Generac Portable Generator RD01523GDAE User Manual

ProtectorSeries  
Owner’s Manual  
For  
Stationary Diesel Generators  
Residential and Commercial  
Model  
RD015 -  
RD020 -  
RD030 -  
RD048 -  
RD050 -  
15 kW 60 Hz  
20 kW 60 Hz  
30 kW 60 Hz  
48 kW 60 Hz (Single Phase Only)  
50 kW 60 Hz (Three Phase Only)  
0066781 - 30 kW 60 Hz  
NOT INTENDED FOR USE IN CRITICAL  
LIFE SUPPORT APPLICATIONS.  
*
*
ONLY QUALIFIED ELECTRICIANS OR  
CONTRACTORS SHOULD ATTEMPT  
INSTALLATION!  
DEADLY EXHAUST FUMES! OUTDOOR  
INSTALLATION ONLY!  
*
This manual should remain with the unit.  
This manual must be used in conjunction  
with the appropriate installation manual.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Section 1 Safety  
1.1 Introduction .......................................................................................................................... 1  
1.2 Safety Information ................................................................................................................ 2  
1.3 General Hazards ................................................................................................................... 2  
1.4 Exhaust Hazards .................................................................................................................. 3  
1.5 Electrical Hazards ................................................................................................................ 3  
1.6 Fire Hazards .......................................................................................................................... 3  
1.7 Explosion Hazards ............................................................................................................... 3  
Section 2 Specifications  
2.1 Emission Information .......................................................................................................... 5  
2.1.1 Emissions Data Plate ....................................................................................................................5  
2.2 Specifications ....................................................................................................................... 6  
2.2.1 Engine ...........................................................................................................................................6  
2.3 Engine Oil Recommendations ............................................................................................ 7  
2.4 Coolant Water Treatment .................................................................................................... 7  
2.5 Fuel Requirements ............................................................................................................... 7  
2.5.1 Fuel Maintenance .........................................................................................................................8  
2.5.2 Fuel Maintenance .........................................................................................................................8  
2.6 Battery Requirements .......................................................................................................... 8  
2.6.1 Battery Charger ............................................................................................................................8  
2.7 Corrosion Protection ........................................................................................................... 8  
2.8 Accessories .......................................................................................................................... 8  
Section 3 Activation and Startup  
3.1 Orientation .......................................................................................................................... 11  
3.2 Remove Side Access Panels ............................................................................................ 11  
3.3 Prime Fuel System ............................................................................................................. 12  
3.4 Install Battery ..................................................................................................................... 12  
3.5 Open Viewing Window ....................................................................................................... 13  
3.6 Start and Run Engine ......................................................................................................... 13  
3.7 Activate Unit ...................................................................................................................... 14  
3.8 Operational Checks ........................................................................................................... 15  
3.8.1 Self Test ......................................................................................................................................15  
3.8.2 Check Manual Transfer Switch Operation ..................................................................................15  
Owner’s Manual for Stationary Diesel Generators  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
3.8.3 Electrical Checks ........................................................................................................................16  
3.8.4 Test Generator Under Load ........................................................................................................16  
3.8.5 Check Automatic Operation ........................................................................................................17  
3.9 Final Instructions ................................................................................................................17  
Section 4 Operation  
4.1 Control Panel ......................................................................................................................19  
4.2 Auto/Manual/Off ..................................................................................................................19  
4.3 Menu Navigation .................................................................................................................20  
4.4 Alarm/Warning Conditions ................................................................................................22  
4.5 Change Time and Date .......................................................................................................22  
4.6 Programmable Timers ........................................................................................................22  
4.6.1 Dealer Programmable ................................................................................................................22  
4.6.1.1 Exercise Time ..................................................................................................................... 22  
4.6.2 User Programmable ...................................................................................................................23  
4.6.2.1 Start-Up Delay Timer .......................................................................................................... 23  
4.6.2.2 Warm-Up Delay Timer ........................................................................................................ 23  
4.7 USB Port for Firmware Updates ........................................................................................23  
4.8 Battery Charger ..................................................................................................................23  
4.9 Transfer Switch Automatic Operation ..............................................................................23  
4.9.1 Automatic Sequence of Operation ..............................................................................................24  
4.9.1.1 Utility Failure ....................................................................................................................... 24  
4.9.1.2 Cranking.............................................................................................................................. 24  
4.9.1.3 Load Transfer...................................................................................................................... 24  
4.10 Transfer Switch Manual Operation .................................................................................24  
4.10.1 Transfer to Generator Power ....................................................................................................25  
4.10.2 Transfer Back to Utility Power ..................................................................................................25  
Section 5 Maintenance  
5.1 Component Locations ........................................................................................................27  
5.2 Access Panels ....................................................................................................................29  
5.2.1 Removal .....................................................................................................................................29  
5.2.2 Installation ..................................................................................................................................29  
5.3 Service Maintenance Intervals ..........................................................................................30  
5.4 Remove From Service ........................................................................................................31  
5.5 30 Hour Break-In .................................................................................................................31  
iv  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
5.6 Daily Maintenance (If Running Continuously) ................................................................. 31  
5.7 Schedule A Maintenance ................................................................................................... 32  
5.7.1 Preliminary Instructions ..............................................................................................................32  
5.7.2 Check Fuel Level and Fill ...........................................................................................................32  
5.7.3 Drain Fuel Filter and Check Fuel Lines/Hoses ...........................................................................32  
5.7.4 Check Coolant Level and Hoses ................................................................................................33  
5.7.5 Check Radiator for Clogging .......................................................................................................34  
5.7.6 Check Lubricating Oil Level ........................................................................................................34  
5.7.7 Check Battery Condition/Fluid Level ...........................................................................................35  
5.7.7.1 Check Condition and Clean ................................................................................................ 35  
5.7.7.2 Check Fluid Level ............................................................................................................... 35  
5.7.7.3 Check State of Charge........................................................................................................ 35  
5.7.7.4 Battery Replacement .......................................................................................................... 35  
5.7.8 Check and Adjust V-Belt .............................................................................................................37  
5.7.8.1 Check.................................................................................................................................. 37  
5.7.8.2 Adjust.................................................................................................................................. 38  
5.7.9 Replace Air Filter Element ..........................................................................................................38  
5.7.10 Drain Breather Canister and Replace Filter ..............................................................................38  
5.7.11 Lubricate Governor Rod Linkage ..............................................................................................39  
5.7.12 Final Instructions .......................................................................................................................39  
5.8 Schedule B Maintenance ................................................................................................... 40  
5.8.1 Replace Lubricating Oil and Oil Filter .........................................................................................40  
5.8.2 Replace Fuel Filter ......................................................................................................................41  
5.8.2.1 Prime Fuel System.............................................................................................................. 41  
5.8.3 Drain/Flush Coolant System .......................................................................................................41  
5.8.4 Final Instructions .........................................................................................................................42  
5.9 Schedule C Maintenance ................................................................................................... 43  
5.10 Return To Service ............................................................................................................ 43  
Section 6 Troubleshooting  
6.1 Engine Troubleshooting .................................................................................................... 45  
6.2 Controller Troubleshooting ............................................................................................... 46  
6.3 Removal From Service During Utility Outages ............................................................... 47  
6.4 Storage ................................................................................................................................ 47  
6.4.1 Prepare For Storage ...................................................................................................................47  
6.4.2 Return From Storage ..................................................................................................................48  
6.5 Attention After Submersion .............................................................................................. 49  
6.6 Attention After Fuel Spillage ............................................................................................. 49  
6.7 Contaminated Fuel Disposal ............................................................................................. 49  
Owner’s Manual for Stationary Diesel Generators  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
WARNING  
California Proposition 65. Engine exhaust and some of  
its constituents are known to the state of California to  
cause cancer, birth defects, and other reproductive  
harm.  
(000004)  
WARNING  
California Proposition 65. This product contains or  
emits chemicals known to the state of California to  
cause cancer, birth defects, and other reproductive  
harm.  
(000005)  
vi  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
Safety  
1.1 — Introduction  
Thank you for purchasing this stationary automatic standby generator set. Every effort was made to ensure that the  
information in this manual was both accurate and complete at the time it was released. However, the manufacturer  
reserves the right to change, alter or otherwise improve this product at any time without prior notice.  
This generator is designed to automatically supply electrical power to operate critical loads during a utility power failure.  
The unit is factory installed in an all-weather metal enclosure and is intended exclusively for outdoor installation  
using only diesel fuel.  
When properly sized, the generator is suitable for supplying typical residential/commercial loads, such as induction  
motors (sump pumps, refrigerators, freezers, air conditioners, furnaces, etc.), electronic components (computers, mon-  
itors, televisions, etc.), lighting, microwaves, and other residential and business loads.  
READ THIS MANUAL THOROUGHLY: The operator is responsible for proper and safe use of this equipment. Read  
and thoroughly understand the contents of this manual before attempting to use the equipment. If any portion of this  
manual is not fully understood, contact the nearest Authorized Service Dealer for assistance.  
SAVE THESE INSTRUCTIONS: The manufacturer suggests that this manual and the rules for safe operation be cop-  
ied and posted near the generator installation site. Safety should be stressed to all operators and potential operators of  
this equipment.  
SAFETY: Throughout this manual, and on tags and decals affixed to the unit, DANGER, WARNING, CAUTION and  
NOTE blocks are used to alert personnel to special instructions about a particular operation, function or service that  
may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:  
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS  
INJURY.  
Indicates a hazardous situation or action which, if not avoided, could result in death or serious injury.  
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.  
NOTE: Notes contain additional information important to an operation or procedure.  
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of informa-  
tion each indicates is as follows:  
This symbol points out important Safety Information that, if not followed, could endanger personal safety and/or  
property of others.  
*
$
This symbol points out a potential Explosion Hazard.  
This symbol points out a potential Fire Hazard.  
!
+
This symbol points out a potential Electrical Shock Hazard.  
These “Safety Alerts” cannot eliminate the hazards that they signal. Strict compliance with these special instructions,  
plus common sense, are major accident prevention measures.  
Owner’s Manual for Stationary Diesel Generators  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety  
1.2 — Safety Information  
Study these safety rules carefully before operating or servicing this equipment. Become familiar with this Owner’s Man-  
ual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated  
and maintained. Many accidents are caused by failing to follow simple rules or precautions.  
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this  
manual, and on tags and decals affixed to the unit are not all-inclusive. If using a procedure, work method or operating  
technique the manufacturer does not specifically recommend, ensure that it is safe for personnel. Also make sure the  
procedure, work method or operating technique used does not render the generator unsafe.  
Despite the safe design of this generator, operating this equipment imprudently, neglecting its mainte-  
nance or being careless can cause possible injury or death. Permit only responsible and capable per-  
sons to install, operate and maintain this equipment.  
*
Potentially lethal voltages are generated by these machines. Ensure steps are taken to make the  
machine safe before attempting to work on the generator.  
*
*
Parts of the generator are rotating and/or hot during operation. Exercise care near a running generator.  
The installation of this generator must always comply with applicable codes, standards, laws and regu-  
lations.  
*
A running generator gives off DEADLY carbon monoxide, an odorless, colorless, poisonous gas.  
Breathing carbon monoxide can cause dizziness, throbbing temples, nausea, muscular twitching, head-  
ache, vomiting, weakness, sleepiness, inability to think clearly, fainting, unconsciousness or even  
death.  
*
The control panel for this unit is intended to be operated by qualified service personnel only.  
*
1.3 — General Hazards  
For safety reasons, this equipment should only be installed, serviced and repaired by a Service Dealer or other  
competent, qualified electrician or installation technician who is familiar with applicable codes, standards, regula-  
tions and product Installation Manual guidelines. The operator also must comply with all such codes, standards,  
regulations and product Installation Manual guidelines.  
