Generac Power Systems Portable Generator 68L User Manual

Serial Number  
QT  
6.8L  
100kW  
Models  
STANDBY GENERATOR  
OWNER'S MANUAL  
A new standard of reliability  
This manual should remain with the unit.  
. 0 v 0 8 / 0 5 e v r 0 1 C 0 o R e  
. 0 F 3 6 t N r 0 o a 5 P  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Important Safety Instructions  
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe  
operation be copied and posted in potential hazard areas. Safety should be stressed to all  
operators, potential operators, and service and repair technicians for this equipment.  
GENERAL HAZARDS  
WARNING:  
For safety reasons, the manufacturer recommends  
that this equipment be installed, serviced and  
repaired by an Authorized Service Dealer or other  
competent, qualified electrician or installation tech-  
nician who is familiar with applicable codes, stan-  
dards and regulations. The operator also must  
comply with all such codes, standards and regula-  
tions.  
The engine exhaust from this product  
contains chemicals known to the state  
of California to cause cancer, birth  
defects or other reproductive harm.  
WARNING:  
This product contains or emits chemicals  
known to the state of California to cause  
• Installation, operation, servicing and repair of this  
(and related) equipment must always comply with  
applicable codes, standards, laws and regulations.  
Adhere strictly to local, state and national electri-  
cal and building codes. Comply with regulations  
the Occupational Safety and Health Administration  
(OSHA) has established. Also, ensure that the  
generator is installed, operated and serviced in  
accordance with the manufacturer’s instructions  
and recommendations. Following installation, do  
nothing that might render the unit unsafe or in  
noncompliance with the aforementioned codes,  
standards, laws and regulations.  
• The engine exhaust fumes contain carbon monox-  
ide gas, which can be DEADLY. This dangerous gas,  
if breathed in sufficient concentrations, can cause  
unconsciousness or even death. For that reason,  
adequate ventilation must be provided. Exhaust  
gases must be piped safely away from any building  
or enclosure that houses the generator to an area  
where people, animals, etc., will not be harmed.  
This exhaust system must be installed properly, in  
strict compliance with applicable codes and stan-  
dards.  
cancer, birth defects or other reproductive harm.  
Study these SAFETY RULES carefully before install-  
ing, operating or servicing this equipment. Become  
familiar with this Owner’s Manual and with the unit.  
The generator can operate safely, efficiently and reli-  
ably only if it is properly installed, operated and  
maintained. Many accidents are caused by failing to  
follow simple and fundamental rules or precautions.  
The manufacturer cannot anticipate every possible  
circumstance that might involve a hazard. The warn-  
ings in this manual, and on tags and decals affixed  
to the unit are, therefore, not all inclusive. If a pro-  
cedure, work method or operating technique is used  
that the manufacturer does not specifically recom-  
mend, ensure that it is safe for others. Also make  
sure the procedure, work method or operating tech-  
nique utilized does not render the generator unsafe.  
DANGER  
Despite the safe design of this generator,  
operating this equipment imprudently, neglect-  
ing its maintenance or being careless can cause  
possible injury or death. Permit only responsible  
and capable persons to install, operate or main-  
tain this equipment.  
• Keep hands, feet, clothing, etc., away from drive  
belts, fans, and other moving or hot parts. Never  
remove any drive belt or fan guard while the unit  
is operating.  
• Adequate, unobstructed flow of cooling and venti-  
lating air is critical in any room or building hous-  
ing the generator to prevent buildup of explosive  
gases and to ensure correct generator operation.  
Do not alter the installation or permit even partial  
blockage of ventilation provisions, as this can seri-  
ously affect safe operation of the generator.  
• Keep the area around the generator clean and  
uncluttered. Remove any materials that could  
become hazardous.  
Potentially lethal voltages are generated by  
these machines. Ensure all steps are taken to  
render the machine safe before attempting to  
work on the generator.  
Parts of the generator are rotating and/or hot  
during operation. Exercise care near running  
generators.  
• When working on this equipment, remain alert  
at all times. Never work on the equipment when  
physically or mentally fatigued.  
• Inspect the generator regularly, and promptly  
repair or replace all worn, damaged or defective  
parts using only factory-approved parts.  
