GENERATORS  
Part 2  
Problem 1 - Generator Produces Zero Voltage or Residual Voltage  
(12-20 kW Continued)  
TEST 4 - PERFORM  
TEST 7 - TEST  
BAD  
FIXED EXCITATION /  
ROTOR AMP DRAW  
F
E
STATOR  
GOOD  
H
PERFORM STATOR  
INSULATION  
RESISTANCE TEST -  
SECTION 1.4  
TEST 13 -  
TEST ROTOR  
ASSEMBLY  
BAD  
BAD  
GOOD  
REPAIR  
OR  
GOOD  
REPLACE  
PERFORM ROTOR  
INSULATION  
RESISTANCE TEST -  
SECTION 1.4  
TEST 13 -  
TEST ROTOR  
ASSEMBLY  
BAD  
BAD  
BAD  
REPAIR  
OR  
REPLACE  
GOOD  
GOOD  
TEST 7 - TEST  
STATOR  
PERFORM ROTOR  
INSULATION  
BAD  
RESISTANCE TEST -  
SECTION 1.4  
GOOD  
GOOD  
PERFORM STATOR  
INSULATION  
RESISTANCE TEST -  
SECTION 1.4  
BAD  
RE-TEST  
TEST 4  
RE-TEST  
TEST 4  
GOOD  
Problem 2 - Generator Produces Zero Voltage or Residual Voltage  
(8/10 kW)  
TEST 9 -  
CHECK  
CAPACITOR  
TEST 1 - CHECK  
MAIN CIRCUIT  
BREAKER  
TEST 8 - TEST  
BRUSHLESS  
STATOR  
TEST 10 - TEST  
DPE WINDING  
ON  
GOOD  
GOOD  
BAD  
GOOD  
BAD  
BAD  
RESET TO  
“ON”  
REPLACE  
STATOR  
OR REPLACE  
IF BAD  
REPLACE  
STATOR  
REPLACE  
REPLACE  
CAPACITOR  
REPLACE  
ROTOR  
TEST 2 -  
CHECK AC  
OUTPUT  
BAD  
TEST 21 -  
FIELD FLASH  
ALTERNATOR  
STOP  
TESTING  
VOLTAGE  
GOOD  
Page 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.3  
trouBlEsHootiNG floWcHarts  
AC GENERATORS  
Part 2  
Problem 3 - Generator Produces Low Voltage at No-Load  
LOW -  
SINGLE CYLINDER  
UNITS  
TEST 15 - ADJUST  
ENGINE GOVERNOR  
TEST 2 - CHECK  
AC OUTPUT  
VOLTAGE  
TEST 14 - CHECK  
AC OUTPUT  
FREQUENCY  
LOW  
TEST 16 - CHECK  
STEPPER MOTOR  
CONTROL  
LOW -  
V-TWIN UNITS  
NO VOLTAGE  
12-20 kW UNITS  
8/10 kW UNITS  
GO TO TEST 4  
GO TO “PROBLEM 2”  
TEST 9 -  
CHECK  
8/10 kW UNITS  
CAPACITOR  
FREQUENCY AND  
FREQUENCY O.K.,  
BUT VOLTAGE LOW  
VOLTAGE O.K.  
TEST 17 - ADJUST  
12-20 kW UNITS  
VOLTAGE  
REGULATOR  
STOP  
TESTS  
VOLTAGE AND FREQUENCY O.K.  
FREQUENCY O.K.,  
BUT VOLTAGE IS  
STILL LOW  
GO TO “PROBLEM 1” FLOW CHART -  
START AT TEST 4 - F/E”  
12-20 kW UNITS  
GO TO “PROBLEM 2”  
8/10 kW UNITS  
Problem 4 - Generator Produces High Voltage at No-Load  
HIGH -  
SINGLE CYLINDER  
UNITS  
TEST 15 - ADJUST  
ENGINE GOVERNOR  
TEST 2 - CHECK  
AC OUTPUT  
VOLTAGE  
TEST 14 - CHECK  
AC OUTPUT  
FREQUENCY  
HIGH  
TEST 16 - CHECK  
STEPPER MOTOR  
CONTROL  
HIGH -  
V-TWIN UNITS  
TEST 9 -  
CHECK  
CAPACITOR  
8/10 kW UNITS  
FREQUENCY AND  
VOLTAGE O.K.  
FREQUENCY O.K.,  
BUT VOLTAGE HIGH  
TEST 17 - ADJUST  
VOLTAGE  
12-20 kW UNITS  
REGULATOR  
STOP  
TESTS  
VOLTAGE AND FREQUENCY O.K.  
FREQUENCY O.K.,  
BUT VOLTAGE IS  
STILL HIGH  
REPLACE DEFECTIVE  
VOLTAGE REGULATOR  
12-20 kW UNITS  
GO TO “PROBLEM 2”  
8/10 kW UNITS  
Page 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.3  
trouBlEsHootiNG floWcHarts  
AC GENERATORS  
Part 2  
Problem 4 - Voltage and Frequency Drop Excessively When Loads Are Applied  
IF RECONFIGURED TO LP GAS,  
VERIFY THAT PROPER  
PROCEDURE WAS FOLLOWED  
(REFER TO SECTION 1.3)  
TEST 18 - CHECK  
VOLTAGE AND  
FREQUENCY  
TEST 19 - CHECK  
FOR OVERLOAD  
CONDITION  
NOT  
OVERLOADED  
BOTH  
LOW  
UNDER LOAD  
OVERLOADED  
GOOD  
UNITS WITH  
UNITS WITH  
SINGLE  
V-TWIN  
CYLINDER  
REDUCE LOADS TO UNIT’S  
RATED CAPACITY  
ENGINES  
ENGINES  
DISCONTINUE  
TESTING  
TEST 16 - CHECK  
STEPPER MOTOR  
CONTROL  
GOOD  
BAD  
TEST 15 - CHECK AND  
ADJUST ENGINE  
GOVERNOR  
REPAIR OR REPLACE  
GOOD  
TEST 20 - CHECK  
ENGINE CONDITION  
REPLACE  
BAD  
BAD  
TEST 8 - TEST  
BRUSHLESS  
STATOR  
GOOD  
TEST 10 - TEST  
DPE WINDING  
GOOD  
8/10 kW UNITS  
GO TO “PROBLEM 18 -  
ENGINE STARTS HARD  
AND RUNS  
ROUGH/LACKS POWER”  
SECTION 4.3  
GOOD  
ENGINE  
CONDITION  
GOOD  
12-20 kW UNITS  
TEST 7 - CHECK  
STATOR AC  
POWER WINDINGS  
LOOK FOR A SHORTED  
CONDITION IN A  
CONNECTED LOAD OR  
IN ONE OF THE LOAD  
CIRCUITS  
GOOD  
BAD  
REPAIR OR REPLACE  
Page 40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
1. Set a volt-ohm-milliammeter (VOM) to its “R x 1” scale  
and zero the meter.  
introduction  
This section is provided to familiarize the service  
technician with acceptable procedures for the test-  
ing and evaluation of various problems that could be  
encountered on standby generators with air-cooled  
engine. Use this section of the manual in conjunction  
with Section 2.3, “Troubleshooting Flow Charts”. The  
numbered tests in this section correspond with those  
of Section 2.3.  
2. With the generator shut down, disconnect all wires from  
the main circuit breaker terminals, to prevent interaction.  
3. With the generator shut down, connect one VOM test  
probe to the Wire 11 terminal of the breaker and the  
other test probe to the Wire E1 terminal.  
4. Set the breaker to its “On” or “Closed” position. The VOM  
should read CONTINUITY.  
Test procedures in this section do not require the use  
of specialized test equipment, meters or tools. Most  
tests can be performed with an inexpensive volt-  
ohm-milliammeter (VOM). An AC frequency meter is  
required, where frequency readings must be taken. A  
clamp-on ammeter may be used to measure AC loads  
on the generator.  
5. Set the breaker to its OFF or “Open” position and the  
VOMshould indicate INFINITY.  
6. Repeat Steps 4 and 5 with the VOM test probes con-  
nected across the breaker’s Wire 44 terminal and the E2  
terminal.  
Testing and troubleshooting methods covered in this  
section are not exhaustive. We have not attempted to  
discuss, evaluate and advise the home standby ser-  
vice trade of all conceivable ways in which service and  
trouble diagnosis might be performed. We have not  
undertaken any such broad evaluation. Accordingly,  
anyone who uses a test method not recommended  
herein must first satisfy himself that the procedure or  
method he has selected will jeopardize neither his nor  
the product’s safety.  
RESULTS:  
1. If the circuit breaker tests good, go on to Test 2.  
2. If the breaker tests bad, it should be replaced.  
E2 TERMINAL  
E1 TERMINAL  
SaFety  
Service personnel who work on this equipment must  
be made aware of the dangers of such equipment.  
Extremely high and dangerous voltages are present  
that can kill or cause serious injury. Gaseous fuels are  
highly explosive and can be ignited by the slightest  
spark. Engine exhaust gases contain deadly carbon  
monoxide gas that can cause unconsciousness or  
even death. Contact with moving parts can cause seri-  
ous injury. The list of hazards is seemingly endless.  
OFF  
When working on this equipment, use common  
sense and remain alert at all times. Never work on  
this equipment while you are physically or mentally  
fatigued. If you don’t understand a component, device  
or system, do not work on it.  
WIRE 11  
TERMINAL  
WIRE 44  
TERMINAL  
teSt 1 – check main circuit Breaker  
DISCUSSION:  
Figure 1. Generator Main Circuit Breaker Test Points  
Often the most obvious cause of a problem is over-  
looked. If the generator main line circuit breaker is set  
to OFF or “Open”, no electrical power will be supplied  
to electrical loads. If loads are not receiving power,  
perhaps the main circuit breaker is open or has failed.  
teSt 2 – check ac output VoltaGe  
DISCUSSION:  
PROCEDURE:  
A volt-ohm-milliammeter (VOM) may be used to check  
the generator output voltage. Output voltage may be  
checked at the unit’s main circuit breaker terminals.  
Refer to the unit’s DATA PLATE for rated line-to-line  
and line-to-neutral voltages.  
The generator main circuit breaker is located on the  
control panel. If loads are not receiving power, make  
sure the breaker is set to “On” or “Closed”.  
If you suspect the breaker may have failed, it can be  
tested as follows (see Figure 1):  
Page 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
PROCEDURE:  
DaNGEr: usE EXtrEmE cautioN  
1. Disconnect Wire 4 from the voltage regulator, 3rd  
terminal from the top. See Figure 2.  
DuriNG tHis tEst.tHE GENErator Will  
BE ruNNiNG. HiGH aND DaNGErous  
VoltaGEs Will BE PrEsENt at tHE  
tEst tErmiNals. coNNEct mEtEr tEst  
clamPs to tHE HiGH VoltaGE tErmiNals  
WHilE tHE GENErator is sHut DoWN.  
staY clEar of PoWEr tErmiNals  
DuriNG tHE tEst. maKE surE mEtEr  
clamPs arE sEcurElY attacHED aND  
Will Not sHaKE loosE.  
*
2. Connect a jumper wire to the disconnected Wire 4 and  
to the 12 volt fused battery supply Wire 15B (located at  
TB1 terminal board).  
3. Set VOM to AC volts.  
4
4
22  
PROCEDURE:  
0
11  
1. With the engine shut down, connect the AC voltmeter  
test leads across the Wires 11 and 44 terminals of the  
generator main circuit breaker (see Figure 1). These  
connections will permit line-to-line voltages to be read.  
6
2
2. Set the generator main circuit breaker to its OFF or  
“Open” position. This test will be conducted with the  
generator running at no-load.  
3. Start the generator, let it stabilize and warm up for a  
minute or two.  
4. Take the meter reading. On 12-20 kW units the no-load  
voltage should be between 249-247 VAC. On 8-10 kW  
units the no-load voltage should be between 220-235 VAC.  
Figure 2. Voltage Regulator  
5. Shut the engine down and remove the meter test leads.  
4. Disconnect Wire 2 from the voltage regulator and con-  
nect one meter test lead to that wire. Disconnect Wire  
6 from the voltage regulator and connect the other  
meter test lead to that wire. Wires 2 and 6 are located  
at the bottom two terminals of the voltage regulator  
(see Figure 2).  
RESULTS:  
1. If Step 4 indicated proper voltages, discontinue testing.  
2. If any other readings were measured, refer back to flow  
chart.  
note: “residual” voltage may be defined as the  
voltage that is produced by rotor residual mag-  
netism alone. the amount of voltage induced into  
the stator ac power windings by residual volt-  
age alone will be approximately 2 to 16 volts ac,  
depending on the characteristics of the specific  
generator. if a unit is supplying residual voltage  
only, either excitation current is not reaching the  
rotor or the rotor windings are open and the exci-  
tation current cannot pass. on current units with  
air-cooled engine, “field boostcurrent flow is  
available to the rotor only during engine cranking.  
5. Set the AUTO-OFF-MANUAL switch to MANUAL. Once  
the engine starts, record the AC voltage.  
6. Set the AUTO-OFF-MANUAL switch to OFF. Reconnect  
Wire 2 and Wire 6.  
7. Disconnect Wire 11 from the voltage regulator and con-  
nect one meter test lead to that wire. Disconnect Wire  
22 from the voltage regulator and connect the other  
meter test lead to that wire (both wires are located at the  
top two terminals of the voltage regulator, see Figure 2).  
8. Set the AUTO-OFF-MANUAL switch to MANUAL. Once  
the engine starts, record the AC voltage.  
teSt 4 – FiXed eXcitation teSt/  
rotor amp draW teSt  
9. Set the AUTO-OFF-MANUAL switch to OFF. Reconnect  
Wire 11 and Wire 22.  
DISCUSSION:  
10.Set VOM to DC amperage.  
Supplying a fixed DC current to the rotor will induce a  
magnetic field in the rotor. With the generator running,  
this should create a proportional voltage output from  
the stator windings.  
11.Remove jumper lead connected to Wire 4 and Wire 15B.  
12.Connect one meter test lead to battery positive 12  
VDC supply Wire 15B, located at TB1 terminal board.  
Page 42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
Connect the other meter test lead to Wire 4 (still dis-  
connected from previous tests). Measure and record  
static rotor amp draw.  
13.Set the AUTO-OFF-MANUAL switch to the MANUAL  
position. Once the engine starts, repeat Step 12.  
Measure and record running rotor amp draw with the  
engine running.  
14.Set the AUTO-OFF-MANUAL switch to OFF. Reconnect  
Wire 4 to the voltage regulator.  
RESULTS:  
Refer to the chart on this page: “Results - Fixed  
Excitation Test/Rotor Amp Draw Test”.  
note: a calculated amp draw can be done by taking  
the battery voltage that is applied divided by the  
actual resistance reading of the rotor. a resistance  
reading can be taken by measuring ohms between  
Wires 4 and 0 at the voltage regulator.  
EXAMPLE:  
moDEl  
5517  
WIRE 2 & 6 VOLTAGE  
WIRE 11 & 22 VOLTAGE  
STATIC ROTOR AMP DRAW  
RUNNING ROTOR AMP DRAW  
87 VAC  
31 VAC  
1.0 AMP  
1.0 AMP  
These results match Column B in the chart. Refer  
back to Problem 1 Flow Chart and follow Letter B.  
teSt 5 – Wire continuity (12-20 kW)  
DISCUSSION:  
The voltage regulator receives unregulated alternating  
current from the stator excitation winding, via Wires 2  
and 6. It also receives voltage sensing from the sta-  
tor AC power windings, via Wires 11 and 22. The  
regulator rectifies the AC from the excitation winding  
and based on the sensing signals, regulates the DC  
current flow to the rotor. The rectified and regulated  
current flow is delivered to the rotor brushes via Wires  
4 (positive) and 0 (negative). This test will verify the  
integrity of Wire 0.  
PROCEDURE:  
1. Set VOM to its “R x 1” scale.  
2. Remove Wire 0 from the voltage regulator, 4th terminal  
from the top. Also voltage regulator is labeled (-) next to  
terminal.  
3. Connect one test lead to Wire 0, connect the other test  
lead to a clean frame ground. The meter should read  
CONTINUITY.  
RESULTS:  
If CONTINUITY was not measured, repair or replace  
the wire as needed.  
Page 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
6. Reconnect Wire 4.  
teSt 6 – check Field BooSt (12-20 kW)  
DISCUSSION:  
RESULTS:  
See “Field Boost Circuit” in Section 2.2. Field boost  
current (from the circuit board) is available to the  
rotor only while the engine is cranking. Loss of field  
boost output to the rotor may or may not affect power  
winding AC output voltage. The following facts apply:  
• A small amount of voltage must be induced into the  
DPE winding to turn the voltage regulator on.  
• If rotor residual magnetism is sufficient to  
induce a voltage into the DPE winding that is  
high enough to turn the voltage regulator on,  
regulator excitation current will be supplied  
even if field boost has failed. Normal AC output  
voltage will then be supplied.  
1. If normal field boost voltage is indicated in Step 6,  
replace the voltage regulator.  
2. If normal field boost voltage is NOT indicated in Step 6,  
check Wire 4 (between regulator and circuit board) for  
open or shorted condition. If wire is good, replace the  
circuit board.  
teSt 7 – teStinG the Stator With a Vom  
(12-20 kW)  
DISCUSSION:  
• If rotor residual magnetism has been lost or is not  
sufficient to turn the regulator on, and field boost  
has also been lost, excitation current will not be  
supplied to the rotor. Generator AC output voltage  
will then drop to zero or nearly zero.  
A Volt-OHM-Milliammmeter (VOM) can be used to test  
the stator windings for the following faults:  
• An open circuit condition  
• A “short-to-ground” condition  
• A short circuit between windings  
5.54 VDC  
note: the resistance of stator windings is very  
low. Some meters will not read such a low resis-  
tance, and will simply indicate continuity.  
recommended is a high quality, digital type meter  
capable of reading very low resistances.  
LINE  
LOAD  
WIRE 44 TEST POINT  
WIRE 11 TEST POINT  
Figure 3. Field Boost Test Points  
Figure 4. Test 7 Test Points  
PROCEDURE:  
PROCEDURE:  
1. Disconnect Wire 4 from the voltage regulator, third  
terminal from the top (see Figure 3).  
1. Isolate the generator from the transfer switch by dis-  
connecting the load wires from the main breaker inside  
the generator.  
2. Set a VOM to read DC volts.  
3. Connect the positive (+) VOM test probe to the terminal  
end of disconnected Wire 4.  
2. Disconnect Stator Leads 22 and 33 from the neutral  
connection and separate the leads.  
4. Connect the common (-) VOM test probe to the  
grounding lug.  
3. Disconnect and isolate Wires 2 and 6 and Wires 11 and 22  
from the voltage regulator.  
5. Crank the engine while observing the VOM reading.  
While the engine is cranking, the VOM should read  
approximately 4-6 Volts DC. When engine is not crank-  
ing, VOM should indicate “zero” volts (see Figure 3).  
4. Make sure all of the disconnected leads are isolated  
from each other and are not touching the frame during  
the test.  
Page 44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
TEST FOR A SHORT CIRCUIT BETWEEN WINDINGS:  
5. Turn the Main Breaker to the "ON" or CLOSED position.  
15. Connect one test lead to stator lead Wire 11 on the load  
side of the main circuit breaker. Connect the other test  
lead to stator lead Wire 33.  
6. Set a VOM to measure resistance.  
7. Connect one meter test lead to Wire 11 on the load side  
of the main breaker. Connect the other meter test lead  
to Wire 22 (power winding). Note the resistance read-  
ing and compare to the specifications in the front of this  
manual.  
a. The meter should read INFINITY.  
b. Any reading other than INFINITY indicates a  
short circuit between windings.  
16.Repeat Step 15 using stator lead Wire 11; Wire 6.  
17.Repeat Step 15 using stator lead Wire 33; Wire 6.  
8. Connect one test lead to stator lead Wire 44 on the load  
side of the main breaker. Connect the other test lead to  
stator lead Wire 33 (power winding). Note the resistance  
reading and compare to the specifications in the front of  
this manual.  
18.Repeat Step 15 using Wire 11 at the voltage regulator;  
Wire 6 at the voltage regulator.  
TEST CONTROL PANEL WIRES FOR CONTINUITY:  
note: Wire 11 and Wire 44 could be switched on  
the main breaker. if an inFinity reading is indi-  
cated try putting the meter leads on the other  
output terminal of the breaker. if inFinity is still  
read then an actual fault may exist.  
19.Connect one test lead to Wire 11 at the voltage regulator  
and the other test lead at stator lead Wire 11. Continuity  
should be measured.  
20.Connect one test lead to Wire 22 at the voltage regulator  
and the other test lead at stator lead Wire 22. Continuity  
9. Connect one test lead to Wire 22 at the voltage regula-  
tor. Connect the other test lead to Wire 11 at the voltage  
regulator (power winding sense leads). Note the resis-  
tance reading and compare to the specifications in the  
front of this manual.  
should be measured.  
RESULTS:  
1. Stator winding resistance values is a test of winding conti-  
nuity and resistance. If a very high resistance or INFINITY  
is indicated, the winding is open or partially open.  
TEST WINDINGS FOR A SHORT TO GROUND:  
10. Make sure all leads are isolated from each other and  
are not touching the frame.  
2. Testing for a “grounded” condition: Any resistance  
reading indicates the winding is grounded.  
11. Connect one test lead to a clean frame ground. Connect  
the other test lead to stator lead Wire 11 on the load  
side of the main circuit breaker.  
3. Testing for a “shorted” condition: Any resistance  
reading indicates the winding is shorted.  
a. The meter should read INFINITY.  
4. If the stator tests good and wire continuity tests good,  
perform “Insulation Resistance Test” in Section 1.5.  
b. Any reading other than INFINITY indicates a  
“short-to-ground” condition.  
5. If any test of wire continuity failed in the control panel,  
repair or replace the wire, terminal or pin connectors for  
that associated wire as needed.  
12. Repeat Step 11 using stator lead Wire 33.  
13.Repeat Step 11 using Wire 22 at the voltage regulator.  
14.Repeat Step 11 using Wire 6 at the voltage regulator.  
note: read Section 1.5, “testing, cleaning and  
drying” carefully. if the winding tests good, per-  
form an insulation resistance test. if the winding  
fails the insulation resistance test, clean and dry  
the stator as outlined in Section 1.5. then, repeat  
the insulation resistance test. if the winding fails  
the second resistance test (after cleaning and  
drying), replace the stator assembly.  
2
6
11P  
11S (12-20 kW)  
22P  
teSt 8 – teSt BruShleSS Stator  
22S (12-20 kW)  
33  
DISCUSSION:  
The brushless stator has three internal windings,  
two main power windings and a DPE winding. This  
test will ensure that there are no shorts between the  
power windings or shorts to ground.  
44  
A VOM meter can be used to test the stator windings  
for the following faults:  
Figure 5. Stator Assembly Leads  
Page 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
• An open circuit condition  
• A “short-to-ground” condition  
• A short circuit between windings  
note: Wire 11 and Wire 44 could be switched on  
the main breaker. if an inFinity reading is indi-  
cated try putting the meter leads on the other  
output terminal of the breaker. if inFinity is still  
read then an actual fault may exist.  
note: the resistance of stator windings is very low.  
Some meters will not read such a low resistance,  
and will simply indicate continuity. recommended  
is a high quality, digital type meter capable of read-  
ing very low resistances.  
TEST WINDINGS FOR A SHORT TO GROUND:  
7. Make sure all leads are isolated from each other and are  
not touching the frame.  
8. Connect one test lead to a clean frame ground. Connect  
the other test lead to stator lead Wire 11.  
PROCEDURE, 8 kW:  
1. Disconnect Stator Leads 11 and 44 from the main circuit  
breaker.  
a. The meter should read INFINITY.  
b. Any reading other than INFINITY indicates a  
“short to ground” condition.  
2. Disconnect Stator Leads 22 and 33 from the neutral  
connection separate the leads.  
9. Repeat Step 7 using stator lead 44  
3. Make sure all of the disconnected leads are isolated  
from each other and are not touching the frame during  
the test.  
TEST FOR A SHORT CIRCUIT BETWEEN WINDINGS:  
10.Connect one test lead to stator lead 11. Connect the  
other test lead to stator lead 33.  
4. Set a VOM to measure resistance.  
5. Connect one test lead to Stator Lead 11. Connect the  
other test lead to Stator Lead 22. Note the resistance  
reading and compare to the specifications in the front of  
this manual.  
a. The meter should read INFINITY.  
b. Any reading other that INFINITY indicates a  
short between windings.  
11.Repeat Step 10 using Wire 44.  
6. Connect one test lead to Stator Lead 33. Connect the  
other test lead to Stator Lead 44. Note the resistance  
reading and compare to the specifications in the front of  
this manual.  
RESULTS:  
1. Stator winding resistance values is a test of winding conti-  
nuity and resistance. If a very high resistance or INFINITY  
is indicated, the winding is open or partially open.  
PROCEDURE, 10 kW:  
2. Testing for a “grounded” condition: Any resistance  
reading indicated the winding is grounded.  
1. Isolate the generator from the transfer switch by dis-  
connecting the load wires from the main breaker inside  
the generator.  
3. Testing for a “shorted” condition: Any resistance reading  
indicated the winding is shorted.  
2. Disconnect Stator Leads 22 and 33 from the neutral  
connection and separate the leads.  
4. If stator tests good and wire continuity tests good, refer  
back to flow chart.  
3. Make sure all of the disconnected leads are isolated  
from each other and are not touching the frame during  
the test.  
teSt 9 – check capacitor  
4. Turn the Main Breaker to the "ON" or CLOSED position.  
DISCUSSION:  
5. Set a VOM to measure resistance.  
The brushless rotor system relies on the charging and  
discharging of a capacitor to induce voltage into the  
rotor and also to regulate voltage once 240 VAC is  
achieved. If the capacitor fails, only residual magnetism  
of the rotor will be measured at the Main Breaker.  
6. See Figure 4 for proper testing points. Connect one  
meter test lead to Wire 11 on the load side of the main  
breaker. Connect the other meter test lead to Wire 22  
(power winding). Note the resistance reading and com-  
pare to the specifications in the front of this manual.  
Danger:the capacitor may need to be dis-  
charged before testing. a capacitor can be  
discharged by crossing the terminals with  
a metal insulated screw driver.  
*
7. Connect one test lead to Stator Lead 44 on the load  
side of the main breaker. Connect the other test lead  
to Stator Lead 33 (power winding). Note the resistance  
reading and compare to the specifications in the front of  
this manual.  
Danger: use proper protective equipment  
when dealing with a capacitor that has  
exploded.  
*
Page 46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
PROCEDURE:  
a. A capacitor that has gone bad can have a  
tendency to explode. Use caution when deal-  
ing with an exploded capacitor, the gel from  
inside a capacitor can cause skin irritation.  
1. Consult the owner’s manual of the meter being used for  
directions on measuring capacitance. Figure 7 shows a  
typical meter and how to check capacitance.  
b. A capacitor is defective if the terminal connec-  
tions are loose on the canister.  
2. Connect the meter leads directly across the terminals of  
the capacitor. The rated µf (micro farad) of the capacitor  
is marked on the side of the canister.  
c. A capacitor is defective if it wobbles while sitting  
on a flat surface.  
d. If any of the above observations are observed,  
replace the capacitor.  
3. The meter should display the correct µf reading 5µf.  
If anything other than the indicated rating is displayed,  
replace the capacitor.  
teSt 10 – teSt dpe WindinG on  
BruShleSS unitS  
DISCUSSION:  
A DPE winding or Displaced Phase Excitation wind-  
ing is used to charge a capacitor that discharges and  
charges releasing a voltage that is induced into the  
rotor. If the DPE winding fails, only residual magnetism  
of the rotor will be measured at the Main Breaker.  
note: the resistance of stator windings is very  
low. Some meters will not read such a low resis-  
tance, and will simply indicate continuity.  
recommended is a high quality, digital type meter  
capable of reading very low resistances.  
Warning: the capacitor may need to be  
discharged before testing. a capacitor can  
be discharged by crossing the terminals  
with a metal insulated screw driver.  
*
Figure 6. Capacitor  
SET TO READ  
CAPACITANCE  
PROCEDURE:  
59.0 µf  
1. Disconnect Wire 2 and Wire 6 from the capacitor.  
2. Set VOM to measure resistance.  
3. Connect one meter lead to Wire 2 and connect the other  
meter lead to Wire 6.  
a. Refer to the specifications in the front of this  
manual for the correct resistance reading.  
+
-
4. Connect one meter lead to Wire 2 and connect the other  
meter lead to a clean frame ground, INFINITY should be  
measured.  
+ -  
5. Disconnect Wires 11 and 44 from the main line circuit  
breaker.  
CAPACITOR  
6. Disconnect Wire 22 and Wire 33 from the neutral connection  
note: isolate all main stator leads before proceeding.  
7. Connect one meter lead to Wire 2 and connect the other  
meter lead to Wire 11. INFINITY should be measured.  
Figure 7. Field Boost Test Points  
8. Repeat Step 7 using Wires 2 and 44.  
RESULTS:  
RESULTS:  
1. Refer back to flow chart  
1. Stator winding resistance values is a test of winding conti-  
nuity and resistance. If a very high resistance or INFINITY  
is indicated, the winding is open or partially open.  
Page 47  
2. Common observations can be made by visually  
inspecting the capacitor.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
2. Testing for a “grounded” condition: Any resistance  
reading indicated the winding is grounded.  
CONTINUITY should be measured. If INFINITY is  
measured repair or replace Wire 0 between the brush  
assembly and the voltage regulator.  
3. Testing for a “shorted” condition: Any resistance reading  
indicated the winding is shorted.  
4. If stator tests good and wire continuity tests good, refer  
back to flow chart.  
4
0
teSt 11 – reSiStance check oF  
rotor circuit (12-20 kW)  
DISCUSSION:  
To verify the zero current draw reading and measure  
the rotor circuit.  
+
-
PROCEDURE:  
1. Disconnect Wire 4 and Wire 0 from the voltage regulator,  
located third and fourth terminals from the top of the  
voltage regulator.  
Figure 8. Checking Brushes and Slip Rings  
3. Wire 4 from the positive (+) brush terminal connects to  
Wire 4 at the voltage regulator. Test this wire for an open  
condition. Remove Wire 4 from the brush assembly.  
Connect one meter test lead to Wire 4. Connect the  
other meter test lead to Wire 4 at the voltage regula-  
tor. CONTINUITY should be measured. If INFINITY is  
measured repair or replace Wire 4 between the brush  
assembly and the voltage regulator.  
2. Set VOM to measure resistance.  
3. Connect one test lead to Wire 4. Connect the other test  
lead to a clean frame ground. Note the resistance reading.  
Compare to specifications in the front of this manual.  
RESULTS:  
1. If the resistance reading is correct, check the VOM meter  
fuse and repeat Test 4.  
4. Connect one meter test lead to Wire 4 Connect the  
other meter test lead to frame ground. INFINITY should  
be measured. If CONTINUITY is measured a short  
to ground exists on Wire 4 repair or replace Wire 4  
between the brush assembly and the voltage regulator.  
2. If INFINITY or a high reading is measured on the VOM,  
refer back to flow chart.  
teSt 12 – check BruSheS and Slip  
rinGS (12-20 kW)  
5. If CONTINUITY was measured in Steps 5 and 6 proceed  
to Step 9.  
DISCUSSION:  
6. Disconnect Wire 0 and Wire 4 from the brush assembly.  
Remove the brush assembly from the bearing carrier.  
Inspect the brushes for excessive wear, or damage.  
The function of the brushes and slip rings is to provide  
for passage of excitation current from stationary compo-  
nents to the rotating rotor. Brushes are made of a spe-  
cial long lasting material and seldom wear out or fail.  
However, slip rings can develop a tarnish or film that  
can inhibit or offer a resistance to the flow of electric-  
ity. Such a non-conducting film usually develops during  
non-operating periods. Broken or disconnected wiring  
can also cause loss of excitation current to the rotor.  
7. Inspect the rotor slip rings. If they appear dull or tarnished,  
they may be polished with fine sandpaper. DO NOT USE  
METALLIC GRIT TO POLISH SLIP RINGS.  
8. If brush assembly and slip rings look good proceed to  
Test 13 (Test Rotor Assembly)  
PROCEDURE:  
9. Wire 0 connects from the voltage regulator in the control  
panel ground lug. Connect one meter test lead to Wire 0  
at the voltage regulator. Connect the other meter test lead  
to the ground terminal in the control panel. CONTINUITY  
should be measured. If INFINITY is measured repair or  
replace Wire 0 between the voltage regulator and the  
ground terminal.  
1. See Figure 8. Carefully inspect brush wires; make sure  
they are properly and securely connected.  
2. Wire 0 from the negative (-) brush terminal connects  
to Wire 0 at the voltage regulator. Test this wire for an  
open condition. Remove Wire 0 from the brush assem-  
bly. Connect one meter test lead to Wire 0. Connect  
the other test lead to Wire 0 at the voltage regulator.  
10.Remove Wire 4 from the voltage regulator.  
Page 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
RESULTS:  
rotor if it fails that test.Then, repeat the test. If the rotor  
fails the second insulation resistance test, it should be  
replaced.  
1. Repair, replace or reconnect wires as necessary.  
2. Replace any damaged slip rings or brush holder.  
3. Clean and polish slip rings as required.  
teSt 14 – check ac output Frequency  
teSt 13 – teSt rotor aSSemBly  
DISCUSSION:  
(12-20 kW)  
The generator AC frequency is proportional to the  
operating speed of the rotor. The 2-pole rotor will sup-  
ply a 60 Hertz AC frequency at 3600 rpm. The unit’s  
AC output voltage is proportional to the AC frequency.  
For example, a unit rated 240 volts (line-to-line) will  
supply that rated voltage (plus or minus 2 percent)  
at a frequency of 60 Hertz. If, for any reason, the  
frequency should drop to 30 Hertz, the line-to-line  
voltage will drop to a matching voltage of 120 volts  
AC. Thus, if the AC voltage output is high or low and  
the AC frequency is correspondingly high or low, the  
engine speed governor may require adjustment.  
DISCUSSION:  
A rotor having completely open windings will cause  
loss of excitation current flow and, as a result,  
generator AC output voltage will drop to “residual”  
voltage. A “shorted” rotor winding can result in a  
low voltage condition.  
PROCEDURE:  
I. Disconnect the brush wires or remove the brush holder,  
to prevent interaction.  
PROCEDURE:  
2. Set a VOM to measure resistance.  
1. Connect an accurate AC frequency meter across the  
Wires 11 and 44 terminals of the generator main line  
circuit breaker (see Figure 1, Section 2.4).  
3. Connect the positive (+) VOM test lead to the posi-  
tive (+) rotor slip ring (nearest the rotor bearing); and  
the common (-) test lead to the negative (-) slip ring.  
The meter should read rotor resistance. Compare to  
“Specifications,” in the front of this manual.  
2. Start the engine, let it stabilize and warm up at no-load.  
3. When engine has stabilized, read the frequency meter.  
The no-load frequency for single cylinder units should  
be about 62-63 Hertz. For V-Twin units, the no-load  
frequency should be about 60 Hertz.  
4. Connect the positive (+) VOM test lead to the positive (+)  
slip ring and the common (-) test lead to a clean frame  
ground. The meter should indicate INFINITY.  
RESULTS:  
RESULTS:  
1. If the AC frequency is high or low, go on to Test 15 for  
single cylinder units, or Test 16 for V-Twin units.  
1. Replace rotor assembly if it is open or shorted.  
2. If frequency is good, but voltage is high or low, go to  
Test 17.  
2. If rotor tests good, perform “Insulation Resistance Test”  
in Section 1.5.  
3. If frequency and voltage are both good, tests may be  
discontinued.  
SLIP RINGS  
teSt 15 – check and adjuSt enGine  
GoVernor (SinGle cylinder unitS)  
DISCUSSION:  
The generator AC frequency output is directly pro-  
portional to the speed of the rotor. A two-pole rotor  
(having a single north and a single south magnetic  
pole) will produce an AC frequency of 60 hertz at  
3600 RPM.  
BEARING  
The generator is equipped with a “voltage over fre-  
quency” type AC voltage regulator. The units AC  
output voltage is generally proportional to AC fre-  
quency. A low or high governor speed will result in a  
correspondingly low or high AC frequency and voltage  
output. The governed speed must be adjusted before  
any attempt to adjust the voltage regulator is made.  
Figure 9. The Rotor Assembly  
NOTE: Be sure to read Section 1.5, “Testing, Cleaning  
and Drying”, carefully. If the rotor tests good, try per-  
forming an insulation resistance test. Clean and dry the  
Page 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
teSt 16 – check Stepper motor  
control (V-tWin enGine unitS)  
SECONDARY  
ADJUST SCREW  
GOVERNOR  
SHAFT  
PROCEDURE:  
1. Remove air cleaner cover to access stepper motor.  
2. Physically grab the throttle and verify the stepper motor,  
linkage and throttle do not bind in any way, if any binding  
is felt repair or replace components as needed. Some  
resistance should be felt as the stepper motor moves  
through it’s travel.  
GOVERNOR  
CLAMP  
BOLT  
PRIMARY  
ADJUST  
SCREW  
3. Physically move the throttle to the closed position by  
pulling the stepper motor arm towards the idle stop. See  
Figures 11 and 12 (for 9/10 kW units) or Figure 13 (for  
12-20 kW Units).  
4. Place the AUTO-OFF-MANUAL switch to MANUAL and  
watch for stepper motor movement. It should move to  
the wide open position during cranking. Once the unit  
starts the stepper motor should move the throttle to a  
position to maintain 60 Hertz.  
Figure 10. Engine Governor Adjustment Single  
Cylinder Engines  
PROCEDURE  
(8 kW UNITS WITH DUAL GOVERNOR SPRINGS):  
5. If no movement is seen in Step 4 remove the control  
panel cover. Verify the six pin connector on the printed  
circuit board is seated properly, remove the connector  
and then replace it and test again. Verify the switches  
are correctly set.  