The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in  
sufficient concentrations, can cause unconsciousness or even death. DO NOT alter or add to the exhaust system  
or do anything that might render the system unsafe or in noncompliance with applicable codes and standards.  
Install a carbon monoxide alarm indoors, according to manufacturer’s instructions/recommendations.  
Adequate, unobstructed flow of cooling and ventilating air is critical for correct generator operation. Do not alter  
the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation  
of the generator. The generator MUST be installed and operated outdoors only.  
Keep hands, feet, clothing, etc. away from drive belts, fans, and other moving or hot parts. Never remove any  
drive belt or fan guard while the unit is operating.  
When working on this equipment, remain alert at all times. Never work on the equipment when physically or men-  
tally fatigued.  
Inspect the generator regularly, and contact the nearest Dealer for parts needing repair or replacement.  
Before performing any maintenance on the generator, remove the control panel fuse and disconnect the Nega-  
tive (-) battery cable to prevent accidental startup. When disconnecting battery cables always remove the NEGA-  
TIVE (-) cable first. When reconnecting the cables, connect the POSITIVE (+) cable first.  
Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may  
result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.  
2
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety  
1.4 — Exhaust Hazards  
Generator engine exhaust contains DEADLY carbon monoxide, an odorless, colorless, poisonous gas. Breathing  
carbon monoxide can cause dizziness, throbbing temples, nausea, muscular twitching, headache, vomiting,  
weakness, sleepiness, inability to think clearly, fainting, unconsciousness or even death. If any carbon monoxide  
poisoning symptom is experienced, move into fresh air and immediately seek medical attention.  
This generator is designed for OUTDOOR installation ONLY. Never operate the generator inside any garage or  
other enclosed space.  
1.5 — Electrical Hazards  
All generators covered by this manual produce dangerous electrical voltages that can cause fatal electrical  
shock. Utility power delivers extremely high and dangerous voltages to the transfer switch, as does the standby  
generator when it is in operation. Avoid contact with bare wires, terminals, connections, etc. while the unit is run-  
ning. Ensure all appropriate covers, guards and barriers are in place, secured and/or locked before operating the  
generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce potential  
shock hazard.  
Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet.  
DANGEROUS ELECTRICAL SHOCK MAY RESULT.  
The generator may crank and start at any time when utility power is lost. When this occurs, load circuits are  
transferred to the STANDBY (generator) power source. Before working on the generator, always move the Main  
Circuit Breaker switch on the control panel down to the OFF (Open) position, press the OFF key on the control  
panel keypad, remove the 7.5 amp fuse, and disconnect the battery negative cable (black) from the battery neg-  
ative (-) terminal.  
In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not  
possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use  
a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is  
unconscious, apply first aid and get immediate medical help.  
Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock,  
or may get caught in moving parts resulting in injury.  
1.6 — Fire Hazards  
For fire safety, the generator must be installed and maintained properly. Installation MUST always comply with  
applicable codes, standards, laws, regulations and product Installation Manual guidelines. Adhere strictly to  
local, state, and national electrical and building codes. Comply with regulations of the Occupational Safety and  
Health Administration (OSHA). Also, ensure that the generator is installed in accordance with the manufacturer’s  
instructions and recommendations. Following proper installation, do nothing that might alter a safe installation  
and render the unit in noncompliance with the aforementioned codes, standards, laws and regulations.  
Keep a fire extinguisher near the generator at all times. Extinguishers rated “ABC” by the National Fire Protection  
Association are appropriate for use on the standby generator. Keep the extinguisher properly charged and be  
familiar with its use. Consult the local fire department with any questions pertaining to fire extinguishers.  
1.7 — Explosion Hazards  
Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible mate-  
rials are left in the generator compartment, or on or near the generator as FIRE or EXPLOSION may result. Keep  
the area surrounding the generator clean and free from debris.  
If this generator is used to power electrical load circuits normally powered by a utility power source,  
it is required by code to install a transfer switch. The transfer switch must effectively isolate the elec-  
+
trical system from the utility distribution system when the generator is operating (NEC 702). Failure to  
isolate an electrical system by such means will result in damage to the generator and also may result  
in injury or death to utility power workers due to backfeed of electrical energy.  
Owner’s Manual for Stationary Diesel Generators  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety  
This page intentionally left blank.  
4
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
Specifications  
2.1 — Emission Information  
The U.S. Environmental Protection Agency (EPA) requires that the generator comply with exhaust emission standards.  
The generator is certified to meet the applicable EPA emission levels, and is certified for use as a stationary engine for  
standby power generation. Any other use may be a violation of federal and/or local laws. To ensure that the engine  
complies with the applicable emission standards for the duration of the engine’s life, it is important to follow the mainte-  
nance specifications in Section 5. This generator is certified to operate on Diesel Fuel No. 2 (KSM2610).  
2.1.1— Emissions Data Plate  
A data plate is riveted to the cylinder head cover to verify compliance with EPA emissions regulations.  
Cylinder Head Cover  
Figure 2-1. Emissions Data Plate (Sample)  
Owner’s Manual for Stationary Diesel Generators  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
2.2 — Specifications  
2.2.1— Engine  
General  
2.3L Engine  
2.4L-49 Engine  
3.4L Engine  
Engine System  
Type  
4 cylinder, in-line, 4 cycle  
Ultra Low Sulfur Diesel  
5 Microns  
4 cylinder, in-line, 4 cycle  
Ultra Low Sulfur Diesel  
5 Microns  
4 cylinder, in-line, 4 cycle  
Ultra Low Sulfur Diesel  
10 Microns  
Fuel Type  
Fuel Filtering  
3.46 in x 3.70 in  
(88 mm x 94 mm)  
3.54 in x 3.70 in  
(90 mm x 94 mm)  
3.86 in x 4.45 in  
(98 mm x 113 mm)  
Bore and Stroke  
Displacement  
139.5 cubic inches (2.286 liter)  
1-3-4-2  
146 cubic inches (2.392 liter)  
1-3-4-2  
208.3 cubic inches (3.41 liter)  
1-3-4-2  
Firing Order  
Direction or Rotation  
CCW - As Viewed From Flywheel  
CCW - As Viewed From Flywheel  
CCW - As Viewed From Flywheel  
685 x 491 x 636 mm  
(26.97 in x 19.33 in x 25.04 in)  
677.1 x 497.8 x 721.3 mm  
(26.66 in x 19.60 in x 28.40 in)  
742 x 587 x 721 mm  
(29.21 in x 23.11 in x 28.39 in)  
Dimensions L x W x H  
Dry Weight  
441 lbs (200 kgs)  
21.3 : 1  
573 lbs (260 kgs)  
21.3 : 1  
551 lbs (250 kgs)  
18.5 : 1  
Compression Ratio  
Cooling System  
Water Pump  
Drive  
Pre-Lubed, Self-Sealing  
Belt  
Pre-Lubed, Self-Sealing  
Belt  
Pre-Lubed, Self-Sealing  
Belt  
Full Open Temperature:  
185° F (85° C)  
Full Open Temperature:  
185° F (85° C)  
Full Open Temperature:  
185° F (85° C)  
Thermostat  
System Coolant Capacity  
Coolant Flow Rate  
Lubricating System  
Oil Pump Type  
2.8 gal (10.6 liter)  
2.8 gal (10.6 liter)  
2.8 gal (10.6 liter)  
10 gal (38 liter)/min at 1800 RPM  
10 gal (38 liter)/min at 1800 RPM  
12.2 gal (46 liter)/min at 1800 RPM  
Gear  
Gear  
Gear  
Oil Filter Type  
Full Flow Spin-On Canister  
Not Applicable  
6.87 qt. (6.5 liter)  
15W-40  
Full Flow Spin-On Canister  
Installed  
Full Flow Spin-On Canister  
Installed  
Oil Cooler  
Crankcase Capacity  
Lubricating Oil  
6.8 qt. (6.4 liter)  
15W-40  
7.4 qt. (7.0 liter)  
15W-40  
Oil Fill Location  
Filler Cap on Valve Cover and/or  
Front Engine Cover  
Filler Cap on Valve Cover and/or  
Front Engine Cover  
Filler Cap on Valve Cover and/or  
Front Engine Cover  
Oil Drain Location  
Oil Pan, Bottom Side  
Oil Pan, Bottom Side  
Oil Pan, Front  
Intake and Exhaust System  
Intake Air System  
Naturally Aspirated  
Turbocharged  
Turbocharged/Aftercooled  
25 in. of Water (6.23 kPa)  
Maximum Allowable  
Intake Restriction  
25 in. of Water (6.23 kPa)  
25 in. of Water (6.23 kPa)  
Maximum Allowable  
Exhaust Back Pressure  
23.6 in. of Water (5.88 kPa)  
Closed Crankcase System  
23.6 in. of Water (5.88 kPa)  
Open Crankcase System  
24 in of Water (5.98 kPa)  
Open Crankcase System  
Breather  
Other Specifications  
Operating Temperature Range  
-20° F to 120° F (-29° C to 49° C)  
-20° F to 120° F (-29° C to 49° C)  
-20° F to 120° F (-29° C to 49° C)  
POWER ADJUSTMENT FOR AMBIENT CONDITIONS  
Temperature Deration........................................................................................3% for every 5 °C above 25 °C or 1.7% for every 5 °F above 77 °F  
Altitude Deration (15, 30, 48 & 50 kW)...................................................... 1% for every 100 m above 915 m or 3% for every 1000 ft above 3000 ft  
Altitude Deration (20 kW) ......................................................................... 1% for every 100 m above 305 m or 3% for every 1000 ft above 1000 ft  
A complete specification sheet is included in the documentation provided with the unit at the time of purchase. For  
additional copies, consult your local Authorized Service Dealer.  
6
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
2.3 — Engine Oil Recommendations  
To maintain the product warranty, use only genuine Generac replacement parts. Generac maintenance kits include  
both the oil filter and air filter, and can be obtained through any Authorized Dealer.  
All Generac maintenance kits meet minimum American Petroleum Institute (API) Service Class CD or better. Select the  
appropriate viscosity oil grade according to the expected operating temperature. After break-in, synthetic oil also can  
be used in the appropriate weight as standard. Once synthetic oil is used, it should be used for the life of the generator.  
It is not recommended to go back to a mineral oil. Do not use special additives.  
º C  
º F  
- 30 - 20 - 10  
- 22 - 4 14  
0
32  
10  
50  
20  
68  
30  
40  
50  
- 40  
- 40  
86 104 122  
15W-40  
All Seasons  
10W-30  
5W-30  
Winter Conditions  
Arctic Conditions  
º C  
º F  
- 30 - 20 - 10  
- 22 - 4 14  
0
32  
10  
50  
20  
68  
30  
40  
50  
- 40  
- 40  
86 104 122  
Figure 2-2. Lubricating Oil Recommendations  
2.4 — Coolant Water Treatment  
Use of improper coolants can damage the engine cooling system. Use demineralized water or distilled water for best  
results. Hard water causes scale deposits, which reduces cooling efficiency and raises internal temperatures, possibly  
leading to engine damage. Use an anti-corrosive to prevent rot in summer and anti-freeze to prevent freezing in winter.  
Dilute the anti-freeze based on a theoretical temperature that is 9-18°F (5-10°C) below the lowest temperature  
expected in the area. A ratio of 40-60% is most common range.  
Freezing Point °F (°C)  
Coolant (% Volume)  
Water (% Volume)  
-13 (-25)  
40  
-31 (-35)  
50  
-58 (-50)  
60  
60  
50  
40  
NOTE: Use only Peak Fleet-Charge® 50/50 ethylene glycol type coolant (available from any authorized  
dealer).  
Do not use propylene glycol type coolant. Using the wrong coolant, mixing different types of coolant,  
or even mixing different brands of the correct type of coolant, can produce unsatisfactory results, pos-  
sibly leading to engine damage.  
*
2.5 — Fuel Requirements  
IMPORTANT! DO NOT use Home Heating Oil or Bio-Diesel Fuel.  