. 0 v 0 8 / 0 5  
e t y S 0 a 0 f 1 R e  
1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Important Safety Instructions  
• Before performing any maintenance on the gen-  
• Generators installed with an automatic transfer  
switch will crank and start automatically when  
normal (utility) source voltage is removed or is  
below an acceptable preset level. To prevent such  
automatic start-up and possible injury to person-  
nel, disable the generator’s automatic start circuit  
(battery cables, etc.) before working on or around  
the unit. Then, place a “Do Not Operate” tag on  
the generator control panel and on the transfer  
switch.  
erator, disconnect its battery cables to prevent  
accidental start-up. Disconnect the cable from the  
battery post indicated by a NEGATIVE, NEG or (–)  
first. Reconnect that cable last.  
• Never use the generator or any of its parts as a  
step. Stepping on the unit can stress and break  
parts, and may result in dangerous operating con-  
ditions from leaking exhaust gases, fuel leakage,  
oil leakage, etc.  
• In case of accident caused by electric shock, imme-  
diately shut down the source of electrical power.  
If this is not possible, attempt to free the victim  
from the live conductor. AVOID DIRECT CONTACT  
WITH THE VICTIM. Use a nonconducting imple-  
ment, such as a dry rope or board, to free the vic-  
tim from the live conductor. If the victim is uncon-  
scious, apply first aid and get immediate medical  
help.  
• Never wear jewelry when working on this equip-  
ment. Jewelry can conduct electricity resulting in  
electric shock, or may get caught in moving com-  
ponents causing injury.  
ELECTRICAL HAZARDS  
• All generators covered by this manual produce  
dangerous electrical voltages and can cause fatal  
electrical shock. Utility power delivers extremely  
high and dangerous voltages to the transfer switch  
as well as the standby generator. Avoid contact  
with bare wires, terminals, connections, etc., on  
the generator as well as the transfer switch, if  
applicable. Ensure all appropriate covers, guards  
and barriers are in place before operating the gen-  
erator. If work must be done around an operating  
unit, stand on an insulated, dry surface to reduce  
shock hazard.  
FIRE HAZARDS  
• Do not handle any kind of electrical device while  
standing in water, while barefoot, or while hands or  
feet are wet. DANGEROUS ELECTRICAL SHOCK  
MAY RESULT.  
• If personnel must stand on metal or concrete while  
installing, operating, servicing, adjusting or repair-  
ing this equipment, place insulative mats over a  
dry wooden platform. Work on the equipment only  
while standing on such insulative mats.  
• Keep a fire extinguisher near the generator at all  
times. Do NOT use any carbon tetra-chloride type  
extinguisher. Its fumes are toxic, and the liquid  
can deteriorate wiring insulation. Keep the extin-  
guisher properly charged and be familiar with its  
use. If there are any questions pertaining to fire  
extinguishers, consult the local fire department.  
• The National Electrical Code (NEC) requires the  
frame and external electrically conductive parts  
of the generator to be connected to an approved  
earth ground. This grounding will help prevent  
dangerous electrical shock that might be caused  
by a ground fault condition in the generator set or  
by static electricity. Never disconnect the ground  
wire.  
• Wire gauge sizes of electrical wiring, cables and  
cord sets must be adequate to handle the maxi-  
mum electrical current (ampacity) to which they  
will be subjected.  
• Before installing or servicing this (and related)  
equipment, make sure that all power voltage  
supplies are positively turned off at their source.  
Failure to do so will result in hazardous and pos-  
sibly fatal electrical shock.  
• Connecting this unit to an electrical system nor-  
mally supplied by an electric utility shall be by  
means of a transfer switch so as to isolate the  
generator electric system from the electric utility  
distribution system when the generator is operat-  
ing. Failure to isolate the two electric system power  
sources from each other by such means will result  
in damage to the generator and may also result  
in injury or death to utility power workers due to  
backfeed of electrical energy.  
EXPLOSION HAZARDS  
• Properly ventilate any room or building housing  
the generator to prevent build-up of explosive gas.  
• Do not smoke around the generator. Wipe up any  
fuel or oil spills immediately. Ensure that no com-  
bustible materials are left in the generator com-  
partment, or on or near the generator, as FIRE or  
EXPLOSION may result. Keep the area surround-  
ing the generator clean and free from debris.  
