Generac Switch 6376 User Manual

Installation and Operating Instructions  
MANUAL TRANSFER SWITCH - MODELS 6294, 6408 and 6376  
WARNING: Generac® transfer switches should be installed by a professional electrician familiar with electrical wiring and codes, and experienced in working with generators.  
Generac accepts no responsibility for accidents, damages or personal injury caused by incorrect installation. This transfer switch is intended for surface mounting INDOORS only.  
Our transfer switches are UL listed to UL 1008 and meet the criteria of National Electrical code Article 702.6 for Optional Standby Systems. CAUTION: If using the generator and  
transfer switch for larger appliances, such as electric water heaters, clothes dryers, electric ranges and small air conditioners, check the labels on the appliances to be sure they do  
NOT exceed the rating of the generator. No appliance should have an amperage rating that exceeds the individual breaker rating in the transfer switch (20 or 30 amps).  
CALIFORNIA PROPOSITION 65 WARNING: Engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects and other reproductive  
harm. This product may contain or emit chemicals known to cause cancer, birth defects and other reproductive harm.  
Thank you for purchasing a Generac Transfer Switch to safely connect a portable  
generator to the load center in your home or business (single phase only) for  
standby power applications. Product features include:  
Generator and Utility feeds mechanically interlocked to prevent dangerous utility or  
generator back feeding – thereby avoiding property damage and serious injury to  
electrical workers.  
Pre-wired for fast, easy connection to the load center.  
Each model can be expanded to up to 10 circuits using standard interchangeable type  
circuit breakers. See Step 2, Section III.  
Accommodates GFCI and Arc-Fault breakers to meet the latest NEC requirements.  
Dual wattmeters help you monitor and balance the loads on your generator, prolonging  
generator life.  
Safe generator connection – Install the Power Inlet Box in a convenience location  
outside for a quick cord connection to your generator.  
Surface Mount enclosure indoors. Not approved for outdoor installation.  
MODEL 6294 KIT SHOWN  
What is Included in this Carton:  
Manual Transfer Switch with wire harness, conduit, fittings and wire connectors (6)  
30 Amp Power Inlet Box (Models 6294 and 6408 only)  
10 Foot Power Cord with L14-30 male and female ends (Models 6294 and 6408 only)  
L14-20 male plug (Model 6408 only)  
Installation Manual and Warranty Registration card  
Tools and Items Needed for Installation:  
¼” nut driver, 2-1/8” hole saw (if flush mounting)  
Screwdrivers, straight blade and Phillips  
Electric drill, drill bits, wallboard saw  
Wire cutter/stripper  
Safety eye goggles  
Anchors and screws to mount transfer switch to wall  
New 60A 2-pole, 240V circuit breaker to install in main load center – should be same manufacturer as existing load center.  
10 gauge 4-wire building wire and conduit to connect between power inlet box and transfer switch  
Optional Items for Installation:  
Arc-fault, GFCI or Surge protection circuit breakers. If Arc-fault, GFCI or Surge protection circuit breakers are used as the branch circuit protector in the main load  
center, they MUST be used in the manual transfer switch. You may be able to re-use your existing AFCI, GFCI and Surge protection circuit breakers in the manual  
transfer switch. See list of compatible breakers below.  
Wire, fittings and conduit to connect the Power Inlet Box to the transfer switch  
White, green, black and red THHN or MTW wire, 10 AWG, 300V rated  
Switched Neutral Kit (SNK). If your portable generator has the neutral bonded to the frame of the generator AND 240V “full-power” receptacle is GFCI protected, you  
will need to install a SNK accessory with your transfer switch to avoid nuisance tripping of the GFCI breaker on the generator.  
NOTE ON NEUTRAL BONDED GENERATORS: Some portable generators are intended for use on jobsites, and therefore are subject to OSHA regulations for GFCI protection on all receptacles.  
These "contractor grade" generators have their neutral wire bonded to the ground wire to pass OSHA inspection on job sites, and when connected to a transfer switch, this may cause nuisance  
tripping of the generator GFCI breaker. If you’re using a neutral bonded generator to power a house or building through a transfer switch, then determine if the neutral bond wire on the  
generator can be disabled without voiding the warranty, preferably by a dealer or a qualified electrician. NOTE: After this action, the generator will no longer pass OSHA inspection on job sites.  