Use No. 2D diesel fuel when temperatures are above freezing. When temperatures are below freezing, blend No.1D  
diesel fuel and No. 2D diesel fuel together for a climate adjusted fuel ratio.  
Starting October 1, 2010, diesel fuel must also meet the following requirements:  
Sulfur content of 15 parts per million (ppm) maximum.  
Minimum Cetane index of 40.  
Owner’s Manual for Stationary Diesel Generators  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
NOTE: Low ambient temperatures as well as engine operation at high altitudes may require the use of fuels  
with higher Cetane ratings.  
Allow at least 5 percent of the tank capacity for fuel expansion. DO NOT OVERFILL!  
2.5.1— Fuel Maintenance  
Always treat diesel fuel for long term storage. Use the approved fuel additive and water abatement material. Test  
stored fuel every 90 days and provide additional treatment if required. Periodically check and dry abatement material  
as necessary.  
2.5.2— Fuel Maintenance  
Always treat diesel fuel for long term storage. Use the approved fuel additive and water abatement material. Test  
stored fuel every 90 days and provide additional treatment if required. Periodically check and dry abatement material  
as necessary.  
2.6 — Battery Requirements  
Group 27F, 12 Volt  
2.3L Engine: For areas where temperatures regularly drop below 32° F (0° C).  
NOTE: Battery dimensions (L x W x H) for Group 27F battery must not exceed 12-1/2" x 6-13/16" x 8-15/16"  
(318 mm x 173 mm x 227 mm).  
Group 31, 12 Volt  
2.4L-49 Engine: For areas where temperatures regularly drop below 32° F (0° C).  
NOTE: Battery dimensions (L x W x H) for Group 31 battery must not exceed 13" x 6-13/16" x 9-7/16"  
(330 mm x 173 mm x 240 mm).  
2.6.1— Battery Charger  
The battery charger is integrated into the control panel module. It operates as a “Smart Charger” which ensures output  
charging levels are safe and continuously optimized to promote maximum battery life.  
2.7 — Corrosion Protection  
Periodically wash and wax the enclosure using automotive type products. Frequent washing is recommended in salt  
water/coastal areas.  
2.8 — Accessories  
The following product accessories are available. Contact a Dealer for additional information.  
1. Scheduled Maintenance Kit (Part No. 006572-0; 15/20 kW)  
2. Scheduled Maintenance Kit (Part No. 006571-0; 30 kW)  
3. Scheduled Maintenance Kit (Part No. 006570-0; 50 kW)  
8. Emergency Stop Switch (Part No. 006510-0)  
9. Touch-Up Paint Kit (Part No. 005704-0)  
10. Five Gallon Spill Box (Part No. 006502-0)  
4. Cold Weather Kit (Part No. 006560-0: 15/20 kW; Part No.  
006559-0: 30 kW; Part No. 006558-0: 50 kW)  
11. Fuel Tank Risers (Part No. 006505-0: 15/20 kW; Part  
No. 006506-0: 30/50 kW)  
5. Vent Extension Support Kit (Part No. 006588-1)  
6. Fuel Fill Drop Tube (Part No. 006507-0)  
7. Lockable Fuel Fill Cap (Part No. 006512-0)  
12. 90% Fuel Fill Level Alarm (Part No. 006504-0)  
13. Spill Box Drain Back (Part No. 006511-0)  
14. Stainless Steel Fuel Lines (Part No. 006513-0:15/20 kW;  
Part No. 006517-0: 30 kW; Part No. 006516-0:  
50 kW)  
8
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
1.  
2.  
3.  
5.  
6.  
4.  
7.  
8.  
9.  
10.  
11.  
12.  
13.  
14.  
Figure 2-3. Product Accessories  
Owner’s Manual for Stationary Diesel Generators  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
This page intentionally left blank.  
10  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
Activation and Startup  
IMPORTANT NOTE: The unit fuel tank has been inspected by AHJ (authority having local jurisdiction) or fire  
marshal and meets all requirements. Unit is fueled and the fuel is treated as per additive directions.  
3.1 — Orientation  
NOTE: The 3.4L engine is depicted in the artwork used in this manual. The location and appearance of some  
components may vary between engine models.  
The side of the enclosure with the viewing window is identified as the rear of the generator set. The right and left sides  
are identified by standing at the rear and looking towards the front of the unit.  
Fuel Priming  
Pump  
Viewing  
Window  
Battery  
Figure 3-1. Enclosure (Rear Left View)  
3.2 — Remove Side Access Panels  
NOTE: Access panels are located at both the front and sides of the enclosure.  
1. Insert key into latch and rotate counterclockwise 1/2 turn. See Figure 3-2.  
2. Raise panel using thumb latch.  
Key  
Thumb Latch  
Figure 3-2. Access Panel Key  
Owner’s Manual for Stationary Diesel Generators  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Activation and Startup  
3.3 — Prime Fuel System  
1. See Figure 3-3. Loosen the air bleed screw and work priming pump until bubbles are observed. Place a shop rag  
around the air bleed screw to catch any loss of fuel.  
2. When all bubbles are purged and replaced by a solid stream of fuel, tighten the air bleed screw.  
3. Check for leaks.  
Priming  
Pump  
Air Bleed  
Screw  
Figure 3-3. Prime Fuel System  
3.4 — Install Battery  
CAUTION: Always connect the positive battery  
$
cable first. If the positive cable should contact  
ground with the negative cable installed, the result-  
ing sparks may cause a battery explosion which  
could result in serious injury.  
2.4L/3.4L Models  
NOTE: On 2.3L models, remove ten screws to release lou-  
vered air intake panel on left side of enclosure.  
1. Loosen two screws with nylon washers to release hold-  
down clamp from battery tray.  
2. Install battery onto tray.  
3. Install two screws with nylon washers to secure hold-  
Red Lead  
From Starter  
down clamp to battery tray.  
4. Install battery positive cable (red) to battery positive (+)  
terminal.  
5. Install battery negative cable (black) to battery negative  
(-) terminal.  
NOTE: On 2.3L models, start ten screws to install louvered  
air intake panel. Alternately tighten screws to 90 in-lbs (10  
N-m) using a crosswise pattern.  
Black Lead  
To Frame  
Battery  
Figure 3-4. Battery Cable Connections  
12  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Activation and Startup  
3.5 — Open Viewing Window  
1. Rotate viewing window upward to access control panel.  
2. To hold viewing window in the open position, remove rod  
from clip at back of window and insert into hole in frame.  
See Figure 3-5.  
Figure 3-5. Viewing Window  
3.6 — Start and Run Engine  
1. Pull up rubber flap covering fuse holder and verify installation of 7.5 amp fuse. See A of Figure 3-6.  
2. Move the Main Circuit Breaker switch down to the OFF (Open) position. See B of Figure 3-6.  
3. Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the  
MANUAL mode. See C of Figure 3-6.  
4. Allow the engine to run until it reaches normal operating temperature.  
5. Press OFF on the control pad to stop the engine. A red LED illuminates to confirm that the system is in the OFF  
mode.  
7.5 Amp Fuse  
and USB Port  
A
B
LCD Screen  
o
OFF  
PUSH TO TRIP  
Main Circuit Breaker  
Control Pad  
C
Figure 3-6. Generator Control Panel  
Owner’s Manual for Stationary Diesel Generators  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Activation and Startup  
3.7 — Activate Unit  
Display Reads:  
Generator Active is displayed on the  
LCD screen when the unit is first  
powered up. After displaying firmware  
and hardware version codes, as well as  
other system information, the Installation  
Wizard is launched, and the Language  
screen is displayed.  
If the wrong language is selected, it may be changed  
later using the Edit menu.  
Up Arrow = (+)  
Language  
-
English  
+
Use UP ARROW or DOWN ARROW to  
scroll to desired language.  
Press ENTER.  
Down Arrow = (-)  
Display Reads:  
Press ENTER.  
Press ESCAPE to abort the activation sequence. NOT  
ACTIVATED is displayed and the generator will run in  
manual mode only. Disconnect and reconnect the  
negative battery cable to restart the activation routine.  
If power is removed after a successful activation, no  
data is lost, but the time and date must be updated.  
Activate me (ENT) or  
ESC to run in manual  
888-9ACTIVATE (922-8482, US & CA  
only) if activation passcode is not avail-  
able.  
Display Reads:  
To Activate go to  
If activation pass code is available, wait a  
few seconds for the next display.  
Display Reads:  
Use UP ARROW or DOWN ARROW to  
increment or decrement the digit to  
correspond to the first number of the  
pass code.  
Press ESCAPE to return to preceding digits if a  
correction becomes necessary.  
SN 1234567890  
If attempts to enter the activation code are  
PASS CODE XXXXX  
unsuccessful, check the number against the code  
given on activategen.com. If it is correct, contact 1-888-  
9ACTIVATE (922-8482, US & CA only).  
Press ENTER.  
Repeat step to enter remaining digits.  
Display Reads:  
Use UP ARROW or DOWN ARROW to  
increment or decrement the hour. Press  
ENTER.  
Select Hour (0-23)  
- 6 +  
Use UP ARROW or DOWN ARROW to  
increment or decrement the minute.  
Press ENTER.  
Use UP ARROW or DOWN ARROW to  
select the month. Press ENTER.  
Use UP ARROW or DOWN ARROW to  
increment or decrement the date. Press  
ENTER.  
Use UP ARROW or DOWN ARROW to  
increment or decrement the year. Press  
ENTER.  
14  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Activation and Startup  
Display Reads:  
Use UP ARROW or DOWN ARROW to  
select either Yes or No.  
Select YES to perform exercise at low speed. Select  
NO to perform exercise at normal operating speed.  
Quite Test Mode?  
Yes No  
Press ENTER.  
Display Reads:  
Set Exercise Time.  
In the AUTO mode, the engine starts and runs once  
each week at the time and day specified. During the  
exercise cycle, the unit runs approximately 12 minutes  
and then shuts down. Transfer of loads to the generator  
does not occur unless utility power fails.  
Use UP ARROW or DOWN ARROW to  
increment or decrement the hour. Press  
ENTER.  
Select Hour (0-23)  
- 1 +  
Use UP ARROW or DOWN ARROW to  
increment or decrement the minute.  
Press ENTER.  
Use UP ARROW or DOWN ARROW to  
scroll to the day of the week. Press  
ENTER.  
3.8 — Operational Checks  
The following procedures require special tools and skills. Contact a Generac Dealer or an authorized  
service provider to perform these tasks.  
+
3.8.1— Self Test  
Upon power up, the controller goes through a system self test which checks for the presence of utility voltage on the  
DC circuits. This is done to prevent damage if the installer mistakenly connects AC utility power sense wires into the  
DC terminal block. If utility voltage is detected, the controller displays a warning message and locks out the generator,  
thereby preventing damage to the controller. Remove power to the controller to clear this warning.  
Utility voltage must be turned on and present at the N1 and N2 terminals inside the generator control panel for this test  
to be performed and pass.  
Before starting, complete the following:  
1. Verify that the generator is OFF. A red LED on the control pad illuminates to confirm that the system is in the OFF  
mode.  
2. Verify that the Main Circuit Breaker switch on the generator control panel is in the OFF (Open) position.  
3. Turn off all circuit breakers/electrical loads that will be powered by the generator.  
4. Check the fuel level, coolant level, and engine lubricating oil level. See Subsections 5.7.2, 5.7.4, and 5.7.6,  
respectively.  
During initial start up only, the generator may exceed the normal number of start attempts and experience an “over  
crank” fault. This is due to accumulated air in the fuel system during installation. Reset the control board and restart up  
to two more times, if necessary. If unit fails to start, contact the local dealer for assistance.  
3.8.2— Check Manual Transfer Switch Operation  
Refer to the manufacturer’s instructions.  