1. Loosen the governor clamp bolt (Figure 10).  
2. Hold the governor lever at its wide open throttle position,  
and rotate the governor shaft clockwise as far as it will  
go. Then, tighten the governor lever clamp bolt to 70  
inch-pounds (8 N-m).  
6. If problem continues the remove six pin connector from  
the printed circuit board. Set Volt meter to measure  
ohms. Carefully measure from the end of the six pin  
harness as follows:  
3. Start the generator; let it stabilize and warm up at  
no-load.  
4. Connect a frequency meter across the generators AC  
output leads.  
note: press down with the meter leads on the  
connectors exposed terminals, do not probe into  
the connector.  
5. Turn the primary adjust screw to obtain a frequency  
reading of 61.5 Hz. Turn the secondary adjust screw to  
obtain a frequency reading of 62.5 Hz.  
a. Connect one meter lead to Red, connect the  
remaining test lead to Orange, approximately  
10 ohms should be measured.  
b. Connect one meter lead to Red, connect the  
remaining test lead to Yellow, approximately 10  
ohms should be measured.  
6. When frequency is correct at no load, check the AC  
voltage reading. If voltage is incorrect, the voltage  
regulator may require adjustment.  
c. Connect one meter lead to Red, connect the  
remaining test lead to Brown, approximately 10  
ohms should be measured.  
RESULTS:  
1. If, after adjusting the engine governor, frequency and  
voltage are good, tests may be discontinued.  
d. Connect one meter lead to Red, connect the  
remaining test lead to Black, approximately 10  
ohms should be measured.  
2. If frequency is now good, but voltage is high or low, refer  
back to flow chart.  
e. Connect one meter lead to Red, connect the  
remaining test to the stepper motor case. No resis-  
tance should be measured INFINITY or Open.  
3. If engine was overspeeding, check linkage and throttle  
for binding. If no governor response is indicated refer to  
engine service manual.  
RESULTS:  
1. If the stepper motor fails any part of Step 6 replace the  
stepper motor.  
4. If engine appears to run rough and results in low fre-  
quency, proceed to Problem 18, Section 4.3.  
2. If the stepper motor passes all steps replace the Printed  
Circuit Board.  
Page 50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
STEPPER MOTOR  
BLACK  
BROWN  
YELLOW  
ORANGE  
RED  
EMPTY  
PULL ARM THIS  
DIRECTION TO  
Figure 14. Six Pin Connector Wire Colors  
CLOSE THROTTLE  
teSt 17 – check and adjuSt VoltaGe  
reGulator (12-20 kW)  
Figure 11. Throttle Positions 9/10 kW Units  
DISCUSSION:  
For additional information, refer to description and  
components Section 2.1.  
STEPPER MOTOR  
PROCEDURE (V-TWIN ENGINE UNITS):  
With the frequency at 60 Hertz, slowly turn the  
slotted potentiometer (Figure 15) until line voltage  
reads 247-249 volts.  
note:the access panel on top of the control panel  
must be removed to adjust the voltage regulator.  
PULL ARM THIS  
DIRECTION TO  
CLOSE THROTTLE  
note: the voltage regulator is housed in the  
back of the generator control panel. the regula-  
tor maintains a voltage in direct proportion to  
frequency at a 2-to-1 ratio. For example, at 60  
hertz, line-to-neutral voltage will be 120 volts.  
STEPPER MOTOR ARM  
Figure 12. Throttle Positions 9/10 kW Units  
PULL ARM THIS  
DIRECTION TO  
CLOSE THROTTLE  
Figure 15. Voltage Adjustment Potentiometer  
RESULTS:  
STEPPER MOTOR  
1. If the frequency and voltage are now good, discontinue tests.  
2. If frequency is now good but voltage is high or low, refer  
back to flow chart.  
STEPPER MOTOR ARM  
Figure 13. Throttle Positions 12-20 kW Units  
Page 51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
teSt 18 – check VoltaGe and  
Frequency under load  
teSt 20 – check enGine condition  
DISCUSSION:  
DISCUSSION:  
If engine speed and frequency drop excessively  
under load, the engine may be under-powered. An  
under-powered engine can be the result of a dirty air  
cleaner, loss of engine compression, faulty fuel set-  
tings, incorrect ignition timing, etc.  
It is possible for the generator AC output frequency  
and voltage to be good at no-load, but they may drop  
excessively when electrical loads are applied. This  
condition, in which voltage and frequency drop exces-  
sively when loads are applied, can be caused by (a)  
overloading the generator, (b) loss of engine power, or  
(c) a shorted condition in the stator windings or in one  
or more connected loads.  
PROCEDURE:  
For engine testing, troubleshooting and repair  
procedures refer to Problem 11 in Section 4.3.  
For further engine repair information refer to the  
PROCEDURE:  
appropriate engine service manuals  
.
1. Connect an accurate AC frequency meter and an AC  
voltmeter across the stator AC power winding leads.  
teSt 21 – Field FlaSh alternator  
2. Start the engine, let it stabilize and warm-up.  
(8-10 kW unitS)  
3. Apply electrical loads to the generator equal to the rated  
capacity of the unit.  
DISCUSSION:  
The alternator utilizes residual magnetism within the  
windings to charge the capacitor. If the generator has  
been sitting for a long period of time with no activity  
the residual magnetism could be lost within the rotor.  
Field flashing the rotor while connected in parallel with  
the capacitor will force a charge of electricity through  
the DPE winding. The voltage that is induced into the  
rotor will return and charge the capacitor enough to  
take over voltage regulation of the unit.  
4. Check the AC frequency and voltage.  
a. Single Cylinder Units: Frequency should not  
drop below approximately 58 Hertz. Voltage  
should not drop below about 230 volts.  
b. V-Twin Engine Units: Frequency should not drop  
below approximately 60 Hertz. Voltage should  
not drop below about 240 volts.  
note: it is crucial that the generator exercise once  
a week to help maintain this residual magnetism.  
RESULTS:  
1. If frequency and voltage drop excessively under load,  
refer back to flow chart.  
Warning: Please keep safety in mind while  
performing this test.  
*
1. Construct an energizing cord that is similar to that shown  
in Figure 17 and connect it as shown in Figure 18.  
2. If frequency and voltage under load are good, dis-  
continue tests.  
PROCEDURE:  
teSt 19 – check For oVerload  
2. Set the AUTO-OFF-MANUAL switch to the OFF position.  
condition  
Warning: Do Not energize the capacitor for  
more than 1 second at a time.  
DISCUSSION:  
*
An “overload” condition is one in which the generator  
rated wattage/amperage capacity has been exceed-  
ed. To test for an overload condition on an installed  
unit, the best method is to use an ammeter. See  
“Measuring Current” in Section 1.5.  
3. Momentarily turn on the energizing cord (one second).  
4. Disconnect the energizing cord from the capacitor.  
5. If the field flash was successful, the generator should  
now be producing approximately 240 VAC at the main  
circuit breaker of the generator when the AUTO-OFF-  
MANUAL is set to the MANUAL position.  
PROCEDURE:  
Use a clamp-on ammeter to measure load current draw, with  
the generator running and all normal electrical loads turned on.  
Warning: Do not field flash alternator more  
than two times in sequence. if the unit has  
not produced power after two attempts, other  
issues exist and need to be addressed.  
RESULTS:  
*
1. If the unit is overloaded, reduce loads to the unit’s rated  
capacity.  
2. If unit is not overloaded, but rpm and frequency drop  
excessively when loads are applied, go to Test 16.  
RESULTS:  
1. Refer back to flow chart.  
Page 52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 2.4  
DiaGNostic tEsts  
AC GENERATORS  
Part 2  
CRIMP ON STANDARD FEMALE BLADE CONNECTORS  
4 ft.  
12 AWG  
MOMENTARY PUSHBUTTON ON/OFF SWITCH  
SINGLE POLE SWITCH ON LIVE SIDE  
12 AWG  
DO NOT SUBSTITUTE ANY OTHER DEVICE  
STANDARD MALE PLUG  
Figure 17. Construction of Energizing Cord  
DEPRESS SWITCH FOR  
ONE SECOND  
PLUG ENERGIZING CORD  
INTO AC OUTLET  
CAPACITOR  
WIRES 2 & 6 TO  
DPE WINDING  
CAPICITOR REMAINS CONNECTED  
TO GENERATOR  
Danger:The capacitor may need to be dis-  
charged before testing. A capacitor can be  
discharged by crossing the terminals with a  
metal insulated screw driver.  
Danger: Use proper protective equipment  
when dealing with a capacitor that has  
exploded.  
GENERATOR  
Figure 18. Energizing Cord Connection  
Page 53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NotEs  
Page 54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
taBlE of coNtENts  
Part  
titlE  
PG#  
50  
54  
64  
3.1. Description and components  
3.2 operational analysis  
3.3 troubleshooting flow charts  
Part 3  
traNsfEr  
sWitcH  
3.4 Diagnostic tests  
66  
air-cooled, automatic  
standby Generators  
Test 28 – Check 23 And 15B  
3.1 Description and Components ...............................................56  
General 56  
Wiring/Connections.............................................76  
Test 29 – Test Transfer Relay TR ........................................77  
Test 30 – Standby Control Circuit .......................................78  
Test 31 – Check Wire 23.....................................................78  
Test 32 – Utility Control Circuit............................................80  
Test 33 – Test Limit Switch SW2 and SW3.........................82  
Test 34 – Check Fuses F1 and F2......................................82  
Test 35 – Check N1 and N2 Wiring.....................................83  
Test 36 – Check N1 and N2 Voltage...................................83  
Test 37 – Check Utility Sensing Voltage  
at the Circuit Board .............................................84  
Test 38 – Check Utility Sense Voltage ................................84  
Test 39 – Check Voltage at  
Terminal Lugs N1, N2 .........................................84  
Test 40 – Check Battery Charger Supply  
Voltage “Pre-Wire Load Center”..........................86  
Test 41 – Check Battery Charger Output  
Voltage “Pre-Wire Load Center”..........................86  
Test 42 – Check Wire 0 and Wire15B  
Enclosure............................................................................56  
Transfer Mechanism............................................................57  
Transfer Relay.....................................................................57  
Neutral Lug .........................................................................58  
Manual Transfer Handle .....................................................58  
Terminal Block ...................................................................58  
Fuse Holder ........................................................................59  
3.2 Operational Analysis.............................................................60  
Operational Analysis...........................................................60  
Utility Source Voltage Available ..........................................62  
Utility Source Voltage Failure .............................................63  
Transfer To Standby ............................................................64  
Transfer To Standby ............................................................65  
Utility Restored ...................................................................66  
Utility Restored, Transfer Switch  
De-energized ......................................................67  
Utility Restored, Retransfer Back To Utility .........................68  
Transfer Switch In Utility......................................................69  
3.3 – Troubleshooting Flowcharts ...............................................70  
Introduction To Troubleshooting ..........................................70  
Problem 7 – In Automatic Mode,  
“Pre-Wire Load Center”.......................................86  
Test 43 – Check Battery Charger  
Supply Voltage  
“RTSN & RTSE Transfer Switch”.........................87  
Test 44 – Check Battery Charger  
No Transfer to Standby..................................................70  
Problem 8 – In Automatic Mode, Generator  
Output Voltage  
Starts When Loss of Utility Occurs,  
“RTSN & RTSE Transfer Switch”.........................87  
Test 45 – Check Wire 0/  
“RTSN & RTSE Transfer Switch........................87  
Test 46 – Check Battery Charger  
Generator Shuts Down When Utility  
Returns But There Is No Retransfer To Utility Power / or  
Generator Transfers to Standby During Exercise Or In  
Manual Mode.................................................................71  
Problem 9 – Blown F1 or F2 Fuse.................................71  
Problem 10 – Units Starts And Transfer  
Supply Voltage  
“GenReady Load Center”....................................90  
Test 47 – Check Battery Charger  
Occurs When Utility Power Is On ..................................72  
Problem 11 – No Battery Charge  
Output Voltage  
“GenReady Load Center”....................................90  
Test 48 – Check Wire 0/15B  
(Pre-Packed Load Center).............................................73  
Problem 12 – No Battery Charge  
“GenReady Load Center”....................................90  
Test 49 – Check Battery Charger  
(RTSN + RTSE Transfer Switch) ...................................73  
Problem 13 – No Battery Charge  
Supply Voltage  
(Gen-Ready Load Center).............................................73  
Problem 14 – No Battery Charge  
(Load Shed Transfer Switch) .........................................73  
3.4 Diagnostic Tests....................................................................74  
General ............................................................................74  
Test 26 – Check Voltage at  
“Load Shed Transfer Switch...............................92  
Test 50 – Check Battery Charger  
Output Voltage  
“Load Shed Transfer Switch...............................92  
Test 51 – Check Wire 0 and Wire 15B  
“Load Shed Transfer Switch...............................94  
Terminal Lugs E1, E2..........................................74  
Test 27 – Check Manual Transfer Switch Operation ...........75  
Page 55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.1  
DEscriPtioN & comPoNENts  
TRANSFER SWITCH  
Part 3  
General  
encloSure  
The “W/V-Type” transfer switch is rated 100 amps at  
250 volts maximum. It is available in 2-pole configura-  
tion only and, for that reason, is usable with 1-phase  
systems only.  
The “W/V-Type” transfer switch enclosure is a NEMA  
1 type (“NEMA” stands for “National Electrical  
Manufacturer’s Association”). Based on NEMA  
Standard 250, the NEMA 1 enclosure may be defined  
as one that is intended for indoor use primarily to  
provide a degree of protection against contact with  
the enclosed equipment and where unusual service  
conditions do not exist.  
Transfer switches do not have an intelligence sys-  
tem of their own. Instead, automatic operation of  
these transfer switches is controlled by a circuit board  
housed in the generator control panel.  
39  
6
11  
5
7
12  
9
itEm DEscriPtioN  
1
GTS LOAD CENTER ENCLOSURE  
COVER GTS LOAD CTR  
TRANSFER SWITCH HOME STANDBY  
COIL UTILITY  
2
3
26  
29  
2
3A  
3
4
3A  
3B  
4
COIL STANDBY  
SCREW  
26  
22  
16  
23  
5
SCREW  
LOCK WASHER”  
9
30  
38  
6
7
RELAY PANEL 12VDC DPDT 10A@240VAC  
LOAD CENTER  
SCREW  
24  
20  
10  
8
15  
26  
9
13  
1
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
26  
27  
28  
29  
30  
31  
RIVET”  
WASHER  
PLUG  
3B  
19  
16  
21  
22  
17  
23  
31  
HARNESS ADAPTER PLATE  
SUBPLATE GTS LOAD CENTER  
U-CHANNEL  
18  
WASHER  
GROMMET  
ARM EXTENDER PIN  
CABLE TIE SELF MOUNTING 4.3LG  
HARNESS GTS-MAIN PANEL W/NEUTRAL  
LUG QUICK DISCONNECT  
SCREW  
14  
8
LUG  
27  
BLOCK TERMINAL  
SCREW WITH WASHER  
SCREW  
ITEMS 32-37  
HARNESS LOAD CENTER INT. CONN (NOT SHOWN)  
FUSEBLOCK  
FUSE 5A  
BATTERY CHARGER  
32-37 CIRCUIT BREAKERS  
38  
39  
HARNESS ENTRY COVER  
HARNESS GTS, EXTERNAL CONNECTION BOX  
Figure 1. Exploded View of W/V-Type Transfer Switch  
Page 56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.1  
DEscriPtioN & comPoNENts  
TRANSFER SWITCH  
Part 3  
source side. Energizing the coil moves the load con-  
tacts to an overcenter position; limit switch action then  
opens the circuit and spring force will complete the  
transfer action to “Standby”. This coil’s bridge rectifier  
is also sealed in the coil wrappings. Replace the coil  
and bridge rectifier as a unit.  
tranSFer mechaniSm  
The 2-pole transfer mechanism consists of a pair  
of moveable LOAD contacts, a pair of stationary  
UTILITY contacts, and a pair of stationary STANDBY  
contacts. The load contacts can be connected to  
the utility contacts by a utility closing coil; or to the  
standby contacts by a standby closing coil. In addi-  
tion, the load contacts can be actuated to either the  
UTILITY or STANDBY side by means of a manual  
transfer handle. See Figures 2 and 3.  
LIMIT SWITCHES SW2 AND SW3:  
Switches are mechanically actuated by load contacts  
movement. When the load contacts are connected to  
the utility contacts, limit switch SW2 opens the utility  
circuit to utility closing coil C1 and limit switch SW3  
closes the standby circuit to standby closing coil C2.  
The limit switches “arm” the system for retransfer  
back to UTILITY when the load contacts are con-  
nected to the STANDBY side. Conversely, when the  
load contacts are connected to the UTILITY side, the  
switches “arm” the system for transfer to STANDBY.  
An open condition in limit switch SW2 will prevent  
retransfer to “Utility”. An open switch SW3 will prevent  
transfer to STANDBY.  
STANDBY  
UTILITY  
LOAD  
N2A  
A
BRIDGE  
RECTIFIER  
N1  
UTILITY  
N2  
CLOSING  
COIL (C1)  
LIMIT  
SWITCH  
(SW2)  
Figure 2. Load Connected to Utility Power Source  
A
126  
205  
MANUAL  
STANDBY  
UTILITY  
TRANSFER  
LEVER  
B
E1  
E2  
LIMIT  
SWITCH  
(SW3)  
STANDBY  
CLOSING  
COIL (C2)  
T2  
T1  
BRIDGE  
RECTIFIER  
E2  
B
LOAD  
Figure 4. The “W/V-Type” Transfer Mechanism  
Figure 3. Load Connected to Standby Power Source  
tranSFer relay  
Transfer relay operation is controlled by a circuit  
board. That circuit board is a part of a control panel  
assembly, mounted on the standby generator set.  
UTILITY CLOSING COIL C1:  
See Figure 4. This coil is energized by rectified util-  
ity source power, to actuate the load contacts to the  
UTILITY power source side. When energized, the coil  
will move the main contacts to an “overcenter” posi-  
tion. A limit switch will then be actuated to open the  
circuit and spring force will complete the retransfer to  
STANDBY. A bridge rectifier, which changes the utility  
source alternating current (AC) to direct current (DC),  
is sealed in the coil wrappings. If coil or bridge rectifier  
replacement becomes necessary, the entire coil and  
bridge assembly should be replaced.  
Figure 5 shows the transfer relay pictorially and  
schematically. Relay operation may be briefly  
described as follows:  
1. Generator battery voltage (12 volts DC) is available to  
the transfer relay coil from the generator circuit board,  
via Wire 15B and Relay Terminal A.  
a. The 12 volts DC circuit is completed through  
the transfer relay coil and back to the generator  
circuit board, via Wire 23.  
STANDBY CLOSING COIL C2:  
b. Circuit board action normally holds the Wire  
23 circuit open to ground and the relay is  
de-energized.  
Coil C2 is energized by rectified standby source  
power, to actuate the load contacts to their “Standby”  
Page 57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.1  
DEscriPtioN & comPoNENts  
TRANSFER SWITCH  
Part 3  
c. When de-energized, the relay’s normally open  
contacts are open and its normally-closed  
contacts are closed.  
neutral luG  
The standby generator is equipped with an  
UNGROUNDED neutral. The neutral lug in the transfer  
switch is isolated from the switch enclosure.  
d. The normally-closed relay contacts will deliver  
utility source power to the utility closing circuit  
of the transfer mechanism.  
e. The normally open relay contacts will deliver  
standby source power to the transfer mecha-  
nism’s standby closing circuit.  
manual tranSFer handle  
The manual transfer handle is retained in the transfer  
switch enclosure by means of a wing stud. Use the  
handle to manually actuate the transfer mechanism  
load contacts to either the UTILITY or STANDBY  
source side.  
194  
Instructions on use of the manual transfer handle  
may be found in Part 5, “Operational Tests and  
Adjustments”.  
A
B
23  
terminal Block  
During system installation, this 3-point terminal block  
must be properly interconnected with an identically  
labeled terminal block in the generator control panel  
assembly.  
1
6
7
9
N1A  
E1  
126  
205  
0
15B  
23  
Figure 5. Transfer Relay Schematic  
2. During automatic system operation, when the genera-  
tor circuit board “senses” that utility source voltage  
has dropped out, the circuit board will initiate engine  
cranking and startup.  
3. When the circuit board “senses” that the engine has  
started, an “engine warm-up timer” on the circuit board  
starts timing.  
4. When the “engine warm-up timer” has timed out, circuit  
board action completes the Wire 23 circuit to ground.  
Figure 6. Transfer Switch Terminal Block  
a. The transfer relay then energizes.  
Terminals used on the terminal block are identified as  
0, 15B and 23.  
b. The relay’s normally-closed contacts open and  
its normally open contacts close.  
c. When the normally open contacts close, standby  
source power is delivered to the standby closing  
coil and transfer to “Standby” occurs.  
UTILITY N1 AND N2:  
Interconnect with identically labeled terminals in the  
generator control panel assembly. This is the utility  
voltage signal to the circuit board. The signal is deliv-  
ered to a step-down transformer in the control module  
assembly and the resultant reduced voltage is then  
delivered to the circuit board. Utility 1 and 2 power is  
used by the circuit board as follows:  
• If utility source voltage should drop below a pre-  
set level, circuit board action will initiate automatic  
cranking and startup, followed by automatic transfer  
to the standby source.  
5. When the generator circuit board “senses” that utility  
source voltage has been restored above a preset level,  
the board will open the Wire 23 circuit to ground.  
a. The transfer relay will de-energize, its normally-  
closed contacts will close and its normally open  
contacts will open.  
b. When the normally-closed relay contacts close,  
utility source voltage is delivered to the utility  
closing coil to energize that coil.  
• Utility source voltage is used to operate a battery  
trickle charge circuit which helps to maintain battery  
state of charge during non-operating periods.  
c. Retransfer back to UTILITY occurs.  
Page 58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.1  
DEscriPtioN & comPoNENts  
TRANSFER SWITCH  
Part 3  
TERMINALS 0, 15B AND 23:  
F2  
These terminals connect the transfer relay to the  
generator circuit board. See “Transfer Relay” in  
Section 3.1.  
N1A  
N2A  
BLACK  
FuSe holder  
The fuse holder holds three (3) fuses, designated as  
fuses F1, F2 and F3. Each fuse is rated 5 amperes.  
F3  
F1  
FUSES F1, F2:  
These two fuses protect the UTILITY 1 and UTILITY 2  
circuit against overload.  
FUSES F3:  
This fuse protects the battery charger against overload.  
N1  
N2  
T1  
Figure 7. The Fuse Holder  
Page 59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.2  
oPEratioNal aNalYsis  
TRANSFER SWITCH  
Part 3  
operational analySiS  
Figure 1 is a schematic for a typical “W/V-Type” transfer switch.  
0
0
0
15B  
E1  
N1A  
CONTROL  
TRANSFER  
15B  
15B  
23  
15B  
23  
A
23  
7
7
9
9
E1  
TR1  
TS TO  
1
4
3
6
GENERATOR  
CONTROL PANEL  
B
N1A  
23  
F2  
N2  
N1  
E1  
E2  
N2  
UTILITY  
126  
205  
SENSING  
N2A  
F1  
240VAC  
OUTPUT  
N1A  
N1A  
N1  
-
+
N1A  
BLK  
WIRE  
RED  
WIRE  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
BC  
E1  
NEUTRAL (WHITE)  
GROUND (GREEN)  
E2  
NEUTRAL  
CONNECTION  
INSIDE  
B
GROUND (GREEN)  
NEUTRAL (WHITE)  
SWITCH  
N2A  
N1A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
RED (MAIN 2)  
205  
B
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
CIRCUIT 14  
CIRCUIT 13  
CIRCUIT 10  
CIRCUIT 9  
CIRCUIT 6  
CIRCUIT 5  
CIRCUIT 2  
CIRCUIT 1  
CIRCUIT 3  
CIRCUIT 4  
CIRCUIT 7  
CIRCUIT 8  
CIRCUIT 11  
CIRCUIT 12  
CIRCUIT 15  
CIRCUIT 16  
E2  
SW3  
COM  
SW2  
COM  
E2  
B
VR1  
C1  
VR2  
C2  
N2A  
A
T1 T1 T2  
SW1  
N2A  
B
E2  
F3  
T1  
T1  
T2  
B
E2  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
LC  
TR1-TRANSFER RELAY  
Figure 1. Schematic  
Page 60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.2  
oPEratioNal aNalYsis  
TRANSFER SWITCH  
Part 3  
Figure 2 is a wiring diagram for a typical “W/V-Type” transfer switch.  
RED  
BLK  
BLK  
RED  
RED  
BLK  
N2A  
N1A  
126  
126  
GRN  
GRN  
A
N2A  
N1A  
N2A  
TR1  
N2A  
1
4
7
3
6
9
1
2
C1  
126  
A
N1  
N2  
205  
E1  
A
B
15B  
23  
N1A  
SW2  
SW3  
E1  
RED  
BLK  
N1A  
N2A  
N1A  
N2A  
SW1  
205  
BLK  
BLK  
RED  
RED  
E1  
T1  
E2  
T2  
205  
2
B
C2  
1
N1A N2A  
E2  
B
E1  
E2  
205  
BC  
A
A
A
BLK  
23  
F1 F2 F3  
RED  
BLK  
RED  
E1  
15B  
B
B
B
-
+
BLK  
WIRE  
RED  
WIRE  
N1 N2  
T1  
T1  
15B  
0
0D4698-T  
1
2
3
TB1  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
TR1-TRANSFER RELAY  
Figure 2. Wiring Diagram  
Page 61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.2  
oPEratioNal aNalYsis  
TRANSFER SWITCH  
Part 3  
utility Source VoltaGe aVailaBle  
Figure 3 is a schematic representation of the transfer switch with utility source power available. The circuit  
condition may be briefly described as follows:  
• Utility source voltage is available to terminal lugs N1 and N2 of the transfer mechanism, transfer switch is in the  
UTILITY position and source voltage is available to T1, T2 and customer load.  
• Utility source voltage is available to limit switch (SW2) via the normally-closed transfer relay contacts (1 and 7)  
and Wire 126. However, SW2 is open and the Circuit to the utility closing coil is open.  
• Utility voltage “sensing” signals are delivered to a circuit board on the generator, via Wire N1A, a 5 amp fuse  
(F1). The second line of the utility voltage “sensing” circuit is via Wire N2A, a 5 amp Fuse (F2).  
0
15B  
23  
0
0
15B  
23  
15B  
E1  
N1A  
CONTROL  
TRANSFER  
15B  
23  
A
7
7
9
9
E1  
TR1  
TS TO  
1
4
3
6
GENERATOR  
CONTROL PANEL  
B
N1A  
23  
F2  
N2  
N1  
E1  
E2  
N2  
UTILITY  
126  
205  
SENSING  
N2A  
F1  
240VAC  
OUTPUT  
N1A  
N1A  
N1  
-
+
RED  
WIRE  
N1A  
BLK  
WIRE  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
BC  
E1  
NEUTRAL (WHITE)  
GROUND (GREEN)  
E2  
NEUTRAL  
CONNECTION  
INSIDE  
B
GROUND (GREEN)  
NEUTRAL (WHITE)  
SWITCH  
N2A  
N1A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
RED (MAIN 2)  
205  
B
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
CIRCUIT 14  
CIRCUIT 13  
CIRCUIT 10  
CIRCUIT 9  
CIRCUIT 6  
CIRCUIT 5  
CIRCUIT 2  
CIRCUIT 1  
CIRCUIT 3  
CIRCUIT 4  
CIRCUIT 7  
CIRCUIT 8  
CIRCUIT 11  
CIRCUIT 12  
CIRCUIT 15  
CIRCUIT 16  
E2  
SW3  
COM  
SW2  
COM  
E2  
B
VR1  
C1  
VR2  
C2  
N2A  
A
T1 T1 T2  
SW1  
N2A  
B
E2  
F3  
T1  
T1  
T2  
B
E2  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
UTILITY  
DC  
LC  
TR1-TRANSFER RELAY  
GROUND  
GENERATOR  
Figure 3. Utility Source Power Available  
Page 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.2  
oPEratioNal aNalYsis  
TRANSFER SWITCH  
Part 3  
utility Source VoltaGe Failure  
If utility source voltage should drop below a preset value, the generator circuit board will sense the dropout. The  
circuit board will then initiate generator cranking and startup after a time delay circuit times out.  
Figure 4 is a schematic representation of the transfer switch with generator power available, waiting to transfer.  
• Generator voltage available E1, E2.  
• Circuit board action holding Wire 23 open to ground.  
• Power available to standby coil C2, upon closure of TR1, normally open contacts (9 & 6) will close and initiate a  
transfer.  
0
15B  
23  
0
0
15B  
23  
15B  
E1  
N1A  
CONTROL  
TRANSFER  
15B  
23  
A
7
7
9
9
E1  
TR1  
TS TO  
1
4
3
6
GENERATOR  
CONTROL PANEL  
B
N1A  
23  
F2  
N2  
N1  
E1  
E2  
N2  
UTILITY  
126  
205  
SENSING  
N2A  
F1  
240VAC  
OUTPUT  
N1A  
N1A  
N1  
-
+
RED  
WIRE  
N1A  
BLK  
WIRE  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
BC  
E1  
NEUTRAL (WHITE)  
GROUND (GREEN)  
E2  
NEUTRAL  
CONNECTION  
INSIDE  
B
GROUND (GREEN)  
NEUTRAL (WHITE)  
SWITCH  
N2A  
N1A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
RED (MAIN 2)  
205  
B
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
CIRCUIT 14  
CIRCUIT 13  
CIRCUIT 10  
CIRCUIT 9  
CIRCUIT 6  
CIRCUIT 5  
CIRCUIT 2  
CIRCUIT 1  
CIRCUIT 3  
CIRCUIT 4  
CIRCUIT 7  
CIRCUIT 8  
CIRCUIT 11  
CIRCUIT 12  
CIRCUIT 15  
CIRCUIT 16  
E2  
SW3  
COM  
SW2  
COM  
E2  
B
VR1  
C1  
VR2  
C2  
N2A  
A
T1 T1 T2  
SW1  
N2A  
B
E2  
F3  
T1  
T1  
T2  
B
E2  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
UTILITY  
DC  
LC  
TR1-TRANSFER RELAY  
GROUND  
GENERATOR  
Figure 4. Generator Power Available, Waiting to Transfer.  
Page 63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.2  
oPEratioNal aNalYsis  
TRANSFER SWITCH  
Part 3  
tranSFer to StandBy  
12 VDC is delivered to the transfer relay via Wire 15B and back to the circuit board via Wire 23. However, circuit  
board action holds the Wire 23 circuit open and the transfer relay remains de-energized. On generator startup, an  
“engine warm-up timer” on the generator circuit board starts timing. When that timer has timed out, circuit board  
action completes the Wire 23 circuit to ground. The transfer relay then energizes, its normally open contacts  
close, and standby source voltage is delivered to the standby closing coil via Wires E1 and E2, the transfer relay  
(TR1) contacts, limit switch (SW3), Wire “B”, and a bridge rectifier. The standby closing coil energizes and the  
main contacts actuate to their “Standby” side.  
0
15B  
23  
0
0
15B  
23  
15B  
E1  
N1A  
CONTROL  
TRANSFER  
15B  
23  
A
7
7
9
9
E1  
TR1  
TS TO  
1
4
3
6
GENERATOR  
CONTROL PANEL  
B
N1A  
23  
F2  
N2  
N1  
E1  
E2  
N2  
UTILITY  
126  
205  
SENSING  
N2A  
F1  
240VAC  
OUTPUT  
N1A  
N1A  
N1  
-
+
RED  
WIRE  
N1A  
BLK  
WIRE  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
BC  
E1  
NEUTRAL (WHITE)  
GROUND (GREEN)  
E2  
NEUTRAL  
CONNECTION  
INSIDE  
B
GROUND (GREEN)  
NEUTRAL (WHITE)  
SWITCH  
N2A  
N1A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
RED (MAIN 2)  
205  
B
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
CIRCUIT 14  
CIRCUIT 13  
CIRCUIT 10  
CIRCUIT 9  
CIRCUIT 6  
CIRCUIT 5  
CIRCUIT 2  
CIRCUIT 1  
CIRCUIT 3  
CIRCUIT 4  
CIRCUIT 7  
CIRCUIT 8  
CIRCUIT 11  
CIRCUIT 12  
CIRCUIT 15  
CIRCUIT 16  
E2  
SW3  
COM  
SW2  
COM  
E2  
B
VR1  
C1  
VR2  
C2  
N2A  
A
T1 T1 T2  
SW1  
N2A  
B
E2  
F3  
T1  
T1  
T2  
B
E2  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
UTILITY  
DC  
LC  
TR1-TRANSFER RELAY  
GROUND  
GENERATOR  
Figure 5. Transfer Action to Standby Position  
Page 64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.2  
oPEratioNal aNalYsis  
TRANSFER SWITCH  
Part 3  
tranSFer to StandBy  
When the standby coil is energized it pulls the transfer switch mechanism to a overcenter position towards the  
standby power source side, the transfer switch mechanically snaps to the standby position. On closure of the  
main contacts to the standby power source side, limit switches SW2 and SW3 are mechanically actuated to “arm”  
the circuit for re- transfer to utility power source side.  
Generator power from E1 and E2 is now connected to the customer load through T1 and T2.  
0
15B  
23  
0
0
15B  
23  
15B  
E1  
N1A  
CONTROL  
TRANSFER  
15B  
23  
A
7
7
9
9
E1  
TR1  
TS TO  
1
4
3
6
GENERATOR  
CONTROL PANEL  
B
N1A  
23  
F2  
N2  
N1  
E1  
E2  
N2  
UTILITY  
126  
205  
SENSING  
N2A  
F1  
240VAC  
OUTPUT  
N1A  
N1A  
N1  
-
+
RED  
WIRE  
N1A  
BLK  
WIRE  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
BC  
E1  
NEUTRAL (WHITE)  
GROUND (GREEN)  
E2  
NEUTRAL  
CONNECTION  
INSIDE  
B
GROUND (GREEN)  
NEUTRAL (WHITE)  
SWITCH  
N2A  
N1A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
RED (MAIN 2)  
205  
B
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
CIRCUIT 14  
CIRCUIT 13  
CIRCUIT 10  
CIRCUIT 9  
CIRCUIT 6  
CIRCUIT 5  
CIRCUIT 2  
CIRCUIT 1  
CIRCUIT 3  
CIRCUIT 4  
CIRCUIT 7  
CIRCUIT 8  
CIRCUIT 11  
CIRCUIT 12  
CIRCUIT 15  
CIRCUIT 16  
E2  
SW3  
COM  
SW2  
COM  
E2  
B
VR1  
C1  
VR2  
C2  
N2A  
A
T1 T1 T2  
SW1  
N2A  
B
E2  
F3  
T1  
T1  
T2  
B
E2  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
UTILITY  
DC  
LC  
TR1-TRANSFER RELAY  
GROUND  
GENERATOR  
Figure 6. Generator Powering Load.  
Page 65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.2  
oPEratioNal aNalYsis  
TRANSFER SWITCH  
Part 3  
utility reStored  
Utility voltage is restored and is available to Terminals N1 and N2. The utility voltage is sensed by the generators  
circuit board. If it is above a preset value for a preset time interval a transfer back to utility power will occur.  
0
15B  
23  
0
0
15B  
23  
15B  
E1  
N1A  
CONTROL  
TRANSFER  
15B  
23  
A
7
7
9
9
E1  
TR1  
TS TO  
1
4
3
6
GENERATOR  
CONTROL PANEL  
B
N1A  
23  
F2  
N2  
N1  
E1  
E2  
N2  
UTILITY  
126  
205  
SENSING  
N2A  
F1  
240VAC  
OUTPUT  
N1A  
N1A  
N1  
-
+
RED  
WIRE  
N1A  
BLK  
WIRE  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
BC  
E1  
NEUTRAL (WHITE)  
GROUND (GREEN)  
E2  
NEUTRAL  
CONNECTION  
INSIDE  
B
GROUND (GREEN)  
NEUTRAL (WHITE)  
SWITCH  
N2A  
N1A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
RED (MAIN 2)  
205  
B
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
CIRCUIT 14  
CIRCUIT 13  
CIRCUIT 10  
CIRCUIT 9  
CIRCUIT 6  
CIRCUIT 5  
CIRCUIT 2  
CIRCUIT 1  
CIRCUIT 3  
CIRCUIT 4  
CIRCUIT 7  
CIRCUIT 8  
CIRCUIT 11  
CIRCUIT 12  
CIRCUIT 15  
CIRCUIT 16  
E2  
SW3  
COM  
SW2  
COM  
E2  
B
VR1  
C1  
VR2  
C2  
N2A  
A
T1 T1 T2  
SW1  
N2A  
B
E2  
F3  
T1  
T1  
T2  
B
E2  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
UTILITY  
DC  
LC  
TR1-TRANSFER RELAY  
GROUND  
GENERATOR  
Figure 7. Utility Restored, Generator Still Providing Output to Load.  
Page 66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.2  
oPEratioNal aNalYsis  
TRANSFER SWITCH  
Part 3  
utility reStored,tranSFer SWitch de-enerGized  
After the preset time interval expires the circuit board will open the Wire 23 circuit to ground. The transfer relay  
de-energizes, it’s normally closed contacts close, and utility source voltage is delivered to the utility closing coil  
(C1), via Wires N1A and N2A, closed Transfer Relay Contacts 1 and 7, and Limit Switch SW2.  