Consult the manufacturer of your generator to determine if the neutral bond can be removed. If it can be disabled, then no modifications to your transfer switch installation are needed. If the  
neutral bond cannot be disabled or voids the generator warranty, you must install a Switched Neutral Kit (SNK) accessory with your transfer switch.  
Compatible Circuit Breakers:  
Siemens/Murray QT, QPH, HQP, QPF (GFCI), QPHF, QFP, QE, QEH, QAF (Arc Fault), QP (Surge Protector)  
Cutler-Hammer Series BD, BR, BQ, GFC  
Challenger Type A, C, HAGF  
Square D Series HOM (Homeline)  
GE Series THQL  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 2 – CIRCUIT WORKSHEET  
Circuit  
A4  
Amperage  
Appliance(s) or Circuits  
15A  
B4  
A5  
B5  
A6  
B6  
15A  
20A  
20A  
20A  
20A  
STEP 2: INSTALLATION PROCEDURE:  
PLEASE READ THIS MANUAL IN ITS ENTIRETY BEFORE ATTEMPTING TO UNPACK, ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THIS EQUIPMENT.  
HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH ENCLOSURES THAT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY. FOLLOW PROPER INSTALLATION,  
OPERATION AND MAINTENANCE PROCEDURES TO AVOID HAZARDOUS VOLTAGES. TURN OFF THE MAIN CIRCUIT BREAKER IN THE LOAD CENTER BEFORE STARTING  
INSTALLATION.  
I. TRANSFER SWITCH INSTALLATION:  
1. Select a location on the left or right side of the load center to mount transfer switch, as it is provided with a 24” flexible conduit wiring harness. Remove the  
front cover of the load center, save the screws. Locate and remove a knockout (KO) on the lower side of the load center that matches the conduit fitting size on  
the wiring harness.  
2. Determine if the wiring harness needs to be shortened. If so, remove the wires from the wiring harness and cut conduit to desired length. [NOTE: The  
Electrical Non-Metallic Tubing (ENT) provided is UL Listed and recognized by the National Electrical Code (NEC). However, some local codes and inspectors  
may prohibit its use in buildings that exceed (3) floors above grade.]  
3. Attach the wiring harness to the load center; hold the transfer switch in position against the wall on which it is to be mounted and using the provided template,  
mark the holes on the wall for the anchoring screws and anchor transfer switch to wall (anchors not provided).  
4. Remove transfer switch cover, save screws, allow the cover to hang down, supported by the wattmeter wires.  
5. Install appropriately sized conduit, fittings and wire between the Power Inlet Box (PIB) mounted on the building exterior and the transfer switch, referring to  
section III – Power Inlet Box installation instructions below. Locate and remove a KO in the transfer switch, pull wire into transfer switch enclosure and secure  
wire with fitting.  
6. Using provided wire connector, connect the generator green ground wire with the green wire inside the transfer switch. Connect the generator white neutral  
wire into neutral bar on the left. Using provided wire connectors, connect the generator black wire to black wiring going to Meter “A”. Repeat for generator red  
wire to Meter “B”. See FIGURE 2 WIRING DIAGRAM. Reinstall transfer switch cover.  
7. In the main load center, remove the wires from the breakers for the loads that will be relocated to the transfer switch. Cut each blue harness wire (A4-B6) to a  
convenient length, strip off 5/8” insulation and connect to the wires removed from the breakers per TABLE 2 with the provided wire connectors.  
8. Remove two adjacent single pole breakers from which the load wires were removed and install the NEW 60A 2-pole circuit breaker (as required in the Other  
Items Needed section) in their place. Insert the unmarked BLACK wires from the harness into the new circuit breaker. Terminate the WHITE and GREEN wire in  
the harness in an open position in the Neutral and Ground bars respectively. If there is no separate ground bar, insert the GREEN wire into an open position in  
the NEUTRAL bar, and tighten.  
9. Reinstall the main load center dead front cover, and turn ON the MAIN breaker in the main load center. Turn ON all branch circuit breakers in both panels. Turn  
ON the UTIL MAIN in the transfer switch. Check that power is restored to all appliances. Installation is now complete.  