• These generator sets may operate using one of  
several types of fuels. All fuel types are potentially  
FLAMMABLE and/or EXPLOSIVE and should be  
handled with care. Comply with all laws regulat-  
ing the storage and handling of fuels. Inspect the  
unit’s fuel system frequently and correct any leaks  
immediately. Fuel supply lines must be prop-  
erly installed, purged and leak tested according to  
applicable fuel-gas codes before placing this equip-  
ment into service.  
• Diesel fuels are highly FLAMMABLE. Gaseous  
fluids such as natural gas and liquid propane  
(LP) gas are extremely EXPLOSIVE. Natural gas  
is lighter than air, and LP gas is heavier than air;  
install leak detectors accordingly.  
. 0 v 0 8 / 0 5  
e t y S 0 a 0 f 1 R e  
1-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Important Safety Instructions  
INTRODUCTION  
This symbol points out potential fire hazard.  
Thank you for purchasing this model of the standby  
generator set product line.  
This symbol points out potential electrical shock  
hazard.  
Every effort was expended to make sure that the  
information and instructions in this manual were  
both accurate and current at the time the manual was  
written. However, the manufacturer reserves the right  
to change, alter or otherwise improve this product(s)  
at any time without prior notice.  
The operator is responsible for proper and safe use  
of the equipment. The manufacturer strongly recom-  
mends that the operator read this Owner's Manual  
and thoroughly understand all instructions before  
using this equipment. The manufacturer also strong-  
ly recommends instructing other users to properly  
start and operate the unit. This prepares them if they  
need to operate the equipment in an emergency.  
READ THIS MANUAL THOROUGHLY  
If any portion of this manual is not understood, con-  
tact the nearest Authorized Service Dealer for start-  
ing, operating and servicing procedures.  
OPERATION AND MAINTENANCE  
It is the operator's responsibility to perform all safety  
checks, to make sure that all maintenance for safe  
operation is performed promptly, and to have the  
equipment checked periodically by an Authorized  
Service Dealer. Normal maintenance service and  
replacement of parts are the responsibility of the  
owner/operator and, as such, are not considered  
defects in materials or workmanship within the terms  
of the warranty. Individual operating habits and usage  
contribute to the need for maintenance service.  
Throughout this publication, and on tags and  
decals affixed to the generator, DANGER, WARNING,  
CAUTION and NOTE blocks are used to alert person-  
nel to special instructions about a particular service  
or operation that may be hazardous if performed  
incorrectly or carelessly. Observe them carefully.  
Their definitions are as follows:  
DANGER  
After this heading, read instructions that, if not  
strictly complied with, will result in personal injury  
or property damage.  
Proper maintenance and care of the generator ensure  
a minimum number of problems and keep operating  
expenses at a minimum. See an Authorized Service  
Dealer for service aids and accessories.  
Operating instructions presented in this manual  
assume that the standby electric system has been  
installed by an Authorized Service Dealer or other  
competent, qualified contractor. Installation of this  
equipment is not a “do-it-yourselfproject.  
After this heading, read instructions that, if not  
strictly complied with, may result in personal  
injury or property damage.  
HOW TO OBTAIN SERVICE  
After this heading, read instructions that, if not  
strictly complied with, could result in damage to  
equipment and/or property.  
When the generator requires servicing or repairs,  
simply contact an Authorized Service Dealer for  
assistance. Service technicians are factory-trained  
and are capable of handling all service needs.  
NOTE:  
After this heading, read explanatory statements  
that require special emphasis.  
When contacting an Authorized Service Dealer or the  
factory about parts and service, always supply the  
complete model number of the unit as given on the  
front cover of this manual or on the DATA LABEL  
affixed to the unit.  
These safety warnings cannot eliminate the hazards  
that they indicate. Common sense and strict compli-  
ance with the special instructions while performing  
the service are essential to preventing accidents.  
Four commonly used safety symbols accompany the  
DANGER, WARNING and CAUTION blocks. The type  
of information each indicates is as follows:  
AUTHORIZED SERVICE DEALER LOCATION  
To locate the nearest AUTHORIZED  
This symbol points out important safety infor-  
SERVICE DEALER, please call this number:  
mation that, if not followed, could endanger  
1-800-333-1322  
or locate us on the web at:  
personal safety and/or property of others.  