0
15B  
23  
0
0
15B  
23  
15B  
E1  
N1A  
CONTROL  
TRANSFER  
15B  
23  
A
7
7
9
9
E1  
TR1  
TS TO  
1
4
3
6
GENERATOR  
CONTROL PANEL  
B
N1A  
23  
F2  
N2  
N1  
E1  
E2  
N2  
UTILITY  
126  
205  
SENSING  
N2A  
F1  
240VAC  
OUTPUT  
N1A  
N1A  
N1  
-
+
RED  
WIRE  
N1A  
BLK  
WIRE  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
BC  
E1  
NEUTRAL (WHITE)  
GROUND (GREEN)  
E2  
NEUTRAL  
CONNECTION  
INSIDE  
B
GROUND (GREEN)  
NEUTRAL (WHITE)  
SWITCH  
N2A  
N1A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
RED (MAIN 2)  
205  
B
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
CIRCUIT 14  
CIRCUIT 13  
CIRCUIT 10  
CIRCUIT 9  
CIRCUIT 6  
CIRCUIT 5  
CIRCUIT 2  
CIRCUIT 1  
CIRCUIT 3  
CIRCUIT 4  
CIRCUIT 7  
CIRCUIT 8  
CIRCUIT 11  
CIRCUIT 12  
CIRCUIT 15  
CIRCUIT 16  
E2  
SW3  
COM  
SW2  
COM  
E2  
B
VR1  
C1  
VR2  
C2  
N2A  
A
T1 T1 T2  
SW1  
N2A  
B
E2  
F3  
T1  
T1  
T2  
B
E2  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
UTILITY  
DC  
LC  
TR1-TRANSFER RELAY  
GROUND  
GENERATOR  
Figure 8. Utility Restored, Transfer Relay De-energized.  
Page 67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.2  
oPEratioNal aNalYsis  
TRANSFER SWITCH  
Part 3  
utility reStored, retranSFer Back to utility  
As the utility coil pulls the transfer switch to an OVER CENTER position, the switch mechanically snaps to Utility.  
On closure of the main contacts to the utility power source side, Limit Switches SW2 and SW3 are mechanically  
actuated to “arm” the circuit for transfer to standby.  
0
15B  
23  
0
0
15B  
23  
15B  
E1  
N1A  
CONTROL  
TRANSFER  
15B  
23  
A
7
7
9
9
E1  
TR1  
TS TO  
1
4
3
6
GENERATOR  
CONTROL PANEL  
B
N1A  
23  
F2  
N2  
N1  
E1  
E2  
N2  
UTILITY  
126  
205  
SENSING  
N2A  
F1  
240VAC  
OUTPUT  
N1A  
N1A  
N1  
-
+
RED  
WIRE  
N1A  
BLK  
WIRE  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
BC  
E1  
NEUTRAL (WHITE)  
GROUND (GREEN)  
E2  
NEUTRAL  
CONNECTION  
INSIDE  
B
GROUND (GREEN)  
NEUTRAL (WHITE)  
SWITCH  
N2A  
N1A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
RED (MAIN 2)  
205  
B
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
CIRCUIT 14  
CIRCUIT 13  
CIRCUIT 10  
CIRCUIT 9  
CIRCUIT 6  
CIRCUIT 5  
CIRCUIT 2  
CIRCUIT 1  
CIRCUIT 3  
CIRCUIT 4  
CIRCUIT 7  
CIRCUIT 8  
CIRCUIT 11  
CIRCUIT 12  
CIRCUIT 15  
CIRCUIT 16  
E2  
SW3  
COM  
SW2  
COM  
E2  
B
VR1  
C1  
VR2  
C2  
N2A  
A
T1 T1 T2  
SW1  
N2A  
B
E2  
F3  
T1  
T1  
T2  
B
E2  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
UTILITY  
DC  
LC  
TR1-TRANSFER RELAY  
GROUND  
GENERATOR  
Figure 9. Utility Restored, Retransfer Back to Utility.  
Page 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.2  
oPEratioNal aNalYsis  
TRANSFER SWITCH  
Part 3  
tranSFer SWitch in utility  
When the transfer switch returns to the utility side, generator shutdown occurs after approximately one (1) minute.  
0
15B  
23  
0
0
15B  
23  
15B  
E1  
N1A  
CONTROL  
TRANSFER  
15B  
23  
A
7
7
9
9
E1  
TR1  
TS TO  
1
4
3
6
GENERATOR  
CONTROL PANEL  
B
N1A  
23  
F2  
N2  
N1  
E1  
E2  
N2  
UTILITY  
126  
205  
SENSING  
N2A  
F1  
240VAC  
OUTPUT  
N1A  
N1A  
N1  
-
+
RED  
WIRE  
N1A  
BLK  
WIRE  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
BC  
E1  
NEUTRAL (WHITE)  
GROUND (GREEN)  
E2  
NEUTRAL  
CONNECTION  
INSIDE  
B
GROUND (GREEN)  
NEUTRAL (WHITE)  
SWITCH  
N2A  
N1A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
RED (MAIN 2)  
205  
B
126  
N2A  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
NO  
CIRCUIT 14  
CIRCUIT 13  
CIRCUIT 10  
CIRCUIT 9  
CIRCUIT 6  
CIRCUIT 5  
CIRCUIT 2  
CIRCUIT 1  
CIRCUIT 3  
CIRCUIT 4  
CIRCUIT 7  
CIRCUIT 8  
CIRCUIT 11  
CIRCUIT 12  
CIRCUIT 15  
CIRCUIT 16  
E2  
SW3  
COM  
SW2  
COM  
E2  
B
VR1  
C1  
VR2  
C2  
N2A  
A
T1 T1 T2  
SW1  
N2A  
B
E2  
F3  
T1  
T1  
T2  
B
E2  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
UTILITY  
DC  
LC  
TR1-TRANSFER RELAY  
GROUND  
GENERATOR  
Figure 10. Transfer Switch in UTILITy.  
Page 69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.3  
trouBlEsHootiNG floW cHarts  
TRANSFER SWITCH  
Part 3  
introduction to trouBleShootinG  
The first step in troubleshooting is to correctly identify the problem. Once that is done, the cause of the an be  
found by performing the tests in the appropriate flow chart.  
Test numbers assigned in the flow charts are identical to test numbers in Section 3.4, “Diagnostic Tests.Section  
3.4 provides detailed instructions for performance of each test.  
Problem 7 – In Automatic Mode, No Transfer to Standby  
TEST 26 – CHECK  
VOLTAGE AT  
TERMINAL LUGS  
E1 & E2  
FIND CAUSE OF NO AC OUTPUT TO  
TRANSFER SWITCH FROM GENERATOR  
BAD  
GOOD  
TEST 27 – CHECK  
MANUAL TRANSFER  
SWITCH OPERATION  
REPAIR OR REPLACE MECHANISM  
REPAIR OR REPLACE AS NEEDED  
REPLACE  
BAD  
GOOD  
TEST 28 – CHECK #23  
AND #15B WIRING  
CONNECTIONS  
BAD  
BAD  
BAD  
GOOD  
TEST 29 – TEST  
TRANSFER  
RELAY  
GOOD  
TEST 30 – CHECK  
STANDBY CONTROL  
CIRCUIT  
REPAIR AS NEEDED  
Page 70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.3  
trouBlEsHootiNG floW cHarts  
TRANSFER SWITCH  
Part 3  
Problem 8 – In Automatic Mode, Generator Starts When Loss of Utility Occurs, Generator  
Shuts Down When Utility Returns But There Is No Retransfer To Utility Power  
OR  
Generator Transfers to Standby During Excercise or in Manual Mode  
TEST 27 – CHECK  
MANUAL TRANSFER  
SWITCH OPERATION  
REPAIR OR REPLACE MECHANISM  
REPAIR OR REPLACE AS NEEDED  
REPLACE  
BAD  
BAD  
BAD  
GOOD  
TEST 31 – CHECK  
WIRE 23  
GOOD  
TEST 29 – TEST  
TRANSFER  
RELAY  
GOOD  
TEST 32 – CHECK  
UTILITY CONTROL  
CIRCUIT  
REPAIR OR REPLACE AS NEEDED  
BAD  
Problem 9 – Blown F1 or F2 Fuse  
TEST 35 – CHECK  
N1 & N2 WIRING  
TEST 34 – CHECK  
FUSE F1 & F2  
INSPECT/REPLACE  
PRINTED CIRCUIT BOARD  
BAD  
GOOD  
GOOD  
BAD  
FINISH  
REPAIR OR REPLACE  
WIRING  
Page 71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.3  
trouBlEsHootiNG floW cHarts  
TRANSFER SWITCH  
Part 3  
Problem 10 – Unit Starts and Transfer Occurs When Utility Power Is On  
8 kW: Green LED Flashes  
10-20 kW: Status – Utility Lost  
REPLACE  
CIRCUIT  
BOARD  
TEST 36 –  
CHECK N1 & N2  
VOLTAGE  
TEST 37 – CHECK  
UTILITY SENSING  
VOLTAGE AT  
GOOD  
GOOD  
CIRCUIT BOARD  
REPAIR OR  
REPLACE  
WIRING  
BAD  
BAD  
CORRECT  
TEST 38 – CHECK  
UTILITY SENSE  
VOLTAGE  
TEST 39 –  
CHECK VOLTAGE  
AT TERMINAL  
UTILITY  
SOURCE  
VOLTAGE  
TEST 34 –  
CHECK FUSE  
F1 & F2  
BAD  
BAD  
GOOD  
LUGS N1 & N2  
GOOD  
BAD  
GOOD  
REPAIR OR REPLACE WIRE  
N1A/N2A BETWEEN N1/N2  
LUGS AND FUSE HOLDER  
REPAIR N1/N2 OPEN WIRING  
BETWEEN TRANSFER  
SWITCH AND GENERATOR  
REPLACE  
GO TO PROBLEM 7  
Page 72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.3  
trouBlEsHootiNG floW cHarts  
TRANSFER SWITCH  
Part 3  
Problem 11 – No Battery Charge  
“Pre-Wire Load Center”  
TEST 40 – CHECK  
BATTERY CHARGER  
SUPPLY VOLTAGE  
TEST 41 – CHECK  
BATTERY CHARGER  
OUTPUT VOLTAGE  
TEST 42 – CHECK  
WIRE 0/15B  
NO BATTERY  
SUPPLY VOLTAGE  
GOOD  
BAD  
GOOD  
BAD  
BAD  
REPLACE PRINTED  
CIRCUIT BOARD  
REPAIR OR  
REPLACE  
REPAIR OR REPLACE  
REPLACE CHARGER  
Problem 12 – No Battery Charge  
“RTSN & RTSE Transfer Switch”  
TEST 43 – CHECK  
BATTERY CHARGER  
SUPPLY VOLTAGE  
TEST 44 – CHECK  
TEST 45 – CHECK  
WIRE 0/15B  
NO BATTERY  
GOOD  
BATTERY CHARGER  
SUPPLY VOLTAGE  
OUTPUT VOLTAGE  
BAD  
GOOD  
BAD  
BAD  
REPLACE PRINTED  
CIRCUIT BOARD  
REPAIR OR  
REPLACE  
REPAIR OR REPLACE  
REPLACE CHARGER  
Problem 13 – No Battery Charge  
“GenReady Load Center”  
TEST 46 – CHECK  
BATTERY CHARGER  
SUPPLY VOLTAGE  
TEST 47 – CHECK  
TEST 48 – CHECK  
WIRE 0/15B  
NO BATTERY  
GOOD  
BATTERY CHARGER  
SUPPLY VOLTAGE  
OUTPUT VOLTAGE  
BAD  
GOOD  
BAD  
BAD  
REPLACE PRINTED  
CIRCUIT BOARD  
REPAIR OR  
REPLACE  
REPAIR OR REPLACE  
REPLACE CHARGER  
Problem 14 – No Battery Charge  
“Load Shed Transfer Switch”  
TEST 49 – CHECK  
BATTERY CHARGER  
SUPPLY VOLTAGE  
TEST 50 – CHECK  
BATTERY CHARGER  
OUTPUT VOLTAGE  
TEST 51 – CHECK  
WIRE 0/15B  
NO BATTERY  
SUPPLY VOLTAGE  
GOOD  
BAD  
GOOD  
BAD  
BAD  
REPLACE PRINTED  
CIRCUIT BOARD  
REPAIR OR  
REPLACE  
REPAIR OR REPLACE  
REPLACE CHARGER  
Page 73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
PROCEDURE:  
General  
1. If the generator engine has started automatically (due to  
a utility power source outage) and is running, check the  
position of the generator main circuit breaker. The circuit  
breaker must be set to its “On” or “Closed” position.  
After confirming that the generator main circuit breaker  
is set to ON (or closed), check the voltage at transfer  
mechanism Terminal Lugs E1 and E2 with an accurate  
AC voltmeter or with an accurate volt-ohm-milliammeter  
(VOM). The generator line-to line voltage should be  
indicated.  
Test numbers in this section correspond to the  
numbered tests in Section 3.3, “Troubleshooting  
Flow Charts”. When troubleshooting, first identify  
the problem. Then, perform the diagnostic tests in  
the sequence given in the flow charts.  
teSt 26 – check VoltaGe at terminal  
luGS e1, e2  
DISCUSSION:  
2. If the generator has been shut down, proceed as follows:  
In automatic mode, the standby closing coil (C2) must  
be energized by standby generator output if transfer to  
the “Standby” source is to occur. Transfer to “Standby”  
cannot occur unless that power supply is available to  
the transfer switch.  
a. On the generator control panel, set the AUTO-  
OFF-MANUAL switch to OFF.  
b. Turn off all power voltage supplies to the trans-  
fer switch. Both the utility and standby power  
supplies must be positively turned off before  
proceeding.  
DaNGEr: BE carEful! HiGH aND  
DaNGErous VoltaGEs arE PrEsENt  
at tErmiNal luGs E1 aND E2 WHEN  
*
c. Check the position of the transfer mechanism  
main contacts. The moveable LOAD contacts must  
be connected to the stationary UTILITY source  
contacts. If necessary, manually actuate the main  
contacts to the “Utility” power source side.  
tHE GENErator is ruNNiNG. aVoiD  
coNtact WitH HiGH VoltaGE tErmiNals  
or DaNGErous aND PossiBlY lEtHal  
ElEctrical sHocK maY rEsult. Do  
Not PErform tHis VoltaGE tEst WHilE  
staNDiNG oN WEt or DamP GrouND,  
WHilE BarEfoot, or WHilE HaNDs or  
fEEt arE WEt.  
d. Actuate the generator main line circuit breaker  
to its “On” or “Closed” position. The utility power  
supply to the transfer switch must be turned off.  
N2A  
A
BRIDGE  
RECTIFIER  
N1  
UTILITY  
N2  
CLOSING  
COIL (C1)  
LIMIT  
SWITCH  
(SW2)  
A
126  
205  
MANUAL  
TRANSFER  
LEVER  
B
E1  
LIMIT  
E2  
SWITCH  
(SW3)  
STANDBY  
CLOSING  
COIL (C2)  
T2  
T1  
E2  
BRIDGE  
RECTIFIER  
B
Figure 1. The Transfer Mechanism  
Page 74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
e. Set the generator AUTO-OFF-MANUAL switch  
to AUTO.  
utility source voltage is available to the standby closing  
coil terminals, but transfer to Standby does not occur,  
the cause of the failure may be (a) a failed standby  
closing coil and/or bridge rectifier, or (b) a seized or  
sticking actuating coil or load contact. This test will help  
you evaluate whether any sticking or binding is present  
in the transfer mechanism.  
(1) The generator should crank and start.  
(2) When the generator starts, an “engine  
warm-up timer” should start timing. After  
about 15 seconds, the transfer relay should  
energize and transfer to the “Standby”  
source should occur.  
PROCEDURE:  
f. If transfer to “Standby” does NOT occur, check  
the voltage across transfer switch Terminal Lugs  
E1 and E2. The generator line-to-line voltage  
should be indicated.  
1. With the generator shut down, set the generator  
AUTO-OFF-MANUAL switch to OFF.  
2. Set the generator main circuit breaker to OFF or “Open”.  
3. Turn off the utility power supply to the transfer switch,  
using whatever means provided (such as a utility source  
main line breaker).  
RESULTS:  
1. If normal transfer to “Standby” occurs, discontinue tests.  
2. If transfer to “Standby” does NOT occur and no voltage  
is indicated across Terminal Lugs E1/E2, determine why  
generator AC output has failed.  
DaNGEr: Do Not attEmPt maNual  
traNsfEr sWitcH oPEratioN uNtil  
all PoWEr VoltaGE suPPliEs to tHE  
sWitcH HaVE BEEN PositiVElY turNED  
off. failurE to turN off all PoWEr  
VoltaGE suPPliEs maY rEsult iN  
EXtrEmElY HaZarDous aND PossiBlY  
lEtHal ElEctrical sHocK.  
*
3. If transfer to “Standby” does NOT occur and voltage  
reading across Terminal Lugs E1/E2 is good, refer to  
Flow Chart.  
teSt 27 – check manual tranSFer  
4. In the transfer switch enclosure, locate the manual  
transfer handle. Handle is retained in the enclosure  
with a wing nut. Remove the wing nut and handle.  
SWitch operation  
DISCUSSION:  
In automatic operating mode, when utility source volt-  
age drops below a preset level, the engine should  
crank and start. On engine startup, an “engine warm-up  
timer” on the generator circuit board should start timing.  
When that timer has timed out (about 15 seconds), the  
transfer relay should energize to deliver utility source  
power to the standby closing coil terminals. If normal  
5. See Figure 2. Insert the un-insulated end of the handle  
over the transfer switch operating lever.  
a. Move the transfer switch operating lever up to  
actuate the load contacts to the Utility position,  
i.e., load connected to the utility source.  
LOAD CONNECTED TO  
LOAD CONNECTED TO  
UTILITY POWER SOURCE  
STANDBY POWER SOURCE  
TRANSFER  
SWITCH  
OPERATING  
LEVER  
MANUAL  
TRANSFER  
HANDLE  
MANUAL  
TRANSFER  
HANDLE  
TRANSFER  
SWITCH  
OPERATING  
LEVER  
Figure 2. Manual Transfer Switch Operation  
Page 75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
b. Actuate the operating lever down to move the  
load contacts against the standby contacts, i.e.,  
load connected to the Standby source.  
caution: after removing the fuse from the bat-  
tery charger, wait 5 minutes before proceeding.  
*
5. Set VOM to measure DC voltage.  
6. Repeat Step 5 several times. As the transfer switch  
operating lever is moved slight force should be needed  
until the lever reaches its center position. As the lever  
moves past its center position, an over-center spring  
should snap the moveable load contacts against the  
stationary STANDBY or UTILITY contacts.  
6. Connect the negative (-) test lead to Wire 0 at the termi-  
nal strip in the transfer switch. Connect the positive (+)  
test lead to Wire 15B at the terminal strip in the transfer  
switch.  
a. If voltage is present, proceed to Step 7.  
7. Finally, actuate the main contacts to their UTILITY power  
source side, i.e., load contacts against the UTILITY contacts  
(upward movement of the operating lever).  
b. If voltage is not present proceed to Step 17.  
7. Connect the positive (+) test lead to Wire 23 at the termi-  
nal strip in the transfer switch.  
RESULTS:  
a. If voltage is present, proceed to Step 8.  
1. If there is no evidence of binding, sticking, or excessive  
force required, refer back to flow chart.  
b. If voltage is not present, set VOM to measure  
resistance.  
c. Remove Wire 23 and Wire 15B going to the  
transfer relay from the transfer switch terminal  
strip. Connect the meter test leads across Wire  
23 and Wire 15B.  
2. If evidence of sticking, binding, excessive force required  
to move main contacts, find cause of binding or sticking  
and repair or replace damaged part(s).  
d. Transfer coil resistance of approximately 115  
ohms should be measured.  
teSt 28 – check 23 and 15B WirinG/  
e. If coil resistance is not measured, remove  
Wire 23 and Wire 15B from the transfer relay.  
Measure across Terminal A and Terminal B of  
the transfer relay.  
connectionS  
DISCUSSION:  
An open circuit in the transfer switch control wir-  
ing can prevent a transfer action from occurring.  
Battery voltage +12 VDC is supplied on Wire 15B.  
This DC voltage is supplied to the transfer relay (TR)  
at Terminal Location “A”. The opposite side of the  
transfer relay (TR) coil (Terminal B) is connected  
to Wire 23. Positive 12 VDC is present on this also.  
Circuit board action will allow current to flow through  
the circuit and the (TR) is energized.  
f. If coil resistance is measured repair or replace  
Wire 23 or Wire 15B between the terminal strip  
and the transfer relay.  
g. If coil resistance is not measured replace trans-  
fer relay and retest.  
8. Connect the negative (-) test lead to the ground lug in  
the generator control panel. Connect the positive (+)  
test lead to Wire 23 in the generator control panel at the  
terminal strip.  
PROCEDURE/ RESULTS:  
Refer to Figure 3.  
a. If voltage is present, proceed to Step 9.  
1. Remove transfer relay mounting screws so that contact  
movement can be visually observed.  
b. If voltage is not present, repair wiring between  
transfer switch and generator control panel.  
9. Remove the J2 connector from the circuit board.  
10.Set VOM to measure resistance.  
2. Set the generator AUTO-OFF-MANUAL switch to the  
AUTO position. Turn off utility power supply to the  
transfer switch, simulating a utility failure. Visually  
watch the transfer relay for contact movement. The  
relay should be energized and contact movement seen  
approximately 10 seconds after the generator starts.  
11.Connect one meter test lead to Wire 23 Pin Location  
J2-5. Connect the other meter test lead to Wire 15B  
Pin Location J2-8. Approximately 115 ohms should be  
measured. (see Figures 4 through 7, Section 4.1).  
a. If the transfer relay energizes, discontinue  
testing. Refer to flow chart.  
a. If approximately 115 ohms is measured proceed  
to Step 12.  
b. If the transfer relay does not energize, continue  
to Step 3.  
b. If infinity or an open is measured, repair Wire 23  
between PCB Connector J2 and the generator  
terminal strip.  
3. Set the generator AUTO-OFF-MANUAL switch to the  
OFF position.  
c. If resistance is not within specification, go to  
Test 29 – Test Transfer Relay.  
4. Remove the battery charger fuse (F3) from the transfer  
switch to disable the battery charge circuit.  
12.Reconnect the J2 connector to the PCB.  
Page 76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
13.Set VOM to measure DC voltage.  
caution: after installing the 7.5a fuse and dis-  
connecting Wire 15B from the generator termi-  
nal strip, wait 5 minutes before proceeding.  
14.Connect the (-) negative meter test lead to Wire 0 at the  
terminal strip in the generator. Connect the (+) positive  
meter test lead to Wire 23 at the terminal strip in the  
generator. 12 VDC should be measured.  
*
27.Connect one meter test lead to Wire 15B. Connect the other  
meter test lead to Wire 0. 12 VDC should be measured.  
15.Place generator AUTO-OFF-MANUAL switch to the  
AUTO position. Turn off utility power supply to the  
transfer switch, simulating a utility failure. After the  
generator starts 10 seconds should elapse before  
transfer occurs. At that time the VOM DC voltage  
should drop to zero. This indicates the PCB energized  
the transfer relay.  
a. If 12 VDC is not measured, replace the printed  
circuit board.  
b. If 12 VDC is measured, a short exists on Wire  
15B or the transfer relay is shorted. Repair or  
replace as needed.  
teSt 29 – teSt tranSFer relay tr  
a. If DC voltage drops to zero, refer to Flow Chart.  
b. If DC voltage remains constant at 12 VDC, pro-  
ceed to Step 16.  
DISCUSSION:  
In automatic operating mode, the transfer relay must  
be energized by circuit board action or standby source  
power will not be available to the standby closing coil.  
Without standby source power, the closing coil will  
remain de-energized and transfer to “Standby” will not  
occur. This test will determine if the transfer relay is  
functioning normally.  
16.With the generator running and utility off, ground Wire 23  
in the control panel at the terminal strip. If transfer relay  
energizes and or transfer occurs, replace the PCB.  
17.Set VOM to measure DC voltage.  
18.Connect the negative (-) test lead to the ground lug in  
the transfer switch. Connect the positive (+) test lead to  
Wire 15B at the terminal strip in the transfer switch.  
126  
205  
a. If voltage is present repair or replace Wire 0  
between transfer switch and generator ground  
lug.  
E1  
b. If voltage is not present proceed to Step 19.  
19.Connect the negative (-) test lead to the ground lug in  
the generator control panel. Connect the positive (+) test  
lead to Wire 15B at the terminal strip in the generator  
control panel.  
a. If voltage is present, repair Wire 15B between  
generator terminal strip and transfer switch  
terminal strip.  
N1A  
23  
15B  
b. If voltage is not present, proceed to Step 20.  
COIL NOMINAL RESISTANCE = 120 Ohms  
20.Remove the J2 connector from the circuit board.  
Figure 3. Transfer Relay Test Points  
21.Set VOM to measure ohms. Connect one meter test lead  
to Wire 15B at the control panel terminal strip. Connect  
the other meter test lead to Wire 15B Pin Location J2-8.  
Continuity should be measured.  
PROCEDURE:  
1. See Figure 3. Disconnect all wires from the transfer  
relay, to prevent interaction.  
a. If continuity is not measured, repair pin connection  
and or Wire 15B between the J2 connector and  
terminal strip.  
2. Set a VOM to its “R x 1” scale and zero the meter.  
3. Connect the VOM test leads across Relay Terminals 6  
and 9 with the relay de-energized. The VOM should read  
INFINITY.  
b. If continuity is measured proceed to Step 22.  
22.Remove the 7.5A fuse.  
23.Reconnect J2 connector.  
DESIRED METER READING  
CONNECT VOM TEST  
LEADS ACROSS  
24.Install the 7.5A fuse.  
ENERGIZED  
Continuity  
Infinity  
DE-ENERGIZED  
25.Disconnect Wire 15B from the generator terminal strip.  
26.Set VOM to measure DC voltage.  
Terminals 6 and 9  
Terminals 1 and 7  
Infinity  
Continuity  
Page 77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
a. If 240 VAC is not measured, replace transfer  
relay.  
4. Using jumper wires, connect the positive (+) post of a  
12 volt battery to relay Terminal “A” and the negative  
(-) battery post to Relay Terminal “B”. The relay should  
energize and the VOM should read CONTINUITY.  
b. If 240 VAC is measured, proceed to Step 9.  
9. Measure across points A and F. 240 VAC should be  
measured.  
5. Now, connect the VOM test leads across Relay Terminals  
1 and 7.  
a. If 240 VAC is not measured, repair or replace  
Wire 205.  
a. Energize the relay and the meter should  
indicate INFINITY.  
b. If 240 VAC is measured, proceed to Step 10.  
b. De-energize the relay and the VOM should read  
CONTINUITY.  
10.Measure across points A and G. 240 VAC should be  
measured.  
a. If 240 VAC is not measured, verify limit switch  
SW3 is wired correctly. Proceed to Test 33.  
RESULTS:  
1. Replace transfer relay if it is defective.  
b. If 240 VAC is measured, proceed to Step 11.  
2. If transfer relay checks good go to Test 31.  
11.Measure across points A and H. 240 VAC should be  
measured.  
a. If 240 VAC is not measured, repair or replace  
Wire B.  
teSt 30 – StandBy control circuit  
b. If 240VAC is measured, replace standby coil C2.  
DISCUSSION:  
coil nominal resistance is 1-2 megohms.  
Refer to Figure 4. The standby coil (C2) requires 240  
VAC to energize. When the transfer relay is energized,  
240 VAC is applied to standby coil C2. Once energized,  
the coil will pull the transfer switch down to the standby  
position. Once in the standby position, limit switch SW3  
will open, removing AC to standby coil C2.  
teSt 31 – check Wire 23  
DISCUSSION:  
Printed circuit board action controls grounding Wire  
23 to initiate a transfer to standby. When Wire 23 is  
grounded the transfer relay (TR1) is energized. To  
initiate a transfer back to utility the TR1 relay must be  
de-energized. If Wire 23 is grounded, TR1 will always  
be energized.  
PROCEDURE/ RESULTS:  
1. Set VOM to measure AC voltage.  
2. Verify the transfer switch is up in the utility position.  
3. Remove Wire E2 from standby coil C2.  
4. Set the generator AUTO-OFF-MANUAL switch in the  
AUTO position. Turn off the utility power supply to the  
transfer switch, simulating a utility failure. The generator  
should start and the transfer relay should energize.  
PROCEDURE/ RESULTS:  
1. Set VOM to measure DC voltage.  
2. Set the generator AUTO-OFF-MANUAL switch in the  
OFF position.  
5. Measure across points A and B. 240 VAC should be  
measured.  
3. Connect the positive (+) meter test lead to Wire 15B  
at the terminal strip in the transfer switch. Connect the  
negative (-) meter test lead to Wire 23 at the terminal  
strip in the transfer switch.  
a. If 240 VAC is not measured go back to Test 26.  
b. If 240 VAC is measured, proceed to Step 6.  
6. Measure across points C (Wire E2 previously removed)  
and B. 240 VAC should be measured.  
a. If 0 VDC is measured, proceed to Step 4.  
b. If 12 VDC is measured, proceed to Step 6.  
a. If 240 VAC is not measured, repair or replace  
Wire E2.  
4. Set the generator AUTO-OFF-MANUAL switch in the  
AUTO position.  
b. If 240 VAC is measured, proceed to Step 7.  
5. Connect the positive (+) meter test lead to Wire 15B  
at the terminal strip in the transfer switch. Connect the  
negative (-) meter test lead to Wire 23 at the terminal  
strip in the transfer switch  
7. Measure across points A and D. 240 VAC should be  
measured.  
a. If 240 VAC is not measured, repair or replace  
Wire E1.  
a. If 12 VDC is measured, procced to Step b.  
b. If 240 VAC is measured, proceed to Step 8.  
b. Navigate to the Digital Output Display Screen  
(see Figure 5).  
8. Measure across points A and E. 240 VAC should be  
measured.  
(1) Press “ESC” until the main menu is reached.  
Page 78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
Figure 4. Standby Control Circuit Test Points  
Page 79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
(2) Press the right arrow key until “Debug” is  
flashing.  
CUSTOMER SIDE  
(3) Press “Enter”.  
N1/N2  
(4) Press the right arrow key until “Outputs” is  
flashing.  
CONTROL BOARD  
CONNECTION  
(5) Press “Enter”.  
N1 N2  
(6) Digital Output 8 is Wire 23 output from the  
board. Refer to Figure 5.  
(7) If Output 8 shows a “1” then the control  
board is grounding Wire 23. Replace the  
printed circuit board.  
GENERATOR  
TERMINAL STRIP  
c. If 0 VDC is measured, the Wire 23 circuit is  
good. Refer to flow chart.  
DEBUG  
Figure 6. Transfer Relay Test Points  
9. Disconnect the J2 connector from the printed circuit board.  
10.Set VOM to measure resistance.  
OUTPUTS  
11.Connect one meter test lead to Wire 23 connected at  
generator terminal strip. See Figure 6. Connect the other  
meter test lead to control panel ground.  
OUTPUTS 1 - 8:  
1 0 1 1 0 0 0 1  
a. If INFINITY or open is measured, replace the  
printed circuit board  
OUTPUT 8  
b. If continuity measured, Wire 23 is shorted to  
ground. Repair or replace Wire 23 between the  
J2 connector and the generator terminal strip.  
Figure 5. The Home Page, Debug and Output Screens  
6. Locate the terminal strip in the generator control panel.  
Disconnect Wire 23 coming in from the transfer switch  
(customer connection, side-see Figure 6).  
teSt 32 – utility control circuit  
DISCUSSION:  
7. Connect the positive (+) meter test lead to Wire 15B at  
the terminal strip in the generator. Connect the nega-  
tive (-) meter test lead to Wire 23 just removed from  
the terminal strip.  
Printed circuit board action controls grounding Wire  
23 to initiate a transfer to standby. When Wire 23 is  
grounded the transfer relay (TR1) is energized. To  
initiate a transfer back to utility the TR1 relay must be  
de-energized. If Wire 23 is grounded, TR1 will always  
be energized.  
a. If 0 VDC is measured, proceed to Step 8.  
b. If 12 VDC is measured, a short to ground exists  
on Wire 23 between the generator and transfer  
switch. Repair or replace Wire 23 as needed  
between generator control panel and transfer  
switch relay (TR1).  
PROCEDURE/ RESULTS:  
Refer to Figure 7.  
1. Turn off utility supply voltage to the transfer switch.  
2. Set VOM to measure AC voltage.  
8. Locate the terminal strip in the generator control panel.  
Disconnect Wire 23 coming in from the transfer switch  
(customer connection, side - see Figure 6).  
3. Set the generator AUTO-OFF-MANUAL switch in the  
OFF position. Remove Wire 15B from the transfer switch  
terminal strip.  
4. Verify the transfer switch is down in the standby position.  
Page 80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
Figure 7. Utility Control Circuit Test Points  
Page 81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
5. Remove Wire N2A from the utility coil C1.  
teSt 33 – teSt limit SWitch SW2 and SW3  
6. Turn on utility power supply to the transfer switch.  
DISCUSSION:  
a. If transfer to utility occurs, Wire 23 is grounded.  
Proceed to Test 31.  
The limit switches are wired to the normally closed  
contacts. When the switches are activated the  
contacts open.  
b. If transfer to utility does not occur, proceed to  
Step 7.  
PROCEDURE:  
7. Measure across points A and B. 240 VAC should be  
measured.  
With the generator shut down, the generator main  
circuit breaker turned OFF, and with the utility power  
supply to the transfer switch turned OFF, test limit  
switch SW2/SW3 as follows:  
a. If 240 VAC is not measured, verify utility source.  
b. If 240 VAC is measured, proceed to Step 8.  
1. To prevent interaction, disconnect Wire 126 and Wire A  
from limit switch SW2 terminals.  
8. Measure across points C (Wire N2A previously removed)  
and B. 240 VAC should be measured.  
2. Set a VOM to its “R x 1” scale and zero the meter.  
a. If 240 VAC is not measured, repair or replace  
Wire N2A.  
3. See Figure 1. Connect the VOM meter test leads  
across the two outer terminals from which the wires  
were disconnected.  
b. If 240 VAC is measured, proceed to Step 9.  
9. Measure across points A and D. 240 VAC should be  
measured.  
4. Manually actuate the main contacts to their Standby  
position. The meter should read CONTINUITY.  
a. If 240 VAC is not measured, repair or replace  
Wire N1A.  
5. Manually actuate the main contacts to their Utility  
position. The meter should read INFINITY.  
b. If 240 VAC is measured, proceed to Step 10.  
10.Measure across points A and E. 240 VAC should be  
measured.  
6. Repeat Steps 4 and 5 several times and verify the VOM  
reading at each switch position.  
a. If 240 VAC is not measured, repair or replace  
Wire N1A.  
7. To prevent interaction, disconnect Wire 205 and Wire B  
from limit switch SW3 terminals.  
b. If 240 VAC is measured, proceed to Step 11.  
11.Measure across points A and F. 240 VAC should be  
measured.  
8. See Figure 1. Connect the VOM meter test leads  
across the two outer terminals from which the wires  
were disconnected.  
a. If 240 VAC is not measured, replace transfer  
relay.  
9. Manually actuate the main contacts to their Standby  
position. The meter should read INFINITY.  
b. If 240 VAC is measured, proceed to Step 12.  
12.Measure across points A and G. 240 VAC should be  
measured.  
10.Manually actuate the main contacts to their Utility  
position. The meter should read CONTINUITY.  
a. If 240 VAC is not measured, repair or replace  
Wire 126.  
11.Repeat Steps 4 and 5 several times and verify the VOM  
reading at each switch position.  
b. If 240 VAC is measured, proceed to Step 13.  
13.Measure across points A and H. 240 VAC should be  
measured.  
RESULTS:  
1. If Limit Switch SW2 or SW3 fails the test, remove and  
replace the switch or adjust switch until it is actuated  
properly.  
a. If 240 VAC is not measured, verify limit switch  
SW2 is wired correctly. Proceed to Test 33.  
b. If 240 VAC is measured, proceed to Step 14.  
14.Measure across points A and I. 240 VAC should be  
measured.  
teSt 34 – check FuSeS F1 and F2  
a. If 240 VAC is not measured, repair or replace  
Wire A.  
DISCUSSION:  
Fuses F1 and F2 are connected in series with the N1  
and N2 circuits, respectively. A blown fuse will open  
the applicable circuit and will result in (a) generator  
startup and transfer to “Standby”, or (b) failure to  
retransfer back to the utility source.  
b. If 240 VAC is measured, replace utility coil C1.  
Coil nominal resistance is 1-2 megohms.  
Page 82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
PROCEDURE:  
6. Connect the positive meter test lead to Wire N1 at the  
terminal block in the control panel.  
1. On the generator panel, set the AUTO-OFF-MANUAL  
switch to OFF.  
a. Connect the negative meter lead to the ground  
lug. INFINITY should be measured.  
2. Turn off the utility power supply to the transfer switch,  
using whatever means provided.  
b. Connect the negative meter lead to Wire  
23 at the terminal strip. INFINITY should be  
measured.  
3. Remove fuses F1 and F2 from the fuse holder (see  
Figure 8).  
c. Connect the negative meter lead to Wire 15B at  
the terminal strip. INFINITY should be measured.  
4. Inspect and test fuses for blown condition. With a VOM  
set to measure resistance, CONTINUITY should be  
measured across the fuse.  
d. Connect the negative meter lead to Wire 0 at the  
terminal strip. INFINITY should be measured.  
e. Connect the negative meter lead to Wire N2 at the  
terminal block. INFINITY should be measured.  
F2  
f. Connect the negative meter lead to the neutral  
connection. INFINITY should be measured.  
N1A  
N2A  
BLACK  
7. Connect the positive meter test lead to Wire N2 at the  
terminal block in the control panel.  
a. Connect the negative meter lead to the ground  
lug. INFINITY should be measured.  
F3  
b. Connect the negative meter lead to Wire 23 at  
the terminal strip. INFINITY should be measured.  
F1  
c. Connect the negative meter lead to Wire 15B at  
the terminal strip. INFINITY should be measured.  
d. Connect the negative meter lead to Wire  
0 at the terminal strip. INFINITY should be  
measured.  