Do not attempt manual transfer switch operation until all power voltage supplies to the transfer switch  
have been positively turned off. Failure to turn off all power voltage supplies will result in extremely  
hazardous and possibly fatal electrical shock.  
+
Owner’s Manual for Stationary Diesel Generators  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Activation and Startup  
3.8.3— Electrical Checks  
Complete electrical checks as follows:  
1. Verify that the generator is OFF. A red LED on the control pad illuminates to confirm that the system is in the OFF  
mode.  
2. Verify that the Main Circuit Breaker switch on the generator control panel is in the OFF (Open) position.  
3. Turn OFF all circuit breakers/electrical loads that will be powered by the generator.  
4. Turn on the utility power supply to the transfer switch using the means provided (such as a utility main line circuit  
breaker).  
The transfer switch is now electrically “hot.” Contact with “hot” parts will result in extremely hazard-  
ous and possibly fatal electrical shock.  
+
5. Use an accurate AC voltmeter to check utility power source voltage across transfer switch terminals N1, N2, and  
N3 (if three phase). Normal line-to-line voltage should be equivalent to rated unit voltage.  
6. Check utility power source voltage across terminals N1, N2, and N3 (if three phase) and the transfer switch neu-  
tral lug.  
7. When certain that utility supply voltage is compatible with transfer switch and load circuit ratings, turn OFF the  
utility power supply to the transfer switch.  
8. Press MANUAL on the control pad to crank and start the engine.  
9. Allow the engine to warm up for about five minutes. Move the Main Circuit Breaker switch on the generator con-  
trol panel up to the ON (or closed) position.  
Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts  
will result in dangerous and possibly fatal electrical shock.  
+
10. Connect an accurate AC voltmeter and a frequency meter across transfer switch terminal lugs E1, E2, and E3 (if  
three phase).  
11. Successively connect the AC voltmeter test leads across terminal lugs E1, E2, and E3 (if three phase) and neu-  
tral; then across E2 and neutral. Voltage reading in each case should match utility voltage reading. If system is  
three phase, verify that generator phase rotation matches utility phase rotation.  
12. Move the Main Circuit Breaker switch on the generator control panel down to the OFF (Open) position.  
13. Press OFF on the control pad to shut the engine down.  
Do not proceed unless certain that generator AC voltage and frequency are correct and within the  
stated limits.  
+
3.8.4— Test Generator Under Load  
To test the generator set with electrical loads applied, proceed as follows:  
1. Verify that the generator is OFF. A red LED on the control pad illuminates to confirm that the system is in the OFF  
mode.  
2. Turn OFF all breakers/electrical loads that will be powered by the generator.  
3. Turn OFF the utility power supply to the transfer switch, using the means provided (such as a utility main line cir-  
cuit breaker).  
Do not attempt manual transfer switch operation until all power voltage supplies to the transfer switch  
have been positively turned off. Failure to turn off all power voltage supplies will result in extremely  
hazardous and possibly fatal electrical shock.  
+
4. Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator’s E1,  
E2, and E3 (if three phase) terminals.  
16  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Activation and Startup  
5. Press MANUAL on the control pad. The engine will crank and start.  
6. Allow the engine to warm up for a few minutes.  
7. Move the Main Circuit Breaker switch on the generator control panel up to the ON (or closed) position. The  
switch is now powered by the standby generator.  
8. Turn ON the circuit breaker/electrical loads powered by the generator.  
9. Connect a calibrated AC voltmeter and a frequency meter across terminal lugs E1, E2, and E3 (if three phase).  
Voltage should be approximately unit rated voltage. Check with clamp on amp meter to ensure unit is not over-  
loaded.  
10. Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications  
of abnormal operation. Check for oil leaks, evidence of overheating, etc.  
11. When testing under load is complete, turn OFF electrical loads.  
12. Move the Main Circuit Breaker switch on the generator control panel up to the OFF (or open) position.  
13. Allow the engine to run at no-load for 2-5 minutes.  
14. Press OFF on the control pad to shut the engine down. A red LED illuminates to confirm that the system is in the  
OFF mode.  
3.8.5— Check Automatic Operation  
To check the system for proper automatic operation, proceed as follows:  
1. Verify that the generator is OFF. A red LED on the control pad illuminates to confirm that the system is in the OFF  
mode.  
2. Install front cover of the transfer switch.  
3. Turn ON the utility power supply to the transfer switch, using the means provided (such as a utility main line cir-  
cuit breaker).  
NOTE: Transfer Switch will transfer back to utility position.  
4. Move the Main Circuit Breaker switch on the generator control panel up to the ON (or closed) position.  
5. Press AUTO on the control pad. The system is now ready for automatic operation.  
6. Turn OFF the utility power supply to the transfer switch.  
With the generator ready for automatic operation, the engine will crank and start when the utility source power is turned  
OFF after a 10 second delay (factory default setting). After starting, the transfer switch connects load circuits to the  
standby side. Let the system operate through its entire automatic sequence of operation.  
With the generator running and loads powered by generator AC output, turn ON the utility power supply to the transfer  
switch. The system transfers back to the utility position and then runs through the cool down cycle and shuts down.  
3.9 — Final Instructions  
1. Use key to install side access panels.  
2. Close viewing window.  
NOTE: Obtain viewing window hasp, if not installed. See  
Figure 3-7. With the retaining tab at the bottom, insert  
square end of hasp into slot below viewing window.  
Push on hasp until it snaps in place. Gently pull on hasp  
to verify that it will not come free.  
3. Install customer supplied padlock into hasp.  
Figure 3-7. Install Viewing Window Hasp  
Owner’s Manual for Stationary Diesel Generators  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Activation and Startup  
This page intentionally left blank.  
18  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4  
Operation  
4.1 — Control Panel  
NOTE: The control panel is intended for use by qualified service personnel only.  
The control panel is located behind the viewing window at the rear of the unit.  
With the control pad set to AUTO, the engine may crank and start at any time without warning. Such  
*
automatic starting occurs during the programmed exercise cycle or when utility power source voltage  
drops below the configured level. To prevent possible injury that might occur during sudden starts,  
always set the control pad to OFF and remove the 7.5 amp fuse before working on or around the gener-  
ator or transfer switch. For added security, place a DO NOT OPERATE tag or placard on both the con-  
trol panel and transfer switch.  
7.5 Amp Fuse  
and USB Port  
LCD Screen  
o
OFF  
PUSH TO TRIP  
AUTO  
MANUAL  
OFF  
Main Circuit Breaker  
ENTER  
Control Pad  
ESCAPE  
Figure 4-1. Generator Control Panel  
4.2 — Auto/Manual/Off  
Feature  
Description  
Press to activate fully automatic operation. Green LED illuminates to confirm that system is in AUTO mode.  
Transfer to standby power occurs if utility power fails.  
AUTO  
Functionality of exercise timer is enabled, if set.  
Press to crank and start engine. Blue LED illuminates to confirm that system is in MANUAL mode.  
Transfer to standby power occurs if utility power fails.  
Functionality of exercise timer is disabled.  
MANUAL  
OFF  
Press to shut down engine, if running. Red LED illuminates to confirm that system is in OFF mode.  
Transfer to standby power does not occur if utility power fails.  
Owner’s Manual for Stationary Diesel Generators  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
LCD Screen  
UP ARROW  
Green  
LED  
Blue  
LED  
Red  
LED  
ENTER  
AUTO  
MANUAL  
OFF  
DOWN ARROW  
ESCAPE  
Figure 4-2. Control Pad and LCD Screen  
4.3 — Menu Navigation  
See Figure 4-3.  
Feature  
Description  
System Menus  
The system returns to the Home screen if the control pad is not used for five minutes. The screen normally  
displays a Status message, such as Ready to Run (Auto mode) or Switched to OFF (Off mode), and the  
total Hours of Protection. If an active alarm/warning condition occurs, the associated Alarm/Warning mes-  
sage is displayed. To clear the Alarm/Warning message, press OFF on the control pad followed by ENTER.  
In the event of multiple Alarms/Warnings, the next message is then displayed. The highest priority alarm is  
always displayed first.  
HOME Screen  
MAIN MENU  
Enables the operator to navigate the software using UP ARROW, DOWN ARROW, ENTER and ESCAPE.  
The Main Menu can be accessed from any sub menu by consecutively pressing ESCAPE. Each time  
ESCAPE is pressed, the preceding menu is displayed. The Main Menu is reached when the System,  
Date/Time, Battery, and Sub Menus are displayed.  
Navigation  
Used to abort a routine or back up to the preceding menu.  
Used to make a selection or save an entry.  
ESCAPE  
ENTER  
UP ARROW  
DOWN ARROW  
Used to move forward or backward from menu to menu or to scroll forward or backward (increment or dec-  
rement) through available selections.  
NOTE: Pressing the control pad illuminates the backlight for 30 seconds. The backlight also illuminates for 30 seconds when-  
ever an active Alarm/Warning message is displayed.  
20  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Switched to “OFF”  
Hours of Protection  
0 (H)  
Home Screen  
Up Arrow = (+)  
Current Date/Time  
02/14/13 07:40  
ESC  
Running Manual  
Running-Utility Lost  
Running-Remote Start  
Running-2 Wire Start  
Running - Exercise  
Switched Off  
ESC  
ENTER  
SYSTEM  
DATE/TIME  
Down Arrow = (-)  
ENTER  
Run Hours (H)  
Battery Condition  
ENTER  
ESC  
BATTERY  
SUB MENUS  
0.0  
Stopped - Auto  
Stopped - Alarm  
“Good” “Inspect Battery” or “Check Battery”  
Main Menu  
ESC  
ENTER  
ENTER  
ESC  
ENTER  
ENTER  
MAINT:  
Run Hrs  
-
-
1 thru 50  
1 thru 50  
+
+
-
Run Log  
+
“Run Log”  
ESC  
ENTER  
HISTORY  
MAINT  
ESC  
ESC  
ENTER  
ESC  
“Alarm Log”  
-
Alarm Log  
+
Maint. Log  
Scheduled  
ENTER  
ENTER  
WARNING MESSAGE(S)  
"Low Battery"  
EDIT  
DEALER  
Access Requires Password  
ENTER  
ESC  
ENTER  
ESC  
"Exercise Set Error"  
"FIRMWARE ERROR-9"  
“Schedule A Maint”  
“Schedule B Maint”  
“Schedule C Maint”  
"Battery Problem"  
"Charger Warning"  
"Charger Missing AC"  
"Overload Warning"  
"Overload Cooldown"  
"SEEPROM ABUSE"  
"USB Warning"  
ENTER  
-
1 thru 50  
+
"Schedule A Serviced"  
"Schedule B Serviced"  
"Schedule C Serviced"  
"Maintenance Reset"  
"Service Schedule A"  
"Service Schedule B"  
"Service Schedule C"  
EXAMPLE:  
“Inspect Battery 200 RnHr or 12/27/13”  
“Service Schedule A, B or C”  
Language  
English  
Language  
Language  
Espanol  
Language  
Francais  
Language  
+
+
-
+
-
+
ESC  
ESC  
“Next Maintenance 200 RnHr or 12/27/13”  
Å
Æ
+
English  
-
+
-
+
-
+
Portuguese  
-
-
"Download Failure"  
"Low Fuel (20%)"  
"Stopping…"  
ESC  
ESC  
ESC  
ESC  
ESC  
ENTER  
Current Date/Time  
Select Hour (0-23)  
Select Min (0-59)  
Select Month (1-12)  
Select Date (1-31)  
Select Year (0-99)  
ENTER  
ENTER  
ENTER  
ENTER  
ENTER  
ENTER  
ALARM MESSAGE(S)*  
"High Engine Temp."  