II. EXPANDING OR RECONFIGURING YOUR TRANSFER SWITCH:  
This transfer switch ships from the factory with certain popular branch circuit breaker sizes. However, the circuit breaker assortment can be modified to  
suit specific requirements, and this does not void the UL Listing. For example, if the 2-pole 20 amp circuit breaker is not needed, it may be removed from  
the panel and replaced with any combination of the following: two separate full size breakers, four tandem (half size) breakers, one full size and two  
tandems, or a quad breaker. If additional circuit(s) are added, the installer is responsible for providing appropriately sized wire(s) for each circuit.  
III. INSTALLING THE POWER INLET BOX (Models 6294 and 6408 Only)  
1. Remove the front cover of the Power inlet box. Remove the 3 screws that secure the flanged inlet to the bottom  
plate. For installations where side clearance exceeds 12” on both sides, remove the 4 screws that secure the  
bottom plate to the box.  
2. Mount the power inlet box on the outside of the building in a convenient location (minimum 24” above grade), using  
the four holes provided in the back of the enclosure. Use sealant around the anchoring screws to keep water from  
entering the box at these mounting holes. Using approved wiring methods, install the wiring through one of the  
knockouts provided in the enclosure. Be sure to seal around the hole in the building where the conduit enters  
through the wall.  
3. Extend wiring inside the power inlet box approx. 8” from the point of entrance. Attach green or bare ground wire to  
green lead provided in power inlet box with wire nut (provided by installer). Strip and insert incoming leads into  
terminals on flanged inlet. Insert white wire (neutral) into nickel-plated screw terminal or white marking on the flanged inlet.  
4. Carefully fold wires into the enclosure and reattach the bottom assembly or inlet onto box with screws removed earlier. Installation is complete.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
STEP 3: USING YOUR TRANSFER SWITCH:  
NEVER run portable generators indoors or in garages, basements, or sheds. Portable generators should always be used at least 5 feet away from windows,  
doors, vents, or any other opening. Carbon Monoxide (CO) from a generator is deadly and can kill you in minutes. Read and follow all generator directions before use.  
A. Transferring from Utility Power to Generator Power:  
1. Move generator outdoors.  
2. Connect male plug of Power Cord into 125/250V receptacle (L14-30) on the generator. Turn ON circuit breaker for the outlet plugged into.  
3. Plug in female connector of the Power Cord to the Power Inlet Box. Turn all circuit breakers in the transfer switch to their OFF position.  
4. Start the generator outdoors, following the procedures described in the generator’s owner’s manual. Turn ON the GENERATOR MAIN circuit breaker in the  
transfer switch. Turn ON circuit breakers in the manual transfer switch one at a time alternating from phase “A” and phase “B”. Watch the meters as you  
turn on successive circuits so that the meters do not continuously exceed the maximum wattage of the generator. It may be necessary to alternate the use of  
larger loads (furnace motors, well pumps, freezers, etc.) to avoid overloading the generator. To promote generator life, loads should be balanced on Phase  
“A” and “B” so that the wattage reading on each meter is within about 1000 watts of the other.  
5. Test your circuits by using the wattmeters or determine wattage from that shown on each appliance. Make a note of any excessive loads which must be  
removed from a given circuit during generator operation in an emergency. [Note: Wattmeters do not show power at very low levels.]  
B. Transferring from Generator Power to Utility Power:  
1. On the transfer switch, turn the GENERATOR MAIN breaker OFF. Then shut down the generator, following the procedures in the generator Owner’s Manual.  
2. On the transfer switch, turn the UTILITY MAIN breaker ON. Then Turn ON any branch circuit breakers in the transfer switch that are OFF.  
3. Unplug the power cord from the generator and the power inlet.  
4. Cool off the generator and store in a dry, secured location.  
To ensure that your generator will work properly when you need it, it is important to start and run your generator under load regularly and keep the tank filled with fresh fuel.  
Perform the above steps at least ONCE A MONTH to keep the generator properly “exercised.” It is not necessary to turn off any circuits in the MAIN load center when  
operating/testing the transfer switch.  
Figure 2 - WIRING DIAGRAM:  
Protected by US Patent  
No. US 6,861,596 B2  
Generac Power Systems, Inc.  
Toll Free: 1-888-GENERAC  
0196990SBY  
© 2012 Generac Power Systems, Inc. All Rights Reserved. GenTran and Generac are registered trademarks of Generac Power Systems, Inc.  