N1  
N2  
T1  
e. Connect the negative meter lead to the neutral  
connection. INFINITY should be measured.  
RESULTS:  
Figure 8. Fuse Holder and Fuses  
If a short is indicated in Step 6 or Step 7, repair wiring  
and re-test.  
RESULTS:  
1. Replace blown fuse(s) as needed.  
teSt 36 – check n1 and n2 VoltaGe  
teSt 35 – check n1 and n2 WirinG  
DISCUSSION:  
Loss of utility source voltage to the generator will initi-  
ate a startup and transfer by the generator. Testing at  
the control panel terminal block will divide the system  
in two, thereby reducing troubleshooting time.  
DISCUSSION:  
A shorted Wire N1 or N2 to ground can cause fuse F1  
or F2 to blow.  
PROCEDURE:  
PROCEDURE:  
1. On the generator panel, set the AUTO-OFF-MANUAL  
switch to OFF.  
1. Set the AUTO-OFF-MANUAL switch to OFF.  
2. Set a VOM to measure AC voltage.  
2. Turn off the utility power supply to the transfer switch,  
using whatever means provided.  
3. See Figure 9. Connect one test lead to Wire N1 at the  
terminal block in the generator control panel. Connect  
the other test lead to Wire N2. Utility line-to-line voltage  
should be measured.  
3. Remove fuses F1, F2, and F3 from the fuse holder (see  
Figure 7).  
4. Remove the generator control panel cover. Disconnect  
the N1/N2 connector that supplies the printed circuit  
board located in the control panel (see Figure 6).  
RESULTS:  
Refer to Flow Chart  
5. Set VOM to measure resistance.  
Page 83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
PROCEDURE:  
With utility source voltage available to terminal lugs  
N1 and N2, use a VOM to test for utility source line-  
to-line voltage across terminal locations N1 and N2  
terminals. Normal line-to-line utility source voltage  
should be indicated.  
240 VAC  
TEST POINTS  
N1A N2A  
N2  
N1  
A
A
A
F1 F2 F3  
Figure 9. Terminal Block Test Points  
B
B
B
teSt 37 – check utility SenSinG  
VoltaGe at the circuit Board  
N1  
N2  
T1  
DISCUSSION:  
Figure 10. Transfer Switch Fuse Block  
If the generator starts and transfer to STANDBY  
occurs in the automatic mode when acceptable  
UTILITY source voltage is available at the terminal  
block, the next step is to determine if sensing voltage  
is reaching the printed circuit board.  
RESULTS:  
1. If voltage reading across the N1 and N2 terminals is  
zero or low, refer to Flow Chart.  
note:the System ready led will flash in auto or  
utility loSt will display on the panel.  
2. If voltage reading is good, refer to Flow Chart.  
PROCEDURE:  
1. Set the AUTO-OFF-MANUAL switch to OFF.  
teSt 39 – check VoltaGe at terminal  
2. Disconnect the N1/N2 connector in the control panel  
(see Figure 6).  
luGS n1, n2  
DISCUSSION:  
3. Set a VOM to measure AC voltage.  
If source voltage is not available to N1/N2 terminals,  
automatic startup and transfer to STANDBY will occur  
when the generator AUTO-OFF-MANUAL switch is  
set to AUTO. This test will prove that “Utility” voltage is  
available to those terminals, or is not available.  
4. Connect one meter test lead to Wire N1. Connect the  
other meter test lead to Wire N2. Approximately 240  
VAC should be measured. See Figure 9.  
RESULTS:  
DaNGEr: ProcEED WitH cautioN! HiGH  
aND DaNGErous VoltaGEs arE PrEsENt  
at tErmiNal luGs N1/N2. coNtact WitH  
HiGH VoltaGE tErmiNals Will rEsult  
iN DaNGErous aND PossiBlY lEtHal  
ElEctrical sHocK. Do Not attEmPt  
tHis tEst WHilE staNDiNG oN WEt or  
DamP GrouND, WHilE BarEfoot, or  
WHilE HaNDs or fEEt arE WEt.  
1. If voltage was measured in Step 4 and the pin connec-  
tions are good, replace the circuit board.  
*
2. If voltage was NOT measured in Step 4, repair or replace  
Wire N1/N2 between connector and terminal block.  
teSt 38 – check utility SenSe VoltaGe  
The N1 and N2 terminals in the transfer switch deliver  
utility voltage “sensing” to a circuit board. If voltage at  
the terminals is zero or low, standby generator startup  
and transfer to the “Standby” source will occur auto-  
matically as controlled by the circuit board. A zero  
or low voltage at these terminals will also prevent  
retransfer back to the “Utility” source.  
PROCEDURE:  
1. Make sure that all main line circuit breakers in the utility  
line to the transfer switch are “On” or “Closed.”  
Page 84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN3.4  
DiaGNostictEsts
TRANSFER SWITCH  
Part 3  
1
2
TRANSFER SWITCH  
C1  
E
A
N1  
N2  
N
SW2  
SW3  
LC  
SW1  
B
A
E1  
T1  
E2  
T2  
B
C2  
1
2
BC  
A
A
A
D
C
B
A
F1 F2 F3  
B
B
B
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
-
+
BLK  
WIRE  
RED  
WIRE  
T1  
15B  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
TB1-TERMINAL STRIP  
0
G
I
F
1
2
3
TB1  
H
GENERATOR  
1
MAIN  
CONTROLLER  
2
3
4
J1  
J3  
K
J
J2  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18  
L
0
M
0
0
0
0
0
PANEL GND  
0
0
0
N
Figure 11. Test 40, 41, and 42 “Pre-Wire Load Center” Test Points.  
Page 85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
PROCEDURE:  
2. Test for utility source line-to-line voltage across Terminal  
Lugs N1 and N2 (see Figure 1). Normal utility source  
voltage should be indicated.  
Refer to Figure 11.  
1. Set VOM to measure DC voltage.  
2. Remove Wire 0 and Wire 15B from transfer switch  
terminal strip points F and G.  
RESULTS:  
1. If low or no voltage is indicated, find the cause of the  
problem and correct.  
3. Measure across points H and I. Battery supply voltage  
(12 VDC) should be measured.  
2. If normal utility source voltage is indicated, refer to  
Flow Chart.  
a. If battery voltage is not measured, wait 5 minutes  
and repeat Step 3.  
b. If battery supply voltage is still not available,  
refer to Flow Chart.  
teSt 40 – check Battery charGer  
Supply VoltaGe  
c. If battery voltage is measured, proceed to Step 4.  
4. Reconnect Wire 0 and Wire 15B previously removed  
in Step 2.  
“pre-Wire load center”  
DISCUSSION:  
5. Measure across points H and I. 13.4 VDC should  
be measured.  
The battery charger is supplied with 120 VAC. The  
output of the battery charger is 13.4 VDC / 2.5A.  
a. If 13.4 VDC is not measured, replace the  
battery charger  
PROCEDURE:  
b. If 13.4 VDC is measured, the charger is working.  
Refer to Figure 11.  
*note: Battery charger voltage will be higher than  
battery supply voltage.  
1. Set VOM to measure AC voltage.  
2. Measure across points A and B. 240 VAC should be  
measured.  
teSt 42 – check Wire 0 and Wire15B  
a. If 240 VAC is not measured, verify load source  
voltage.  
“pre-Wire load center”  
b. If 240 VAC is measured go to Step 3.  
DISCUSSION:  
3. Measure across points A and C. 240 VAC should be  
measured.  
In order for the battery charger to function, battery supply  
voltage must be available to the battery charger.  
a. If 240 VAC is not measured, repair or replace  
Wire T1.  
PROCEDURE:  
Refer to Figure 11.  
b. If 240VAC is measured, proceed to Step 4.  
1. Set VOM to measure DC voltage.  
4. Measure across points A and D. 240 VAC should be  
measured.  
2. Disconnect Wire 0 and Wire 15B from generator terminal  
strips, locations J and K.  
a. If 240 VAC is not measured, replace fuse F3.  
b. If 240VAC is measured, proceed to Step 5.  
3. Wait five (5) minutes after removing wires.  
5. Remove Fuse F3. Measure across points D and C.  
120 VAC should be measured.  
4. Measure across points L and M on the terminal strip.  
12 VDC should be measured.  
a. If 120 VAC is not measured, verify neutral wire  
is connected at point E. If good, replace battery  
charger, then retest.  
a. If 12 VDC is measured, proceed to Step 6.  
b. If 12 VDC is not measured, proceed to Step 5.  
5. Measure across points M and N. 12 VDC should be  
measured.  
b. If 120VAC is measured, refer to Flow Chart.  
a. If 12 VDC is measured, repair or replace Wire  
0 between the generator terminal strip and the  
ground lug.  
teSt 41 – check Battery charGer  
output VoltaGe  
“pre-Wire load center”  
b. If 12 VDC is not measured, proceed to Step 8.  
6. Set VOM to measure resistance.  
DISCUSSION:  
7. Connect the meter test leads across the disconnected  
Wire 0 and Wire 15B. Approximately 115 Ohms should  
be measured.  
The battery charger is supplied with 120VAC. The out-  
put of the battery charger is 13.4 VDC / 2.5A.  
Page 86  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
a. If 115 Ohms is measured, proceed to Step 10.  
teSt 44 – check Battery charGer  
output VoltaGe  
“rtSn & rtSe tranSFer SWitch”  
b. If zero resistance or CONTINUITY is measured,  
connect the meter test leads across Terminals  
A and B on the transfer relay (TR1)  
c. If zero resistance is measured, a short exists.  
Replace TR1.  
DISCUSSION:  
The battery charger is supplied with 120 VAC. The  
output of the battery charger is 13.4 VDC/2.5A.  
d. If 115 Ohms is measured, repair or replace  
Wire 15B between the generator and the  
transfer switch.  
PROCEDURE:  
8. Set VOM to measure resistance.  
Refer to Figure 12 or Figure 12A.  
1. Set VOM to measure DC voltage.  
9. Disconnect the J2 connector from the printed circuit board.  
10.Measure across point M and pin location J2-8 of the con-  
nector just removed. Continuity should be measured.  
2. Remove and isolate battery charger black and red leads  
from generator terminal strip points G and H.  
a. If continuity is not measured, repair or replace  
Wire 15B between the J2 connector and the  
terminal strip.  
3. Measure across points G and H. Battery supply voltage  
(12 VDC) should be measured.  
a. If battery voltage is not measured, wait 5 minutes  
and repeat Step 3. If battery supply voltage is still  
not available, refer to Flow Chart.  
b. If continuity is measured and the pin connection  
looks good, the internal fuse on the PCB has  
failed. Replace printed circuit board.  
b. If battery voltage is measured, proceed to Step 4.  
4. Reconnect battery charger black and red lead wires  
previously removed in Step 2.  
teSt 43 – check Battery charGer  
Supply VoltaGe  
“rtSn & rtSe tranSFer SWitch”  
5. Measure across points G and H. 13.4 VDC should be  
measured.  
a. If 13.4 VDC is not measured, replace the  
battery charger  
DISCUSSION:  
The battery charger is supplied with 120 VAC. The  
output of the battery charger is 13.4 VDC/2.5A.  
b. If 13.4 VDC is measured, the charger is working.  
*note : Battery charger voltage will be higher  
than battery supply voltage.  
PROCEDURE:  
Refer to Figure 12 or Figure 12A.  
1. Set VOM to measure AC voltage.  
teSt 45 – check Wire 0/15B  
2. Measure across points A and B. 240 VAC should be  
measured.  
“rtSn & rtSe tranSFer SWitch”  
a. If 240 VAC is not measured, verify load source  
voltage.  
DISCUSSION:  
In order for the battery charger to function, battery supply  
voltage must be available to the battery charger.  
b. If 240 VAC is measured, proceed to Step 3.  
3. Measure across points A and C. 240 VAC should be  
measured.  
PROCEDURE:  
Refer to Figure 12 or Figure 12A.  
1. Set VOM to measure DC voltage.  
a. If 240 VAC is not measured, repair or replace  
wire between fuse block and T1 terminal.  
2. Remove and isolate battery charger black and red leads  
from generator terminal strip points G and H.  
b. If 240VAC is measured, proceed to Step 4.  
4. Measure across points A and D. 240 VAC should be  
measured.  
3. Measure across points G and H on the terminal strip.  
12VDC should be measured.  
a. If 240 VAC is not measured, replace 5A fuse.  
b. If 240 VAC is measured, proceed to Step 5.  
a. If 12 VDC is measured, the charger should be  
functioning.  
5. Measure across points E and F. 120 VAC should be  
measured.  
b. If 12 VDC is not measured, proceed to Step 4.  
4. Remove Wire 0 and Wire 15B from generator terminal  
strip locations G and H.  
a. If 120 VAC is not measured, repair or replace  
supply wires BC line and BC 00.  
5. Wait five (5) minutes after removing wires.  
b. If 120 VAC is measured, refer to flow chart.  
Page 87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
F U S E  
5 A M P  
1 9 4  
2 3  
1 5 B  
2 3  
N 2  
N 1  
N 2  
N 1  
2 3  
1 5 B  
0
B C L I N E  
B C 0 0  
2 3  
1 5 B  
0
Figure 12. Test 43, 44, and 45 “RTSN Transfer Switch” Test Points.  
Page 88  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
1 5 B  
2 3  
N 2  
N 1  
F U S E  
5 A M P  
B C L I N E  
B C 0 0  
2 3  
1 5 B  
0
B C L I N E  
B C 0 0  
2 3  
1 5 B  
0
Figure 12A. Test 43, 44, and 45 “RTSE Transfer Switch” Test Points.  
Page 89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
b. If 120 VAC is measured, proceed to Step 3.  
6. Measure across points G and H on the terminal strip.  
12 VDC should be measured.  
3. Measure across points C and D. 120 VAC  
should be measured.  
a. If 12 VDC is measured, proceed to Step 8.  
b. If 12 VDC is not measured, proceed to Step 7.  
a. If 120 VAC is not measured, repair or replace  
Wire BC LINE or BC 00 between the load cen-  
ter and the generator.  
7. Measure across point H and ground lug. 12 VDC should  
be measured.  
b. If 120 VAC is measured, refer to Flow Chart.  
a. If 12 VDC is measured, repair or replace Wire  
0 between the generator terminal strip and the  
ground lug.  
teSt 47 – check Battery charGer  
output VoltaGe  
b. If 12 VDC is not measured, proceed to Step 8.  
“Genready load center”  
8. Set VOM to measure resistance.  
9. Connect the meter test leads across the disconnected  
Wire 0 and Wire 15B. Approximately 115 Ohms should  
be measured.  
DISCUSSION:  
The battery charger is supplied with 120VAC. The  
output of the battery charger is 13.4 VDC / 2.5A.  
a. If 115 Ohms is measured, proceed to Step 11.  
PROCEDURE:  
b. If zero resistance or CONTINUITY is measured,  
connect the meter test leads across Terminals  
A and B on the transfer relay (TR1)  
Refer to Figure 13.  
1. Set VOM to measure DC voltage.  
c. If zero resistance is measured, a short exists.  
Replace TR1.  
2. Remove and isolate battery charger black and red leads  
from generator terminal strip points E and F.  
d. If 115 Ohms is measured, repair or replace  
Wire 15B between the generator and the  
transfer switch.  
3. Measure across points E and F. Battery supply voltage  
(12 VDC) should be measured.  
10.Disconnect the J2 connector from the printed circuit  
board.  
a. If battery voltage is not measured, wait 5 min-  
utes and repeat Step 3. If battery supply voltage  
is still not available, refer to Flow Chart.  
11.Measure across point M and pin location J2-8 of the con-  
nector just removed. CONTINUITY should be measured.  
b. If battery voltage is measured, proceed to Step 4.  
4. Reconnect battery charger black and red lead wires  
previously removed in Step 2.  
a. If CONTINUITY is not measured, repair or  
replace Wire 15B between the J2 connector  
and the terminal strip.  
5. Measure across points E and F. 13.4 VDC should be  
measured.  
b. If CONTINUITY was measured and the pin con-  
nection looks good, the internal fuse on the PCB  
has failed. Replace the printed circuit board.  
a. If 13.4 VDC is not measured, replace the  
battery charger.  
b. If 13.4 VDC is measured, the charger is working.  
teSt 46 – check Battery charGer  
Supply VoltaGe  
*note: Battery charger voltage will be higher than  
battery supply voltage.  
“Genready load center”  
teSt 48 – check Wire 0/15B  
“Genready load center”  
DISCUSSION:  
The battery charger is supplied with 120VAC. The  
output of the battery charger is 13.4 VDC / 2.5A.  
DISCUSSION:  
PROCEDURE:  
In order for the battery charger to function, battery supply  
voltage must be available to the battery charger.  
Refer to Figure 13.  
1. Set VOM to measure AC voltage.  
PROCEDURE:  
2. Measure across points A and B. 120 VAC should be  
measured.  
Refer to Figure 13.  
1. Set VOM to measure DC voltage.  
a. If 120 VAC is not measured, verify that load  
source voltage is available, and that the duplex  
circuit breaker in ON.  
2. Remove and isolate battery charger black and red leads  
from generator terminal strip points E and F.  
Page 90  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
B C L I N E  
B C 0 0  
B C L I N E  
B C 0 0  
2 3  
1 5 B  
0
2 3  
1 5 B  
0
B C - 0 0  
B C - L I N E  
Figure 13. Test 46, 47, and 48 “GenReady Load Center” Test Points.  
Page 91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
PROCEDURE:  
3. Measure across points G and H on the terminal strip.  
12VDC should be measured.  
Refer to Figure 14.  
1. Set VOM to measure AC voltage.  
a. If 12 VDC is measured, the charger should be  
functioning.  
2. Measure across points A and B. 240 VAC should be  
measured.  
b. If 12 VDC is not measured, proceed to Step 4.  
4. Remove Wire 0 and Wire 15B from generator terminal  
strip locations E and F.  
a. If 240 VAC is not measured, verify load source  
voltage at ATS.  
b. If 240 VAC is measured, proceed to Step 3.  
5. Wait five (5) minutes after removing wires.  
3. Measure across points A and C. 240 VAC should be  
measured.  
6. Measure across points E and F on the terminal strip.  
12 VDC should be measured.  
a. If 240 VAC is not measured, repair or replace  
Wire T1 between LSS and J3 terminal of load  
shed controller.  
a. If 12 VDC is measured, proceed to Step 8.  
b. If 12 VDC is not measured, proceed to Step 7.  
7. Measure across point H and ground lug. 12 VDC should  
be measured.  
b. If 240VAC is measured, proceed to Step 4.  
4. Measure across points C and D. 120 VAC should be  
measured.  
a. If 12 VDC is measured, repair or replace Wire  
0 between the generator terminal strip and the  
ground lug.  
a. If 120 VAC is not measured, repair or replace  
Wire 00 between J3 terminal and neutral block  
(NB).  
b. If 12 VDC is not measured, proceed to Step 8.  
8. Set VOM to measure resistance.  
b. If 120 VAC is measured, proceed to Step 5.  
9. Connect the meter test leads across the disconnected  
Wire 0 and Wire 15B. Approximately 200 Ohms should  
be measured.  
5. Measure across points E and D. 120 VAC should be  
measured.  
a. If 120 VAC is not measured, replace fuse F3 on  
load shed controller.  
a. If 200 Ohms is measured, proceed to Step 11.  
b. If 120 VAC is measured, proceed to Step 6.  
b. If zero resistance or CONTINUITY is measured,  
connect the meter test leads across BAT- and  
XFER on the load center motor.  
6. Measure across points E and F. 120 VAC should be  
measured.  
c. If zero resistance is measured, a short exists.  
Replace the load center motor.  
a. If 120 VAC is not measured, replace load shed  
controller.  
d. If 200 Ohms to INFINITY is measured, repair  
or replace Wire 15B between the generator and  
the load center.  
b. If 120 VAC is measured, refer to Flow Chart.  
teSt 50 – check Battery charGer  
output VoltaGe  
10.Disconnect the J2 connector from the printed circuit board.  
11.Measure across point M and pin location J2-8 of the  
connector just removed. CONTINUITY should be  
measured.  
“load Shed tranSFer SWitch”  
DISCUSSION:  
a. If CONTINUITY is not measured, repair or  
replace Wire 15B between the J2 connector  
and the terminal strip.  
The battery charger is supplied with 120 VAC. The  
output of the battery charger is 13.4 VDC/2.5A.  
b. If CONTINUITY is measured and the pin con-  
nection looks good, the internal fuse on the PCB  
has failed. Replace the printed circuit board.  
PROCEDURE:  
Refer to Figure 14.  
1. Set VOM to measure DC voltage.  
2. Remove and isolate battery charger black and red leads  
from generator terminal strip points G and H.  
teSt 49 – check Battery charGer  
Supply VoltaGe  
3. Measure across points G and H. Battery supply voltage  
(12 VDC) should be measured.  
“load Shed tranSFer SWitch”  
a. If battery voltage is not measured, wait 5 min-  
utes and repeat Step 3. If battery supply voltage  
is still not available, refer to Flow Chart.  
DISCUSSION:  
The battery charger is supplied with 120 VAC. The  
output of the battery charger is 13.4 VDC/2.5A.  
b. If battery voltage is measured, proceed to Step 4.  
Page 92  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
A D L C O O N N E C T I O N  
N O N - E S S E N T I A L  
O U T P U T C O N N E C T I O N  
G E N E R A  
O T R  
E 1 A  
6
5
4
3
2
1
7
6
5
4
3
2
1
3
6
2
5
1
4
3
2
5
1
4
6
9
B
9
8
7
8
7
B
A
A
1
2
3
Figure 14. Test 49, 50, and 51 “Load Shed Transfer Switch” Test Points.  
Page 93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 3.4  
DiaGNostic tEsts  
TRANSFER SWITCH  
Part 3  
4. Reconnect battery charger black and red lead wires  
previously removed in Step 2.  
7. In the generator control panel, measure across Wire 15B  
and Wire 0 at the customer connection. 12 VDC should  
be measured.  
5. Measure across points G and H. 13.4 VDC should be  
measured.  
a. If 12 VDC is measured, repair or replace Wire  
0 or Wire 15B between the generator terminal  
strip and the ground lug.  
a. If 13.4 VDC is not measured, replace the  
battery charger.  
b. If 12 VDC is not measured, proceed to Step 5.  
b. If 13.4 VDC is measured, the charger is working.  
8. Set VOM to measure resistance.  
*note: Battery charger voltage will be higher than  
battery supply voltage.  
9. Connect the meter test leads across the disconnected  
Wire 0 and Wire 15B. Approximately 115 Ohms should  
be measured.  
teSt 51 – check Wire 0 and Wire 15B  
a. If 115 Ohms is measured, proceed to Step 11.  
“load Shed tranSFer SWitch”  
b. If zero resistance or CONTINUITY is measured,  
connect the meter test leads across locations J  
and k on the load shed controller, Figure 12.  
DISCUSSION:  
In order for the battery charger to function, battery supply  
voltage must be available to the battery charger.  
c. If zero resistance is measured, a short exists.  
Replace the transfer relay (TR).  
d. If 200 115 is measured, repair or replace Wire  
15B between the generator and the transfer  
switch.  
PROCEDURE:  
Refer to Figure 14.  
1. Set VOM to measure DC voltage.  
10.Disconnect the J2 connector from the printed circuit  
board.  
2. Remove and isolate battery charger black and red leads  
from terminal strip points G and H.  
11.In the generator control panel, measure across Wire  
15B at the customer connection and pin location J2-8  
of the connector just removed. CONTINUITY should be  
measured.  
3. Measure across points I and J on the terminal strip. 12  
VDC should be measured.  
a. If 12 VDC is measured, the charger should be  
functioning.  
a. If CONTINUITY is not measured, repair or  
replace Wire 15B between the J2 connector  
and the terminal strip.  
b. If 12 VDC is not measured, proceed to Step 4.  
4. Remove Wire 0 and Wire 15B from generator terminal  
strip. Refer to Figure 6.  
b. If CONTINUITY is measured, proceed to Step 12.  
12. In the generator control panel, measure across Wire  
0 at the customer connection and the ground lug.  
CONTINUITY should be measured.  
5. Wait five (5) minutes after removing wires.  
6. Measure across points J and K on the terminal strip.  
Refer to Figure 6. 12 VDC should be measured.  
a. If CONTINUITY is not measured, repair or  
replace Wire 0 between the customer connection  
and the ground lug.  
a. If 12 VDC is measured, proceed to Step 8.  
b. If 12 VDC is not measured, proceed to Step 7.  
b. If CONTINUITY is measured and the pin con-  
nection of J2 looks good, the internal fuse on the  
PCB has failed. Replace the printed circuit board.  
Page 94  
Download from Www.Somanuals.com. All Manuals Search And Download.  
taBlE of coNtENts  
Part  
titlE  
PaGE#  
76  
4.1. Description and components  
4.2 operational analysis  
82  
Part 4  
Dc coNtrol  
4.3  
troubleshooting flow charts  
96  
4.4 Diagnostic tests  
103  
air-cooled, automatic  
standby Generators  
4.1 Description and Components....................................96  
General ...................................................................96  
Terminal Strip / Interconnection Terminal.................96  
Circuit Board ............................................................96  
Auto-Off-Manual Switch...........................................96  
7.5 Amp Fuse...........................................................96  
Menu System Navigation.......................................102  
4.2 Operational Analysis ...............................................104  
Introduction ............................................................104  
Utility Source Voltage Available..............................104  
Initial Dropout of Utility Source Voltage..................106  
Test 57 – Try a Manual Start .................................123  
Test 58 – Auto-Off-Manual Switch  
(V-Twin Only)............................................123  
Test 59 – Test Auto Operations ..............................124  
Test 60 – Check 7.5 Amp Fuse..............................124  
Test 61 – Check Battery.........................................124  
Test 62 – Check Wire 56 Voltage ...........................126  
Test 63 – Test Starter Contactor Relay  
(V-twin Only) ............................................126  
Test 64 – Test Starter Contactor  
(Single Cylinder Engine) ..........................127  
Test 65 – Test Starter Motor...................................128  
Test 66 – Check Fuel Supply and Pressure...........130  
Utility Voltage Dropout and  
Engine Cranking ......................................108  
Test 67 – Check Circuit Board  
Engine Startup and Running..................................110  
Initial Transfer to the “Standby” Source ..................112  
Wire 14 Output.........................................131  
Test 68 – Check Fuel Solenoid ..............................132  
Test 69 – Check Choke Solenoid...........................132  
Test 70 – Check for Ignition Spark.........................134  
Test 71 – Check Spark Plugs.................................136  
Utility Voltage Restored /  
Re-transfer to Utility .................................114  
Engine Shutdown...................................................116  
4.3 Troubleshooting Flowcharts.....................................118  
Test 72 – Check Engine / Cylinder Leak  
Problem 15 – Engine Will Not Crank  
When Utility Power Source Fails .......................118  
Down Test / Compression Test.................136  
Test 73 – Check Shutdown Wire............................137  
Problem 16 – Engine Will Not Crank When  
AUTO-OFF-MANUAL Switch  
is Set to “MANUAL ............................................118  
Test 74 – Check and Adjust  
Ignition Magnetos.....................................138  
Test 75 – Check Oil Pressure Switch  
Problem 17 – Engine Cranks  
but Won’t Start...................................................119  
and Wire 86..............................................141  
Test 76 – Check High Oil  
Problem 18 – Engine Starts Hard and  
Runs Rough / Lacks Power / Backfires .............120  
Temperature Switch .................................142  
Test 77 – Check and Adjust Valves........................142  
Test 78 – Check Wire 18 Continuity.......................143  
Test 79 – Test Exercise Function............................144  
Problem 19 – Shutdown Alarm /  
Fault Occurred...................................................121  
Problem 20 – 7.5 Amp Fuse (F1) Blown...........122  
Problem 21 – Generator Will Not Exercise........122  
Problem 22 – No Low Speed Exercise..............122  
4.4 Diagnostic Tests ......................................................123  
Introduction ...........................................................123  
Test 80 – Check Cranking and  
Running Circuits.......................................144  
Test 81 – Check to see if Low Speed  
Function is enabled..................................146  
Test 82 – Check operation of the  
Test 56 – Check Position Of  
Choke Solenoid........................................146  
Auto-Off- Manual Switch .........................123  
Page 95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.1  
DEscriPtioN aND comPoNENts  
DC CONTROL  
Part 4  
General  
circuit Board  
This section will familiarize the reader with the various  
components that make up the DC control system.  
The circuit board controls all standby electric system  
operations including (a) engine startup, (b) engine  
running, (c) automatic transfer, (d) automatic retrans-  
fer, and (e) engine shutdown. In addition, the circuit  
board performs the following functions:  
• Delivers “field boost” current to the generator rotor  
windings (see “Field Boost Circuit” in Section 2.2).  
Major DC control system components that will be  
covered include the following:  
• A Terminal Strip / Interconnection Terminal  
• A Circuit Board.  
• An AUTO-OFF-MANUAL Switch.  
• A 7.5 Amp Fuse.  
• Starts and “exercises” the generator once every  
seven days.  
• Provides automatic engine shutdown in the event of  
low oil pressure, high oil temperature, overspeed,  
no RPM sense, overcrank, or low battery.  
terminal Strip / interconnection  
terminal  
An 18-pin and a 4-pin connector are used to inter-  
connect the circuit board with the various circuits of  
the DC systems. Connector pin numbers, associated  
wires and circuit functions are listed in the CHART on  
the next page.  
The terminals of this terminal strip are connected to  
identically numbered terminals on a transfer switch  
terminal board. The terminal board connects the  
transfer switch to the circuit board.  
If the Utility sensing voltage drops below a preset  
value, circuit board action will initiate automatic  
generator startup and transfer to the “Standby”  
source side.  
The terminal board provides the following connection  
points:  
A. UTILITY 1 and UTILITY 2  
The crank relay and fuel solenoid valve are energized  
by circuit board action at the same time.  
1. Connect to identically marked terminals on a  
transfer switch terminal board.  
B. 23 and 15B  
DIGITAL INPUT/OUTPUT FUNCTIONS:  
1. Connect to identically numbered terminals on  
the terminal board of the transfer switch.  
Postion Digital inputs  
Digital outputs  
Not Used  
Not Used  
Not Used  
Not Used  
Fuel  
1
2
3
4
5
6
7
8
Low Oil Pressure  
High Temperature  
Internal Use  
Internal Use  
Internal Use  
Not Used  
2. This circuit connects the circuit board to the  
transfer relay coil in the transfer switch.  
N1 N2  
Starter  
Auto  
Ignition  
Manual  
Transfer  
DaNGEr:tHE GENErator ENGiNE Will  
craNK aND start WHEN tHE 7-DaY  
EXErcisEr sWitcH is actuatED.tHE uNit  
Will also craNK aND start EVErY 7  
DaYs tHErEaftEr, oN tHE DaY aND at tHE  
timE of DaY tHE sWitcH Was actuatED.  
*
TERMINAL STRIP  
auto-oFF-manual SWitch  
This 3-position switch permits the operator to (a)  
select fully automatic operation, (b) start the generator  
manually, or (c) stop the engine and prevent automatic  
startup. Switch terminals are shown pictorially and  
schematically in Figure 6, below.  
Figure 1. Terminal Strip  
Page 96  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.1  
DEscriPtioN aND comPoNENts  
DC CONTROL  
Part 4  
7.5 amp FuSe  
This fuse protects the circuit board against excessive  
current. If the fuse has blown, engine cranking and  
operation will not be possible. Should fuse replace-  
ment become necessary, use only an identical 7.5  
amp replacement fuse.  
Figure 2. A Typical 7.5 Amp Fuse  
1
2
1. CONTROL PANEL  
2. 7.5 AMP FUSE  
3. STARTER CONTACTOR RELAY  
(10-20 KW)  
5
4
3
4. 4 POSITION TERMINAL BLOCK  
5. TERMINAL BLOCK  
6. CIRCUIT BREAKER (8KW)  
7. 15 AMP GFCI DUPLEX OUTLET  
(17 & 20 KW)  
8. CIRCUIT BREAKER (17 & 20 KW)  
9. CIRCUIT BREAKER (10-20 KW)  
10. LED DISPLAY  
TO ENGINE  
DIVIDER PANEL  
6
8
7
TO ENGINE  
DIVIDER PANEL  
10  
9
Figure 3. Control Panel Component Identification  
Page 97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.1  
DEscriPtioN aND comPoNENts  
DC CONTROL  
Part 4  
18 17 16 15 14 13 12 11 10  
4
2
3
1
18 17 16 15 14 13 12 11 10  
4
2
3
1
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
J2  
J1  
J2 CONNECTOR  
(PCB END)  
J1 CONNECTOR  
(PCB END)  
3
4
10 11 12 13 14 15 16 17 18  
1
2
1
2
3
4
5
6
7
8
9
J1 CONNECTOR  
(HARNESS END)  
J2 CONNECTOR  
(HARNESS END)  
1
2
N1/N2 CONNECTOR  
(PCB END)  
N1/N2 CONNECTOR  
(HARNESS END)  
Figure 4. 8 kW Printed Circuit Boards and J1 Connector  
8 kW J1 connector Pin Descriptions  
PiN  
WirE  
circuit fuNctioN  
PiN  
J2-7  
J2-8  
WirE  
circuit fuNctioN  
J1-1  
85  
High temperature shutdown:  
Shutdown occurs when Wire 85 is  
grounded by contact closure in HTO  
NOT USED  
15B  
Provides an electrical connection for  
charge current to reach the battery  
from the battery charger. Provides  
12VDC to the Transfer Relay  
J1-2  
86  
Low oil pressure shutdown: Shutdown  
occurs when Wire 86 is grounded by  
loss of oil pressure to the LOP  
J2-9  
J2-10  
J2-11  
NOT USED  
J1-3  
J1-4  
13  
18  
12 VDC source voltage for the circuit  
board  
0
Common Ground  
56  
12 VDC output to starter contactor for  
single cylinder engines.  
Ignition Shutdown: Circuit board  
action grounds Wire 18 for ignition  
shutdown.  
J2-15  
J2-16  
NOT USED  
NOT USED  
J2-1  
J2-2  
J2-3  
0
0
INTERNAL USE  
INTERNAL USE  
J2-17  
NOT USED  
J2-18  
NOT USED  
14  
12 VDC output for engine run condi-  
tion. Used for fuel solenoid.  
Wired Plug 1  
Wired Plug 2  
N1  
N2  
240 VAC sensing for control board.  
240 VAC sensing for control board.  
J2-5  
23  
Switched to ground for transfer relay  
operation  
J2-6  
NOT USED  
Page 98  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.1  
DEscriPtioN aND comPoNENts  
DC CONTROL  
Part 4  
18 17 16 15 14 13 12 11 10  
4
2
3
1
18 17 16 15 14 13 12 11 10  
4
2
3
1
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
J2  
J1  
J2 CONNECTOR  
(PCB END)  
J1 CONNECTOR  
(PCB END)  
3
4
10 11 12 13 14 15 16 17 18  
1
2
1
2
3
4
5
6
7
8
9
J3  
(STEPPER MOTOR)  
J1 CONNECTOR  
(HARNESS END)  
J2 CONNECTOR  
(HARNESS END)  
1
2
N1/N2 CONNECTOR  
(PCB END)  
N1/N2 CONNECTOR  
(HARNESS END)  
REMOTE WIRELESS CONNECTION  
Figure 5. 10 kW Printed Circuit Board and J1 Connector  
10 kW J1 connector Pin Descriptions  
PiN  
WirE  
circuit fuNctioN  
PiN  
WirE  
circuit fuNctioN  
J1-1  
85  
High temperature shutdown:  
Shutdown occurs when Wire 85 is  
grounded by contact closure in HTO  
J2-8  
15B  
Provides an electrical connection for  
charge current to reach the battery  
from the battery charger. Provides 12  
VDC to the Transfer Relay  
J1-2  
86  
Low oil pressure shutdown: Shutdown  
occurs when Wire 86 is grounded by  
loss of oil pressure to the LOP  
J2-9  
820  
Positive voltage (+5 VDC) for status  
LEDs.  
J1-3  
J1-4  
13  
18  
12 VDC source voltage for the circuit  
board  
J2-10  
J2-11  
0
Common Ground  
56  
12 VDC output to starter contactor  
relay for V-Twin engines  
Ignition Shutdown: Circuit board  
action grounds Wire 18 for ignition  
shutdown.  
J2-12  
J2-13  
NOT USED  
818  
90  
Grounded by board to turn on the  
Alarm (Red) LED.  
J2-1  
J2-2  
J2-3  
INTERNAL USE ONLY  
INTERNAL USE ONLY  
J2-14  
J2-15  
NOT USED  
14  
12 VDC output for engine run condi-  
tion. Used for fuel solenoid and choke  
solenoid operation.  
Switched to ground for choke sole-  
noid operation  
J2-16  
J2-17  
INTERNAL USE ONLY  
NOT USED  
J2-4  
J2-5  
817  
23  
Grounded by printed circuit board to  
turn on System Ready (Green) LED.  