"Low Oil Pressure"  
"Overcrank"  
"Overspeed"  
"RPM Sense Loss"  
"Underspeed"  
“Controller Fault"  
"Ignition Fault Code"  
"WIRING ERROR"  
"Over Voltage"  
"Under Voltage"  
"Overload Remove Load"  
"Canbus Error"  
Å
9/12/13 12:22  
Æ
-
14  
+
-
0
+
-
2
+
-
13  
+
-
13  
+
ESC  
ESC  
ESC  
ESC  
Exercise Time  
Quiet Test Mode ?  
Select Hour (0-23)  
Select Min (0-59)  
Select Day  
Wednesday  
ENTER  
ENTER  
ENTER  
ENTER  
ESC  
Å
14:00 Wednesday  
Æ
-
YES or NO  
+
-
14  
+
-
0
+
-
+
*NOTE: Any key other than Enter will  
force you out of Firmware Update  
Select “Yes” then Press “Enter” to continue or Press  
“ESCAPE” to escape out of updating.  
Possible Message(s)  
Corrupted File  
Firmware Update  
"Are You Sure?"  
"- Yes or No +"  
ENTER  
ENTER  
Firmware Update*  
"Main V XXX To V XXX "  
"GUI V XXX To XXX"  
When the controller powers up the very first screen  
displays the version number for a few seconds.  
"Governor Fault"  
"Missing Cam Pulse"  
"Missing Crank Pulse"  
"Ruptured Tank"  
"Low Fuel (10%)"  
"E-Stop"  
Invalid File  
ESC  
Å
Insert USB  
Æ
ESC  
Å
Press Enter  
Æ
File Not Found  
Unsupported Device  
Controller Fault  
When update is complete remove Thumb Drive, then  
follow the Install Wizard Menu.  
Å
2-1500  
Æ
Start up Delay (sec)  
Warmup Time (sec)  
ESC  
ESC  
Default: 10s  
2.3L & 2.4L Units Only  
"Fuse Problem"  
-
5-30  
+
*Note: E-Codes Not Shown  
Pre Heat  
Å
5-1500  
Æ
Default: 5s  
Default: 5s  
ESC  
Figure 4-3. Navigation Menu  
Owner’s Manual for Stationary Diesel Generators  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
4.4 — Alarm/Warning Conditions  
The owner/operator is alerted to Alarm and/or Warning conditions via the control panel LCD screen. All Alarm condi-  
tions cause the generator to shut down. The Warning messages alert the operator to conditions that do not disable the  
unit or require immediate correction.  
The possible Alarm/Warning messages are listed below.  
Alarm Messages  
Warning Messages  
High Engine Temperature  
Low Oil Pressure  
Overcrank  
Low Battery  
Exercise Set Error  
FIRMWARE ERROR-9  
Schedule A Maintenance  
Schedule B Maintenance  
Schedule C Maintenance  
Battery Problem  
Overspeed  
RPM Sense Loss  
Underspeed  
Controller Fault  
Ignition Fault Code  
WIRING ERROR  
Over Voltage  
Charger Warning  
Charger Missing AC  
Overload Warning  
Overload Cooldown  
SEEPROM ABUSE  
USB Warning  
Under Voltage  
Overload Remove Load  
Canbus Error  
Governor Fault  
Missing Cam Pulse  
Missing Crank Pulse  
Ruptured Tank  
Low Fuel (10%)  
E-Stop  
Download Failure  
Low Fuel (20%)  
Stopping…  
Fuse Problem  
NOTE: Unless properly trained to correct and clear Alarm/Warning conditions, contact an Authorized Dealer or trained  
service technician.  
4.5 — Change Time and Date  
To change the time and date after activation, see the Navigation Menu in Figure 4-3. If power is lost (battery is discon-  
nected/reconnected, control panel fuse is removed/installed, etc.), the display automatically prompts the user for the  
Time and Date. All other information is retained in memory.  
4.6 — Programmable Timers  
4.6.1— Dealer Programmable  
4.6.1.1—Exercise Time  
A programmable exercise time is provided. In the AUTO mode, the engine starts and runs once each week at the time  
and day specified. During the exercise cycle, the unit runs approximately 12 minutes and then shuts down. Transfer of  
loads to the generator does not occur unless utility power fails.  
NOTE: A Dealer password is required to change the Exercise time.  
22  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
4.6.2— User Programmable  
4.6.2.1—Start-Up Delay Timer  
A programmable line interrupt delay (or Start-Up Delay) timer is provided. When utility voltage fails (falls below 60% of  
nominal), the start-up delay timer is started. If the voltage rises above the Utility Volts Low threshold, the timer is reset.  
If the utility voltage remains below the threshold during the duration of the timer, the unit cranks and starts.  
NOTE: The factory default setting is five seconds, but is adjustable from 2 to 1500 seconds.  
4.6.2.2—Warm-Up Delay Timer  
A programmable Warm-Up Delay timer is provided. As soon as the generator starts, the warm-up timer is started.  
When the warm-up timer expires, the control transfers load to the generator (through the transfer switch) if the utility  
voltage is less than 80% of nominal. If utility voltage is greater than the threshold at expiration of the warm-up time, the  
load is not transferred to the generator and a cool-down period begins. At the end of the cool-down period, the gener-  
ator stops.  
NOTE: The factory default setting is five seconds, but is adjustable from 5 to 1500 seconds.  
4.7 — USB Port for Firmware Updates  
A USB port is located beneath the rubber flap on the control panel, and is provided for firmware updates. Firmware  
updates must be performed by an Authorized Service Dealer.  
NOTE: The USB port is intended for use with a USB thumb drive only. The USB port is not intended for charging  
devices such as phones or laptops. Do not connect any consumer electronics to the USB port.  
4.8 — Battery Charger  
NOTE: The battery charger is integrated into the control panel module.  
The battery charger ensures:  
Output is continually optimized to promote maximum battery life.  
Charging levels are safe.  
NOTE: A warning message is displayed on the LCD screen when the battery requires service.  
4.9 — Transfer Switch Automatic Operation  
In AUTO, the generator starts automatically when utility source voltage drops below the preset level. Once the unit  
starts, loads are transferred to the standby power source.  
To select automatic operation:  
1. Verify that the transfer switch main contacts are set to the UTILITY position (loads connected to the utility power  
source).  
2. Verify that normal UTILITY power source voltage is available to transfer switch terminal lugs N1, N2 and N3 (if  
three phase).  
3. Move the Main Circuit Breaker switch on the control panel up to the ON (Closed) position.  
4. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.  
Owner’s Manual for Stationary Diesel Generators  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
4.9.1— Automatic Sequence of Operation  
4.9.1.1—Utility Failure  
If the control pad is set to AUTO when the utility power fails (falls below 60% of nominal, dealer programmable), a ten  
second Start-Up Delay timer is started (user programmable). If utility power is still absent when the time expires, the  
engine cranks and starts.  
Once started, a five second engine Warm-Up Delay timer starts (user programmable). When the time has elapsed, the  
load is transferred to the generator. If utility power is restored (above 80% of nominal, dealer programmable) between  
the time the engine is first started and expiration of the warm-up time, the controller completes the start cycle and then  
runs through its normal cool-down cycle (while the load remains on the utility source throughout the episode).  
4.9.1.2—Cranking  
The cyclic cranking is controlled as follows:  
Fifteen (15) seconds crank, seven (7) seconds rest, seven (7) seconds crank, seven (7) seconds rest; this sequence is  
repeated for a total of six (6) crank cycles.  
4.9.1.3—Load Transfer  
With the generator running, the transfer of load is dependent upon the operating mode as follows:  
Starts and runs if utility power fails (falls below 60% of nominal) for five consecutive sec-  
onds (adjustable).  
Starts a five second (adjustable) engine warm-up timer.  
Does not execute transfer if utility power returns before expiration of warm-up timer (but  
finishes the warm-up and cool-down cycles).  
Transfers back to utility once utility power returns (above 80% of nominal) for fifteen  
consecutive seconds.  
Only shuts down if OFF is pressed or an alarm shutdown occurs.  
AUTO  
Once utility power returns, starts a cool-down cycle before it shuts down.  
NOTE: Cool-down cycle is five minutes if turbocharger equipped, one minute if naturally  
aspirated.  
EXERCISE  
Only works in the AUTO mode.  
Does not exercise if generator is already running in AUTO.  
During exercise cycle, transfers only if utility power fails for ten consecutive seconds.  
Engine cranks and runs even if utility power is present, but does not transfer to generator.  
Transfers to generator if utility fails (falls below 60% of nominal) for ten consecutive sec-  
MANUAL  
onds.  
Transfers back to utility when utility returns for fifteen consecutive seconds. The engine  
continues to run until the AUTO or OFF key is pressed.  
4.10 — Transfer Switch Manual Operation  
DO NOT attempt to activate the transfer switch manually until all power voltage supplies to the switch  
have been completely turned off. Failure to turn off all power voltage supplies may result in extremely  
hazardous and possibly fatal electrical shock.  
Prior to automatic operation, manually exercise the transfer switch to verify that there is no binding or interference with  
proper operation of the mechanism. Manual operation of the transfer switch is required if automatic operation fails.  
24  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
IMPORTANT NOTE: Always use the applicable transfer switch owner's manual for actual manual transfer  
switch operation instructions. The information presented here describes a typical V-style transfer switch,  
which is not used for three phase applications.  
4.10.1— Transfer to Generator Power  
When utility power fails, manually transfer to standby power and start the generator as follows:  
1. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.  
2. Move the Main Circuit Breaker switch down to the OFF (Open) position.  
3. Turn off the utility power supply to the transfer switch using the means provided (such as a utility main line circuit  
breaker).  
4. Use the manual transfer handle inside the transfer switch to move the main contacts to the STANDBY position  
(loads connected to the standby power source).  
5. Press MANUAL on the control pad. The engine cranks and starts.  
6. Allow the engine to run for two minutes to bring it up to normal operating temperature.  
7. Move the Main Circuit Breaker switch up to the ON (Closed) position.  
Manual Transfer  
Handle  
Load Connected to Utility  
Load Connected to Standby  
Transfer Switch  
Operating Lever  
NOTE: V-style transfer switch not used for three phase applications.  
Figure 4-4. Manual Transfer Switch Operation (Typical)  
4.10.2— Transfer Back to Utility Power  
When utility power is restored, manually transfer back to utility power and shut down the generator as follows:  
NOTE: Verify that utility voltage has returned and is at the proper value.  
1. Move the Main Circuit Breaker switch down to the OFF (Open) position.  
2. Allow the engine to run for two minutes at no-load to bring it up to normal operating temperature.  
3. Press OFF on the control pad to shut down the engine.  
4. Verify that utility power supply to the transfer switch is turned off.  
5. Use the manual transfer handle inside the transfer switch to move the main contacts to the UTILITY position  
(loads connected to the utility power source).  
6. Turn on the utility power supply to the transfer switch using the means provided.  
7. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.  
Owner’s Manual for Stationary Diesel Generators  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
This page intentionally left blank.  
26  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5  
Maintenance  
5.1 — Component Locations  
The side of the enclosure with the viewing window is identified as the rear of the generator set. The right and left sides  
are identified by standing at the rear and looking towards the front of the unit.  
Viewing  
Window  
7.5 Amp Fuse  
and USB Port  
Main Circuit Breaker  
Control Pad  
and LCD Screen  
Left Side  
Right Side  
Figure 5-1. Rear View  
V-Belt  
Air Filter  
Oil Drain  
Hose  
Oil Filter Oil Level  
Oil Fill Cap  
Dipstick  
Figure 5-2. Right Side View  
Owner’s Manual for Stationary Diesel Generators  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Breather Canister  
and Filter  
Fuel Filter/Air Bleed  
Fuel Return Hose  
Fuel Supply Hose  
Coolant  
Drain Hose  
Governor  
Linkage  
Coolant Overflow  
Reservoir  
Battery  
Figure 5-3. Left Side View  
Fuel Tank  
Primary Vent  
Emergency Vent  
Primary Tank  
Fuel Filler Spout  
Emergency Vent  
Secondary Tank  
Fuel Level Gauge  
Figure 5-4. Front View  
NOTE: The 3.4L engine is depicted in the artwork used in this manual. The location and appearance of some  
components may vary between engine models.  