This symbol points out potential explosion  
hazard.  
www.generac.com  
. 0 v 0 8 / 0 5  
e t y S 0 a 0 f 1 R e  
1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
General Information  

Identification Code  
IDENTIFICATION RECORD  
Use this code to obtain important information about  
the generator. For example, if the code is:  
DATA LABEL  
Every generator set has a DATA LABEL that contains  
important information pertinent to the generator. The  
data label, which can be found attached to the gen-  
erator’s lower connection box, lists the unit’s serial  
number and its rated voltage, amps, wattage capacity,  
phase, frequency, rpm, power factor, etc.  
M Q T 1 0 0 5 4 A N S N A  
M — Designates generators capable of paralleling.  
NOTE: Only 100kW and 150kW, 6.8L units  
are currently available for this configura-  
tion.  
QT — Quiet Test Generator Series  
100 — kw Rating  
GENERATOR SET DATA  
MADE IN USA  
5.4 — Engine Size in Liters  
SERIAL  
RATED KVA  
RATED AMPS  
ALT RPM  
MODEL  
A Voltage Code: A = 120/240, Single-phase;  
G = 120/208, Three-phase; K = 277/480,  
Three-phase; J = 120/240, Three-phase;  
L = 346/600, Three-phase  
PHASE  
RATED KW  
RATED VOLTAGE  
POWER FACTOR  
ENGINE RPM  
HERTZ  
PRODUCTION DATE  
N Fuel: N = Natural Gas; V = Vapor Propane  
S — Enclosure Material: A = Aluminum; S  
= Steel (Corrosion Resistant Aluminum  
Enclosure Material, Steel is Standard)  
N — Emission Equipment: N = No Equipment;  
Y = Catalytic Converter and Air/Fuel Ratio  
Controller  
ALTERNATOR SUBTRANSIENT REACTANCE  
ALTERNATOR TRANSIENT REACTANCE  
CLASS  
ROTOR  
STATOR WINDING INSULATION AT 25°C AMBIENT  
GENERAC POWER SYSTEMS, INC.  
WAUKESHA, WI  
A — Industrial Dealer Product  
NOTE:  

Voltage Codes  
The identification code letter following the unit’s  
engine size is the generator’s “voltage code.”  
For actual information related to this particular  
model, please refer to the Manual Drawing Listing  
located at the end of this manual, or to the data  
label affixed to the unit.  

Groups and Assembly Numbers  

Generator Model and Serial Number  
The manual drawing listing lists the groups and cor-  
responding assembly numbers for each unit. The  
assembly numbers refer to exploded view drawing  
numbers that are applicable to the specific generator  
model. These drawings are located in the back half  
of this manual.  
This number is the key to numerous engineering and  
manufacturing details pertaining to your unit. Always  
supply this number when requesting service, order-  
ing parts or seeking information.  
. C v 0 4 / 0 6  
I d e n t y 0 0 1 R e  
2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Equipment Description  
EQUIPMENT DESCRIPTION  
COOLANT RECOMMENDATIONS  
This equipment is a revolving field, alternating cur-  
rent generator set. It is powered by a gaseous fueled  
engine operating at 1800 rpm for 4-pole direct drive  
units, 3600 rpm for 2-pole direct drive units and  
2300 - 3000 rpm for quiet drive gear units. See the  
Specifications section for exact numbers. The unit  
comes complete with a sound attenuated enclosure,  
internally mounted muffler, control console, main-  
line circuit breaker, battery charger, and protective  
alarms as explained in the following paragraph.  
Use a mixture of half low silicate ethylene glycol  
base anti-freeze and deionized water. Cooling system  
capacity is listed in the specifications. Use only deion-  
ized water and only low silicate anti-freeze. If desired,  
add a high quality rust inhibitor to the recommended  
coolant mixture. When adding coolant, always add  
the recommended 50-50 mixture.  