J2-18  
NOT USED  
Switched to ground for transfer relay  
operation  
J3  
Control wires for Stepper Motor  
240 VAC sensing for control board.  
240 VAC sensing for control board.  
J2-6  
J2-7  
NOT USED  
NOT USED  
Wired Plug-1  
Wired Plug-2  
N1  
N2  
Page 99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.1  
DEscriPtioN aND comPoNENts  
DC CONTROL  
Part 4  
18 17 16 15 14 13 12 11 10  
4
2
3
1
18 17 16 15 14 13 12 11 10  
4
3
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
2
1
J2  
J1  
J2 CONNECTOR  
(PCB END)  
J1 CONNECTOR  
(PCB END)  
3
4
10 11 12 13 14 15 16 17 18  
1
2
1
2
3
4
5
6
7
8
9
J3  
(STEPPER MOTOR)  
J1 CONNECTOR  
(HARNESS END)  
J2 CONNECTOR  
(HARNESS END)  
1
2
N1/N2 CONNECTOR  
(PCB END)  
N1/N2 CONNECTOR  
(HARNESS END)  
REMOTE WIRELESS CONNECTION  
Figure 6. 12/14 kW Printed Circuit Board and J1 Connector  
12/14 kW J1 connector Pin Descriptions  
PiN  
WirE  
circuit fuNctioN  
PiN  
WirE  
circuit fuNctioN  
J1-1  
85  
High temperature shutdown:  
Shutdown occurs when Wire 85 is  
grounded by contact closure in HTO  
J2-8  
15B  
Provides an electrical connection for  
charge current to reach the battery  
from the battery charger. Provides 12  
VDC to the Transfer Relay  
J1-2  
86  
Low oil pressure shutdown: Shutdown  
occurs when Wire 86 is grounded by  
loss of oil pressure to the LOP  
J2-9  
820  
Positive voltage (+5 VDC) for status  
LEDs.  
J1-3  
J1-4  
13  
18  
12 VDC source voltage for the circuit  
board  
J2-10  
J2-11  
0
Common Ground  
56  
12 VDC output to starter contactor  
relay for V-Twin engines  
Ignition Shutdown: Circuit board  
action grounds Wire 18 for ignition  
shutdown.  
J2-12  
J2-13  
NOT USED  
818  
90  
Grounded by board to turn on the  
Alarm (Red) LED.  
J2-1  
J2-2  
J2-3  
INTERNAL USE ONLY  
INTERNAL USE ONLY  
J2-14  
J2-15  
NOT USED  
14  
12 VDC output for engine run condi-  
tion. Used for fuel solenoid and choke  
solenoid operation.  
Switched to ground for choke sole-  
noid operation  
J2-16  
J2-17  
INTERNAL USE ONLY  
NOT USED  
J2-4  
J2-5  
817  
23  
Grounded by printed circuit board to  
turn on System Ready (Green) LED.  
J2-18  
NOT USED  
Switched to ground for transfer relay  
operation  
J3  
Control wires for Stepper Motor  
240 VAC sensing for control board.  
240 VAC sensing for control board.  
J2-6  
J2-7  
NOT USED  
NOT USED  
Wired Plug-1  
Wired Plug-2  
N1  
N2  
Page 100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.1  
DEscriPtioN aND comPoNENts  
DC CONTROL  
Part 4  
18 17 16 15 14 13 12 11 10  
4
2
3
1
18 17 16 15 14 13 12 11 10  
4
2
3
1
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
J2  
J1  
J2 CONNECTOR  
(PCB END)  
J1 CONNECTOR  
(PCB END)  
3
4
10 11 12 13 14 15 16 17 18  
1
2
1
2
3
4
5
6
7
8
9
J3  
(STEPPER MOTOR)  
J1 CONNECTOR  
(HARNESS END)  
J2 CONNECTOR  
(HARNESS END)  
1
2
N1/N2 CONNECTOR  
(PCB END)  
N1/N2 CONNECTOR  
(HARNESS END)  
REMOTE WIRELESS CONNECTION  
Figure 7. 16, 17 and 20 kW Printed Circuit Board and J1 Connector  
16, 17 and 20 kW J1 connector Pin Descriptions  
PiN  
WirE  
circuit fuNctioN  
PiN  
WirE  
circuit fuNctioN  
J1-1  
85  
High temperature shutdown:  
Shutdown occurs when Wire 85 is  
grounded by contact closure in HTO  
J2-8  
15B  
Provides an electrical connection for  
charge current to reach the battery  
from the battery charger. Provides 12  
VDC to the Transfer Relay  
J1-2  
86  
Low oil pressure shutdown: Shutdown  
occurs when Wire 86 is grounded by  
loss of oil pressure to the LOP  
J2-9  
820  
Positive voltage (+5 VDC) for status  
LEDs.  
J1-3  
J1-4  
13  
18  
12 VDC source voltage for the circuit  
board  
J2-10  
J2-11  
0
Common Ground  
56  
12 VDC output to starter contactor  
relay for V-Twin engines  
Ignition Shutdown: Circuit board  
action grounds Wire 18 for ignition  
shutdown.  
J2-12  
J2-13  
4
Field Boost output  
818  
Grounded by board to turn on the  
Alarm (Red) LED.  
J2-1  
J2-2  
J2-3  
INTERNAL USE ONLY  
INTERNAL USE ONLY  
J2-14  
J2-15  
819  
90  
Grounded by board to turn on the  
Maintenance Required (Yellow) LED.  
14  
12VDC output for engine run condi-  
tion. Used for fuel solenoid and choke  
solenoid operation.  
Switched to ground for choke sole-  
noid operation  
J2-4  
J2-5  
817  
23  
Grounded by printed circuit board to  
turn on System Ready (Green) LED.  
J2-16  
J2-17  
INTERNAL USE ONLY  
NOT USED  
Switched to ground for transfer relay  
operation  
J2-18  
NOT USED  
J3  
Control wires for Stepper Motor  
240 VAC sensing for control board.  
240 VAC sensing for control board.  
J2-6  
J2-7  
NOT USED  
NOT USED  
Wired Plug-1  
Wired Plug-2  
N1  
N2  
Page 101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.1  
DEscriPtioN aND comPoNENts  
DC CONTROL  
Part 4  
2
1
FEMALE SIDE  
MALE SIDE  
C3  
1
2
Figure 8. Choke Solenoid Connector Pin Number Identification  
CHANGING SETTINGS (EDIT MENU):  
menu SyStem naViGation  
To change a setting such as display contrast, go to  
the EDIT menu and use the +/- keys to navigate to  
the setting to change. Once this setting is displayed  
(e.g. Contrast), press the ENTER key to go into the  
edit mode. Use the +/- keys to change the setting,  
press the ENTER key to store the new setting.  
To get to the MENU, use the "Esc" key from any page.  
It may need to be pressed many times before getting  
to the menu page. The currently selected menu is  
displayed as a flashing word. Navigate to the menu  
required by using the +/- keys. When the menu required  
is flashing, press the ENTER key. Depending on the  
menu selected, there may be a list of choices pre-  
sented. Use the same navigation method to select the  
desired screen (refer to the Menu System diagram).  
note: if the enter key is not pressed to save the  
new setting, it will only be saved temporarily. the  
next time the battery is disconnected, the setting  
will revert back to the old setting.  
Page 102  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.1  
DEscriPtioN aND comPoNENts  
DC CONTROL  
Part 4  
Page 103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
introduction  
This “Operational Analysis” is intended to familiarize the service technician with the operation of the DC control  
system on units with air-cooled engine. A thorough understanding of how the system works is essential to sound  
and logical troubleshooting. The DC control system illustrations on the following pages represent a 14 kW unit.  
utility Source VoltaGe aVailaBle  
See Figure 1, below. The circuit condition with the AUTO-OFF-MANUAL switch set to AUTO and with “Utility”  
source power available can be briefly described as follows:  
2
6
2
6
0
4
0
VOLTAGE  
REGULATOR  
0
4
4
22  
11  
22  
11  
POWER  
WINDING  
44  
33  
22  
STATOR  
6
2
11  
POWER  
WINDING  
BA  
0
4
0
4
IM2  
18  
SP2  
IM1  
18  
SP1  
85  
86  
HTO  
LOP  
56  
0
0
SCR  
0
0
13  
13  
0
13  
13  
BATTERY  
12V  
SCR  
16  
SC  
SM  
Page 104  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
• Utility source voltage is available to transfer switch Terminal Lugs N1/N2. With the transfer switch main contacts  
at their “Utility” side, this source voltage is available to Terminal Lugs T1/T2 and to the “Load” circuits.  
• Utility voltage is delivered to the Control Board Wires N1/N2, fuses F1/F2, connected wiring, and Control Panel  
UTILITY 1 and UTILITY 2 terminals. A voltage of 240 AC is delivered to the circuit board.  
• Battery output is delivered to the circuit board via Wire 13 when the Battery is installed.  
Figure 1. circuit condition - utility Source Voltage available  
CB  
44  
240 VAC  
GENERATOR  
OUTPUT  
11  
NEUTRAL  
33  
22  
00  
CONTROLLER DISPLAY  
Ready to Run  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
N1 N2  
LED BOARD  
1
85  
J1  
2
3
4
86  
13  
820  
1
2
3
4
TO  
PCB  
7.5 AMP FUSE  
L1  
L2  
817  
818  
819  
18  
SELF RESETTING FUSE  
GOVERNOR  
ACTUATOR  
J3  
J2  
10 11 12 13 14 15 16 17 18  
1
2
3
4
5
6
7
8
9
4
0
14  
23  
15B  
0
56  
820  
817  
818  
14  
14  
FS  
CS  
90  
819  
GROUND  
0
0
15B  
23  
+ BATTERY  
TRANSFER  
0
= 12 VDC ALWAYS PRESENT  
= AC VOLTAGE  
0
= GROUND FOR CONTROL PURPOSES  
= 12 VDC DURING CRANKING ONLY  
= 12 VDC DURING ENGINE RUN CONDITION  
= DC FIELD EXCITATION  
LEGEND  
BA - BRUSH ASSEMBLY  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
SP_ - SPARK PLUG  
= 5 VDC TO LED  
Page 105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
initial dropout oF utility Source VoltaGe  
Refer to Figure 2, below. Should a “Utility” power source failure occur, circuit condition may be briefly described  
as follows:  
• The circuit board constantly senses for an acceptable “Utility” source voltage, via transfer switch fuses F1/F2,  
transfer switch UTILITY 1 and UTILITY 2 terminals, connected wiring, control panel UTILITY 1 and UTILITY 2  
terminals, and Wires N1/N2.  
2
6
2
6
0
4
0
VOLTAGE  
REGULATOR  
0
4
4
22  
11  
22  
11  
POWER  
WINDING  
44  
33  
22  
STATOR  
6
2
11  
POWER  
WINDING  
BA  
0
4
0
4
IM2  
18  
SP2  
IM1  
18  
SP1  
85  
86  
HTO  
LOP  
56  
0
0
SCR  
0
0
13  
13  
0
13  
13  
BATTERY  
12V  
SCR  
16  
SC  
SM  
Page 106  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
• Should utility voltage drop below approximately 65 percent of the nominal source voltage, a programmable  
timer on the circuit board will turn on.  
• In Figure 2, the 10-second timer is still timing and engine cranking has not yet begun.  
• The AUTO-OFF-MANUAL switch is shown in its AUTO position. Battery voltage is available to the circuit board  
via Wire 13, a 7.5 amp fuse (F1), and Wire 15B.  
Figure 2. circuit condition - initial dropout of utility Source Voltage  
CB  
44  
240 VAC  
GENERATOR  
OUTPUT  
11  
NEUTRAL  
33  
22  
00  
CONTROLLER DISPLAY  
Utility Loss Delay  
Pausing 10 sec  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
N1 N2  
LED BOARD  
1
85  
J1  
2
3
4
86  
13  
820  
1
2
3
4
TO  
PCB  
7.5 AMP FUSE  
L1  
L2  
817  
818  
819  
18  
SELF RESETTING FUSE  
GOVERNOR  
ACTUATOR  
J3  
J2  
10 11 12 13 14 15 16 17 18  
1
2
3
4
5
6
7
8
9
4
0
14  
23  
15B  
0
56  
820  
817  
818  
14  
14  
FS  
CS  
90  
819  
GROUND  
0
0
15B  
23  
+ BATTERY  
TRANSFER  
0
= 12 VDC ALWAYS PRESENT  
= AC VOLTAGE  
0
= GROUND FOR CONTROL PURPOSES  
= 12 VDC DURING CRANKING ONLY  
= 12 VDC DURING ENGINE RUN CONDITION  
= DC FIELD EXCITATION  
LEGEND  
BA - BRUSH ASSEMBLY  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
SP_ - SPARK PLUG  
= 5 VDC TO LED  
Page 107  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
utility VoltaGe dropout and enGine crankinG  
• After ten (10) seconds and when the circuit board’s 10-second timer has timed out, if utility voltage is still below  
65 percent of nominal, circuit board action will energize the circuit board’s crank and run relays simultaneously.  
• Printed circuit board action delivers 12 volts DC to a starter contactor relay (SCR), via Wire 56. When the SCR  
energizes, its contacts close and battery power is delivered to a starter contactor (SC). When the SC energizes,  
its contacts close and battery power is delivered to the starter motor (SM). The engine cranks.  
2
6
2
6
0
4
0
VOLTAGE  
REGULATOR  
0
4
4
22  
11  
22  
11  
POWER  
WINDING  
44  
33  
22  
STATOR  
6
2
11  
POWER  
WINDING  
BA  
0
4
0
4
IM2  
18  
SP2  
IM1  
18  
SP1  
85  
86  
HTO  
LOP  
56  
0
0
SCR  
0
0
13  
13  
0
13  
13  
BATTERY  
12V  
SCR  
16  
SC  
SM  
Page 108  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
• Printed circuit board action delivers 12 volts DC to the fuel solenoids (FS1 & FS2), via Wire 14. The fuel solenoids  
energize open and fuel is available to the engine. Wire 14 supplies power to the choke solenoid (CS). Circuit board  
action grounds Wire 90, energizing the choke solenoid cyclically during cranking and continuously while running.  
• As the engine cranks, magnets on the engine flywheel induce a high voltage into the engine ignition magnetos  
(IM1/IM2). A spark is produced that jumps the spark plug (SP1/SP2) gap.  
• During cranking, Wire 4 supplies 3-5 VDC (9-10 VDC isolated) to the rotor for field flash.  
• With ignition and fuel flow available the engine can start.  
Figure 3. circuit condition - engine cranking  
CB  
44  
240 VAC  
GENERATOR  
OUTPUT  
11  
NEUTRAL  
33  
22  
00  
CONTROLLER DISPLAY  
Cranking Attempt #1  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
N1 N2  
LED BOARD  
1
85  
J1  
2
3
4
86  
13  
820  
1
2
3
4
TO  
PCB  
7.5 AMP FUSE  
L1  
L2  
817  
818  
819  
18  
SELF RESETTING FUSE  
GOVERNOR  
ACTUATOR  
J3  
J2  
10 11 12 13 14 15 16 17 18  
1
2
3
4
5
6
7
8
9
4
0
14  
23  
15B  
0
56  
820  
817  
818  
14  
14  
FS  
CS  
90  
819  
GROUND  
0
0
15B  
23  
+ BATTERY  
TRANSFER  
0
= 12 VDC ALWAYS PRESENT  
= AC VOLTAGE  
0
= GROUND FOR CONTROL PURPOSES  
= 12 VDC DURING CRANKING ONLY  
= 12 VDC DURING ENGINE RUN CONDITION  
= DC FIELD EXCITATION  
LEGEND  
BA - BRUSH ASSEMBLY  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
SP_ - SPARK PLUG  
= 5 VDC TO LED  
Page 109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
enGine Startup and runninG  
With the fuel solenoids open and ignition occurring, the engine starts. Engine startup and running may be briefly  
described as follows:  
• Voltage pulses from the ignition magnetos are delivered to the circuit board via Wire 18. Once the circuit board  
determines that the engine is running, the circuit board (a) terminates cranking, and (b) terminates the choke  
solenoid (CS), and (c) turns on an “engine warm-up timer”.  
2
6
2
6
0
4
0
VOLTAGE  
REGULATOR  
0
4
4
22  
11  
22  
11  
POWER  
WINDING  
44  
33  
22  
STATOR  
6
2
11  
POWER  
WINDING  
BA  
0
4
0
4
IM2  
18  
SP2  
IM1  
18  
SP1  
85  
86  
HTO  
LOP  
56  
0
0
SCR  
0
0
13  
13  
0
13  
13  
BATTERY  
12V  
SCR  
16  
SC  
SM  
Page 110  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
• The “engine warm-up timer” will run for about 5 seconds. When this timer finishes timing, board action will  
initiate transfer to the STANDBY power source. As shown in Figure 4 (below), the timer is still running and  
transfer has not yet occurred.  
• Generator AC output is available to transfer switch Terminal Lugs E1/E2 and to the normally open contacts of a  
transfer relay. However, the transfer relay is de-energized and its contacts are open.  
Figure 4. circuit condition - engine Startup and running  
CB  
44  
240 VAC  
GENERATOR  
OUTPUT  
11  
NEUTRAL  
33  
22  
00  
CONTROLLER DISPLAY  
Running - Utility Lost  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
N1 N2  
LED BOARD  
1
85  
J1  
2
3
4
86  
13  
820  
1
2
3
4
TO  
PCB  
7.5 AMP FUSE  
L1  
L2  
817  
818  
819  
18  
SELF RESETTING FUSE  
GOVERNOR  
ACTUATOR  
J3  
J2  
10 11 12 13 14 15 16 17 18  
1
2
3
4
5
6
7
8
9
4
0
14  
23  
15B  
0
56  
820  
817  
818  
14  
14  
FS  
CS  
90  
819  
GROUND  
0
0
15B  
23  
+ BATTERY  
TRANSFER  
0
= 12 VDC ALWAYS PRESENT  
= AC VOLTAGE  
0
= GROUND FOR CONTROL PURPOSES  
= 12 VDC DURING CRANKING ONLY  
= 12 VDC DURING ENGINE RUN CONDITION  
= DC FIELD EXCITATION  
LEGEND  
BA - BRUSH ASSEMBLY  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
SP_ - SPARK PLUG  
= 5 VDC TO LED  
Page 111  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
initial tranSFer to the “StandBy” Source  
The generator is running, the circuit board’s “engine warm-up timer” is timing, and generator AC output is avail-  
able to transfer switch terminal lugs E1 and E2 and to the open contacts on the transfer relay. Initial transfer to  
the STANDBY power supply may be briefly described as follows:  
• 12 volts DC output is delivered to the transfer relay (TR) actuating coil, via Wire 15B, and terminal A of the  
transfer relay (TR) in the transfer switch. This 12 volts DC circuit is completed back to the board, via transfer  
relay terminal B and Wire 23. However, circuit board action holds the Wire 23 circuit open to ground and the  
transfer relay (TR) is de-energized.  
2
6
2
6
0
4
0
VOLTAGE  
REGULATOR  
0
4
4
22  
11  
22  
11  
POWER  
WINDING  
44  
33  
22  
STATOR  
6
2
11  
POWER  
WINDING  
BA  
0
4
0
4
IM2  
18  
SP2  
IM1  
18  
SP1  
85  
86  
HTO  
LOP  
56  
0
0
SCR  
0
0
13  
13  
0
13  
13  
BATTERY  
12V  
SCR  
16  
SC  
SM  
Page 112  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
• When the circuit board’s “engine warm-up timer” times out, circuit board action completes the Wire 23 circuit to  
ground. The transfer relay then energizes and its normally open contacts close.  
• Standby power is now delivered to the standby closing coil (C2), via Wires E1/E2, the normally open transfer  
relay contacts, Wire 205, limit switch XB1, Wire B, and a bridge rectifier. The standby closing coil energizes and  
the main current carrying contacts of the transfer switch are actuated to their STANDBY source side.  
• As the main contacts move to their STANDBY source side, a mechanical interlock actuates limit switch XB1 to  
its open position and limit switch XA1 to its “Utility” side position. When XB1 opens, standby closing coil C2 3  
de-energizes.  
• Standby power is delivered to the LOAD terminals (T1/T2) of the transfer switch.  
Figure 5. circuit condition - initial transfer to Standby  
CB  
44  
240 VAC  
GENERATOR  
OUTPUT  
11  
NEUTRAL  
33  
22  
00  
CONTROLLER DISPLAY  
Running - Utility Lost  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
N1 N2  
LED BOARD  
1
85  
J1  
2
3
4
86  
13  
820  
1
2
3
4
TO  
PCB  
7.5 AMP FUSE  
L1  
L2  
817  
818  
819  
18  
SELF RESETTING FUSE  
GOVERNOR  
ACTUATOR  
J3  
J2  
10 11 12 13 14 15 16 17 18  
1
2
3
4
5
6
7
8
9
4
0
14  
23  
15B  
0
56  
820  
817  
818  
14  
14  
FS  
CS  
90  
819  
GROUND  
0
0
15B  
23  
+ BATTERY  
TRANSFER  
0
= 12 VDC ALWAYS PRESENT  
= AC VOLTAGE  
0
= GROUND FOR CONTROL PURPOSES  
= 12 VDC DURING CRANKING ONLY  
= 12 VDC DURING ENGINE RUN CONDITION  
= DC FIELD EXCITATION  
LEGEND  
BA - BRUSH ASSEMBLY  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
SP_ - SPARK PLUG  
= 5 VDC TO LED  
Page 113  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
utility VoltaGe reStored / re-tranSFer to utility  
The “Load” is powered by the standby power supply. The circuit board continues to seek an acceptable utility  
source voltage. On restoration of utility source voltage, the following events will occur:  
• On restoration of utility source voltage above 75 percent of the nominal rated voltage, a “retransfer time delay”  
on the circuit board starts timing. The timer will run for about fifteen (15) seconds.  
• At the end of fifteen (15) seconds, the “retransfer time delay” will stop timing and circuit board action will open  
the Wire 23 circuit to ground. The transfer relay (TR) will then de-energize.  
• When the transfer relay (TR) de-energizes, its normally-closed contacts close. Utility source voltage is then  
delivered to the utility closing coil (C1), via Wires N1A/N2A, the closed TR contacts, Wire 126, limit switch XA1,  
and a bridge rectifier.  
2
6
2
6
0
4
0
VOLTAGE  
REGULATOR  
0
4
4
22  
11  
22  
11  
POWER  
WINDING  
44  
33  
22  
STATOR  
6
2
11  
POWER  
WINDING  
BA  
0
4
0
4
IM2  
18  
SP2  
IM1  
18  
SP1  
85  
86  
HTO  
LOP  
56  
0
0
SCR  
0
0
13  
13  
0
13  
13  
BATTERY  
12V  
SCR  
16  
SC  
SM  
Page 114  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
• The utility closing coil (C1) energizes and moves the main current carrying contacts to their NEUTRAL  
position. The main contacts move to an over center position past NEUTRAL and spring force closes them  
to their UTILITY side. LOAD terminals are now powered by the UTILITY source.  
• Movement of the main contacts to UTILITY actuates limit switches XA1/XB1. XA1 opens and XB1 actuates to  
its STANDBY source side.  
• The generator continues to run.  
Figure 6. circuit condition - utility Voltage restored  
CB  
44  
240 VAC  
GENERATOR  
OUTPUT  
11  
NEUTRAL  
33  
22  
00  
CONTROLLER DISPLAY  
Running / Cooling Down  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
N1 N2  
LED BOARD  
1
85  
J1  
2
3
4
86  
13  
820  
1
2
3
4
TO  
PCB  
7.5 AMP FUSE  
L1  
L2  
817  
818  
819  
18  
SELF RESETTING FUSE  
GOVERNOR  
ACTUATOR  
J3  
J2  
10 11 12 13 14 15 16 17 18  
1
2
3
4
5
6
7
8
9
4
0
14  
23  
15B  
0
56  
820  
817  
818  
14  
14  
FS  
CS  
90  
819  
GROUND  
0
0
15B  
23  
+ BATTERY  
TRANSFER  
0
= 12 VDC ALWAYS PRESENT  
= AC VOLTAGE  
0
= GROUND FOR CONTROL PURPOSES  
= 12 VDC DURING CRANKING ONLY  
= 12 VDC DURING ENGINE RUN CONDITION  
= DC FIELD EXCITATION  
LEGEND  
BA - BRUSH ASSEMBLY  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
SP_ - SPARK PLUG  
= 5 VDC TO LED  
Page 115  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
enGine ShutdoWn  
Following retransfer back to the utility source, an “engine cool-down timer” on the circuit board starts timing. When  
that timer has timed out (approximately one minute), circuit board action will de-energize the circuit board’s run  
relay. The following events will then occur:  
• The DC circuit to Wire 14 and the fuel solenoids (FS1 & FS2) will be opened. The fuel solenoids will de-  
energize and close to terminate the engine fuel supply.  
2
6
2
6
0
4
0
VOLTAGE  
REGULATOR  
0
4
4
22  
11  
22  
11  
POWER  
WINDING  
44  
33  
22  
STATOR  
6
2
11  
POWER  
WINDING  
BA  
0
4
0
4
IM2  
18  
SP2  
IM1  
18  
SP1  
85  
86  
HTO  
LOP  
56  
0
0
SCR  
0
0
13  
13  
0
13  
13  
BATTERY  
12V  
SCR  
16  
SC  
SM  
Page 116  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.2  
oPEratioNal aNalYsis  
DC CONTROL  
Part 4  
• Circuit board action will connect the engine’s ignition magnetos (IM1 & IM2) to ground, via Wire 18. Ignition will  
be terminated.  
• Without fuel flow and without ignition, the engine will shut down.  
Figure 7. circuit condition - retransfer to “utilityand engine Shutdown  
CB  
44  
240 VAC  
GENERATOR  
OUTPUT  
11  
NEUTRAL  
33  
22  
00  
CONTROLLER DISPLAY  
Ready to Run  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
N1 N2  
LED BOARD  
1
85  
J1  
2
3
4
86  
13  
820  
1
2
3
4
TO  
PCB  
7.5 AMP FUSE  
L1  
L2  
817  
818  
819  
18  
SELF RESETTING FUSE  
GOVERNOR  
ACTUATOR  
J3  
J2  
10 11 12 13 14 15 16 17 18  
1
2
3
4
5
6
7
8
9
4
0
14  
23  
15B  
0
56  
820  
817  
818  
14  
14  
FS  
CS  
90  
819  
GROUND  
0
0
15B  
23  
+ BATTERY  
TRANSFER  
0
= 12 VDC ALWAYS PRESENT  
= AC VOLTAGE  
0
= GROUND FOR CONTROL PURPOSES  
= 12 VDC DURING CRANKING ONLY  
= 12 VDC DURING ENGINE RUN CONDITION  
= DC FIELD EXCITATION  
LEGEND  
BA - BRUSH ASSEMBLY  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
SP_ - SPARK PLUG  
= 5 VDC TO LED  
Page 117  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.3  
trouBlEsHootiNG floW cHarts  
DC CONTROL  
Part 4  
Problem 15 – Engine Will Not Crank When Utility Power Source Fails  
*8 kW system ready  
light will be flashing  
TEST 56 – CHECK  
POSITION OF  
AUTO-OFF-MANUAL  
SWITCH  
TEST 57 – TRY A  
MANUAL START  
SWITCH IS  
IN “AUTO”  
VERIFY UTILITY  
SOURCE IS “OFF”*  
OFF  
ENGINE DOES  
NOT CRANK  
ON  
ENGINE  
CRANKS  
SWITCH IS “OFF”  
TURN “OFF” -  
RETEST  
GO TO PROBLEM 16  
SET TO “AUTO” -  
RETEST  
REPLACE CONTROLLER  
8 kW  
ASSEMBLY  
TEST 58 – TEST  
AUTO-OFF-MANUAL  
SWITCH  
TEST 59 – CHECK  
AUTO OPERATION  
OF CONTROLLER  
REPLACE CONTROLLER  
ASSEMBLY  
10 kW - 20 kW  
BAD  
BAD  
REPLACE CONTROLLER  
ASSEMBLY  
Problem 16 – Engine Will Not Crank When AUTO-OFF-MANUAL Switch is Set to “MANUAL”  
*8 kW - battery led should be off  
TEST 62 – CHECK  
GOOD  
TEST 61 – CHECK  
BATTERY  
GOOD  
TEST 60 – CHECK  
7.5 AMP FUSE  
WIRE 56 VOLTAGE  
GOOD  
BAD  
RECHARGE /  
REPLACE  
TEST 63 – CHECK  
STARTER  
BAD  
BAD  
CONTACTOR RELAY  
(V-TWIN ONLY)  
REPLACE  
REPLACE  
8 kW  
CONTROLLER  
ASSEMBLY  
BAD  
GOOD  
BAD  
TEST 59 – TEST  
AUTO-OFF-MANUAL  
SWITCH  
10 kW - 20 kW  
REPLACE  
NOTE: If a starting problem is encountered,  
the engine itself should be thoroughly  
checked to eliminate it as the cause of starting  
difficulty. It is a good practice to check the  
engine for freedom of rotation by removing the  
spark plugs and turning the crankshaft over  
slowly by hand, to be sure it rotates freely.  
TEST 64 –  
CHECK STARTER  
CONTACTOR  
TEST 65 – TEST  
STARTER MOTOR  
GOOD  
GOOD  
WARNING: DO NOT ROTATE  
ENGINE WITH ELECTRIC STARTER  
REPLACE  
BAD  
WITH  
BAD  
SPARK PLUGS REMOVED.  
ARCING AT THE PLUG ENDS MAY  
IGNITE THE LP OR NG VAPOR  
EXITING THE SPARK PLUG HOLE.  
Page 118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.3  
trouBlEsHootiNG floW cHarts  
DC CONTROL  
Part 4  
Problem 17 – Engine Cranks but Won’t Start  
TEST 66 – CHECK  
FUEL SUPPLY AND  
PRESSURE  
TEST 67 – CHECK  
TEST 68 – CHECK  
GOOD  
GOOD  
CIRCUIT BOARD  
FUEL SOLENOID  
WIRE 14 OUTPUT  
BAD  
BAD  
BAD  
GOOD  
REPLACE FUEL SOLENOID  
REPLACE CIRCUIT BOARD  
FIND AND CORRECT  
CAUSE OF NO FUEL  
OR LOW PRESSURE  
TEST 16 – CHECK  
STEPPER MOTOR  
CONTROL  
TEST 69 – CHECK  
CHOKE SOLENOID  
V-TWIN UNITS  
GOOD  
GOOD  
BAD  
BAD  
REPAIR OR REPLACE  
REPLACE CHOKE  
SOLENOID  
CHECK AIR FILTER -  
REPLACE AS NEEDED  
SINGLE CYLINDER UNITS  
TEST 70 –  
CHECK FOR  
IGNITION  
SPARK  
TEST 72 –  
CHECK ENGINE  
COMPRESSION  
TEST 77 –  
CHECK AND  
ADJUST VALVES  
TEST 71 –  
CHECK SPARK  
PLUGS  
GOOD  
GOOD  
GOOD  
BAD  
BAD  
BAD  
GOOD  
BAD  
CLEAN,  
REGAP OR  
REPLACE  
READJUST  
CHECK  
FLYWHEEL  
KEY  
REPLACE FUEL  
REGULATOR  
GOOD  
TEST 73 – CHECK  
SHUTDOWN WIRE  
TEST 74 – CHECK  
IGNITION  
GOOD  
MAGNETOS  
BAD  
BAD  
REPAIR OR  
REPLACE SHORTED  
WIRE 18 OR CIRCUIT  
BOARD  
REFER TO ENGINE  
SERVICE MANUAL  
ADJUST OR  
REPLACE  
Page 119  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.3  
trouBlEsHootiNG floW cHarts  
DC CONTROL  
Part 4  
Problem 18 – Engine Starts Hard and Runs Rough / Lacks Power / Backfires  
IF RECONFIGURED TO LP GAS,  
TEST 66 – CHECK  
FUEL SUPPLY AND  
PRESSURE  
CHECK AIR FILTER -  
REPLACE AS NEEDED  
VERIFY THAT PROPER  
PROCEDURE WAS FOLLOWED.  
(REFER TO SECTION 1.3)  
GOOD  
GOOD  
BAD  
FIND AND CORRECT  
CAUSE OF NO FUEL  
OR LOW PRESSURE  
TEST 69 – CHECK  
CHOKE SOLENOID  
BAD  
READJUST  
REPLACE CHOKE SOLENOID  
TEST 71 –  
BAD  
TEST 77 –  
CHECK AND  
ADJUST VALVES  
TEST 70 –  
CHECK FOR  
IGNITION SPARK  
GOOD  
GOOD  
CHECK SPARK  
BAD  
PLUGS  
BAD  
TEST 74 – CHECK  
IGNITION MAGNETOS  
CLEAN, REGAP  
OR REPLACE  
GOOD  
GOOD  
BAD  
TEST 15 - CHECK  
AND ADJUST  
ENGINE  
GOVERNOR  
SINGLE CYLINDER UNITS  
BAD  
READJUST  
ADJUST OR  
REPLACE  
TEST 16 – CHECK  
STEPPER MOTOR  
CONTROL  
GOOD  
V-TWIN UNITS  
TEST 72 – CHECK  
ENGINE  
COMPRESSION  
BAD  
TEST 78 – CHECK  
FUEL REGULATOR  
GOOD  
REPAIR OR  
REPLACE  
GOOD  
BAD  
BAD  
REPAIR OR  
REPLACE  
REFER TO ENGINE  
SERVICE MANUAL  
CHECK  
FLYWHEEL  
KEY  
Page 120  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.3  
trouBlEsHootiNG floW cHarts  
DC CONTROL  
Part 4  
Problem 19 – Shutdown Alarm/Fault Occured  
CHECK FAULT LIGHTS  
OVERCRANK  
PROCEED TO PROBLEM 16  
CHECK INSTALLATION FOR  
PROPER AIRFLOW OR  
REPLACE DEFECTIVE SWITCH  
TEST 76 – CHECK HIGH  
OIL TEMPERATURE  
SWITCH  
HIGH TEMP  
REPAIR LINKAGE IF BINDING.  
CHECK THROTTLE OPERATION.  
REFER TO ENGINE SERVICE  
MANUAL  
TEST 15 – CHECK  
AND ADJUST  
ENGINE GOVERNOR  
TEST 14 - CHECK  
AC OUTPUT  
FREQUENCY  
OVERSPEED  
SINGLE CYLINDER UNITS  
BAD  
TEST 16 – CHECK  
STEPPER MOTOR  
REPAIR OR  
REPLACE  
V-TWIN UNITS  
BAD  
BAD  
CONTROL  
TEST 73 – CHECK  
SHUTDOWN  
WIRE  
TEST 70 –  
TEST 78 – CHECK  
WIRE 18  
CONTINUITY  
GOOD  
OR  
BAD  
CHECK FOR  
IGNITION  
SPARK  
NO RPM  
SENSE  
GOOD  
GOOD  
BAD  
BAD  
REPAIR OR  
REPLACE SHORTED  
WIRE 18 OR CIRCUIT  
BOARD  
REPAIR OR  
REPLACE  
NO SIGNAL  
TEST 74 – CHECK  
IGNITION  
MAGNETOS  
TEST 75 – CHECK OIL  
PRESSURE SWITCH  
AND WIRE 86  
LOW OIL  
PROCEED TO PROBLEMS 10-13  
LOW BATTERY  
Page 121  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.3  
trouBlEsHootiNG floW cHarts  
DC CONTROL  
Part 4  
Problem 20 – 7.5 Amp Fuse (F1) Blown  
FUSE BLOWS WHEN  
PLACED IN “AUTO”  
OR “MANUAL”  
TEST 80 – CHECK  
CRANKING AND  
RUNNING CIRCUITS  
Problem 21 – Generator Will Not Exercise  
TEST 79 – TEST  
EXERCISE  
FUNCTION  
Problem 22 – No Low Speed Exercise  
TEST 81 - CHECK TO SEE  
DISABLED  
ENABLE  
IF LOW SPEED FUNCTION  
IS ENABLED  
ENABLED  
TEST 82 - CHECK  
OPERATION OF  
CHOKE SOLENOID  
REPLACE  
CONTROLLER  
GOOD  
OPERATING NORMALLY  
TEST 69 – TEST  
CHOKE  
SOLENOID  
BAD  
REPLACE  
Page 122  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
3. If engine cranks but won’t start, go to Problem 17 in  
Section 4.3.  
introduction  
Perform these “Diagnostic Tests” in conjunction with  
the “Troubleshooting Flow Charts” of Section 4.3.  
4. If engine cranks and starts, but transfer to “Standby”  
does NOT occur, go to Problem 7 in Section 3.3.  
The test procedures and methods presented in this  
section are not exhaustive. The manufacturer could not  
possibly know of, evaluate and advise the service trade  
of all conceivable ways in which testing and trouble  
diagnosis might be performed. The manufacturer has  
not undertaken any such broad evaluation.  
5. If transfer to “Standby” occurs, but retransfer back to  
“Utility” does NOT occur when utility source voltage is  
restored, go to Problem 8 in Section 3.3.  
teSt 57 – try a manual Start  
teSt 56 – check poSition oF auto-oFF-  
manual SWitch  
DISCUSSION:  
The first step in troubleshooting for an “engine won’t  
crank” condition is to determine if the problem is  
peculiar to automatic operations only or if the engine  
won’t crank manually either.  
DISCUSSION:  
If the standby system is to operate automatically, the  
generator AUTO-OFF-MANUAL switch must be set to  
AUTO. That is, the generator will not crank and start  
on occurrence of a “Utility” power outage unless that  
switch is at AUTO. In addition, the generator will not  
exercise every seven (7) days as programmed unless  
the switch is at AUTO.  
PROCEDURE:  
1. On the generator panel, set the AUTO-OFF-MANUAL  
switch to OFF.  
2. Set the generator main line circuit breaker to its OFF (or  
open) position.  
AUTO  
3. Set the generator AUTO-OFF-MANUAL switch to MANUAL.  
a. The engine should crank cyclically through it’s  
“crank-rest” cycles until it starts.  
OFF  
b. Let the engine stabilize and warm up for a few  
minutes after it starts.  
MANUAL  
RESULTS:  
1. If the engine cranks manually but does not crank  
automatically, go to Problem 15, Section 4.3.  
2. If the engine does not crank manually, proceed to  
Problem 16 in the “Troubleshooting Flow Charts”.  
Figure 1. AUTO-OFF-MANUAL Switch Positions  
PROCEDURE:  
teSt 58 – auto-oFF-manual SWitch  
(V-tWin only)  
With the AUTO-OFF-MANUAL switch set to AUTO,  
test automatic operation. Testing of automatic opera-  
tion can be accomplished by turning off the Utility  
power supply to the transfer switch. When the utility  
power is turned off, the standby generator should  
crank and start. Following startup, transfer to the  
standby source should occur. Refer to Section 1.8 in  
this manual.  