28  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.2 — Access Panels  
Access panels are located at both the front and sides of the enclosure.  
5.2.1— Removal  
1. Insert key into latch and rotate counterclockwise 1/2 turn. See Figure 5-5.  
2. Raise panel using thumb latch.  
5.2.2— Installation  
1. Lower panel into position using thumb latch.  
2. Insert key into latch and rotate clockwise 1/2 turn.  
Key  
Thumb Latch  
Figure 5-5. Access Panel Key  
Owner’s Manual for Stationary Diesel Generators  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.3 — Service Maintenance Intervals  
NOTE: Use only Genuine Generac parts to ensure warranty coverage.  
All generator service must be performed by a qualified service person only.  
*
It is important to perform all maintenance at the interval specified in the Service Maintenance Schedule. This  
ensures safe and proper operation, as well as compliance with applicable emissions standards. Critical emissions  
maintenance must be performed for the Emissions Warranty to remain valid. Service and repairs may be performed by  
any qualified service technician or repair shop.  
Observe the maintenance tasks and intervals shown in the table below.  
Schedule A  
Every  
Schedule B  
Every  
Schedule C  
Every  
Daily If Running  
Continuously  
30 Hours  
Engine Break In  
Service  
Year or  
2 Years or  
250 Hours  
1000 Hours  
125 Hours  
Check Fuel Level and Fill  
Drain Fuel Filter  
Check Fuel Lines and Hoses  
Check Coolant Level  
Check Coolant Hoses  
Check Radiator for Clogging  
Check Lubricating Oil Level  
Check Battery Condition/Fluid Level  
Check/Adjust V-Belt Tension  
Replace Air Filter Element  
Drain Breather Canister and Replace Filter  
Lubricate Governor Rod Linkage  
Replace Lubricating Oil and Oil Filter  
Replace Fuel Filter Element  
Drain/Flush Coolant System  
Inspect Fuel Tank  
Check/Adjust Fuel Injection Valve  
Pressure  
Adjust Intake/Exhaust Valve Clearance  
Check/Adjust Fuel Injection Pump Timing  
Tighten Critical Fasteners  
NOTE: If the unit reaches a Schedule A or Schedule B maintenance interval with 900 to 999 total hours, have  
an authorized service provider perform the Schedule C maintenance tasks as well (and reset the A-B-C/Year  
maintenance schedule counter).  
30  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.4 — Remove From Service  
To ensure safety, follow the steps below prior to inspection, maintenance or service.  
IMPORTANT NOTE: If currently experiencing a utility outage, see Subsection 6.3 —Removal From Service  
During Utility Outages for special instructions.  
1. Open the viewing window. See Subsection 3.5 —Open Viewing Window.  
2. Move the Main Circuit Breaker switch down to the OFF (Open) position. See A of Figure 5-6.  
3. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode. See B of  
Figure 5-6.  
4. Remove T1 fuse from transfer switch.  
5. Pull up rubber flap covering fuse holder and remove 7.5 amp fuse. See C of Figure 5-6.  
6. Place a DO NOT OPERATE tag or placard on both the control panel and transfer switch.  
7. If the unit has been running, wait five minutes for the engine to cool.  
7.5 Amp Fuse  
and USB Port  
C
A
LCD Screen  
o
OFF  
PUSH TO TRIP  
Main Circuit Breaker  
Control Pad  
B
Figure 5-6. Generator Control Panel  
5.5 — 30 Hour Break-In  
Perform the following task:  
Replace Lubricating Oil and Oil Filter  
NOTE: See Subsection 5.8.1 under Schedule B Maintenance.  
5.6 — Daily Maintenance (If Running Continuously)  
Perform the following tasks:  
Check Fuel Level and Fill  
Drain Fuel Filter  
Check Coolant Hoses  
Check Radiator for Clogging  
Check Lubricating Oil Level  
Check Fuel Lines and Hoses  
Check Coolant Level  
NOTE: See Subsection 5.7.1 through Subsection 5.7.6 under Schedule A Maintenance.  
Owner’s Manual for Stationary Diesel Generators  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.7 — Schedule A Maintenance  
NOTE: Perform Schedule A maintenance once each year or after 125 hours of service, whichever comes first.  
5.7.1— Preliminary Instructions  
1. See Subsection 5.4 —Remove From Service.  
2. Remove access panels at the front and both sides of the enclosure. See Subsection 5.2 —Access Panels.  
3. Remove battery negative cable (black) from battery negative (-) terminal.  
NOTE: For general location of components, see Subsection 5.1 —Component Locations.  
5.7.2— Check Fuel Level and Fill  
1. Observe fuel gauge to note level of fuel in tank. See Figure 5-7.  
2. Remove fuel fill cap from filler pipe.  
3. Add fuel until needle on fuel gauge approaches the F(ull) mark.  
4. Install fuel fill cap onto filler pipe.  
Figure 5-7. Check Fuel Level Gauge and Fill  
5.7.3— Drain Fuel Filter and Check Fuel Lines/Hoses  
1. Slowly loosen water drain plug. See Figure 5-8.  
2. Place a shop rag under the drain to catch any loss of water/fuel.  
3. Work priming pump until water is drained and replaced by solid fuel. Tighten the water drain plug.  
4. Check fuel filter and fuel lines/hoses for leaks. Tighten filter, fittings and hose clamps, if necessary.  
5. Check hoses for nicks, cuts, tears or general deterioration. Replace as necessary.  
32  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Priming  
Pump  
Fuel  
Filter  
Water  
Drain Plug  
Figure 5-8. Drain Water From Fuel Filter  
5.7.4— Check Coolant Level and Hoses  
Do not add coolant when the engine is hot. Steam and scalding fluids can cause severe burns.  
*
NOTE: On 2.3L models, remove ten screws to release louvered air discharge panel on left side of enclosure.  
1. Verify that the coolant level is between the HOT and COLD marks on the overflow reservoir. See Figure 5-9.  
NOTE: Coolant expands when hot, so the level may be higher than the HOT mark. Do not add coolant higher  
than the HOT mark.  
2. If the coolant level is below the COLD mark, remove fill cap from overflow reservoir and add coolant. See Sub-  
section 2.4 —Coolant Water Treatment.  
3. Check coolant hoses for leaks. Tighten hose clamps, if necessary.  
4. Check hoses for nicks, cuts, tears or general deterioration. Replace as necessary.  
NOTE: On 2.3L models, install louvered air discharge panel. Alternately tighten ten screws to 90 in-lbs using a  
crosswise pattern.  
Drain Hose  
Coolant  
Reservoir  
Figure 5-9. Coolant Overflow Reservoir and Drain Hose  
Owner’s Manual for Stationary Diesel Generators  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.7.5— Check Radiator for Clogging  
Direct beam of flashlight through openings in fan guard to inspect the radiator fins. Carefully look for debris, accumula-  
tions of dirt or other deposits. If necessary, clean as follows:  
1. On right side of enclosure, loosen two clamps at each end of turbocharger exhaust outlet pipe. Remove pipe,  
clamps and rubber couplings from engine.  
2. Remove oil drain hose from holding clamp.  
3. Remove four screws with nylon washers to release fan guard from radiator shroud.  
4. On left side of enclosure, loosen two clamps at each end of air intake pipe. Remove pipe, clamps and rubber  
couplings from engine.  
5. Remove coolant hoses from holding clamps.  
6. Remove four screws with nylon washers to release fan guard from radiator shroud.  
7. Carefully remove any debris from radiator fins. Use warm soapy water and a soft bristled brush to remove dirt  
and other deposits, if necessary.  
8. On left side of enclosure, install four screws with nylon washers to fasten fan guard to radiator shroud.  
9. Install coolant hoses into holding clamps.  
10. Install clamps and rubber couplings onto each end of air intake pipe. Install pipe to air heater and radiator shroud.  
Tighten clamps.  
11. On right side of enclosure, install four screws with nylon washers to fasten fan guard to radiator shroud.  
12. Install oil drain hose into holding clamp.  
13. Install clamps and rubber couplings onto each end of turbocharger exhaust outlet pipe. Install pipe to turbo-  
charger outlet and radiator shroud. Tighten clamps.  
5.7.6— Check Lubricating Oil Level  
1. Remove dipstick and wipe with a clean cloth. See A of Figure 5-10.  
2. Completely insert the dipstick and then remove it.  
3. Verify that the oil level is at or near the H(igh) mark.  
NOTE: Each hash mark or line below the H(igh) mark represents one liter. Add oil whenever the level is one  
liter or more below the H(igh) mark.  
4. If necessary, remove the oil fill cap and slowly add oil until the level is at the H(igh) mark. See B of Figure 5-10.  
DO NOT OVERFILL.  
5. Install dipstick and oil fill cap.  
6. Check oil drain hose for leaks. Check hose for nicks, cuts, tears or general deterioration. Replace as necessary.  
A
2.3 Liter  
2.4 Liter  
B
3.4 Liter  
Figure 5-10. Oil Level Dipstick  
34  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.7.7— Check Battery Condition/Fluid Level  
5.7.7.1— Check Condition and Clean  
NOTE: On 2.3L models, remove ten screws to release louvered air intake panel on left side of enclosure.  
1. Verify that top of battery is clean and dry. Dirt and electro-  
lyte on top of the battery can cause battery to self-dis-  
charge. Clean battery top with a solution of baking soda  
(sodium bicarbonate) and water (5 teaspoons baking  
soda per quart or liter of water). When solution stops bub-  
bling, rinse off the battery with clean water.  
2. Clean cable clamps and battery terminals using a wire  
brush or sandpaper to remove any oxidation.  
3. Inspect battery screws, clamps and cables for breakage,  
loose connections and corrosion. Tighten and clean as  
necessary.  
4. Check the battery posts for melting or damage caused by  
over tightening.  
5. Inspect battery for discoloration, raised top or a warped  
or distorted case, which might indicate that the battery  
has been frozen, overheated or overcharged.  
Red Lead  
From Starter  
6. Inspect the battery case for cracks or leaks.  
7. Check the battery fluid level of unsealed batteries. See  
Subsection 5.7.7.2—Check Fluid Level.  
8. Check the battery state of charge. See Subsection  
5.7.7.3—Check State of Charge.  
Black Lead  
To Frame  
9. Replace battery if necessary. See Subsection 5.7.7.4—  
Battery Replacement.  
Battery  
NOTE: On 2.3L models, start ten screws to install louvered  
air intake panel. Alternately tighten screws to 90 in-lbs (10  
N-m) using a crosswise pattern.  
Figure 5-11. Battery Cable Connections  
5.7.7.2— Check Fluid Level  
Check the fluid level of unsealed batteries. If necessary, fill with  
distilled water only. DO NOT use tap water.  
5.7.7.3— Check State of Charge  
Check the state of charge using a Digital Multimeter. Recharge and retest if state of charge is below manufacturer's  
recommendations. Replace battery if necessary.  
5.7.7.4— Battery Replacement  
Removal  
Always disconnect the negative battery cable first. If the positive cable should contact ground with the  
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-  
ous injury.  
$
1. Remove battery negative cable (black) from battery negative (-) terminal.  
2. Remove battery positive cable (red) from battery positive (+) terminal.  
3. Install rubber protective cover over battery positive (+) terminal.  
4. Loosen two screws with nylon washers to release battery hold-down clamp from battery tray.  
5. Grasp battery strap next to battery positive (+) terminal, and lift battery.  
6. When battery tilts sideways, remove from opening.  
7. Remove rubber protective cover from battery positive (+) terminal.  
Owner’s Manual for Stationary Diesel Generators  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Installation  
Always connect the positive battery cable first. If the positive cable should contact ground with the  
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-  
ous injury.  