Do not use any chromate base rust inhibitor  
All AC connections, including the power leads from  
the alternator, 120 volt battery charger input and  
control connections to the transfer switch are avail-  
able in the main connection box.  
with ethylene glycol base anti-freeze or chro-  
mium hydroxide (“green slime”) forms and will  
cause overheating. Engines that have been oper-  
ated with a chromate base rust inhibitor must  
be chemically cleaned before adding ethylene  
glycol base anti-freeze. Using any high silicate  
anti-freeze boosters or additives will also cause  
overheating. The manufacturer also recommends  
that any soluble oil inhibitor is NOT used for this  
equipment.  
The generator incorporates the following generator  
features:  
• Rotor and Stator insulation is Class H rated as  
defined by NEMA MG1-32.6, NEMA MG1-1.66.  
The generator is self ventilated and drip-proof con-  
structed.  
• The voltage waveform deviation, total harmonic  
content of the AC waveform and telephone influ-  
ence factor have been evaluated and are acceptable  
according to NEMA MG1-32.  
DANGER  
Do not remove the radiator pressure cap while  
the engine is hot or serious burns from boiling  
liquid or steam could result.  
Ethylene glycol base antifreeze is poisonous.  
Do not use mouth to siphon coolant from the  
radiator, recovery bottle or any container. Wash  
hands thoroughly after handling. Never store  
used antifreeze in an open container because  
animals are attracted to the smell and taste of  
antifreeze even though it is poisonous to them.  
ENGINE OIL RECOMMENDATIONS  
The unit has been filled with 15W-40 engine oil at  
the factory. Use a high-quality detergent oil classified  
For Service CC, SD, SE, SF.” Detergent oils keep the  
engine cleaner and reduce carbon deposits. Use oil  
having the following SAE viscosity rating, based on  
the ambient temperature range anticipated before the  
next oil change:  
Temperature  
Above 80° F (27° C)  
32° to 80° F (0° to 27° C)  
Below 32° F (0° C)  
Oil Grade (Recommended)  
SAE 30W or 15W-40  
SAE 20W-20 or 15W-40  
See Note  
Any attempt to crank or start the engine before  
it has been properly serviced with the recom-  
mended oil may result in an engine failure.  
NOTE:  
For temperatures below 32° F, it is strongly recom-  
mended to use the optional Cold Weather Start Kit  
(part number listed in the Specification Section).  
The oil grade for temperatures below 32° F is 5W-  
30 synthetic oil.  
. 0 v 0 8 / 0 5  
E q u i p 0 0 1 R e  
3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Engine Protective Devices  
OIL PRESSURE SENSING  
ENGINE PROTECTIVE DEVICES  
The standby generator may be required to operate for  
long periods of time without an operator on hand to  
monitor such engine conditions as coolant tempera-  
ture, oil pressure or rpm. For that reason, the engine  
has several devices designed to protect it against  
potentially damaging conditions by automatically  
shutting down the unit when the oil pressure is too  
low, the coolant temperature is too high, the coolant  
level is too low, or the engine is running too fast.  
An analog Oil Pressure Sender (OPS) is used for  
monitoring the engine oil pressure. This sender  
allows the control panel to measure and display the  
Engine oil pressure.  
The OPS is a resistive device, whose resistance  
changes based on engine oil pressure. The resistance  
of the sender results in a voltage being developed  
across the sender. As the oil pressure increases,  
the resistance will decrease, causing the voltage to  
decrease. This changing voltage is converted to 4-  
20mA signal by a signal conditioner module. The  
corresponding 4-20mA signal is read by the control  
panel and displayed as the oil pressure.  
NOTE:  
Engine protective switches and sensors are men-  
tioned here for the reader's convenience. Also refer  
to the applicable control panel manual for addi-  
tional automatic engine shutdown information.  
The control panel will monitor and display oil pres-  
sure anytime the DC input to the control panel is  
present.  
COOLANT TEMPERATURE SENSING  
An analog Water Temperature Sender (WTS) is locat-  
ed in the engine's cooling system. This sender is con-  
nected to the panel and allows the panel to monitor  
and display the temperature of the coolant system.  
Should the oil pressure drop below the 8 psi range,  
the engine shutdown is initiated. The unit should not  
be restarted until oil is added. Turn the AUTO/OFF/  
MANUAL switch to the OFF position, then back to  
AUTO to restart.  