PN 500507 Rev B  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instructions d'installation et d'utilisation  
COMMUTATEUR DE TRANSFERT MANUEL - MODÈLES 6294, 6408 et 6376  
AVERTISSEMENT : Les commutateurs de transfert Generac ®doivent être installés par un électricien professionnel qui se connaît bien en câbles et codes électriques et a de  
l'expérience avec les génératrices. Generac décline toute responsabilité pour les accidents, les dommages ou les blessures causés par une installation incorrecte. Ce  
commutateur de transfert sera monté en surface uniquement À L'INTÉRIEUR. Nos commutateurs de transfert sont homologués UL selon le standard UL 1008 et répondent aux  
critères du Code électrique national, article 702.6 portant sur les systèmes de secours secondaires. ATTENTION : Si vous utilisez la génératrice et le commutateur de transfert  
pour des appareils plus grands, tels que les chauffe-eau électriques, les sécheuses à linge, les cuisinières électriques et les petits climatiseurs, lisez les étiquettes sur les appareils  
pour vérifier qu'ils ne dépassent PAS la puissance de la génératrice. L'intensité de l'appareil ne devrait pas dépasser le calibre du disjoncteur individuel du commutateur de transfert  
(20 ou 30 ampères). Avertissement conformément à la California Proposition 65: L'État de Californie avertit que l'échappement du moteur et certains de ses composants  
peuvent causer le cancer, des malformations congénitales ou autres anomalies de la reproduction. Ce produit peut contenir ou émettre des produits chimiques qui, selon l'État de  
Californie, peuvent causent le cancer, des malformations congénitales ou autres anomalies de la reproduction.  
Nous vous remercions d'avoir acheté une trousse de commutateur de transfert  
Generac pour brancher une génératrice portable en toute sécurité au centre de  
distribution de votre maison ou de votre bureau (monophasé seulement) pour des  
applications à alimentation de secours. Quelques caractéristiques du produit :  
L'alimentation de la génératrice et l'alimentation électrique normale sont verrouillées  
mécaniquement pour empêcher la réalimentation du circuit normal ou de la  
génératrice qui peut être dangereuse - et éviter ainsi tout dégât matériel et de graves  
blessures des électriciens.  
Précâblé pour faciliter le raccordement rapide au centre de distribution.  
L'on peut ajouter tout au plus 10 circuits à chaque modèle à l'aide de disjoncteurs  
standard interchangeables. Voir l'étape 2, section III.  
Compatible avec les disjoncteurs GFCI et d'amorçage d'arc pour répondre aux  
dernières exigences de NEC.  
Les wattmètres doubles vous permettent de surveiller et équilibrer les charges de la  
génératrice, prolongeant ainsi sa vie.  
Raccordement de la génératrice en toute sécurité - installez la boîte d'entrée  
d'alimentation dans un endroit facilement accessible à l'extérieur pour y brancher  
rapidement la génératrice.  
Boîtier de montage en surface à l'intérieur. Non approuvé pour l'installation à  
l'extérieur.  
Modèle 6294  
Le paquet contient :  
un commutateur de transfert manuel avec faisceau électrique, conduit, raccords et serre-fils (6)  
Boîte d'entrée d'alimentation de 30 ampères (modèles 6294 et 6408)  
Cordon d'alimentation de 10 pieds avec des bouts mâle et femelle L14-30 ((modèles 6294 et 6408)  
Manuel d'installation et carte de garantie  
Outils et objets nécessaires pour l'installation :  
tournevis à douille de 1/4 po, scie cloche de 2-1/8 po (en cas d'encastrement)  
Tournevis, aube droite et Phillips  
Perceuse électrique, forets, scie à panneau mural  
Coupe-fil / outil à dénuder  
Lunettes de protection  
Ancrages et vis pour monter le commutateur de transfert sur le mur  
Un nouveau disjoncteur bipolaire de 60A, 240V à installer dans le centre de distribution principal - même fabricant que le centre de distribution actuel.  