$
1. Install rubber protective cover over battery posi-  
tive (+) terminal. See A of Figure 5-12.  
2. Grasp battery strap next to battery positive (+)  
terminal, and lift battery.  
3. When battery tilts sideways, insert into opening.  
B
See B of Figure 5-12.  
A
4. Return battery to the horizontal position while  
sliding it onto battery tray.  
5. Tighten two screws with nylon washers to  
secure hold-down clamp to battery tray.  
6. Remove rubber protective cover from battery  
positive (+) terminal.  
7. Install battery positive cable (red) to battery  
positive (+) terminal.  
8. Install battery negative cable (black) to battery  
negative (-) terminal.  
A = Protective Cover  
B = Battery Strap  
Figure 5-12. Install Battery (2.3L Models)  
36  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.7.8— Check and Adjust V-Belt  
5.7.8.1— Check  
Check the V-belt deflection. Too little belt deflection accelerates belt wear, while too much deflection leaves the pulley  
idle, overheats the engine, and no-load is generated. Adjust the belt deflection as follows:  
1. On right side of enclosure, loosen two clamps at each end of turbocharger exhaust outlet pipe. Remove pipe,  
clamps and rubber couplings from engine.  
2. Remove oil drain hose from holding clamp.  
3. Remove four screws with nylon washers to release fan guard from radiator shroud.  
4. Perform visual inspection as follows:  
Inspect belt for cracks, fraying, excessive wear or other damage.  
Verify that belt is free of grease and oil. Replace belt if contaminated.  
NOTE: Use a solution of soap and warm water to clean pulleys, if necessary. Avoid use of solvents, but if  
used, always follow by a soap and water wash.  
5. Using a suitable gauge, apply 22 Ibs (10 kgf) force midway between the crankshaft and alternator pulleys. See  
Figure 5-13.  
6. Take note of gauge reading. If belt deflection is not within specification, see Subsection 5.7.8.2—Adjust.  
Belt Condition  
New  
Deflection  
8-12 mm  
Used  
10-15 mm  
7. Install four screws with nylon washers to fasten fan guard to radiator shroud.  
8. Install oil drain hose into holding clamp.  
9. Install clamps and rubber couplings onto each end of turbocharger exhaust outlet pipe. Install pipe to turbo-  
charger outlet and radiator shroud. Tighten clamps.  
Belt Deflection Gauge  
Alternator Pulley  
Crankshaft Pulley  
Figure 5-13. Check V-Belt Deflection  
Owner’s Manual for Stationary Diesel Generators  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.7.8.2— Adjust  
1. Loosen tension adjuster screw (top). Loosen hex nut on pivot screw (bottom). Rotate alternator outward to  
reduce belt deflection, rotate inward to increase belt deflection.  
2. Tighten tension adjuster screw (top) to 17-22 ft-lbs (23-30 N-m). Tighten hex nut on pivot screw (bottom) to 33-43  
ft-lbs (45-58 N-m).  
3. Recheck belt deflection and repeat steps as necessary.  
5.7.9— Replace Air Filter Element  
1. Remove wing nut from threaded rod to release air cleaner cover. See Figure 5-14.  
2. Remove the air filter element and discard.  
3. Thoroughly clean air cleaner cover of any dust, dirt, or debris.  
4. Place new air filter element against adapter flange.  
NOTE: The air filter element is not directional.  
5. Install air cleaner cover over threaded rod. Install wing nut and tighten until snug.  
Element  
Cover  
Wing Nut  
Figure 5-14. Air Cleaner Cover and Filter Element  
5.7.10— Drain Breather Canister and Replace Filter  
NOTE: This procedure only applies to turbocharged engines (2.4L/3.4L models).  
1. Observe sight glass for level of oil in canister. See Figure 5-15.  
2. When oil level approaches top of sight glass, remove plug at bottom of canister to drain oil.  
3. Install drain plug at bottom of canister and tighten until snug.  
4. Loosen clamp and remove filter element.  
5. Install new filter element onto canister and tighten clamp.  
6. Inspect hoses for nicks, cuts, tears or signs of deterioration. Replace as necessary.  
7. Check for leakage. Tighten clamps if leaks are found.  
NOTE: Dispose of used fuel filter at a proper collection center.  
38  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Filter  
Element  
Clamp  
Drain Plug  
Sight  
Glass  
Figure 5-15. Drain Breather Canister and Replace Filter  
5.7.11— Lubricate Governor Rod Linkage  
1. Lubricate both ends of rod with a silicone spray. See Figure 5-16.  
2. Verify that rod moves freely without binding.  
Figure 5-16. Lubricate Governor Rod Ends  
5.7.12— Final Instructions  
1. Install battery negative cable (black) onto battery negative (-) terminal.  
2. Install access panels at the front and both sides of the enclosure. See Subsection 5.2 —Access Panels.  
3. See Subsection 5.10 —Return To Service.  
Owner’s Manual for Stationary Diesel Generators  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.8 — Schedule B Maintenance  
NOTE: Perform Schedule B maintenance every two years or after 250 hours of service, whichever comes first.  
Before proceeding below, first perform all tasks listed under Schedule A Maintenance.  
NOTE: For general location of components, see Subsection 5.1 —Component Locations.  
5.8.1— Replace Lubricating Oil and Oil Filter  
1. Remove oil drain hose from holding clamp. See Figure 5-17.  
2. Use one wrench to hold hex on hose fitting (to prevent rotation), and use second wrench to remove drain plug.  
3. Drain oil into a suitable container.  
4. Install drain plug onto end of oil drain hose.  
5. Install oil drain hose into holding clamp.  
6. Rotate oil filter counterclockwise to remove from oil filter adapter.  
7. Apply a light coat of clean engine oil to gasket of new oil filter.  
8. Install oil filter by hand until gasket just contacts oil filter adapter. Tighten oil filter an additional 3/4 to one full turn.  
9. Remove fill cap and fill engine with the recommended oil. See Subsection 2.3 —Engine Oil Recommendations.  
10. Install fill cap.  
11. Install battery negative cable (black) onto battery negative (-) terminal.  
12. Pull up rubber flap covering fuse holder and install 7.5 amp fuse.  
13. Press MANUAL on the control pad to start the engine.  
14. Allow the engine to run for one minute. Check for leaks while the engine is running.  
15. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.  
16. Wait a few minutes for the engine to cool and to allow oil to drain back to the oil pan.  
17. Check oil level and add oil as necessary. DO NOT OVERFILL.  
18. Install fill cap.  
NOTE: Dispose of used oil and oil filter at a proper collection center.  
Figure 5-17. Oil Fill Cap and Drain Hose  
40  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.8.2— Replace Fuel Filter  
1. Slowly loosen water drain plug. See Figure 5-18.  
2. Rotate filter counterclockwise to remove from filter adapter.  
3. Install new filter by hand until gasket just contacts filter adapter. Tighten filter an additional 3/4 to one full turn.  
4. Tighten water drain plug.  
NOTE: Dispose of used fuel filter at a proper collection center.  
5. See Subsection 5.8.2.1—Prime Fuel System.  
Priming  
Pump  
Fuel  
Filter  
Water  
Drain Plug  
Air Bleed  
Screw  
Figure 5-18. Prime Fuel System  
5.8.2.1— Prime Fuel System  
1. Place a shop rag near the air bleed screw to catch any loss of fuel.  
2. Loosen the air bleed screw and work priming pump until bubbles are observed.  
3. When all bubbles are purged and replaced by a solid stream of fuel, depress pump handle and tighten the air  
bleed screw.  
4. Check for leaks.  
5.8.3— Drain/Flush Coolant System  
NOTE: On 2.3L models, remove ten screws to release louvered air discharge panel on left side of enclosure.  
1. Disconnect and empty coolant overflow reservoir.  
2. Install and connect coolant overflow reservoir.  
Verify that the engine is cool before removing the radiator cap. The cooling system is under pressure,  
so steam and hot liquid can come out forcefully when the cap is loosened.  
*
3. Slowly unscrew radiator cap.  
4. Locate drain cock at bottom left side of radiator. Rotate hex fitting to open drain cock. See A of Figure 5-19.  
Owner’s Manual for Stationary Diesel Generators  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5. Remove coolant drain hose from holding clamp.  
6. Use wrench to hold hex on hose fitting (to prevent rotation), and use second wrench to remove drain plug.  
7. Drain coolant into a suitable container.  
8. Install plug at end of drain hose.  
9. Install drain hose in holding clamp.  
10. Rotate hex fitting to close radiator drain cock.  
11. Obtain at least 2.8 gallons (10.6 liters) of coolant. See Subsection 2.4 —Coolant Water Treatment.  
12. Rotate and remove plastic cover at top of enclosure and insert funnel into filler neck. See B of Figure 5-19.  
13. Slowly pour coolant into filler neck until radiator is full.  
14. Install radiator cap.  
15. Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the  
MANUAL mode.  
16. Allow engine to run until the thermostat opens, as indicated by heating of the top radiator hose.  
17. Check coolant hoses for leaks. Tighten clamps, if necessary.  
18. Press OFF on the control pad to shut the engine down.  
19. Wait five minutes for the engine to cool.  
20. Repeat steps 4-20 to drain and refill cooling system.  
21. Install plastic cover at top of enclosure and rotate until tight.  
22. Check hoses for nicks, cuts, tears or general deterioration. Replace as necessary.  
NOTE: On 2.3L models, start ten screws to install louvered air discharge panel. Alternately tighten screws to 90 in-lbs  
using a crosswise pattern.  
A
B
NOTE: Drain hose removed for  
illustration purposes.  
Figure 5-19. Drain/Fill Coolant System  
5.8.4— Final Instructions  
1. Install left and right side access panels. See Subsection 5.2 —Access Panels.  
2. See Subsection 5.10 —Return To Service.  
42  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.9 — Schedule C Maintenance  
NOTE: Perform Schedule C maintenance after 1000 hours of service. Before proceeding below, first perform all  
tasks listed under Schedule A Maintenance and Schedule B Maintenance.  
The following procedures require special tools and skills. Contact a Generac Dealer or an authorized  
service provider to perform these tasks.  
*
Inspect Fuel Tank  
Check/Adjust Fuel Injection Valve Pressure  
Check/Adjust Fuel Injection Pump Timing  
Adjust Intake/Exhaust Valve Clearance  
Tighten Critical Fasteners  
NOTE: Reset the A-B-C/Year time maintenance schedule counter using the Dealer Sub Menu (password  
required).  
5.10 — Return To Service  
After inspection, maintenance or service of the generator, return the unit to service following the steps below.  
1. Pull up rubber flap covering fuse holder and install 7.5 amp fuse. See A of Figure 5-20.  
2. Install T1 fuse in transfer switch.  
3. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode. See B  
of Figure 5-20.  
4. Move the Main Circuit Breaker switch up to the ON (Closed) position. See C of Figure 5-20.  
5. Close the viewing window.  
6. Remove the DO NOT OPERATE tag or placard from both the control panel and transfer switch.  
7. Reset the time and date.  
7.5 Amp Fuse Holder  
A
C
LCD Screen  
o
OFF  
PUSH TO TRIP  
Main Circuit Breaker  
Control Pad  
B
Figure 5-20. Generator Control Panel  
Owner’s Manual for Stationary Diesel Generators  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
This page intentionally left blank.  
44  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6  
Troubleshooting  
6.1 — Engine Troubleshooting  
Problem  
Cause  
Correction  
Replace 7.5 amp fuse in generator con-  
trol panel. Correct short circuit condi-  
tion if fuse blows again.  
Fuse blown.  
Loose, corroded or defective bat-  
tery cables.  
Tighten, clean or replace as neces-  
sary.*  
The engine will not crank.  
Tighten, clean or replace as neces-  
sary.*  
Defective starter contact.  
Defective starter motor.  
Tighten, clean or replace as neces-  
sary.*  
Dead Battery.  