The WTS is a resistive device whose resistance chang-  
es based on coolant temperature. The resistance of  
the sender results in a voltage being developed across  
the sender. As the Coolant temperature increases,  
the resistance will decrease, causing the voltage to  
decrease. This changing voltage is converted to 4-  
20mA signal by a signal conditioner module. The  
corresponding 4-20mA signal is read by the control  
panel and displayed as the coolant temperature.  
OVERCRANK SHUTDOWN  
When the control panel receives a start signal, it ini-  
tiates the programmed starting sequence. The start  
sequence consists of the number of crank attempts,  
the length of each crank attempt, and the rest time  
between each crank attempt. If the engine has not  
started by the end of the final crank attempt, an  
Overcrank alarm is generated, the control panel will  
sound the alarm and display the message "Failed to  
start".  
The control panel will monitor and display the cool-  
ant temperature anytime the DC input to the control  
panel is present.  
If the temperature exceeds approximately 140° C  
(284° F), the engine shutdown will be initiated. The  
generator will automatically restart and the display  
will reset once the temperature has returned to an  
operating level.  
OVERSPEED SHUTDOWN  
A speed circuit controls engine cranking, start-up,  
operation and shutdown. Engine speed signals are  
delivered to the circuit board whenever the unit is  
running. Should the engine over speed above a safe,  
preset value, the circuit board initiates an automatic  
engine shutdown. Contact the nearest Authorized  
Dealer if this failure occurs.  
LOW COOLANT LEVEL  
A Low Coolant Level (LCL) sensor is placed in the  
generators coolant system. This sensor allows the  
panel to detect a Low Coolant Level condition.  
RPM SENSOR LOSS SHUTDOWN  
If the speed signal to the control panel is lost, engine  
shutdown will occur.  
The LCL is a resistive device whose resistance changes  
rapidly based on the presence or absence of coolant.  
The resistance of the LCL results in a voltage being  
developed across the LCL. This voltage changes as  
the resistance changes. This changing voltage is con-  
verted to 4-20mA signal by a signal conditioner mod-  
ule. The corresponding 4-20mA signal is read by the  
control panel and displayed as the low coolant level.  
DC FUSE  
This fuse is located inside of the control panel. It  
protects the panel wiring and components from  
damaging overload. Always remove this fuse before  
commencing work on the generator. The unit will  
not start or crank if the fuse is blown. Replace the  
fuse with one of the same size, type, and rating. (See  
the exploded views and parts lists at the end of this  
If the level of the engine coolant drops below the level  
of the low coolant level sensor, the engine shutdown  
will be initiated.  
manual for replacement part number.)  
. B v 1 0 / 0 5  
E n g P r o t 0 0 2 R  
4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Fuel Systems  
PROPANE VAPOR WITHDRAWAL FUEL SYSTEM  
FUEL SYSTEM  
This type of system utilizes the vapors formed above  
the liquid fuel in the supply tank. Approximately 10  
to 20 percent of the tank capacity is needed for fuel  
expansion from the liquid to the vapor state. The  
vapor withdrawal system is generally best suited for  
smaller engines that require less fuel. The installer  
should be aware of the following:  
FUEL REQUIREMENTS  
The standby generator may be equipped with one of  
the following fuel systems:  
• Natural gas fuel system  
• Propane vapor (PV) fuel system  
• Liquid propane (LP) fuel system  
The Manual Drawing Listing that is affixed to the  
unit includes the “Identification Code,” which may be  
used to identify the type of fuel system installed on  
the unit.  
• The natural gas and LP gas systems are similar.  
However, the natural gas system delivers gas at a  
pressure of approximately five inches water col-  
umn to the carburetor.  
• When ambient temperatures are low and engine  
fuel consumption is high, the vapor withdrawal  
system may not function efficiently.  
• Ambient temperatures around the supply tank  
must be high enough to sustain adequate vaporiza-  
tion, or the system will not deliver the needed fuel  
volume.  
• In addition to the cooling effects of ambient air, the  
vaporization process itself provides an additional  
cooling effect.  
Recommended fuels should have a Btu content of at  
least 1,000 Btu's per cubic foot for natural gas; or at  
least 2,520 Btu's per cubic foot for LP gas. Ask the  
fuel supplier for the Btu content of the fuel.  