Fil de bâtiment calibre 4 et conduit pour relier la boîte d'entrée d'alimentation et le commutateur de transfert  
Articles facultatifs pour l'installation :  
Disjoncteurs GFCI, d'amorçage d'arc et de protection contre les surtensions. Si les disjoncteurs GFCI, d'amorçage d'arc et de protection contre les surtensions sont  
utilisés en tant que protecteurs de la dérivation au centre de distribution principal, ils DOIVENT être utilisés dans le commutateur de transfert manuel. Vous pouvez  
réutiliser les disjoncteurs AFCI, GFCI et de protection contre les surtensions existant actuellement dans le commutateur de transfert manuel. Voir la liste de  
disjoncteurs compatibles ci-dessous.  
Des câbles, de raccords et du conduit pour relier la boîte d'entrée d'alimentation au commutateur de transfert  
Du câble blanc, vert, noir et rouge THHN ou MTW, 10 AWG pour 300V  
Switched Neutral Kit (SNK). Si la génératrice portable a le neutre lié à son cadre ET la prise de courant de 240V a une protection GFCI, vous devez installer un  
accessoire SNK avec le commutateur de transfert pour éviter le déclenchement intempestif du disjoncteur GFCI de la génératrice.  
NOTE SUR LES GÉNÉRATRICES À NEUTRE LIÉ À LA MASSE : Certaines génératrices portables sont prévues pour l'usage sur chantiers et sont assujetties aux règlements d'OSHA visant la protection GFCI de toutes les prises  
de courant. Ces génératrices de catégorie professionnelle ont le neutre lié au fil de masse pour réussir l'inspection d'OSHA sur les chantiers et une fois relié à un commutateur de transfert, ceci peut causer le déclenchement  
intempestif du disjoncteur GFCI de la génératrice. Si vous utilisez une génératrice au neutre lié à la masse pour alimenter une maison ou un immeuble par l'intermédiaire d'un commutateur de transfert, vous devez déterminer  
si le fil de neutre de la génératrice peut être désactivé sans annuler la garantie par un concessionnaire ou un électricien qualifié, de préférence. NOTE : Ayant effectué cette opération, la génératrice ne réussira plus  
l'inspection d'OSHA sur chantiers. Communiquez avec le fabricant de votre génératrice pour déterminer si le fil de neutre peut être enlevé. S'il peut être désactivé, vous n'avez besoin d'apporter aucune autre modification à  
votre installation de commutateur de transfert. Si le fil de neutre ne peut pas être désactivé ou si cela annule la garantie de la génératrice, vous devez installer l'accessoire appelé Switched Neutral Kit (SNK-6297) avec le  
commutateur de transfert.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Disjoncteurs compatibles :  
Siemens/Murray QT, QPH, HQP, QPF (GFCI), QPHF, QFP, QE, QEH, QAF (amorçage d'arc), QP (protecteur contre les surtensions)  
Série BD, BR, BQ, GFC de Cutler-Hammer  
Challenger Type A, C, HAGF  
Série Square D HOM (Homeline)  
Série THQL de GE  
TABLEAU 1 - CARACTÉRISTIQUES  
Modèle :  
6294 – 6408 – 6376  
Nombre de circuits disponibles sur le commutateur de  
transfert  
6
Nombre maximum de circuits  
10  
DISJONCTEUR OBLIGATOIRE POUR LE CENTRE DE  
DISTRIBUTION PRINCIPAL (non fourni)  
Disjoncteur principal de l'alimentation normale  
Disjoncteur principal de l'alimentation par génératrice  
Les disjoncteurs sont fournis avec l'appareil  
Intensité maximum de la génératrice  
Intensité maximum de la génératrice  
Tension  
Bipolaire de 60 ampères  
Bipolaire de 60 ampères  
Bipolaire de 30 ampères  
2 - unipolaire de 15 ampères, 2 - unipolaire de 20 ampères, 1 - bipolaire de 20 ampères  
7500 continu / 9000 surcharge  
30 ampères  
125/250 volts  
Boîtier type NEMA  
Configuration NEMA de l'entrée mâle dans la boîte d'entrée  
d'alimentation  
1 - à l'intérieur uniquement  
L14-30  
Phase  
1
Calibre minimum du cordon d'alimentation  
10/4  
*Note: Si les disjoncteurs différentiels de fuite à la terre (GFCI), les interrupteurs d'amorçage d'arc (AFCI) ou les disjoncteurs de protection contre les surtensions sont utilisés en tant que  
protecteurs de la dérivation dans le centre de distribution principal, ils DOIVENT être utilisés dans le commutateur de transfert. Les disjoncteurs GFCI et AFCI exig