PROCEDURE:  
1. Press the “ESC” key on the controller until the home  
page is reached.  
2. Press the right arrow key until “Debug” flashes. Press  
“Enter” and the following screen will appear. See Figure  
2, Screen 2.  
Following generator startup and transfer to the standby  
source, turn ON the utility power supply to the transfer  
switch. Retransfer back to the “Utility” source should  
occur. After an “engine cooldown timer” has timed out,  
generator shutdown should occur.  
3. Press “Enter” when “Inputs” is flashing.  
4. With the Inputs Screen displayed, place the AUTO-  
OFF-MANUAL switch to the AUTO Position. If the  
controller reads an input from the switch, Input 7 will  
change from “0” to “1”.  
RESULTS:  
1. If normal automatic operation is obtained, discontinue  
tests.  
2. If engine does not crank when utility power is turned off,  
proceed to Problem 15 Flow Chart, Section 4.3.  
Page 123  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
PROCEDURE:  
1. Simulate a power failure by disconnecting main breaker.  
2. If the generator does not perform the sequence of  
events listed in the above discussion, replace the  
printed circuit board.  
1
2
DEBUG  
INPUTS  
RESULTS:  
Refer back to flow chart  
teSt 60 – check 7.5 amp FuSe  
DISCUSSION:  
The 7.5 amp fuse is located on the generator control  
console. A blown fuse will prevent battery power from  
reaching the circuit board, with the same result as  
setting the AUTO-OFF-MANUAL switch to OFF.  
3
INPUT 7  
INPUT 8  
PROCEDURE:  
Remove the 7.5 amp fuse (F1) by pushing the fuse.  
Figure 2. The Home Page, Debug and Input Screens  
RESULTS:  
1. If the fuse if good, refer back to Flow Chart.  
5. With the Inputs Screen displayed place the AUTO-OFF-  
MANUAL switch to the MANUAL Position. If the control-  
ler reads an input from the switch input 8 will change  
from “0” to “1”.  
2. If the fuse is bad, it should be replaced. Use only an  
identical 7.5 amp replacement fuse.  
3. If fuse continues to blow, proceed to Problem 20  
Flow Chart.  
6. With the AUTO-OFF-MANUAL Switch in the OFF  
position, both inputs will read zero.  
RESULTS:  
teSt 61 – check Battery  
1. If controller failed either Step 4 or Step 5 ,replace the  
controller assembly.  
DISCUSSION:  
Battery power is used to (a) crank the engine and  
(b) to power the circuit board. Low or no battery  
voltage can result in failure of the engine to crank,  
either manually or during automatic operation. The  
trickle charger that is included in the generator will not  
recharge a dead battery.  
2. If the controller passed Step 4 and Step 5, refer back  
to flow chart.  
teSt 59 – teSt auto operationS  
PROCEDURE:  
DISCUSSION:  
a. inspect Battery cables:  
1. Visually inspect battery cables and battery posts.  
initial conditions: The generator is in AUTO, ready  
to run, and load is being supplied by the utility source.  
When utility fails (below 65% of nominal), a 10 second  
(optionally programmable) line interrupt delay time is  
started. If the utility is still gone when the timer expires,  
the engine will crank and start. Once started, a five (5)  
second engine warm-up timer will be initiated. When  
the warm-up timer expires, the control will transfer the  
load to the generator. If the utility power is restored  
(above 75% of nominal) at any time from the initiation  
of the engine start until the generator is ready to accept  
a load (5 second warm-up time has not elapsed), the  
controller will complete the start cycle and run the  
generator through its normal cool down cycle; however,  
the load will remain on the utility source.  
2. If cable clamps or terminals are corroded, clean away all  
corrosion.  
3. Install battery cables, making sure all cable clamps are  
tight.The red battery cable from the starter contactor (SC)  
must be securely attached to the positive (+) battery post;  
the black cable from the frame ground stud must be tightly  
attached to the negative (-) battery post.  
4. Disconnect both negative and positive cables.  
*note: disconnect negative battery cable first.  
5. Using a DC Volt meter, measure DC volts on the battery.  
Page 124  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
B. perform a load test on the Battery:  
(maintenance Free Battery)  
b. An average reading of 1.230 means the battery  
is 75% charged.  
1. Using a lead acid battery load tester test the load  
capability of the battery.  
c. An average reading of 1.200 means the battery  
is 50% charged.  
d. An average reading of 1.170 indicates the bat-  
tery is 25% charged.  
2. Follow the load tester’s manufacturer’s instructions carefully.  
USE A TEMPERATURE  
COMPENSATED  
HYDROMETER  
CHECK EACH CELL  
AFTER CHARGING  
Figure 3. A Typical Battery Load Tester  
Figure 4. Using a Battery Hydrometer  
5. Test Battery Condition:  
c. te s t B a t t e r y S t a t e o f c h a r g e :  
(non-maintenance Free Battery)  
a. If the difference between the highest and lowest  
reading cells is greater than 0.050 (50 points),  
battery condition has deteriorated and the bat-  
tery should be replaced.  
1. Use an automotive type battery hydrometer to test  
battery state of charge.  
b. However, if the highest reading cell has a  
specific gravity of less than 1.230, the test  
for condition is questionable. Recharge the  
battery to a 100 percent state of charge, and  
then repeat the test for condition.  
2. Follow the hydrometer manufacturer’s instructions  
carefully. Read the specific gravity of the electrolyte  
fluid in all battery cells.  
3. If cells are low, distilled water can be added to refill cell  
compartment.  
RESULTS:  
4. If the hydrometer does not have a “percentage of charge”  
scale, compare the reading obtained to the following:  
1. Remove the battery and recharge with an automotive  
battery charger, if necessary.  
a. An average reading of 1.260 indicates the  
battery is 100% charged.  
2. If battery condition is bad, replace with a new battery.  
1220  
1230  
1240  
1250  
1260  
Cell #  
Specific Gravity  
32  
28  
24  
20  
16  
12  
8
LIQUID  
LEVEL  
1
2
3
4
5
6
1.255  
1.260  
1.235  
1.250  
1.240  
1.225  
HIGH READING  
1270  
4
80°  
0
4
26.6°  
35 POINTS DIFFERENCE  
LOW READING  
8
12  
16  
20  
24  
28  
32  
Figure 5. Reading a Battery Hydrometer  
Page 125  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
RESULTS:  
teSt 62 – check Wire 56 VoltaGe  
1. If battery voltage is indicated in Step 3 refer back to  
flow chart.  
DISCUSSION:  
During an automatic start or when starting manually,  
a crank relay on the circuit board should energize.  
Each time the crank relay energizes, the circuit board  
should deliver 12 VDC to a starter contactor relay  
(SCR), or starter contactor (SC), and the engine  
should crank. This test will verify (a) that the crank  
relay on the circuit board is energizing, and (b) that  
circuit board action is delivering 12 VDC to the starter  
contactor relay or starter contactor.  
DEBUG  
PROCEDURE:  
1. Set a VOM to measure DC voltage.  
2. Connect the positive (+) test probe of a DC voltmeter  
(or VOM) to the Wire 56 connector of the starter  
contactor relay (SCR, on models with V-twin engines)  
or the starter contactor (SC, on models with single  
cylinder engines). Connect the common (-) test probe  
to frame ground.  
OUTPUTS  
OUTPUTS 1 - 8:  
1 0 1 1 0 0 0 1  
3. Observe the meter. Then, set the AUTO-OFF-MANUAL  
switch to the MANUAL position. The meter should  
indicate battery voltage. If battery voltage is measured,  
stop testing and refer back to flow chart.  
OUTPUT 6  
Figure 6. The Home Page, Debug and Output Screens  
4. Navigate to the Digital output display screen.  
a. Press “ESC” until the main menu is reached.  
b. Press the right arrow key until “Debug” is flashing.  
c. Press “Enter”.  
teSt 63 – teSt Starter contactor  
relay (V-tWin only)  
d. Press the right arrow key until “Outputs” is flashing.  
e. Press “Enter”.  
DISCUSSION:  
f. Digital Output 6 is Wire 56 output from the  
board. Refer to Figure 6.  
The starter contactor relay (SCR) located in the con-  
trol panel must be energized for cranking to occur.  
Once the SCR is energized, it’s normally open con-  
tacts will close and battery voltage will be available  
to Wire 16 and to the starter contactor (SC).  
5. Actuate the AUTO-OFF-MANUAL switch to the MANUAL  
position and observe digital output Number 6. If the  
printed circuit board is working correctly output Number  
6 will change from a “0” to a “1”. If output did not change  
replace printed circuit board.  
16  
13  
6. Set a VOM to measure resistance.  
note: remove 7.5 amp fuse before disconnecting  
j1 connector.  
16  
13  
COM  
7. Remove Wire 56 from the starter contactor relay (V-twin  
units) or from the starter contactor (single cylinder  
units). Connect one meter test lead to disconnected  
Wire 56. Remove the J2 Connector from the printed  
circuit board. Connect the other test lead to Wire 56 at  
J2. CONTINUITY should be measured. If CONTINUITY  
is not measured, repair or replace Wire 56.  
NO  
56  
0
56  
0
Figure 7. The Starter Contactor Relay  
Page 126  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
PROCEDURE:  
1. Connect the positive (+) meter test lead to the starter  
contactor stud (to which the red battery cable connects).  
Connect the common (-) meter test lead to a clean frame  
ground. Battery voltage (12 VDC) should be indicated.  
1. Set a VOM to measure DC voltage.  
2. Remove Wire 13 from the Starter Contactor Relay located  
under the printed circuit board.  
2. Connect the positive (+) meter test lead to the starter  
contactor stud to which the starter motor cable attaches  
(see Figure 8 or Figure 9). Connect the common (-) test  
lead to frame ground.  
3. Connect the positive (+) meter test lead to the Wire 13  
connector. Connect the negative (-) meter test lead to a  
clean frame ground. Battery voltage should be measured.  
4. Reconnect Wire 13 to the SCR.  
a. No voltage should be indicated initially.  
5. Remove Wire 16 from the SCR. Connect the positive (+)  
meter test lead to the SCR terminal from which Wire 16  
was removed. Connect the negative (-) meter test lead  
to a clean frame ground.  
b. Set the AUTO-OFF-MANUAL switch to MANUAL.  
The meter should now indicate battery voltage  
as the starter contactor energizes.  
56  
TO ECB  
16  
6. Set the AUTO-OFF-MANUAL switch to MANUAL.  
Observe the meter reading. Battery voltage should be  
measured. If battery voltage is not measured, proceed  
to Step 7.  
TO STARTER  
stEP 2  
TEST POINT  
7. Set the VOM to measure resistance.  
stEP 1  
TEST POINT  
8. Remove Wire 0 from the SCR. Connect the positive (+)  
meter test lead to the disconnected Wire 0. Connect  
the negative (-) meter test lead to a clean frame ground.  
CONTINUITY should be measured.  
13  
0
TO FUSE (F1)  
RESULTS:  
13  
TO GROUND  
1. If battery voltage is not measured in Step 3, repair or  
replace wiring between the starter contactor relay and  
the starter solenoid.  
TO BATTERY  
Figure 8. The Starter Contactor (Single Cylinder Units)  
2. If battery voltage is not measured in Step 6 and  
CONTINUITY is measured in Step 8, replace the starter  
contactor relay.  
RESULTS:  
1. If battery voltage was indicated in Step 1, but NOT in  
Step 2b, replace the starter contactor.  
3. If battery voltage is measured in Step 6 refer back to  
flow chart.  
2. If battery voltage was indicated in Step 2b, but the  
engine did NOT crank, refer back to flow chart.  
teSt 64 – teSt Starter contactor  
(SinGle cylinder enGine)  
stEP 1  
TEST POINT  
STARTER  
CONTACTOR  
DISCUSSION:  
The starter contactor (SC) must energize and its  
heavy duty contacts must close or the engine will not  
crank. This test will determine if the starter contactor  
is in working order.  
stEP 2  
TEST POINT  
STARTER  
MOTOR  
PROCEDURE:  
Carefully inspect the starter motor cable that runs  
from the battery to the starter motor. Cable connec-  
tions must be clean and tight. If connections are  
dirty or corroded, remove the cable and clean cable  
terminals and terminal studs. Replace any cable that  
is defective or badly corroded.  
Figure 9. The Starter Contactor (V-twin Units)  
Use a DC voltmeter (or a VOM) to perform this test.  
Test the starter contactor as follows:  
Page 127  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
teSt 65 – teSt Starter motor  
CONDITIONS AFFECTING STARTER MOTOR  
PERFORMANCE:  
1. A binding or seizing condition in the starter motor bearings.  
2. A shorted, open or grounded armature.  
a. Shorted armature (wire insulation worn and  
wires touching one another). Will be indicated  
by low or no RPM.  
b. Open armature (wire broken) will be indicated  
by low or no RPM and excessive current draw.  
c. Grounded armature (wire insulation worn and wire  
touching armature lamination or shaft). Will be  
indicated by excessive current draw or no RPM.  
Figure 10. Starter Motor (V-Twin Engines)  
3. A defective starter motor switch.  
4. Broken, damaged or weak magnets.  
5. Starter drive dirty or binding.  
DISCUSSION:  
Test 62 verified that circuit board action is delivering  
DC voltage to the starter contactor relay (SCR). Test  
63 verified the operation of the SCR. Test 64 verified  
the operation of the starter contactor (SC). Another  
possible cause of an “engine won’t crank” problem is  
a failure of the starter motor.  
PROCEDURE:  
The battery should have been checked prior to this  
test and should be fully charged.  
Set a VOM to measure DC voltage (12 VDC). Connect  
the meter positive (+) test lead to the starter contactor  
stud which has the small jumper wire connected to  
the starter. Connect the common (-) test lead to the  
starter motor frame.  
Figure 11. Starter Motor (Single Cylinder Engines)  
CHECkING THE PINION:  
When the starter motor is activated, the pinion gear  
should move and engage the flywheel ring gear. If the  
pinion does not move normally, inspect the pinion for  
binding or sticking.  
Set the AUTO-OFF MANUAL Switch to its “MANUAL”  
position and observe the meter. Meter should indicate  
battery voltage, starter motor should operate and  
engine should crank.  
RESULTS:  
1. If battery voltage is indicated on the meter but starter  
motor did NOT operate, remove and bench test the  
starter motor (see following test).  
2. If battery voltage was indicated and the starter motor tried  
to engage (pinion engaged), but engine did NOT crank,  
check for mechanical binding of the engine or rotor.  
If engine turns over slightly, go to Test 77 “Check and  
Adjust Valves.”  
PINION  
Figure 12. Check Pinion Gear Operation (V-Twin)  
Page 128  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
Figure 15. Tachometer  
PINION  
TEST BRACkET:  
A starter motor test bracket may be made as shown  
in Figure 16. A growler or armature tester is available  
from an automobile diagnostic service supplier.  
Figure 13. Check Pinion Gear Operation  
(Single Cylinder)  
METAL STOCK  
1/4" THICK STEEL  
2.625"  
0.5"  
TOOLS FOR STARTER PERFORMANCE TEST:  
3.5"  
The following equipment may be used to complete a  
performance test of the starter motor:  
1.0"  
4"  
• A clamp-on ammeter.  
• A tachometer capable of reading up to 10,000 rpm.  
• A fully charged 12 volt battery.  
12"  
DRILL TWO HOLES — 1/2"  
FOR STARTER  
MOUNTING BRACKET  
2"  
MEASURING CURRENT:  
DRILL TWO HOLES — 1/2"  
FOR MOUNTING TACHOMETER  
TAP FOR 1/4-20 NC SCREWS  
To read the current flow, in AMPERES, a clamp-on  
ammeter may be used. This type of meter indicates  
current flow through a conductor by measuring the  
strength of the magnetic field around that conductor.  
Figure 16. Test Bracket  
REMOVE STARTER MOTOR:  
It is recommended that the starter motor be removed  
from the engine when testing starter motor perfor-  
mance. Assemble starter to test bracket and clamp  
test bracket in vise, Figure 17.  
TESTING STARTER MOTOR:  
1. A fully charged 12 volt battery is required.  
2. Connect jumper cables and clamp-on ammeter as  
shown in Figure 17.  
3. With the starter motor activated (jump the terminal on the  
starter contactor to battery voltage), note the reading on  
the clamp-on ammeter and on the tachometer (rpm).  
note: take the reading after the ammeter and  
tachometer are stabilized, approximately 2-4  
seconds.  
Figure 14. Clamp-On Ammeter  
4. A starter motor in good condition will be within the fol-  
lowing specifications:  
TACHOMETER:  
A tachometer is available from your parts source.  
The tachometer measures from 800 to 50,000 rpm,  
(see Figure 15).  
V-twin  
3250  
62  
Single Cylinder  
Minimum rpm  
4500  
9
Maximum Amps  
Page 129  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
tENDs to sEttlE iN HiGH PlacEs. lP  
(ProPaNE) Gas is HEaViEr tHaN air, aND  
tENDs to sEttlE iN loW arEas. EVEN  
tHE sliGHtEst sParK caN iGNitE tHEsE  
GasEs aND causE aN EXPlosioN.  
PROCEDURE:  
A water manometer or a gauge that is calibrated in  
“ounces per square inch” may be used to measure  
the fuel pressure. Fuel pressure at the inlet side of  
the fuel solenoid valve should be between 5-7 inches  
water column for natural gas (NG) or 10-12 inches  
water column for LP gas.  
CLAMP ON  
AMP METER  
STARTER  
CONTACTOR  
STARTER  
MOTOR  
1. See Figures 18, 19 or 20 for the gas pressure test point on  
the fuel regulator. The fuel pressure can be checked at Port  
1 on all fuel regulators, and at Port 3 on 12-20 kW units.  
2. With the manometer connected properly, crank the engine.  
Nominal fuel pressure should be measured. If pressure is  
not measured while cranking refer back to flow chart.  
TACHOMETER  
VISE  
12 VOLT  
BATTERY  
Figure 17. Testing Starter Motor Performance  
PORT 1  
PORT 2  
teSt 66 – check Fuel Supply and  
preSSure  
DISCUSSION:  
The air-cooled generator was factory tested and  
adjusted using natural gas as a fuel. If desired, LP  
(propane) gas may be used. However, when convert-  
ing to propane, some minor adjustments are required.  
The following facts apply:  
• An adequate gas supply and sufficient fuel pressure  
must be available or the engine will not start.  
Figure 18 (8 kW) Gas Pressure Test point  
• Minimum recommended gaseous fuel pressure  
at the generator fuel inlet connection is 5 inches  
water column for natural gas (NG) or 10 inches  
water column for LP gas.  
• Maximum gaseous fuel pressure at the generator  
fuel inlet connection is 7 inches water column for  
natural gas or 12 inches water column for LP gas.  
PORT 1  
PORT 2  
• When propane gas is used, only a “vapor withdrawal”  
system may be used. This type of system utilizes  
the gas that forms above the liquid fuel. The vapor  
pressure must be high enough to ensure engine  
operation.  
• The gaseous fuel system must be properly tested for  
leaks following installation and periodically thereafter.  
No leakage is permitted. Leak test methods must  
comply strictly with gas codes.  
SOLENOID REMOVED  
DaNGEr: GasEous fuEls arE HiGHlY  
EXPlosiVE. Do Not usE flamE or HEat  
to tEst tHE fuEl sYstEm for lEaKs.  
Natural Gas is liGHtEr tHaN air, aND  
*
Figure 19 (10 kW) Gas Pressure Test point  
Page 130  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
PROCEDURE: 12-20 kW UNITS  
1. Set the AUTO-OFF-MANUAL switch to OFF.  
2. Set a VOM to measure DC voltage.  
PORT 3  
3. Disconnect Wire 14 from the fuel solenoid (FS).  
4. Connect the positive test lead to the disconnected Wire  
14 from Step 3. Connect the negative test lead to a  
clean frame ground.  
PORT 1  
PORT 2  
5. Set AUTO-OFF-MANUAL switch to the MANUAL position.  
The meter should indicate battery voltage.  
a. If battery voltage is indicated, refer back to  
flow chart.  
b. If battery voltage is not measured, navigate to  
the Digital Output display.  
c. Press “ESC” until the display screen is present.  
d. Press the right arrow key until “Debug” is flashing.  
Press “Enter”.  
e. Press the right arrow key until “Outputs” is  
flashing. Press “Enter”.  
Figure 20 (12-20 kW) Gas Pressure Test point  
note: Where a primary regulator is used to estab-  
lish fuel inlet pressure, adjustment of that regula-  
tor is usually the responsibility of the fuel supplier  
or the fuel supply system installer.  
12-20 kW UNITS ONLY:  
note:the test port (port 3) below the fuel solenoid  
maybe used to take a fuel pressure reading before  
the fuel solenoid. consistent pressure should be  
measured at this port while the generator is run-  
ning and when the generator is off.  
DEBUG  
RESULTS:  
1. If fuel supply and pressure are adequate, but engine will  
not start refer back to flow chart.  
OUTPUTS  
OUTPUTS 1 - 8:  
2. If generator starts but runs rough or lacks power, repeat  
the above procedure with the generator running and  
under load. The fuel system must be able to maintain  
10-12 inches water column at all load requirements for  
propane, and 5-7 inches water column for natural gas.  
If proper fuel supply and pressure is maintained, refer to  
Problem 18 Flow Chart.  
1 0 1 1 0 0 0 1  
OUTPUT 5  
Figure 21. The Home Page, Debug and Output  
Screens  
f. Output 5 is Wire 14 out from the printed circuit  
board. If the printed circuit board is functioning  
properly, Output 5 will change from a “0” to a “1”  
while the unit is cranking.  
teSt 67 – check circuit Board Wire 14  
output  
g. If voltage was not measured in Step 5 and  
output did not change in Step 5f, replace the  
printed circuit board.  
DISCUSSION:  
During any cranking action, the circuit board’s crank  
relay and run relay both energize simultaneously.  
When the run relay energizes, it’s contacts close and  
12 VDC is delivered to Wire 14 and to a fuel solenoid.  
The solenoid energizes open to allow fuel flow to the  
engine. This test will determine if the circuit board is  
working properly.  
note: disconnect the 7.5 amp Fuse before dis-  
connecting the j2 connector.  
h. If voltage was not measured in Step 5 and out-  
put changed in Step 5f, remove the J1 connec-  
tor from the printed circuit board. See Figures  
on Pages 92-95.  
Page 131  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
i. Set a VOM to measure resistance.  
If gas pressure is measured, the fuel solenoid is operat-  
ing. If gas pressure is not measured, repair or replace the  
fuel solenoid.  
j. Connect one meter test lead to Wire 14 that  
was disconnected in Step 3.  
k. Connect the other meter test lead to Wire 14 at  
J2-3. See Figures on Pages 92-95.  
PROCEDURE: 10 kW UNITS  
l. CONTINUITY should be measured. If  
CONTINUITY is measured, repeat Step 5 and  
then retest.  
1. Remove the hose from fuel solenoid (FS2) and install a  
manometer to Port 2 on the fuel regulator. See Figure 19.  
2. Set the AUTO-OFF-MANUAL Switch to MANUAL.  
m. If CONTINUITY is not measured, repair or  
replace Wire 14 between the J2 Connector and  
the fuel solenoid.  
3. Proper gas pressure should be measured during crank-  
ing. If gas pressure is measured, both fuel solenoids are  
operating. Discontinue testing.  
PROCEDURE: 8 kW UNITS  
4. If gas pressure was not measured in Step 3, remove fuel  
solenoid FS2 and install a manometer to the bottom port  
of the fuel regulator.  
1. Set AUTO-OFF-MANUAL switch to OFF.  
2. Set a VOM to measure DC voltage.  
3. Disconnect Wire 14 from the fuel solenoid.  
5. Set the AUTO-OFF-MANUAL Switch to MANUAL.  
4. Connect the positive test lead to disconnected Wire 14  
and the negative test lead to a clean frame ground.  
6. Proper gas pressure should be measured during crank-  
ing. If gas pressure is measured, fuel solenoid FS1 is  
operating. Replace fuel solenoid FS2. If gas pressure is  
not measured, repair or replace fuel solenoid FS1.  
5. Set the AUTO-OFF-MANUAL switch to the MANUAL  
position.  
6. Battery voltage should be measured. If battery voltage is  
measured, refer back to flow chart.  
RESULTS:  
Refer to flow chart.  
note: disconnect the 7.5 amp fuse before discon-  
necting the j2 connector.  
teSt 69 – check choke Solenoid  
7. Disconnect the J2 connector from printed circuit board.  
8. Set VOM to measure resistance.  
DISCUSSION:  
9. Connect the positive test lead to disconnected Wire 14  
and the negative test lead to J2 Pin 3.  
The automatic choke is active cyclically during crank-  
ing and energized ON during running. For low speed  
exercise the choke will be closed.  
10.CONTINUITY should be measured. If CONTINUITY is  
not measured, repair or replace Wire 14 between J2 Pin  
3 and the fuel solenoid.  
The 12-20 kW units utilize a plate that covers the  
throttle bores. The choke is closed if the solenoid is  
not energized.  
The 10 kW unit utilizes a throttle plate located in  
the choke housing and the choke is open when the  
solenoid is de-energized.  
RESULTS:  
Refer to flow chart.  
The 8 kW unit has a choke solenoid that is closed  
during the entire crank cycle when the solenoid is  
energized and the engine is cranking.  
teSt 68 – check Fuel Solenoid  
PROCEDURE: 10-20 kW UNITS  
DISCUSSION:  
1. Operational Check: Set the AUTO-OFF-MANUAL  
Switch to MANUAL. While cranking, the choke solenoid  
should pull the choke plate open cyclically. The dura-  
tion of the cycle will vary depending on it’s position in  
the crank cycle sequence. Refer to the Crank Cycle  
Sequence Table on the following page for crank cycle  
sequences and duration times. If the choke solenoid  
does not pull in, verify that the choke can be manually  
opened. There should be no binding or interference.  
In Test 67, if battery voltage was delivered to Wire 14,  
the fuel solenoid should have energized open. This test  
will verify whether or not the fuel solenoid is operating.  
Fuel Solenoid FS1 nominal resistance – 27-33 ohms.  
Fuel Solenoid FS2 nominal resistance – 29 ohms.  
PROCEDURE: 8 AND 12-20 kW UNITS  
1. Install a manometer to Port 2 on the fuel regulator. See  
Figure 18 or Figure 20.  
2. Disconnect the C3 Connector.  
2. Set the AUTO-OFF-MANUAL Switch to MANUAL.  
3. Proper gas pressure should be measured during cranking.  
Page 132  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
7. With the generator running at a speed of approximately  
60 Hertz, verify that the choke is energized and hold-  
ing the choke plate open. Repeat Step 2 procedure,  
however, once the unit starts, manually hold the choke  
open while taking the voltage measurement.  
CHOKE PLATE  
CHOKE SOLENOID  
CHOKE SOLENOID  
CHOKE PLATE  
Figure 22. Solenoid De-Energized, Choke Closed  
12-20 kW Units  
CHOKE HOUSING  
CHOKE PLATE  
Figure 24. Exploded View Showing Location of Choke  
Plate - 10 kW Units  
14  
90  
14  
90  
CHOKE SOLENOID  
Figure 23. Solenoid Energized, Choke Open  
12-20 kW Units  
2
1
1
2
3. Set a VOM to measure DC voltage.  
MALE SIDE  
FEMALE SIDE  
4. Connect the positive (+) test lead to Wire 14 (Pin 1) of the  
C3 Connector going to the control panel (Female Side).  
Connect the negative (-) test lead to Wire 90 (Pin 2).  
Figure 25. C3 Choke Solenoid Connector  
5. Set the AUTO-OFF-MANUAL Switch to MANUAL. While  
cranking, battery voltage should be measured cyclically.  
If battery voltage was not measured, verify continuity  
of Wire 90 between the C3 Connector and the printed  
circuit board J1 Connector, Pin Location J1-23. Verify  
continuity of Wire 14 between the C3 Connector and  
J2 connector Pin Location J2-3. Repair or replace any  
wiring as needed.  
RESULTS:  
1. If Battery voltage was not measured in Step 5 and wire  
continuity is good, replace the printed circuit board.  
2. If Choke Solenoid coil resistance is not measured in  
Step 6, replace the Choke Solenoid.  
PROCEDURE: 8 kW UNITS  
6. Disconnect C3 Connector. Set a VOM to measure resis-  
tance. Connect the positive (+) test lead to Wire 14 (Pin  
1) of C3 Connector going to the choke solenoid (Male  
Side). Connect the negative (-) test lead to Wire 90 (Pin  
2). Approximately 3.7 ohms should be measured.  
1. Operational Check: Set the AUTO-OFF-MANUAL  
Switch to MANUAL. While cranking the choke solenoid  
should energize and pull the choke plate closed. If the  
choke solenoid does not pull in, verify that the choke  
can be manually closed. There should be no binding or  
interference.  
Page 133  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
2. Disconnect the C3 Connector.  
2. If Choke Solenoid coil resistance is not measured in  
Step 8, replace the Choke Solenoid.  
3. Set a VOM to measure DC voltage.  
3. If battery voltage was not measured in Step 4, replace  
the printed circuit board.  
4. Connect the positive (+) test lead to Wire 56 (Pin 1) of  
C3 Connector going to the control panel (Female Side)  
Connect the negative (-) test lead to Wire 0 (Pin 2).  
teSt 70 – check For iGnition Spark  
5. Set the AUTO-OFF-MANUAL Switch to MANUAL. While  
cranking, battery voltage should be measured. If battery  
voltage was not measured, verify continuity of Wire  
0 between C3 Connector and a clean frame ground.  
Verify continuity of Wire 56 between the C3 Connector  
and Wire 56 connector and J2 Connector Pin Location  
J2-11. Repair or replace any wiring as needed.  
DISCUSSION:  
If the engine cranks but will not start, perhaps an  
ignition system failure has occurred. A special “spark  
tester” can be used to check for ignition spark.  
PROCEDURE:  
6. Disconnect C3 Connector.  
1. Remove spark plug leads from the spark plugs  
(Figure 28).  
7. Set a VOM to measure resistance.  
2. Attach the clamp of the spark tester to the engine  
cylinder head.  
8. Connect the positive (+) test lead to Wire 56 (Pin 1) of  
C3 Connector going to the choke solenoid (Male Side).  
Connect the negative (-) test lead to Wire 0 (Pin 2).  
Approximately 3.7 ohms should be measured.  
3. Attach the spark plug lead to the spark tester terminal.  
4. Crank the engine while observing the spark tester. If  
spark jumps the tester gap, you may assume the engine  
ignition system is operating satisfactorily.  
RESULTS:  
1. If Battery voltage was not measured in Step 5 and wire  
continuity is good, replace the printed circuit board.  
note: the engine flywheel must rotate at 350 rpm  
(or higher) to obtain a good test of the solid state  
ignition system.  
crank cycle sequence table  
1=CHOkED  
Note:the first second of each crank cycle is equal to two (2) revolutions of the engine.  
0=OPEN  
Seconds  
crank cycle 1  
10 kW  
1
0
0
2
0
1
3
0
1
4
0
0
5
1
0
6
0
1
7
0
1
8
0
1
9
0
0
10  
1
11  
1
12  
0
13  
0
14  
0
15  
0
16  
0
12 kW-20 kW  
0
0
1
1
1
1
1
crank cycle 2  
10 kW  
Seconds  
0
0
0
1
0
1
0
0
1
0
0
0
0
0
0
0
0
0
1
0
1
0
0
1
0
1
0
1
0
1
0
1
12 kW-20 kW  
crank cycle 3  
10 kW  
Seconds  
Seconds  
Seconds  
0
0
1
0
1
1
1
1
1
1
0
1
0
1
12 kW-20 kW  
crank cycle 4  
10 kW  
0
0
1
1
0
0
0
0
0
0
0
0
0
0
12 kW-20 kW  
crank cycle 5  
10 kW  
0
0
1
1
1
0
1
0
1
0
0
0
0
1
12 kW-20 kW  
Page 134  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
CHOKE VALVE IN OPEN POSITION  
CHOKE SOLENOID  
AIR BOX  
CHOKE VALVE IN CLOSED POSITION  
Figure 26. 8kW Choke Solenoid  
Figure 28. Checking Ignition Spark  
To determine if an engine miss is ignition related,  
connect the spark tester in series with the spark plug  
wire and the spark plug (Figure 29). Then, crank and  
start the engine. A spark miss will be readily apparent.  
If spark jumps the spark tester gap regularly but the  
engine miss continues, the problem is in the spark  
plug or in the fuel system.  
Figure 27. Spark Tester  
note: a sheared flywheel key may change  
ignition timing but sparking will still occur  
across the spark tester gap.  
Page 135  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
NORMAL  
MISFIRES  
Figure 29. Checking Engine Miss  
RESULTS:  
1. If no spark or very weak spark occurs, go to Test 73.  
PRE-IGNITION  
DETONATION  
2. If sparking occurs but engine still won’t start, go to Test 71.  
3. When checking for engine miss, if sparking occurs at  
regular intervals but engine miss continues, go to Test 20.  
Figure 30. Spark Plug Conditions  
4. When checking for engine miss, if a spark miss is readily  
apparent, go to Test 74.  
teSt 71 – check Spark pluGS  
DISCUSSION:  
If the engine will not start and Test 70 indicated good  
ignition spark, perhaps the spark plug(s) are fouled or  
otherwise damaged. Engine miss may also be caused  
by defective spark plug(s).  
PROCEDURE:  
1. Remove spark plugs and clean with a penknife or use a  
wire brush and solvent.  
Figure 31. Checking Spark Plug Gap  
2. Replace any spark plug having burned electrodes or  
cracked porcelain.  
3. Set gap on new or used spark plugs as follows:  
teSt 72 – check enGine / cylinder leak  
doWn teSt / compreSSion teSt  
kW  
rating  
recommended  
Plug  
Engine size  
Plug Gap  
GENERAL:  
410 cc  
530 cc  
990 cc  
999 cc  
8 kW  
0.030 inch  
0.030 inch  
RC14YC  
BPR6HS  
RC14YC  
RC12YC  
Most engine problems may be classified as one or a  
combination of the following:  
• Will not start  
• Starts hard  
• Lack of power  
• Runs rough  
• Vibration  
• Overheating  
• High oil consumption  
10 kW  
10-17 kW 0.040 inch  
20 kW 0.030 inch  
RESULTS:  
1. Clean, re-gap or replace spark plugs as necessary.  
2. If spark plugs are good, refer back to flow chart.  
Page 136  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
DISCUSSION:  
PROCEDURE:  
The Cylinder Leak Down Tester checks the sealing  
(compression) ability of the engine by measuring air  
leakage from the combustion chamber. Compression  
loss can present many different symptoms. This test  
is designed to detect the section of the engine where  
the fault lies before disassembling the engine.  
1. Remove both spark plugs.  
2. Insert a compression gauge into either cylinder.  
3. Crank the engine until there is no further increase in  
pressure.  
4. Record the highest reading obtained.  
PROCEDURE:  
5. Repeat the procedure for the remaining cylinder and  
record the highest reading.  
1. Remove a spark plug.  
2. Gain access to the flywheel. Remove the valve cover.  
RESULTS:  
3. Rotate the engine crankshaft until the piston reaches top  
dead center (TDC). Both valves should be closed.  
The difference in pressure between the two cylinders  
should not exceed 25 percent. If the difference is  
greater than 25 percent, loss of compression in the  
lowest reading cylinder is indicated.  
4. Lock the flywheel at top dead center.  
5. Attach cylinder leak down tester adapter to spark plug  
hole.  
example 1: if the pressure reading of cylinder #1 is  
165 psi and of cylinder #2, 160 psi, the difference  
is 5 psi. divide “5” by the highest reading (165) to  
obtain the percentage of 3.0 percent.  
6. Connect an air source of at least 90 psi to the leak  
down tester.  
example 2: no. 1 cylinder reads 160 psi; no. 2  
cylinder reads 100 psi. the difference is 60 psi.  
divide “60” by “160” to obtain “37.5” percent. loss  
of compression in no. 2 cylinder is indicated.  
7. Adjust the regulated pressure on the gauge to 80 psi.  
8. Read the right hand gauge on the tester for cylinder  
pressure. 20 percent leakage is normally acceptable.  
Use good judgement, and listen for air escaping at the  
carburetor, the exhaust, and the crankcase breather.  
This will determine where the fault lies.  
If compression is poor, look for one or more of the fol-  
lowing causes:  
• Loose cylinder head bolts  
• Failed cylinder head gasket  
• Burned valves or valve seats  
• Insufficient valve clearance  
• Warped cylinder head  
9. Repeat Steps 1 through 8 on remaining cylinder.  
RESULTS:  
• Air escapes at the carburetor – check intake valve.  
• Air escapes through the exhaust – check exhaust  
valve.  
• Air escapes through the breather – check piston  
rings.  
• Air escapes from the cylinder head – the head  
gasket should be replaced.  
• Warped valve stem  
• Worn or broken piston ring(s)  
• Worn or damaged cylinder bore  
• Broken connecting rod  
• Worn valve seats or valves  
• Worn valve guides  
note: refer to engine Service manual for further  
engine service information.  
CHECk COMPRESSION:  
Lost or reduced engine compression can result in (a)  
failure of the engine to start, or (b) rough operation.  
One or more of the following will usually cause loss of  
compression:  
teSt 73 – check ShutdoWn Wire  
• Blown or leaking cylinder head gasket  
• Improperly seated or sticking-valves  
DISCUSSION:  
Circuit board action during shutdown will ground Wire  
18. Wire 18 is connected to the Ignition Magneto(s).  
The grounded magneto will not be able to produce  
spark.  
• Worn Piston rings or cylinder. (This will also result in  
high oil consumption)  
note: For the single cylinder engine, the minimum  
allowable compression pressure for a cold engine  
is 60 psi.  