Charge or replace battery.  
Out of fuel.  
Replenish fuel. Turn on fuel valve.  
*
Defective fuel solenoid.  
The engine cranks but will not  
start.  
Replace F1 5 amp fuse if fuse blows  
again.*  
Open F1 5 amp fuse.  
Defective fuel system.  
No fuel to pump.  
*
Prime fuel system.*  
The engine starts hard and runs  
rough.  
Air cleaner plugged or damaged.  
Check/replace air cleaner.  
Defective keypad.  
*
*
The generator is set to OFF, but  
the engine continues to run.  
Defective control board.  
Main line circuit breaker is in the  
OFF (OPEN) position.  
Reset circuit breaker to ON (CLOSED)  
position.  
There is no AC output from the  
generator.  
Generator internal failure.  
Defective transfer switch coil.  
Defective transfer relay.  
*
*
*
There is no transfer to standby  
after utility source failure.  
Transfer relay circuit open.  
Defective control logic board.  
Engine over filled with oil.  
Engine breather defective.  
Incorrect oil type or viscosity.  
Damaged gasket, seal or hose.  
*
*
Adjust oil to correct level.  
*
Unit consumes large amounts of  
oil.  
See Engine Oil Recommendations.  
Check for oil leaks.  
* Contact an Authorized Service Dealer for assistance.  
Owner’s Manual for Stationary Diesel Generators  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
6.2 — Controller Troubleshooting  
Active Alarm  
Problem  
Solution  
NOT ACTIVATED  
Unit will not start in AUTO with utility loss.  
Refer to activation section in Owner’s Manual.  
Check MLCB. Contact servicing dealer if MLCB is in the ON  
position.  
NONE  
NONE  
Unit running in AUTO but no power in house.  
Unit will not start in AUTO with utility loss.  
Check screen for start delay countdown. If the start up delay is  
greater than expected, contact servicing dealer to adjust from 2  
to 1500 seconds.  
HIGH  
TEMPERATURE  
Check ventilation around the intake, exhaust and rear of gener-  
ator. Contact serving dealer if no obstruction is found.  
Unit shuts down during operation.  
Unit shuts down during operation.  
Clear alarm and remove household loads from the generator.  
Put back in AUTO and restart.  
OVERLOAD  
Clear alarm and remove household loads from the generator.  
Put back in AUTO and restart. If problem returns, contact servic-  
ing dealer to investigate possible fuel issue.  
Unit was running and shuts down, attempts to  
restart.  
RPM SENSE LOSS  
LOW OIL  
PRESSURE  
Check oil level. Add oil per Owner’s Manual. Contact servicing  
dealer if oil level is correct.  
Unit will not start in AUTO with utility loss.  
Unit will not start in AUTO with utility loss.  
Unit will not start in AUTO with utility loss.  
Clear alarm. From the MAIN menu on the control panel, navi-  
gate to the BATTERY MENU. Contact servicing dealer if battery  
is GOOD. Replace battery If CHECK BATTERY is displayed.  
RPM SENSE LOSS  
OVERCRANK  
Clear alarm. Attempt to start the unit in MANUAL. If it does not  
start or starts and runs rough, contact servicing dealer.  
Check ATO 7.5 amp fuse. Replace with same type fuse if bad.  
Contact servicing dealer if fuse is good.  
FUSE PROBLEM  
OVERSPEED  
Unit will not start in AUTO with utility loss.  
Unit will not start in AUTO with utility loss.  
Unit will not start in AUTO with utility loss.  
Contact servicing dealer.  
Contact servicing dealer.  
UNDER  
VOLTAGE  
UNDERSPEED  
MISWIRE  
Unit will not start in AUTO with utility loss.  
Unit will not start in AUTO with utility loss.  
Unit will not start in AUTO with utility loss.  
Contact servicing dealer.  
Contact servicing dealer.  
Contact servicing dealer.  
OVERVOLTAGE  
Clear alarm. From the MAIN menu on the control panel, navi-  
gate to the BATTERY MENU. Contact servicing dealer if battery  
is GOOD. Replace battery If CHECK BATTERY is displayed.  
LOW BATTERY  
Warning active.  
BATTERY PROBLEM  
CHARGER WARNING  
Warning active.  
Warning active.  
Contact servicing dealer.  
Contact servicing dealer  
Perform SERVICE SCHEDULE A maintenance; press ENTER  
to clear.  
SERVICE SCHEDULE A  
SERVICE SCHEDULE B  
SERVICE SCHEDULE C  
Warning active.  
Warning active.  
Warning active.  
Perform SERVICE SCHEDULE B maintenance; press ENTER  
to clear.  
Perform SERVICE SCHEDULE C maintenance; press ENTER  
to clear.  
46  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
6.3 — Removal From Service During Utility Outages  
If, during prolonged utility outages, the user wishes to remove the unit from service to conserve fuel, reduce run hours,  
or to perform maintenance tasks, then complete the steps listed below.  
IMPORTANT NOTE: Failure to abide by this procedure can result in equipment damage.  
To remove the generator from service while running in AUTO and online, proceed as follows:  
1. Turn the main utility disconnect to OFF (Open).  
2. Open the viewing window. See Subsection 3.5 —Open Viewing Window.  
3. Move the Main Circuit Breaker switch down to the OFF (Open) position.  
4. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.  
NOTE: If inspection and/or maintenance tasks are to be performed, complete the additional steps listed below.  
5. Remove T1 fuse from transfer switch.  
6. Pull up rubber flap covering fuse holder and remove 7.5 amp fuse.  
7. Remove battery negative cable (black) from battery negative (-) terminal.  
8. Place a DO NOT OPERATE tag or placard on both the control panel and transfer switch.  
To return the generator to service, proceed as follows:  
NOTE: If inspection and/or maintenance tasks were performed, start with step 1. If the unit was just shut down  
to conserve fuel or to reduce run hours, start at step 5.  
1. Install battery negative cable (black) onto battery negative (-) terminal.  
2. Pull up rubber flap covering fuse holder and install 7.5 amp fuse.  
3. Install T1 fuse in transfer switch.  
4. Remove the DO NOT OPERATE tag or placard from both the control panel and transfer switch.  
5. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode. Allow  
the generator to start and run for a few minutes.  
6. Move the Main Circuit Breaker switch up to the ON (Closed) position.  
7. Turn the main utility disconnect to ON (Closed).  
8. Close the viewing window.  
6.4 — Storage  
6.4.1— Prepare For Storage  
If the generator cannot be exercised every seven days and will be out of service longer than 90 days, prepare for stor-  
age as follows:  
1. Open the viewing window. See Subsection 3.5 —Open Viewing Window.  
2. Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the  
MANUAL mode.  
3. Allow the engine to run until it reaches normal operating temperature.  
4. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.  
5. Move the Main Circuit Breaker switch on the control panel down to the OFF (Open) position.  
6. Pull up rubber flap covering fuse holder and remove 7.5 amp fuse.  
7. Turn off utility power to the transfer switch.  
8. Place a DO NOT OPERATE tag or placard on both the control panel and transfer switch.  
9. Wait five minutes for the engine to cool.  
Owner’s Manual for Stationary Diesel Generators  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
10. Remove right side access panel. See Subsection 5.2 —Access Panels.  
11. Remove oil drain hose from holding clamp.  
12. Use one wrench to hold hex on hose fitting (to prevent rotation), and use second wrench to remove drain plug.  
13. Drain oil into a suitable container.  
14. Install drain plug onto end of oil drain hose.  
15. Install oil drain hose into holding clamp.  
16. Rotate oil filter counterclockwise to remove from oil filter adapter.  
17. Apply a light coat of clean engine oil to gasket of new oil filter.  
18. Install oil filter by hand until gasket just contacts oil filter adapter. Tighten oil filter an additional 3/4 to one full turn.  
19. Remove oil fill cap and fill engine with the recommended oil. See Subsection 2.3 —Engine Oil Recommenda-  
tions.  
20. Install oil fill cap.  
21. Install right side access panel. See Subsection 5.2 —Access Panels.  
NOTE: Dispose of used oil and oil filter at a proper collection center.  
22. Remove left side access panel. See Subsection 5.2 —Access Panels.  
NOTE: On 2.3L models, remove ten screws to release louvered air intake panel.  
Always disconnect the negative battery cable first. If the positive cable should contact ground with the  
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-  
ous injury.  
$
23. Remove battery negative cable (black) from battery negative (-) terminal.  
24. Remove battery positive cable (red) from battery positive (+) terminal.  
25. Remove two screws to release battery hold-down clamp from platform.  
26. Remove battery and store on a wooden board in a cool, dry room. Do not store the battery on a concrete or  
earthen floor.  
27. Install left side access panel. See Subsection 5.2 —Access Panels.  
NOTE: On 2.3L models, start ten screws to install louvered air intake panel. Alternately tighten screws to 90 in-  
lbs.  
28. Thoroughly clean and wipe down the generator. See Subsection 2.7 —Corrosion Protection.  
6.4.2— Return From Storage  
To return the unit to service after storage, proceed as follows:  
1. Thoroughly clean and wipe down the generator. See Subsection 2.7 —Corrosion Protection.  
2. Remove left side access panel. See Subsection 5.2 —Access Panels.  
NOTE: On 2.3L models, remove ten screws to release louvered air intake panel.  
3. Install battery onto tray oriented with the negative (-) post toward the front of the enclosure.  
4. Install two screws with nylon washers to secure battery hold-down clamp to tray.  
5. Check battery. See Subsection 5.7.7—Check Battery Condition/Fluid Level..  
Always connect the positive battery cable first. If the positive cable should contact ground with the  
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-  
ous injury.  
$
6. Install battery positive cable (red) onto battery positive (+) terminal.  
7. Install battery negative cable (black) onto battery negative (-) terminal.  
48  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
8. Install left side access panel. See Subsection 5.2 —Access Panels.  
NOTE: On 2.3L models, start ten screws to install louvered air intake panel. Alternately tighten screws to 90 in-  
lbs.  
9. Remove right side access panel. See Subsection 5.2 —Access Panels.  
10. Check oil level and add oil as necessary. DO NOT OVERFILL.  
11. Open the viewing window. See Subsection 3.5 —Open Viewing Window.  
12. Pull up rubber flap covering fuse holder and install 7.5 amp fuse.  
13. Move the Main Circuit Breaker switch up to the ON (Closed) position.  
14. Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the  
MANUAL mode.  
15. Allow the engine to run until it is reaches normal operating temperature. Check for leaks while the engine is run-  
ning.  
16. Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.  
17. Install right side access panel. See Subsection 5.2 —Access Panels.  
18. Turn on utility power to the transfer switch.  
19. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.  
20. Reset the time and date.  
21. Close the viewing window.  
6.5 — Attention After Submersion  
Do NOT start and operate the generator if it has been submerged in water. Have a Dealer thoroughly clean, dry, and  
inspect the generator following any submersion. If the structure (home) has been flooded, it should be inspected by a  
certified electrician to ensure there won’t be any electrical problems during generator operation or when utility power is  
returned.  
6.6 — Attention After Fuel Spillage  
Contact reputable local company that performs clean up and disposal services.  
6.7 — Contaminated Fuel Disposal  
Contact reputable local company that performs purging, burnishing and disposal services.  
Owner’s Manual for Stationary Diesel Generators  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
This page intentionally left blank.  
50  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
Owner’s Manual for Stationary Diesel Generators  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
52  
Owner’s Manual for Stationary Diesel Generators  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Part No. 0K3220 Rev. J 05/07/2015 Printed in USA  
© Generac Power Systems, Inc. All rights reserved  
Specifications are subject to change without notice.  
No reproduction allowed in any form without prior written  
consent from Generac Power Systems, Inc.  
Generac Power Systems, Inc.  
S45 W29290 Hwy. 59  
Waukesha, WI 53189  
1-888-GENERAC (1-888-436-3722)  
generac.com  