PROCEDURE:  
1. On V-twin generators, remove Wire 18 from the stud  
located above the oil cooler. On single cylinder gen-  
erators, disconnect Wire 18 at the bullet connector. See  
Figures 32 or 33.  
note: it is extremely difficult to obtain an accu-  
rate compression reading without special equip-  
ment. For that reason, compression values are  
not published for the V-twin engine. testing has  
proven that an accurate compression indication  
can be obtained using the following method.  
Page 137  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
RESULTS:  
WIRE 18 CONNECTION  
1. If INFINITY was not measured in Step 4, repair or replace  
shorted ground Wire 18 between the J1 Connector from  
the circuit board to the stud or bullet connector.  
2. If INFINITY was measured in Step 4, replace the circuit  
board and retest for spark.  
3. If ignition spark still has not occurred, proceed to Test 74.  
teSt 74 – check and adjuSt iGnition  
maGnetoS  
DISCUSSION:  
In Test 70, a spark tester was used to check for  
engine ignition. If sparking or weak spark occurred,  
one possible cause might be the ignition magneto(s).  
This test consists of checking ohm values across the  
primary and secondary windings of the magneto and  
adjusting the air gap between the ignition magneto(s)  
and the flywheel. The flywheel and flywheel key will  
also be checked during this test. A diode is installed  
before the primary winding inside the coil. This is  
done to inhibit a spark occurring on both magnetos at  
the same time.  
Figure 32. Wire 18 Connection 10-20 kW Units  
2. Depending on engine type, do the following:  
a. On V-twin units, remove Wire 56 from the  
Starter Contactor Relay (SCR). Using a jumper  
lead, jump 12 VDC from Wire 15B at TB1  
(Customer Connection) to the terminal on the  
SCR from which Wire 56 was removed. The  
generator will start cranking. As it is cranking,  
repeat Test 70. Reconnect Wire 56 when done.  
PROCEDURE: TESTING MAGNETOS V-TWIN ONLY  
b. On single cylinder units, connect a jumper lead  
from the stud to which Wire 56 is connected  
on the Starter Contactor (SC) and 12 VDC  
Wire 15B at TB1 (Customer Connection). The  
generator will start cranking. As it is cranking,  
repeat Test 70.  
1. Disconnect the J1 connector from the printed circuit  
board.  
2. Disconnect spark plug wires from the spark plugs on  
cylinder one and two.  
3. Set VOM to measure resistance.  
WIRE 18  
CONNECTION  
4. Connect the positive (red) meter lead to the bolt connec-  
tor where Wire 18 was disconnected in Step 1. Connect  
the negative (black) meter lead to a clean frame ground.  
A resistance of approximately 300K 10K ohms should  
be measured. This reading is the primary winding of  
both coils in parallel.  
5. Connect the positive meter lead to the spark plug  
wire and connect the negative meter lead to a clean  
frame ground. Approximately 14K 3 ohms should be  
measured. This reading is the secondary winding of  
both coils in parallel. If INFINITY, or a low or high ohm  
reading is measured, replace the magnetos.  
6. Connect the negative (black) meter lead to the bolt  
connector where Wire 18 was disconnected in Step 1.  
Connect the positive (red) meter lead to the spark plug  
wire on cylinder number two. The meter should indicate  
INFINITY.This step is testing the diodes in both magnetos  
to ensure they are still functioning.  
Figure 33. Wire 18 Connection 8 kW Units  
3. If spark now occurs with Wire 18 removed, check for  
a short to ground. Remove the J1 Connector from the  
circuit board.  
4. Set a VOM to measure resistance. Connect one test lead  
to Wire 18 (disconnected in Step 1). Connect the other  
test lead to a clean frame ground. INFINITY should be  
measured.  
7. Repeat Step 6 on cylinder two. If INFINITY is not  
measured, replace the magnetos.  
note: it is recommended to replace magnetos  
in pairs.  
5. Reconnect the J1 Connector to the circuit board.  
Page 138  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
PROCEDURE, ADJUSTING MAGNETO FLYWHEEL GAP:  
where Wire 56 was disconnected in Step 7. The  
engine should crank once the jumper from 15B  
is connected.  
note: the air gap between the ignition magneto  
and the flywheel on single cylinder engines is not  
adjustable. proceed directly to Step 10 for single  
cylinder engines. For V-twin engines, proceed as  
follows.  
8. If spark was not indicated, replace magnetos.  
note: if gap is only adjusted, ensure to properly  
test the magnetos by cranking the engine over  
before reassembly occurs. Spark should be  
present on both cylinders before reassembly  
should be completed.  
1. See Figure 34. Rotate the flywheel until the magnet is  
under the module (armature) laminations.  
2. Place a 0.008-0.012 inch (0.20-0.30mm) thickness  
gauge between the flywheel magnet and the module  
laminations.  
9. If air gap was not out of adjustment, test ground wires.  
10.Set a VOM to the measure resistance.  
note: a business card is approximately 0.010  
inch thick.  
11.Disconnect the engine wire harness from the ignition  
magnetos (Figure 35).  
3. Loosen the mounting screws and let the magnet pull the  
magneto down against the thickness gauge.  
a. On V-twin generators, remove Wire 18 from the  
stud located above the oil cooler. See Figure 45.  
4. Tighten both mounting screws.  
b. On single cylinder generators, disconnect Wire  
18 at the bullet connector. See Figure 44.  
5. To remove the thickness gauge, rotate the flywheel.  
6. Repeat the above procedure for the second magneto.  
ENGINE  
WIRE  
STUD CONNECTOR  
HARNESS  
0.008-0.012" GAUGE  
SPARk PLUG  
WIRE 18 TO  
CIRCUIT BOARD  
REMOVE LEADS  
SPARk PLUG  
Figure 35. Engine Ground Harness  
12.Connect one meter test lead to one of the wires removed  
from the ignition magneto(s). Connect the other test  
lead to frame ground. INFINITY should be measured. If  
CONTINUITY is measured, replace the shutdown harness.  
MAGNETO  
Figure 34. Setting Ignition Magneto (Armature)  
Air Gap  
13.Now check the flywheel magnet by holding a screwdriver  
at the extreme end of its handle and with its point down.  
When the tip of the screwdriver is moved to within 3/4  
inch (19mm) of the magnet, the blade should be pulled  
in against the magnet.  
7. Repeat Test 70 and check for spark across the spark  
tester gap  
a. A spark test may be conducted with unit dis-  
sembled by following this procedure.  
14.For rough running or hard starting engines check the fly-  
wheel key. The flywheel's taper is locked on the crankshaft  
taper by the torque of the flywheel nut. A keyway is provided  
for alignment only and theoretically carries no load.  
b. Battery must be connected.  
c. J2 Connector must be connected to the printed  
circuit board.  
d. Remove Wire 56 from the SCR located beneath  
the printed circuit board.  
note: if the flywheel key becomes sheared  
or even partially sheared, ignition timing can  
change. incorrect timing can result in hard start-  
ing or failure to start.  
Warning: make sure all debris is cleared from the  
engine compartment and all body parts are clear  
from flywheel before proceeding.  
15.As stated earlier, the armature air gap is fixed for single  
cylinder engine models and is not adjustable. Visually  
inspect the armature air gap and hold down bolts.  
e. Refer to Test 70 to check for spark.  
f. Utilizing a jumper wire, connect a wire to the  
15B terminal block. Connect the other end to  
Page 139  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
RESULTS:  
If sparking still does not occur after adjusting the  
armature air gap, testing the ground wires and  
performing the basic flywheel test, replace the  
ignition magneto(s).  
PROCEDURE, REPLACING MAGNETOS:  
1. Follow all steps of the Major Disassembly procedures  
that are located in Section 6.  
2. Once the magnetos are visible, make note to how  
they are connected.  
Figure 38.  
note: each magneto has its own part number.  
Verify the part number prior to installation.  
note: magneto gap between flywheel needs to  
be 0.010 inch.  
3. Cylinder one is the back cylinder (Figure 36) and  
cylinder two is the front cylinder (Figure 37).  
5. Long plug wire (B) will be installed on front cylinder  
number two.  
6. Short plug Wire (A) will be installed on back cylinder  
number one.  
7. Verify installation of magnetos correctly by ensuring both  
spark plug wires point to the back of the enclosure and  
shutdown terminals are nearest cylinder head as shown  
in Figures 39 and 40.  
Figure 36. Cylinder One (Back, Short)  
Figure 39.  
Figure 37. Cylinder Two (Front, Long)  
4. When installing new magnetos there will be one  
with a short plug wire and one with a longer plug  
wire (Figure 38).  
Figure 40.  
Page 140  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
2. Check engine crankcase oil level.  
teSt 75 – check oil preSSure SWitch  
and Wire 86  
a. Check engine oil level.  
b. If necessary, add the recommended oil to  
the dipstick FULL mark. DO NOT OVERFILL  
ABOVE THE FULL MARk.  
DISCUSSION:  
If the oil pressure switch contacts have failed in their  
closed position, the engine will probably crank and  
start. However, shutdown will then occur within about  
5 (five) seconds. If the engine cranks and starts, then  
shuts down almost immediately with a LOP fault light,  
the cause may be one or more of the following:  
3. With oil level correct, try starting the engine.  
a. If engine still cranks and starts, but then shuts  
down, go to Step 4.  
b. If engine cranks and starts normally, discon-  
tinue tests.  
• Low engine oil level.  
• Low oil pressure.  
4. Do the following:  
• A defective oil pressure switch.  
a. Disconnect Wire 86 and Wire 0 from the oil  
pressure switch terminals. Remove the switch  
and install an oil pressure gauge in its place.  
PROCEDURE:  
1. Navigate to the Digital inputs display screen.  
a. Press “ESC” until the main menu is reached.  
b. Press the right arrow key until “Debug” is flashing.  
c. Press “Enter”.  
b. Start the engine while observing the oil pres-  
sure reading on gauge.  
c. Note the oil pressure.  
(1) Normal oil pressure is approximately 35-40  
psi with engine running. If normal oil pres-  
sure is indicated, go to Step 4 of this test.  
d. Press the right arrow key until “Inputs” is flashing.  
e. Press “Enter”.  
(2) If oil pressure is below about 4.5 psi, shut  
engine down immediately. A problem exists  
in the engine lubrication system.  
note: the oil pressure switch is rated at 10 psi  
for V-twin engines, and 8 psi for single cylinder  
engines.  
DEBUG  
INPUTS  
INPUTS 1 - 8:  
1 0 1 1 0 0 0 1  
INPUT 1  
Figure 42. Oil Pressure Switch  
Figure 41. The Home Page, Debug and Input Screens  
5. Remove the oil pressure gauge and reinstall the oil  
pressure switch. Do NOT connect Wire 86 or Wire 0 to  
the switch terminals.  
f. Digital Input 1 is Wire 86 from the Low Oil  
Pressure switch to the board. Refer to Figure 41.  
a. Set a VOM to measure resistance.  
g. Set the AUTO-OFF-MANUAL switch to the  
MANUAL position.  
b. Connect the VOM test leads across the switch  
terminals. With engine shut down, the meter  
should read CONTINUITY. If INFINITY is  
measured with the engine shutdown, replace  
the LOP switch.  
h. Observe Input 1 for a change from "1" to "0". A  
change from "1" to "0" indicates that the control  
board sensed the LOP switch change states. If  
the generator still shuts down, replace printed  
circuit board.  
c. Crank and start the engine. The meter should  
read INFINITY.  
i. If the input did not change states, proceed  
to Step 2  
6. Set a VOM to measure resistance.  
Page 141  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
a. Disconnect the J1 Connector from the printed  
circuit board.  
short to ground. Remove J1 Connector from the circuit  
board. Set the VOM to measure resistance. Connect  
one test lead to Wire 85 (disconnected from High Oil  
Temperature Switch). Connect the other test lead to a  
clean frame ground. INFINITY should be measured.  
b. Connect one test lead to Wire 86 (disconnected  
from LOP). Connect the other test lead to Pin  
Location 4 (Wire 86) of the J1 Connector at the  
Circuit Board (for all models). CONTINUITY  
should be measured. If CONTINUITY is not  
measured, repair or replace Wire 86 between  
the LOP switch and the J1 Connector.  
TESTING HIGH OIL TEMPERATURE SWITCH:  
6. Remove the High Oil Temperature Switch.  
c. Connect one test lead to Wire 0 ( disconnected  
from LOP). Connect the other test lead to a clean  
frame ground. CONTINUITY should be measured.  
If CONTINUITY is NOT measured repair or replace  
Wire 0 between the LOP and the ground terminal  
connection on the engine mount.  
7. Immerse the sensing tip of the switch in oil as shown in  
Figure 43, along with a suitable thermometer.  
8. Set a VOM to measure resistance. Then, connect the  
VOM test leads across the switch terminal and the  
switch body. The meter should read INFINITY.  
7. If the LOP switch tests good in Step 5 and oil pressure  
is good in Step 4 but the unit still shuts down with a LOP  
fault, check Wire 86 for a short to ground. Set a VOM to  
measure resistance. Disconnect the J1 Connector from  
the circuit board. Remove Wire 86 from the LOP switch.  
Connect one test lead to Wire 86. Connect the other  
test lead to a clean frame ground. INFINITY should be  
measured. If CONTINUITY is measured, repair or replace  
Wire 86 between the LOP switch and the J1 Connector.  
9. Heat the oil in the container. When the thermometer  
reads approximately 283°-305° F. (139°-151° C.), the  
VOM should indicate CONTINUITY.  
RESULTS:  
1. Replace switch if it fails the test.  
teSt 76 – check hiGh oil temperature  
SWitch  
DISCUSSION:  
If the temperature switch contacts have failed in a closed  
position, the engine will fault out on “OVERTEMP”. If the  
unit is in an overheated condition, the switch contacts will  
close at 293° F. This will normally occur from inadequate  
airflow through the generator.  
Figure 43. Testing the Oil Temperature Switch  
PROCEDURE:  
RESULTS:  
1. Verify that the engine has cooled down (engine block  
is cool to the touch). This will allow the contacts in the  
High Oil Temperature Switch to close.  
1. If the switch fails Step 4, or Steps 8-9, replace the  
switch.  
2. If INFINITY was NOT measured in Step 5, repair or  
replace Wire 85 between the Circuit Board and the High  
Oil Temperature Switch.  
2. Check the installation and area surrounding the generator.  
There should be at least three feet of clear area around  
the entire unit. Make sure that there are no obstructions  
preventing incoming and outgoing air.  
3. Disconnect Wire 85 and Wire 0 from the High Oil  
Temperature Switch.  
teSt 77 – check and adjuSt ValVeS  
DISCUSSION:  
4. Set a VOM to measure resistance. Connect the test  
leads across the switch terminals. The meter should  
read INFINITY.  
Improperly adjusted valves can cause various engine  
related problems including, but not limited to, hard  
starting, rough running and lack of power. The valve  
adjustment procedure for both the single cylinder and  
the V-twin engines is the same.  
5. If the switch tested good in Step 4, and a true overtem-  
perature condition has not occurred, check Wire 85 for a  
Page 142  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
PROCEDURE: (INTAkE AND EXHAUST)  
2. Connect one meter test lead to Wire 18 that is connected  
to the bolt connector shown in Figure 46. Connect the  
other meter test lead to a clean frame ground.  
Make sure that the piston is at Top Dead Center  
(TDC) of it’s compression stroke (both valves  
closed). The valve clearance should be 0.05-0.1mm  
(0.002-0.004 in.) cold.  
3. Set the AUTO-OFF-MANUAL switch to the MANUAL  
position.  
Check and adjust the valve to rocker arm clearance  
as follows:  
4. When the generator comes up to rated speed, measure and  
record the voltage reading. 4-6 VAC should be measured.  
1. Remove the four (4) screws from the rocker cover.  
2. Remove the rocker cover and rocker cover gasket.  
5. If the correct voltage was not measured in Step 4, refer  
back to flow chart. If the correct voltage was measured,  
proceed to Step 6.  
3. Loosen the rocker arm jam nut. Use a 10mm allen wrench  
to turn the pivot ball stud and check the clearance  
between the rocker arm and the valve stem with a flat  
feeler gauge (see Figure 44).  
WIRE 18  
CONNECTION  
4. When the valve clearance is correct, hold the pivot ball  
stud with the allen wrench and tighten the rocker arm  
jam nut. Torque the jam nut to 174 inch pounds. After  
tightening the jam nut, recheck the valve clearance to  
make sure it did not change.  
BALL STUD  
Figure 45. Wire 18 Connection 8 kW Units  
JAM NUT  
WIRE 18 CONNECTION  
0.076 mm  
(0.003") SHIM  
Figure 44  
5. Re-install the rocker cover gasket, rocker cover and  
the four (4) screws.  
Figure 46. Wire 18 Connection 10-20 kW Units  
RESULTS:  
Adjust valve clearance as necessary, then retest.  
6. Set a VOM to measure resistance.  
7. Disconnect the J1 Connector from the printed circuit  
board.  
teSt 78 – check Wire 18 continuity  
8. Verify the continuity of Wire 18. Connect one meter  
test lead to a clean frame ground. Connect the other  
meter test lead to Pin Location J1-4 for all models. A  
reading of 275K - 325K ohms should be measured. If  
CONTINUITY is measured (0.1 ohms) a short to ground  
could be present.  
DISCUSSION:  
During cranking and running the printed circuit board  
receives a pulse from the ignition magnetos via Wire  
18. This signal has an AC voltage of 4-6 volts on  
V-Twin engines only. If this signal is not received by  
the printed circuit board the unit will shut down due to  
no RPM sensing.  
9. Disconnect Wire 18 from the stud connector. Continue to  
leave J1 disconnected from Step 7.  
PROCEDURE: (V-TWIN ONLY)  
1. Set a VOM to measure AC voltage.  
Page 143  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
10.Connect one meter test lead to Wire 18 removed from  
the stud connector. Connect the other meter test lead to  
a clean frame ground. INFINITY should be measured.  
If CONTINUITY is measured, repair or replace Wire 18  
between the stud connector and the J1 Connector.  
3. Press the right arrow key till a line is present under “EDIT”.  
4. Press “Enter”.  
5. Press the right arrow key until “EXERCISE TIME/DAY” is  
displayed.  
6. Press “Enter”.  
RESULTS:  
Refer to flow chart.  
READY TO RUN  
PROCEDURE: (SINGLE CYLINDER)  
1. Set a VOM to measure resistance.  
1 2 / 1 0 / 0 8 0 9 : 3 0 M o n  
2. Remove Wire 18 from the in-line bullet connector.  
Disconnect the J1 Connector from the printed circuit  
board.  
DATE AND TIME  
3. Verify the continuity of Wire 18. Connect one meter test  
lead to Wire 18 removed from the stud connector or  
bullet connector. Connect the other meter test lead to  
Pin Location J1-4. CONTINUITY should be measured.  
If CONTINUITY is not measured, repair or replace Wire  
18 as needed.  
MAIN  
MENU  
RESULTS:  
Refer to flow chart.  
EDIT  
teSt 79 – teSt eXerciSe Function  
Figure 47. The Date and Time, and Main Menu  
Screens  
DISCUSSION:  
The following parameters must be met in order for the  
weekly exercise to occur:  
• AUTO-OFF-MANUAL switch set to AUTO.  
7. Adjust exercise time to about 3 to 4 minutes ahead of  
the date and time noted in Step 1.  
8. Press “ESC” until “READY TO RUN” is displayed. The  
AUTO-OFF-MANUAL switch must be in AUTO for the  
unit to exercise.  
PROCEDURE: 8kW  
1. Set the AUTO-OFF-MANUAL switch to MANUAL. The  
generator should start. Set AUTO-OFF-MANUAL switch  
back to AUTO. Verify that AUTO-OFF-MANUAL switch  
has been in AUTO for weekly exercise to function.  
9. Watch the generator display and note the time. When the  
date and time reaches the time that was programmed  
for exercise, the unit will display "Running in Exercise" if  
the exercise feature is working properly.  
2. Hold the Set Exercise switch until the generator starts  
(approximately 10 seconds) and then release. All of  
the red LEDs will flash for approximately 10 seconds  
and then stop. The generator will start and run for  
approximately 12 minutes and then shutdown on it’s  
own. The exerciser will then be set to start and run at  
that time of that day each week. If the unit does not  
start, replace the circuit board.  
RESULTS:  
1. In all models, if the unit starts in MANUAL, but fails to  
exercise without any ALARMS present, replace the  
printed circuit board.  
teSt 80 – check crankinG and runninG  
PROCEDURE: 10kW-20kW  
circuitS  
note: make a record of the date and time the  
generator is set to exercise.  
DISCUSSION:  
1. Record the current date and time of the unit.  
This test will check all of the circuits that are “HOT”  
with battery voltage and which could cause the Main  
Fuse to blow.  
2. Press the “ESC” key till the main menu is displayed.  
Page 144  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
PROCEDURE:  
a. Connect one meter test lead to the SC terminal  
from which Wire 56 was removed. Connect the  
other meter test lead to the ground terminal, 4  
ohms should be measured. If zero resistance  
was measured, replace the SC.  
1. Set a VOM to measure resistance.  
2. Disconnect the J2 Connector from the controller.  
3. Connect one meter test lead to the ground terminal.  
Connect the other meter test lead to each of the follow-  
ing J2 connector pin locations.  
b. Connect one meter test lead to the CS connec-  
tor Wire 56. Connect the other meter test lead  
to the CS connector Wire 90. 4 ohms should  
be measured. If zero resistance was measured,  
replace the Choke Solenoid.  
J2-11 Wire 56  
8kW  
If CONTINUITY was measured,  
go to Step 4. Average nominal  
resistance reading is 4 ohms:  
Single Cylinder Starter Contactor  
(SC) 4 ohms,  
c. If coil resistance was measured in the Starter  
Contactor, and Choke Solenoid Wire 56 is short-  
ed to ground between the J2 Connector and SC  
or CS, repair or replace the shorted wire.  
5. Disconnect Wire 56 from the Starter Contactor Relay  
(SCR). Disconnect the Choke Solenoid (CS) connector.  
Choke Solenoid (CS) is 4 ohms.  
a. Connect one meter test lead to the SCR terminal  
from which Wire 56 was removed. Connect the  
other meter test lead to the ground terminal. 4  
ohms should be measured. If zero resistance was  
10 kW - 20 kW If CONTINUITY was measured,  
go to Step 5.  
Average nominal resistance reading  
is 150-160 ohms.  
measured, replace the Starter Contactor Relay  
.
b. Connect one meter test lead to the CS connec-  
tor Wire 56. Connect the other meter test lead  
to the CS connector Wire 90. 4 ohms should  
be measured. If zero resistance was measured,  
V-twin Starter Contact Relay  
(SCR): 150-160 ohms.  
Choke Solenoid (CS) 4 ohms.  
replace the Choke Solenoid.  
J2-3 Wire 14  
If coil resistance was measured in SCR and CS Wire  
56 is shorted to ground between J2 connector and SC  
or CS, repair or replace the shorted wire.  
8kW  
If CONTINUITY was measured,  
go to Step 6. Average nominal  
resistance reading is 16 ohms:  
Fuel Solenoid (FS): 16 ohms.  
6. Disconnect Wire 14 from the Fuel Solenoid (FS).  
a. Connect one meter test lead to the FS terminal  
from which Wire 14 was removed. Connect the  
other meter test lead to the ground terminal. 16  
ohms should be measured. If zero resistance  
was measured, replace the Fuel Solenoid.  
10kw  
If CONTINUITY was measured,  
go to Step 7. Average nominal  
resistance reading is 16 ohms.  
Fuel Solenoids (FS) 16 ohms,  
(FS2) 7 ohms. Choke Solenoid  
(CS) 4 ohms.  
b. If coil resistance was measured in FS Wire 14  
is shorted to ground between J2 connector and  
FS, repair or replace the shorted wire.  
10 kW - 20 kW If CONTINUITY was measured,  
go to Step 8. Average nominal  
7. Disconnect Wire 14 from the Fuel Solenoid (FS), Fuel  
Solenoid 2 (FS2), and Choke Solenoid (CS),  
resistance reading is 16 ohms.  
a. Connect one meter test lead to the FS terminal  
from which Wire 14 was removed. Connect the  
other meter test lead to the ground terminal. 16  
ohms should be measured. If zero resistance  
was measured, replace the Fuel Solenoid.  
Fuel Solenoid (FS) 16 ohms.  
Choke Solenoid (CS) 4 ohms.  
J2-12 Wire 4  
b. Connect one meter test lead to the FS2 termi-  
nal from which Wire 14 was removed. Connect  
the other meter test lead to the ground terminal.  
7 ohms should be measured. If zero resistance  
10 kW - 20 kW If RESISTANCE was measured,  
go to Step 9.  
For average nominal resistance  
reading of the rotor, refer to the  
front of the manual.  
was measured, replace Fuel Solenoid 1.  
c. At the CS connector, connect one meter test  
lead to Wire 14 connect the other meter test  
lead to Wire 90. 4 ohms should be measured.  
If zero resistance was measured, replace the  
4. Disconnect Wire 56 and Wire 0 from the Starter  
Contactor (SC). Disconnect the Choke Solenoid  
(CS) connector.  
Choke Solenoid.  
Page 145  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 4.4  
DiaGNostic tEsts  
DC CONTROL  
Part 4  
d. If coil resistance was measured in CS and FS,  
and FS2 Wire 14 is shorted to ground between  
J2 connector and CS, FS, or FS2, repair or  
replace the shorted wire.  
PROCEDURE:  
1. Press the “ESC” key till the main menu is reached.  
2. Press the right arrow key until “Edit” is flashing.  
3. Press “Enter”  
8. Disconnect Wire 14 from the Fuel Solenoid (FS) and  
Choke Solenoid (CS).  
4. Press the right arrow key until “Exercise Time” appears  
on the controller.  
a. Connect one meter test lead to the FS terminal  
from which Wire 14 was removed. Connect the  
other meter test lead to the ground terminal. 16  
ohms should be measured. If zero resistance  
was measured, replace the FS.  
5. Press “Enter”.  
6. Press the right arrow key until the Low speed exercise  
option is displayed.  
b. At the CS connector, connect one meter test  
lead to Wire 14. Connect the other meter test  
lead to Wire 90. 4 ohms should be measured.  
If zero resistance was measured, replace the  
Choke Solenoid.  
7. Ensure that it is enabled.  
RESULTS:  
Refer back to flow chart.  
c. If coil resistance was measured in the Choke  
Solenoid, and FS Wire 14 is shorted to ground  
between the J2 Connector and CS or FS, repair  
or replace the shorted wire.  
teSt 82 – check operation oF the  
choke Solenoid  
9. Disconnect Wire 4 and Wire 0 from the Voltage Regulator  
(VR).  
DISCUSSION:  
a. At the J2 connector, connect one meter test  
lead to Wire 4. Connect the other meter  
test lead to a clean frame ground. Note the  
resistance reading and compare to the rotor  
resistance in the front of this manual. If zero  
resistance was measured, test Wire 4 for a  
short to ground. Check brushes, slip rings,  
and rotor.  
The choke solenoid should be closed when it is in low  
speed exercise.  
PROCEDURE:  
1. Remove the air box cover and filter from the engine.  
2. Refer to test 79 for Test Exercise Function  
3. When the generator starts and the display reflects that  
it is exercising, confirm that the choke solenoid is fully  
closed over one port.  
teSt 81 – check to See iF loW Speed  
Function iS enaBled  
RESULTS:  
DISCUSSION:  
1. If the solenoid did not close, confirm that utility voltage is  
present. If the generator believes that there is a power  
outage it will run at full speed until utility is returned.  
The Low speed exercise function when it is  
enabled allows the generator to exercise at 2400  
rpm. If it is disabled it will exercise at its 3600 rpm  
during exercise.  
2. If the solenoid closed, replace the controller.  
Page 146  
Download from Www.Somanuals.com. All Manuals Search And Download.  
taBlE of coNtENts  
titlE  
Part  
5.1. system functional tests  
Part 5  
oPEratioNal  
tEsts  
air-cooled, automatic  
standby Generators  
5.1 System Functional Tests................................ 148  
Introduction....................................................148  
Manual Transfer Switch Operation .................148  
Electrical Checks ...........................................148  
Generator Tests Under Load..........................149  
Checking Automatic Operation ......................150  
Setting The Exercise Timer............................150  
Page 147  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 5.1  
sYstEm fuNctioNal tEsts  
OPERATIONAL TESTS  
AND ADJUSTMENTS  
Part 5  
iN DaNGErous aND PossiBlY lEtHal  
ElEctrical sHocK.  
introduction  
Following home standby electric system installation  
and periodically thereafter, the system should be  
tested Functional tests of the system include the  
following:  
4. Remove the manual transfer handle from the enclosure.  
5. Place open end of the manual transfer handle over  
transfer switch operating lever.  
• Manual transfer switch operation.  
• System voltage tests.  
• Generator Tests Under Load.  
Testing automatic operation.  
6. To connect LOAD terminal lugs to the utility power  
source, move, the handle upward.  
7. To connect LOAD terminals to the standby power source,  
move the handle downward.  
Before proceeding with functional tests, read instruc-  
tions and information on tags or decals affixed to the  
generator and transfer switch. Perform all tests in the  
exact order given in this section.  
8. Actuate the switch to UTILITY and to MANUAL several  
times. Make sure no evidence of binding or interference  
is felt.  
manual tranSFer SWitch operation  
9. When satisfied that manual transfer switch operation  
is correct, actuate the main contacts to their UTILITY  
position (Load connected to the utility power supply).  
“W/V-TYPE” TRANSFER SWITCHES:  
1. On the generator panel, set the AUTO-OFF-MANUAL  
switch to OFF.  
electrical checkS  
2. Turn OFF the utility power supply to the transfer switch  
using whatever means provided (such as a “Utility” main  
line circuit breaker).  
Complete electrical checks as follows:  
1. Set the generator main circuit breaker to its OFF (or  
open) position.  
3. Set the generator main line circuit breaker to OFF  
(or open).  
2. Set the generator AUTO-OFF-MANUAL switch to the  
OFF position.  
DaNGEr: BE surE to turN off all  
PoWEr VoltaGE suPPliEs to tHE  
traNsfEr sWitcH BEforE attEmPtiNG  
3. Turn off all loads connected to the transfer switch  
Terminals T1 and T2.  
*
maNual oPEratioN. failurE to turN  
off PoWEr VoltaGE suPPliEs to  
tHE traNsfEr sWitcH maY rEsult  
4. Turn on the utility power supply to the transfer switch  
using the means provided (such as a utility main line  
circuit breaker).  
LOAD CONNECTED TO  
LOAD CONNECTED TO  
UTILITY POWER SOURCE  
STANDBY POWER SOURCE  
TRANSFER  
SWITCH  
OPERATING  
LEVER  
MANUAL  
TRANSFER  
HANDLE  
MANUAL  
TRANSFER  
HANDLE  
TRANSFER  
SWITCH  
OPERATING  
LEVER  
Figure 1. Manual Operation “V-Type” Switch  
Page 148  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 5.1  
sYstEm fuNctioNal tEsts  
OPERATIONAL TESTS  
AND ADJUSTMENTS  
Part 5  
Generally, if both ac frequency and voltage are  
high or low, the engine governor requires adjust-  
ment. if frequency is correct, but voltage is high  
or low, the generator voltage regulator requires  
adjustment.  
DANGER  
tHE traNsfEr sWitcH is NoW ElEctri-  
callY Hot”, coNtact WitH “Hot” Parts  
Will rEsult iN EXtrEmElY HaZarDous  
aND PossiBlY fatal ElEctrical sHocK.  
ProcEED WitH cautioN.  
+
Generator teStS under load  
To test the generator set with electrical loads applied,  
proceed as follows:  
5. Use an accurate AC voltmeter to check utility power  
source voltage across transfer switch Terminals N1 and  
N2. Nominal line-to-line voltage should be 240 volts AC.  
1. Set generator main circuit breaker to its OFF (or  
open) position.  
2. Turn OFF all loads connected to the Transfer Switch  
Terminals T1 and T2.  
6. Check utility power source voltage across Terminals N1  
and the transfer switch neutral lug; then across Terminal  
N2 and neutral. Nominal line-to-neutral voltage should  
be 120 volts AC.  
3. Set the generator AUTO-OFF-MANUAL switch to OFF.  
4. Turn off the utility power supply to the transfer switch,  
using the means provided (such as a utility main line  
circuit breaker).  
7. When certain that utility supply voltage is compatible  
with transfer switch and load circuit ratings, turn off the  
utility power supply to the transfer switch.  
8. On the generator panel, set the AUTO-OFF-MANUAL  
switch to MANUAL. The engine should crank and start.  
9. Let the engine warm up for about five minutes to allow  
internal temperatures to stabilize. Then, set the generator  
main circuit breaker to its “ON” (or closed) position.  
Do Not attEmPt maNual traNsfEr  
sWitcH oPEratioN uNtil all PoWEr  
VoltaGE suPPliEs to tHE traNsfEr  
sWitcH HaVE BEEN PositiVElY turNED  
off. failurE to turN off all PoWEr  
VoltaGE suPPliEs Will rEsult iN  
EXtrEmElY HaZarDous aND PossiBlY  
fatal ElEctrical sHocK.  
+
DANGER  
ProcEED WitH cautioN! GENErator  
PoWEr VoltaGE is NoW suPPliED to  
tHE traNsfEr sWitcH. coNtact WitH  
liVE traNsfEr sWitcH Parts Will  
rEsult iN DaNGErous aND PossiBlY  
fatal ElEctrical sHocK.  
+
5. Manually set the transfer switch to the STANDBY posi-  
tion, i.e., load terminals connected to the generator  
E1/E2 terminals. The transfer switch operating lever  
should be down.  
6. Set the generator AUTO-OFF-MANUAL switch to  
MANUAL. The engine should crank and start immediately.  
10.Connect an accurate AC voltmeter and a frequency  
meter across transfer switch Terminal Lugs E1 and E2.  
Voltage should be 242-252 volts; frequency should read  
about 61-63 Hertz (7/8 kW units) and about 60 Hertz on  
10-20 kW units.  
7. Let the engine stabilize and warm up for a few minutes.  
8. Set the generator main circuit breaker to its ON (or  
closed) position. Loads are now powered by the standby  
generator.  
11.Connect the AC voltmeter test leads across Terminal  
Lug E1 and neutral; then across E2 and neutral. In both  
cases, voltage reading should be 121-126 volts AC.  
9. Turn ON electrical loads connected to transfer switch T1  
and T2. Apply an electrical load equal to the full rated  
wattage/amperage capacity of the installed generator.  
12.Set the generator main circuit breaker to its OFF (or open)  
position. Let the engine run at no-load for a few minutes to  
stabilize internal engine generator temperatures.  
10.Connect an accurate AC voltmeter and a frequency  
meter across Terminal Lugs E1 and E2.  
13.Set the generator AUTO-OFF-MANUAL switch to OFF.  
The engine should shut down.  
a. 7/8kW voltage should be greater than 230 volts  
and frequency should be greater than 58 Hz.  
note: it is important that you do not proceed until  
you are certain that generator ac voltage and fre-  
quency are correct and within the stated limits.  
b. 10-20 kW voltage should be greater than 240  
volts and frequency should be 60 Hz.  
Page 149  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 5.1  
sYstEm fuNctioNal tEsts  
OPERATIONAL TESTS  
AND ADJUSTMENTS  
Part 5  
the unit runs for approximately 12 minutes and then  
shuts down. Transfer of loads to the generator output  
does not occur during the exercise cycle unless utility  
power is lost.  
11.Let the generator run at full rated load for 20-30 minutes.  
Listen for unusual noises, vibration or other indications  
of abnormal operation. Check for oil leaks, evidence of  
overheating, etc.  
PROCEDURE 8 kW UNITS:  
12.When testing under load is complete, turn off electrical  
loads.  
A switch on the control panel (see Figure 3.1) permits  
selection of the day and time for the system to exercise.  
At the chosen time, perform the following sequence to  
select the desired day and time of day the system will  
exercise. Remember, seasonal time changes affect the  
exercise settings.  
13.Set the generator main circuit breaker to its OFF (or  
open) position.  
14.Let the engine run at no-load for a few minutes.  
1. Verify that the AUTO-OFF-MANUAL switch is set to  
AUTO.  
15.Set the AUTO-OFF-MANUAL switch to OFF. The engine  
should shut down.  
2. Press and hold the “Set Exercise” switch for several  
seconds. All the red LED’s will stop flashing immediately  
and the generator will start.  
checkinG automatic operation  
To check the system for proper automatic operation,  
proceed as follows:  
3. The generator will start and run for approximately 12  
minutes and then shut down. The exerciser is now set to  
run at this time of day each week. Example: If the “Set  
Exercise” is pressed on Saturday afternoon at 2:00 p.m.  
the generator will start and exercise for approximately  
12 minutes every Saturday at 2:00 p.m.  
1. Set generator main circuit breaker to its OFF (or open)  
position.  
2. Check that the AUTO-OFF-MANUAL switch is set to OFF.  
3. Turn off the utility power supply to the transfer switch,  
using means provided (such as a utility main line circuit  
breaker).  
10-20 kW - INSTALLATION ASSISTANT:  
Upon first power up of the generator, the display inter-  
face will enter an installation assistant. The assistant  
will prompt the user to set the minimum settings to  
operate.These settings are simply: “Current Date/Time”  
and “Exercise Day/Time”. The maintenance intervals  
will be initialized when the exercise time is entered.  
4. Manually set the transfer switch to the UTILITY position, i.e.,  
load terminals connected to the utility power source side.  
5. Turn on the utility power supply to the transfer switch,  
using the means provided (such as a utility main line  
circuit breaker).  
The exercise settings can be changed at any time  
via the “EDIT” menu (see Appendix, “Menu System”).  
If the 12 volt battery is disconnected or the fuse  
removed, the Installation Assistant will operate upon  
power restoration. The only difference being that the  
display will only prompt the customer for the current  
Time and Date.  
6. Set the AUTO-OFF-MANUAL switch to AUTO. The  
system is now ready for automatic operation.  
7. Turn off the utility power supply to the transfer switch.  
With the AUTO-OFF-MANUAL switch at AUTO, the  
engine should crank and start when the utility source  
power is turned off. After starting, the transfer switch  
should connect load circuits to the standby side. Let  
the system go through its entire automatic sequence  
of operation.  
ALL UNITS:  
note: if the installer tests the generator prior to  
installation, press the “enter” key to avoid set-  
ting the exercise time. this will ensure that the  
customer will still be prompted to enter an exercise  
time when the unit is first powered up.  
With the generator running and loads powered by  
generator AC output, turn ON the utility power supply  
to the transfer switch. The following should occur:  
• After about fifteen seconds, the switch should  
transfer loads back to the utility power source.  
note: the exerciser will only work in the auto  
mode and will not work unless this procedure  
is performed. the current date/time will need to  
be reset every time the 12 volt battery is discon-  
nected and then reconnected, and/or when the  
fuse is removed.  
• About one minute after retransfer, the engine should  
shut down.  
SettinG the eXerciSe timer  
This generator is equipped with an exercise timer.  
Once it is set, the generator will start and exercise  
every seven days, on the day of the week and at the  
time of day specified. During this exercise period,  
Page 150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
taBlE of coNtENts  
titlE  
Part  
6.1. major Disassembly  
Part 6  
DisassEmBlY  
air-cooled, automatic  
standby Generators  
6.1 Major Disassembly........................................ 152  
Front Engine Access......................................152  
Major Disassembly.........................................156  
Torque Requirements  
(Unless Otherwise Specified)............162  
Page 151  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
2. Remove controller: Using a Phillips screwdriver remove the  
four mounting screws from the controller. See Figure 3.  
Front enGine acceSS  
SAFETY:  
1. Set the AUTO-OFF-MANUAL switch to OFF.  
2. Remove the 7.5 amp main fuse. See Figure 1.  
3. Remove the N1 and N2 fuse from the transfer switch.  
Figure 3.  
3. Remove control harnesses:  
a. Remove engine wiring harness at the J1 port.  
b. Remove control wiring harness at the J2 port.  
Figure 1. Remove 7.5 Amp Fuse  
c. Remove stepper motor wiring harness at the J3  
4. Turn off fuel supply to the generator and remove the flex-  
line from the fuel regulator.  
port. See Figure 4.  
5. Remove utility power from the generator.  
6. Remove front door.  
7. Remove battery from the generator.  
FRONT ENGINE ACCESS:  
1. Remove Controls Cover: Using a Torx T-27 socket  
remove two bolts and ground washer from the controls  
cover. Remove the controls cover. See Figure 2.  
Figure 4.  
Figure 2.  
Page 152  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
4. Remove Stator Wires: Remove all wires from the voltage  
regulator, remove the neutral and ground wires from  
landing lugs, and remove N1 & N2 wires from main bea-  
kers. See Figure 5.  
5. Remove Control Wires: Remove Wires #N1,#N2, #0,  
#15B, #23, GFCI Outlet, and unit status lights from the  
control box. See Figure 6.  
Figure 7.  
Figure 5.  
Figure 8.  
7. Remove engine intake baffle: Using a 10mm socket  
remove the two bolts from the engine intake baffle. Pull  
baffle toward you carefully, there are tabs holding the  
backside of the baffle to the divider panel. See Figure 9.  
Figure 6.  
6. Remove controller mounting box: Using an 8mm socket  
remove the two screws from the rear of the control-  
ler mounting box. See Figure 7. Using a 10mm socket  
remove the two bolts from under the front of the control-  
ler mounting box. See Figure 8.  
Figure 9.  
Page 153  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
8. Loosen side panel: Using a 10mm socket remove the  
two bolts from the base of the enclosure side panel. See  
Figure 10.  
10.Remove fuel regulator: Remove the two fuel hoses at  
the top of the regulator. Using a 10mm socket remove  
one 10mm bolt from the base of the plenum and one  
10mm bolt from the base of the fuel regulator. Flex  
the enclosure side out to allow for room to remove the  
regulator assemble. See Figure 12.  
9. Unbolt enclosure side panel mounting bracket: Using a  
10mm socket remove the two bolts from the enclosure  
side panel mounting bracket. See Figure 11.  
Figure 12.  
Figure 10.  
11.Remove engine divider panel: Using a 10mm socket  
remove the rear 10mm bolt from the base of the  
enclosure. See Figure 13. Remove the front 10mm  
bolt from the base of the enclosure. See Figure 14.  
Figure 11.  
Figure 13.  
Page 154  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
Figure 16.  
13.Unbolt Oil Cooler: Using a 10mm socket remove the two  
10mm bolts from the front of the oil cooler. See Figure  
17. Remove the two 10mm bolts from the rear of the oil  
cooler. See Figure 18.  
Figure 14.  
12.Remove Air Box: Using a 6mm allen wrench remove the  
four intake manifold socket head cap screws. See Figure  
15. Using a 4mm allen wrench, remove the four airbox  
allen head shoulder bolts. While removing the airbox  
remove the four rubber washers. See Figure 16.  
Figure 17.  
Figure 15.  
Figure 18.  
Page 155  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
14.Remove Blower Housing: Using a 4mm allen wrench  
remove one button head cap screw from top of blower  
housing. Using a 10mm socket remove one 10mm bolt  
from the top of the blower housing. See Figure 19. Using  
a 10mm socket remove four 10mm bolts from the right-  
side of the blower housing, (see Figure 20) and four  
10mm bolts from the left-side of the blower housing. See  
Figure 21. Remove blower housing.  
Figure 21.  
major diSaSSemBly  
SAFETY:  
1. Set the AUTO-OFF-MANUAL switch to OFF.  
2. Remove the 7.5 amp main fuse. See Figure 22.  
3. Remove the N1 and N2 fuse from the transfer switch.  
Figure 19.  
Figure 22. Remove 7.5 Amp Fuse  
4. Turn off fuel supply to the generator and remove the flex-  
line from the fuel regulator.  
5. Remove utility power from the generator.  
6. Remove front door.  
Figure 20.  
7. Remove battery from the generator.  
Page 156  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
STATOR/ROTOR/ENGINE REMOVAL:  
1. Remove Top Exhaust Enclosure Covers: Using a 10mm  
socket, remove the nine bolts from the exhaust top cov-  
ers. Remove covers. See Figure 23.  
Figure 25.  
4. Remove Exhaust Flex Pipe: Using a ½” socket remove  
the front and rear muffler clamp. Slide exhaust flex  
toward engine completely exposing the muffler flange.  
See Figure 26.  
Figure 23.  
2. Remove Side Exhaust Enclosure Cover: Using a 10mm  
socket, remove the five bolts from the exhaust side  
cover. Remove side covers. See Figure 24.  
Figure 26.  
5. Remove Muffler and Tail Pipe: Using a ½” socket remove  
the muffler clamp and tail pipe. Using a 10mm socket,  
remove the four bolts from the muffler mounts and  
remove muffler. See Figure 27.  
Figure 24.  
3. Remove Exhaust Flex Cover: Using a 10mm socket,  
remove the two bolts from the exhaust flex pipe cover.  
Remove the cover. See Figure 25.  
Page 157  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
Figure 27.  
Figure 29.  
6. Remove Left-side enclosure: Using a 10mm ratchet  
wrench remove the horizontal 10mm bolt that connects  
the side panel to the back panel. Using a 10mm socket,  
remove three bolts from the base of the enclosure. See  
Figure 28. Using a 10mm socket and wrench remove  
the top hinge bolt and loosen the bottom bolt. See  
Figure 29. Holding the roof, remove the bottom hinge  
bolt, remove the side panel by sliding it forward then re-  
install the hinge bolt.  
7. Remove Fan Housing Cover: Using a 10mm socket  
remove four bolts from the fan housing cover. Remove  
the fan housing cover. See Figure 30.  
Figure 30.  
8. Remove Rotor Bolt: Using a 9/16” socket, remove rotor  
bolt. Figure 31.  
Figure 28.  
Page 158  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
10.Remove Brushes: Using a 7mm socket remove brushes.  
See Figure 33.  
Figure 31.  
9. Remove Fan: Attach a steering wheel puller to the fan  
using two M8 x 1.25 bolts. Remove the fan from the  
rotor. Figure 32.  
Figure 33.  
11.Remove Alternator Divider Panel: Using a 10mm socket  
remove two bottom base bolts. Using a T27 torx driver  
remove one top rear bolt. Remove the panel. See Figure 34.  
Figure 32.  
Figure 34.  
Page 159  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
12.Remove Brush Wires: Using a side cutters remove the  
tie wraps securing the brush wires to the outside of sta-  
tor. See Figure 35.  
Figure 37.  
15.Alternator Air Intake Bellows Removal: Remove alterna-  
tor intake bellows. See Figure 38.  
Figure 35.  
13.Remove Controls Cover: Using a Torx T-27 socket  
remove two bolts and ground washer from the controls  
cover. Remove the controls cover. See Figure 36.  
Figure 38.  
16.Rear Bearing Carrier Removal: Using a 13mm socket,  
remove the two nuts from the alternator mounting brack-  
et rubber mounts. Lift the back end of the alternator up  
and place a 2”x 4” piece of wood under the engine. See  
Figure 40. Using a 13mm socket, remove the four stator  
hold down bolts. See Figure 41. Using a small rubber  
mallet remove the rear bearing carrier. See Figure 42.  
Remove stator. See Figure 43.  
Figure 36.  
14.Remove Stator Wires: Remove all wires from the voltage  
regulator, remove the common and ground wires from  
landing lugs, and remove N1 & N2 wires from main bea-  
kers. See Figure 37.  
Page 160  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
17.Rotor Removal: Cut 2.5 inches from the rotor bolt. Slot  
the end of the bolt to suit a flat blade screwdriver. Slide  
the rotor bolt back through the rotor and use a screw-  
driver to screw it into the crankshaft. Use a 3” M12x1.75  
bolt to screw into rotor. Apply torque to the 3” M12x1.75  
bolt until taper breaks. See Figure 43.  
Figure 39.  
Figure 42.  
11.Remove Engine: Using a 13mm socket, remove the two  
engine mount nuts with ground wires. See Figure 43.  
Figure 40.  
Figure 43.  
Figure 41.  
Page 161  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sEctioN 6.1  
maJor DisassEmBlY  
DISASSEMBLY  
Part 6  
12.Remove Engine: Using proper lifting equipment remove  
the engine. See Figure 44.  
torque requirementS  
(unleSS otherWiSe SpeciFied)  
STATOR BOLTS ................................................ 6 ft-lbs ( +1 / -0 )  
ROTOR BOLT ................................................................ 30 ft-lbs  
ENGINE ADAPTOR ....................................................... 25 ft-lbs  
EXHAUST MANIFOLD .................................................. 18 ft-lbs  
M5-0.8 TAPTITE SCREW INTO ALUMINUM .......... 25-50 in-lbs  
M5-0.8 TAPTITE SCREW INTO PIERCED HOLE ... 25-50 in-lbs  
M6-1.0 TAPTITE SCREW INTO ALUMINUM .......... 50-96 in-lbs  
M6-1.0 TAPTITE SCREW INTO PIERCED HOLE ... 50-96 in-lbs  
M6-1.0 TAPTITE SCREW INTO WELDNUT ............ 50-96 in-lbs  
M8-1.25 TAPTITE SCREW INTO ALUMINUM ......... 12-18 ft-lbs  
M8-1.25 TAPTITE SCREW INTO PIERCED HOLE ... 12-18 ft-lbs  
M6-1.0 NYLOK NUT ONTO WELD STUD .............. 16-65 in-lbs  
M6-1.0 NYLOK NUT ONTO HINGE STUD ............. 30-36 in-lbs  
note: torques are dynamic values with ±10% toler-  
ance unless otherwise noted.  
Figure 44.  
Page 162  
Download from Www.Somanuals.com. All Manuals Search And Download.  
taBlE of coNtENts  
titlE  
DWG#  
0G7945  
0G8511  
0G7946  
0G8512  
0G7947  
0G8513  
0G7948  
0G8514  
0G8186  
0G8515  
0G7958  
WiriNG DiaGram, 8 KW HsB  
scHEmatic, 8 KW HsB  
WiriNG DiaGram, 10 KW HsB  
scHEmatic, 10 KW HsB  
Part 7  
ElEctrical  
Data  
WiriNG DiaGram, 14 KW HsB  
scHEmatic, 14 KW HsB  
WiriNG DiaGram, 17 KW HsB  
scHEmatic, 17 KW HsB  
WiriNG DiaGram, 20 KW HsB  
scHEmatic, 20 KW HsB  
WiriNG DiaGram  
9/10/12/16 circuit traNsfEr sWitcH  
air-cooled, automatic  
standby Generators  
0G7959  
scHEmatic  
9/10/12/16 circuit traNsfEr sWitcH  
Page 163  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
WiriNG DiaGram, 8 KW HomE staNDBY  
Part 7  
DraWiNG #0G7945  
CONTROL PANEL  
ENGINE COMPARTMENT  
CAPACITOR  
6
2
10  
22  
10  
33  
44  
11  
STATOR  
10  
10  
SP1  
IM1  
18  
N2  
N1  
1
2
85  
1
85  
86  
13  
18  
MAIN  
CONTROLLER  
2
3
4
86  
J1  
HTO  
LOP  
0
J2  
0
1 2 3 4  
5
6 7 8 9 10 1112 1314 15 16 1718  
15B  
23  
1
RED  
56  
2
0
CHOKE  
SOLENOID  
BLK  
13  
0
14  
0
0
56  
16  
SM  
SC  
56  
56  
0
0
0
0
0
0
0
0
PANEL GND  
6
6
13  
ENGINE  
GND  
FRAME  
GND  
0
0
Page 164  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
Part 7  
WiriNG DiaGram, 8 KW HomE staNDBY  
DraWiNG #0G7945  
CUSTOMER CONNECT AREA  
240V GENERATOR  
OUTPUT TO TRANSFER  
SWITCH CONTACTOR  
CB  
44  
11  
LEGEND  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
GND - GROUND  
HTO - HIGH TEMPERATURE SWITCH  
IM1 - IGNITON MODULE  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SM - STARTER MOTOR  
SP1 - SPARK PLUG  
- SPLICE  
14  
14  
FUEL  
SOLENOID  
14  
N1  
00  
0
BATTERY  
WARMER  
14  
OPTIONAL  
BLACK  
RED  
0
13  
NOTE: ALL WIRES 18 AWG  
300V UL LISTED UNLESS  
SHOWN OTHERWISE  
+ -  
12V  
BATTERY  
0
0
AWG SIZE  
12  
CUSTOMER SUPPLIED  
Page 165  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
scHEmatic, 8 KW HomE staNDBY  
Part 7  
DraWiNG #0G8511  
EXCITATION WINDING  
CB  
2
6
CAPACITOR  
44  
11  
240 VAC  
GENERATOR  
OUTPUT  
POWER  
WINDING  
44  
NEUTRAL  
33  
33  
STATOR  
22  
22  
00  
11  
POWER  
WINDING  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N2  
N1  
N1  
IM  
18  
SP  
1
85  
86  
13  
18  
2
J1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
3
4
J2  
1 2 3 4  
5
6 7 8 9 10 1112 1314 15 16 1718  
85  
86  
14  
23  
15B 0 56  
HTO  
LOP  
56  
56  
0
0
GROUND  
0
CS  
0
SC  
FS  
0
15B  
23  
+ BATTERY  
TRANSFER  
0
0
13  
0
13  
BATTERY  
12V  
SC  
16  
0
SM  
LEGEND  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SM - STARTER MOTOR  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
HTO - HIGH TEMPERATURE SWITCH  
IM - IGNITION MODULE  
SP - SPARK PLUG  
Page 166  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
Part 7  
scHEmatic, 8 KW HomE staNDBY  
DraWiNG #0G8511  
PAGE LEFT PLANK INTENTIONALLY  
Page 167  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
WiriNG DiaGram, 10 KW HomE staNDBY  
Part 7  
DraWiNG #0G7946  
CONTROL PANEL  
ENGINE COMPARTMENT  
CAPACITOR  
6
2
10  
22  
10  
33  
STATOR  
44  
10  
10  
11  
N.C. N.C.  
IC  
IC  
SP1  
SP2  
0
4
IM1  
IM2  
18  
N2  
N1  
1
2
85  
1
85  
86  
13  
18  
MAIN  
CONTROLLER  
2
3
4
86  
J1  
HTO  
LOP  
0
J3  
0
J2  
1 2 3 4  
5
6 7 8 9 10 1112 1314 15 16 1718  
15B  
23  
820  
817  
818  
819  
1
RED  
14  
14  
2
90  
90  
CHOKE  
SOLENOID  
0
0
BLK  
0
GOVERNOR  
ACTUATOR  
0
14  
14  
0
0
13  
16  
13  
SCR  
SM  
A
B
0
0 0  
13  
SC  
16  
0
0
56  
0
0
16  
13  
0
16  
0
PANEL GND  
6
6
ENGINE  
GND  
FRAME  
GND  
0
Page 168  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
Part 7  
WiriNG DiaGram, 10 KW HomE staNDBY  
DraWiNG #0G7946  
CUSTOMER CONNECT AREA  
240V GENERATOR  
OUTPUT TO TRANSFER  
SWITCH CONTACTOR  
CB  
44  
11  
LEGEND  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
GND - GROUND  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITON MODULE  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
SP_ - SPARK PLUG  
- SPLICE  
- DISCONNECT SPLICE  
IC  
LED BOARD  
20  
20  
20  
20  
1
820  
L1  
2
3
4
817  
818  
819  
L3  
L1: GREEN = SYSTEM READY  
L3: RED = ALARM  
14  
14  
FUEL  
SOLENOID  
14  
FUEL  
SOLENOID  
14  
0
N1  
00  
0
BATTERY  
WARMER  
14  
OPTIONAL  
BLACK  
RED  
0
13  
NOTE: ALL WIRES 18 AWG  
300V UL LISTED UNLESS  
SHOWN OTHERWISE  
+ -  
12V  
BATTERY  
0
0
AWG SIZE  
12  
CUSTOMER SUPPLIED  
Page 169  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
scHEmatic, 10 KW HomE staNDBY  
Part 7  
DraWiNG #0G8512  
EXCITATION WINDING  
2
6
CB  
CAPACITOR  
44  
11  
240 VAC  
GENERATOR  
OUTPUT  
POWER  
WINDING  
44  
NEUTRAL  
33  
33  
STATOR  
22  
22  
00  
11  
POWER  
WINDING  
N1  
240 VAC  
UTILITY  
INPUT  
IM2  
IM1  
18  
18  
OPTIONAL  
BATTERY WARMER  
SP2  
SP1  
N2  
N2  
N1  
N1  
LED BOARD  
1
85  
86  
13  
18  
2
J1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
3
4
1 2 3 4  
J3  
J2  
1 2 3 4  
5
6 7 8 9 10 1112 1314 15 16 1718  
85  
86  
0
14  
23  
15B 0 56  
0
GOVERNOR  
ACTUATOR  
HTO  
0
LOP  
820  
14  
0
817  
818  
14  
FS  
SCR  
CS  
90  
FS  
0
819  
0
GROUND  
0
15B  
23  
0
+ BATTERY  
TRANSFER  
0
13  
13  
0
13  
BATTERY  
12V  
13  
SCR  
0
16  
SC  
SM  
LEGEND  
CB - CIRCUIT BREAKER, MAIN OUTPUT LOP - LOW OIL PRESSURE SWITCH  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
SP_ - SPARK PLUG  
Page 170  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
Part 7  
scHEmatic, 10 KW HomE staNDBY  
DraWiNG #0G8512  
PAGE LEFT BLANK INTENTIONALLY  
Page 171  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
WiriNG DiaGram, 14 KW HomE staNDBY  
Part 7  
DraWiNG #0G7947  
CONTROL PANEL  
ENGINE COMPARTMENT  
2
2
6
6
0
4
VOLTAGE  
REGULATOR  
0
4
22  
11  
22  
11  
11  
IC  
IC  
22  
10  
6
22  
33  
2
10  
STATOR  
CLOSEST TO BEARING  
10  
44  
11  
BA  
10  
4
0
4
0
0
SP1  
IM1  
18  
N2  
N1  
1
2
SP2  
IM2  
85  
1
85  
86  
13  
18  
MAIN  
CONTROLLER  
86  
2
J1  
3
4
HTO  
LOP  
0
J3  
0
J2  
1 2 3 4  
5
6 7 8 9 10 1112 1314 15 16 1718  
4
15B  
23  
820  
817  
818  
819  
1
RED  
14  
14  
90  
2
90  
CHOKE  
SOLENOID  
0
0
BLK  
0
GOVERNOR  
ACTUATOR  
0
14  
14  
0
0
13  
16  
13  
SCR  
A
SM  
B
0
0
13  
0
SC  
16  
0
0
56  
0
0
16  
13  
0
16  
PANEL GND  
6
6
ENGINE  
GND  
FRAME  
GND  
0
0
Page 172  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
Part 7  
WiriNG DiaGram, 14 KW HomE staNDBY  
DraWiNG #0G7947  
CUSTOMER CONNECT AREA  
240V GENERATOR  
OUTPUT TO TRANSFER  
SWITCH CONTACTOR  
CB  
44  
11  
LEGEND  
BA - BRUSH ASSEMBLY  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
GND - GROUND  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITON MODULE  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
SP_ - SPARK PLUG  
- SPLICE  
- DISCONNECT SPLICE  
LED BOARD  
IC  
20  
20  
20  
20  
1
820  
L1  
2
3
4
817  
818  
L3  
L1: GREEN = SYSTEM READY  
L3: RED = ALARM  
819  
14  
14  
FUEL  
SOLENOID  
14  
N1  
00  
0
BATTERY  
WARMER  
14  
OPTIONAL  
BLACK  
RED  
0
13  
NOTE: ALL WIRES 18 AWG  
300V UL LISTED UNLESS  
SHOWN OTHERWISE  
+ -  
12V  
BATTERY  
0
0
AWG SIZE  
12  
CUSTOMER SUPPLIED  
Page 173  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
scHEmatic, 14 KW HomE staNDBY  
Part 7  
DraWiNG #0G8513  
2
6
2
6
0
4
0
4
VOLTAGE  
REGULATOR  
0
4
22  
11  
22  
11  
POWER  
WINDING  
44  
33  
STATOR  
6
2
22  
11  
POWER  
WINDING  
BA  
0
4
0
4
IM2  
18  
SP2  
IM1  
18  
SP1  
85  
86  
HTO  
LOP  
56  
0
0
SCR  
0
0
13  
13  
0
13  
13  
BATTERY  
12V  
SCR  
16  
SC  
SM  
Page 174  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
Part 7  
scHEmatic, 14 KW HomE staNDBY  
DraWiNG #0G8513  
CB  
44  
240 VAC  
GENERATOR  
OUTPUT  
11  
NEUTRAL  
33  
22  
00  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N1  
N1 N2  
LED BOARD  
1
85  
86  
13  
18  
2
J1  
820  
1
2
3
4
CONTROLLER  
PRINTED CIRCUIT BOARD  
3
L1  
817  
818  
819  
4
L2  
GOVERNOR  
ACTUATOR  
J3  
J2  
1 2 3 4  
0 14  
5
6 7 8 9 10 1112 1314 15 16 1718  
4
23  
15B 0 56  
820  
817  
818  
14  
14  
FS  
CS  
90  
819  
GROUND  
0
0
15B  
23  
+ BATTERY  
TRANSFER  
0
0
LEGEND  
BA - BRUSH ASSEMBLY  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
SP_ - SPARK PLUG  
Page 175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
WiriNG DiaGram, 17 KW HomE staNDBY  
Part 7  
DraWiNG #0G7948  
CONTROL PANEL  
ENGINE COMPARTMENT  
2
2
6
6
0
4
VOLTAGE  
REGULATOR  
0
4
22  
11  
22  
11  
11  
IC  
IC  
22  
10  
6
22  
33  
2
10  
STATOR  
CLOSEST TO BEARING  
10  
44  
11  
BA  
10  
4
0
4
0
0
SP1  
IM1  
18  
N2  
N1  
1
2
SP2  
IM2  
85  
1
85  
MAIN  
CONTROLLER  
2
86  
86  
13  
18  
J1  
3
4
HTO  
LOP  
0
J3  
0
J2  
1 2 3 4  
5
6 7 8 9 10 1112 1314 15 16 1718  
4
15B  
23  
820  
817  
818  
819  
1
RED  
14  
14  
90  
2
90  
CHOKE  
SOLENOID  
0 0  
0
BLK  
0
GOVERNOR  
ACTUATOR  
0
14  
14  
0
0
13  
16  
13  
SCR  
A
SM  
B
0
0
13  
0
SC  
16  
0
0
56  
0
0
16  
13  
0
16  
PANEL GND  
6
6
ENGINE  
GND  
FRAME  
GND  
0
0
Page 176  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
Part 7  
WiriNG DiaGram, 17 KW HomE staNDBY  
DraWiNG #0G7948  
CUSTOMER CONNECT AREA  
240V GENERATOR  
OUTPUT TO TRANSFER  
SWITCH CONTACTOR  
CB  
11C  
00  
14  
44  
14  
11  
14  
0
0
11C  
5
4
14  
00  
00  
3
1
2
LED BOARD  
120V/15A  
DUPLEX  
20  
20  
20  
20  
1
820  
L1  
2
3
4
817  
818  
L3  
L1: GREEN = SYSTEM READY  
L2: YELLOW = MAINTENANCE REQ'D  
L3: RED = ALARM  
LEGEND  
BA - BRUSH ASSEMBLY  
L2  
819  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
GND - GROUND  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITON MODULE  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
SP_ - SPARK PLUG  
- SPLICE  
- DISCONNECT SPLICE  
IC  
14  
14  
FUEL  
SOLENOID  
14  
N1  
00  
0
14  
BLACK  
BATTERY  
WARMER  
RED  
0
13  
OPTIONAL  
+ -  
12V  
BATTERY  
0
0
NOTE: ALL WIRES 18 AWG  
300V UL LISTED UNLESS  
SHOWN OTHERWISE  
CUSTOMER SUPPLIED  
AWG SIZE  
12  
Page 177  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
scHEmatic, 17 KW HomE staNDBY  
Part 7  
DraWiNG #0G8514  
2
6
2
6
0
4
0
4
VOLTAGE  
REGULATOR  
0
4
22  
11  
22  
11  
POWER  
WINDING  
44  
33  
STATOR  
6
2
22  
11  
POWER  
WINDING  
BA  
0
4
IM2  
IM1  
18  
18  
SP2  
SP1  
0
4
18  
85  
86  
13  
85  
86  
HTO  
LOP  
56  
0
0
SCR  
0
0
13  
13  
13  
13  
BATTERY  
12V  
SCR  
16  
0
SC  
13  
0
SM  
Page 178  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
Part 7  
scHEmatic, 17 KW HomE staNDBY  
DraWiNG #0G8514  
CB1  
44  
240 VAC  
GENERATOR  
OUTPUT  
11  
CB2  
33  
22  
00  
NEUTRAL  
00  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N2  
N1  
N1  
11C  
120 VAC  
ACCESSORY  
POWER  
1
00  
0
2
J1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
OUTPUT  
3
4
GOVERNOR  
ACTUATOR  
J3  
J2  
1 2 3 4  
5
6 7 8 9 10 1112 1314 15 16 1718  
LED BOARD  
4
820  
1
2
3
4
14  
23  
15B 0 56  
L1  
L2  
L3  
817  
818  
819  
820  
817  
818  
14  
14  
FS  
CS  
90  
819  
GROUND  
0
0
15B  
23  
+ BATTERY  
TRANSFER  
0
0
LEGEND  
BA - BRUSH ASSEMBLY  
CB_- CIRCUIT BREAKER, MAIN OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
SP_ - SPARK PLUG  
Page 179  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
WiriNG DiaGram, 20 KW HomE staNDBY  
Part 7  
DraWiNG #0G8186  
CONTROL PANEL  
ENGINE COMPARTMENT  
2
2
6
6
0
4
VOLTAGE  
REGULATOR  
0
4
22  
11  
22  
11  
11  
IC  
IC  
22  
8
6
22  
33  
2
8
STATOR  
CLOSEST TO BEARING  
8
44  
11  
BA  
8
4
0
4
0
0
SP1  
IM1  
18  
N2  
N1  
1
2
SP2  
IM2  
85  
1
85  
MAIN  
CONTROLLER  
86  
86  
13  
18  
2
J1  
3
4
HTO  
LOP  
0
J3  
0
J2  
1 2 3 4  
5
6 7 8 9 10 1112 1314 15 16 1718  
4
15B  
23  
820  
817  
818  
819  
1
RED  
14  
14  
90  
2
90  
CHOKE  
SOLENOID  
0
BLK  
0
14  
GOVERNOR  
ACTUATOR  
0
14  
0
0
13  
16  
13  
SCR  
A
SM  
B
0
0
13  
0
SC  
16  
0
0
56  
0
0
16  
13  
0
16  
PANEL GND  
6
6
ENGINE  
GND  
FRAME  
GND  
0
0
Page 180  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
Part 7  
WiriNG DiaGram, 20 KW HomE staNDBY  
DraWiNG #0G8186  
CUSTOMER CONNECT AREA  
240V GENERATOR  
OUTPUT TO TRANSFER  
SWITCH CONTACTOR  
CB  
11C  
00  
14  
44  
11  
14  
14  
0
0
11C  
5
14  
4
00  
00  
3
1
2
LED BOARD  
120V/15A  
DUPLEX  
20  
20  
20  
20  
1
820  
L1  
2
3
4
817  
818  
L3  
L1: GREEN = SYSTEM READY  
L2: YELLOW = MAINTENANCE REQ'D  
L3: RED = ALARM  
LEGEND  
L2  
819  
BA - BRUSH ASSEMBLY  
CB - CIRCUIT BREAKER, MAIN OUTPUT  
GND - GROUND  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITON MODULE  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
SP_ - SPARK PLUG  
- SPLICE  
- DISCONNECT SPLICE  
IC  
14  
14  
FUEL  
SOLENOID  
14  
0
N1  
00  
14  
BLACK  
RED  
0
13  
BATTERY  
WARMER  
OPTIONAL  
+ -  
12V  
BATTERY  
0
0
NOTE: ALL WIRES 18 AWG  
300V UL LISTED UNLESS  
SHOWN OTHERWISE  
CUSTOMER SUPPLIED  
AWG SIZE  
12  
Page 181  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
scHEmatic, 20 KW HomE staNDBY  
Part 7  
DraWiNG #0G8515  
2
6
2
6
0
4
0
4
VOLTAGE  
REGULATOR  
22  
11  
22  
11  
POWER  
WINDING  
44  
33  
STATOR  
22  
6
2
11  
POWER  
WINDING  
BA  
0
4
IM2  
IM1  
18  
18  
SP2  
SP1  
0
4
18  
85  
86  
13  
85  
86  
HTO  
LOP  
56  
0
0
SCR  
0
0
13  
13  
13  
13  
BATTERY  
12V  
SCR  
16  
0
SC  
SM  
13  
0
Page 182  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA  
Part 7  
scHEmatic, 20 KW HomE staNDBY  
DraWiNG #0G8515  
CB1  
44  
240 VAC  
GENERATOR  
OUTPUT  
11  
CB2  
33  
22  
00  
NEUTRAL  
00  
N1  
240 VAC  
UTILITY  
INPUT  
OPTIONAL  
BATTERY WARMER  
N2  
N2  
N1  
N1  
11C  
120 VAC  
ACCESSORY  
POWER  
OUTPUT  
1
00  
0
2
J1  
CONTROLLER  
PRINTED CIRCUIT BOARD  
3
4
GOVERNOR  
ACTUATOR  
J3  
J2  
1 2 3 4  
5
6 7 8 9 10 1112 1314 15 16 1718  
LED BOARD  
4
820  
1
2
3
4
14  
23  
15B 0 56  
L1  
L2  
L3  
817  
818  
819  
820  
817  
818  
14  
14  
FS  
CS  
90  
819  
GROUND  
0
0
15B  
23  
+ BATTERY  
TRANSFER  
0
0
LEGEND  
BA - BRUSCH ASSEMBLY  
CB_ - CIRCUIT BREAKER OUTPUT  
CS - CHOKE SOLENOID  
FS - FUEL SOLENOID  
HTO - HIGH TEMPERATURE SWITCH  
IM_ - IGNITION MODULE  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
SCR - STARTER CONTROL RELAY  
SM - STARTER MOTOR  
SP_ - SPARK PLUG  
Page 183  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WiriNG DiaGram, HomE staNDBY  
traNsfEr sWitcH, 9/10/12/16 circuit  
ELECTRICAL DATA  
Part 7  
DraWiNG #0G7958  
WHT  
WHT  
RED  
BLK  
BLK  
RED  
BLK  
WHT  
RED  
WHT  
N
ALL CIRCUIT  
LC  
GROUNDED  
CONDUCTORS NOT  
SHOWN FOR  
CLARITY  
B
A
16 CIRCUIT LOAD CENTER  
14 CIRCUIT LOAD CENTER  
12 CIRCUIT LOAD CENTER  
10 CIRCUIT LOAD CENTER  
8 CIRCUIT LOAD CENTER  
Page 184  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WiriNG DiaGram, HomE staNDBY  
traNsfEr sWitcH, 9/10/12/16 circuit  
ELECTRICAL DATA  
Part 7  
DraWiNG #0G7958  
RED  
RED  
BLK  
BLK  
RED  
BLK  
N2A  
N1A  
126  
126  
GRN  
GRN  
A
N2A  
N2A  
N1A  
TR1  
N2A  
1 3  
4 6  
7 9  
1
2
C1  
126  
A
N1  
N2  
205  
E1  
A B  
15B  
23  
N1A  
SW2  
SW3  
E1 BLK  
RED  
N1A  
N2A  
N1A  
N2A  
SW1  
205  
BLK  
RED  
BLK  
RED  
E1  
T1  
E2  
T2  
205  
2
B
C2  
1
N1AN2A  
E2 B  
205  
E1  
E2  
BC  
A
A
A
BLK  
RED  
BLK  
RED  
E1  
23  
15B  
F1 F2 F3  
B
B
B
-
BLK  
WIRE  
+
RED  
WIRE  
N1 N2  
T1  
T1  
15B  
0
0D4698-T  
1 2 3  
TB1  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
TR1-TRANSFER RELAY  
Page 185  
Download from Www.Somanuals.com. All Manuals Search And Download.  
scHEmatic, HomE staNDBY  
traNsfEr sWitcH, 9/10/12/16 circuit  
ELECTRICAL DATA  
Part 7  
DraWiNG #0G7959  
0
0
0
15B  
E1  
N1A  
CONTROL  
TRANSFER  
15B  
15B  
23  
15B  
23  
A
23  
7 7 9 9  
E1  
N1A  
TR1  
TS TO  
GENERATOR  
CONTROL PANEL  
1 4 3 6  
B
23  
F2  
N2  
N1  
E1  
E2  
N2  
UTILITY  
SENSING  
240VAC  
OUTPUT  
126  
205  
N2A  
F1  
N1A  
N1A  
N1  
-
+
N1A  
BLK  
WIRE  
RED  
WIRE  
E1  
BLACK  
RED  
TO GENERATOR  
OUTPUT  
BC  
E1  
NEUTRAL (WHITE)  
GROUND (GREEN)  
E2  
NEUTRAL  
CONNECTION  
INSIDE  
SWITCH  
B
GROUND (GREEN)  
NEUTRAL (WHITE)  
N2A  
N1A  
240VAC TO  
MAIN DISTRIBUTION  
PANEL  
RED (MAIN 2)  
205  
B
126  
N2A  
NO  
BLACK (MAIN 1)  
E1  
NO  
NC  
NC  
CIRCUIT 14  
CIRCUIT 13  
CIRCUIT 10  
CIRCUIT 9  
CIRCUIT 6  
CIRCUIT 5  
CIRCUIT 2  
CIRCUIT 1  
CIRCUIT 3  
CIRCUIT 4  
CIRCUIT 7  
CIRCUIT 8  
CIRCUIT 11  
CIRCUIT 12  
CIRCUIT 15  
CIRCUIT 16  
E2  
SW3  
SW2  
COM  
E2  
COM  
B
VR1  
C1  
VR2  
C2  
N2A  
A
T1T1T2  
SW1  
N2A  
B E2  
F3  
T1  
T1  
T2  
B
E2  
LEGEND  
BC-BATTERY CHARGER  
C1-UTILITY COIL & RECTIFIER  
C2-GENERATOR COIL & RECTIFIER  
F1,F2,F3-5A, 600V FUSE  
LC-CIRCUIT BREAKER (LOADS)  
(16 CIRCUIT SHOWN FOR REFERENCE ONLY)  
N-NEUTRAL  
SW1-AUTOMATIC TRANSFER SWITCH  
SW2,SW3-LIMIT SWITCHES  
TB1-TERMINAL STRIP  
LC  
TR1-TRANSFER RELAY  
Page 186  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 187  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 188  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Generac Power Systems, Inc.  
Highway 59 & Hillside Rd.  
P.O. Box 8  
Waukesha, WI 53187  
1-888-GENERAC  
MyGenerac.com  
©2008 Generac Power Systems, Inc. All rights reserved.  
Specifications are subject to change without notice.  
Part No. 0G9266 rev. A / Printed in USA 09.08  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Generac Power Systems Portable Generator Transfer Switches and Accessories User Manual
Generac Power Systems Portable Generator SG010 User Manual
Generac Power Systems Portable Generator 004987 2 005396 0 User Manual
Generac Power Systems Portable Generator 00862 1 User Manual
Generac Power Systems Portable Generator 16L 18 kW User Manual