Required fuel pressure for natural gas is 11 inches  
to 14 inches water column (0.4 to 0.5 psi); and for  
liquid propane, 11 inches to 14 inches of water  
column (0.4 to 0.5 psi).  
NOTE:  
Any piping used to connect the generator to the  
fuel supply should be of adequate size to ensure  
the fuel pressure NEVER drops below 11 inches  
water column for natural gas or 11 inches water  
column for liquid propane for all load ranges.  
LP FUEL SYSTEM  
LP is supplied as a liquid in pressure tanks. It is  
usually made up of propane, butane, or a mixture of  
the two gases. Propane tends to vaporize readily even  
at temperatures as low as -20° F (-29° C). However,  
butane reverts to its liquid state when temperatures  
drop below 32° F (0° C).  
NOTE:  
It is the responsibility of the installer to make sure  
that only the correct recommended fuel is sup-  
plied to the generator fuel system. Thereafter, the  
owner/operator must make certain that only the  
proper fuel is supplied.  
LP in a liquid withdrawal system must be converted  
to its gaseous state before it is introduced into the  
engine carburetor. A vaporizer-converter is generally  
used to accomplish this. In such a converter, heated  
engine coolant is ported through the converter to  
provide the necessary heat for conversion of the fuel  
from a liquid to a gaseous state.  
NATURAL GAS FUEL SYSTEM  
Natural gas is supplied in its vapor state. In most  
cases, the gas distribution company provides piping  
from the main gas distribution line to the standby  
generator site. The following information applies to  
natural gas fuel systems.  
• Gas pressure in a building is usually regulated by  
national, state and local codes.  
To reduce gas pressure to a safe level before  
the gas enters a building, a primary regulator is  
needed. The natural gas supplier may or may not  
supply such a regulator.  
• It is the responsibility of the gas supplier to make  
sure sufficient gas pressure is available to operate  
the primary regulator.  
• Gas pressure at the inlet to the fuel shutoff sole-  
noid should not exceed approximately 14 inches  
water column (0.5 psi). Optimum pressure at the  
fuel shutoff solenoid is 11 inches water column  
(0.4 psi).  
. A v 0 5 / 0 6  
F u e l S y s 0 0 2 R  
5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Specifications  
Engine Lubrication System  
SPECIFICATIONS  
Type of Oil Pump...................................................................... Gear  
Oil Filter.............................................................Full Flow, Cartridge  
Crankcase Oil Capacity....................................................6 U.S. qts.  
GENERATOR  
Type............................................................................. Synchronous  
Rotor Insulation ................................................................... Class H  
Stator Insulation .................................................................. Class H  
Total Harmonic Distortion......................................................< 3.5%  
Telephone Interference Factor (TIF)..........................................< 50  
Alternator Output Leads 3-phase........................................... 6-wire  
Bearings .........................................................................Sealed Ball  
Coupling ..........................................................................Gear Drive  
Load Capacity (Standby Rating) ..........................................100kW*  
COOLING SYSTEM  
Type.......................................................................................Closed  
Water Pump.................................................................... Belt Driven  
Fan Speed................................................................................ 1670  
Fan Diameter.....................................................................26 inches  
Fan Mode ................................................................................Puller  
Air Flow (inlet air including alternator and  
combustion air).......................................................... 5500 ft3/min.  
Coolant Capacity........................................................ (4.5 U.S. gal.)  
Heat Rejection to Coolant ..........................................342,000 Btu/h  
Maximum Operating Air Temp. on Radiator ..............60° C (150° F)  
Maximum Ambient Temperature................................50° C (140° F)  
* NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349,  
ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural  
gas.  
Excitation System............................................................. Brushless  
Generator Output Voltage/kW - 60 Hz  
120/240V, 1-phase, 1.0 pf  
120/208V, 3-phase, 0.8 pf  
kW  
100  
100  
100  
Amp CB Size  
417  
347  
150  
450  
400  
175  
FUEL SYSTEM  
277/480V, 3-phase, 0.8 pf  
Type of Fuel..................................................LP Vapor/Natural Gas*  
Carburetor ...................................................................... Down Draft  
Secondary Fuel Regulator .................................................Standard  
Fuel Shut-off Solenoid........................................................Standard  
Operating Fuel Pressure .................... 11 in. - 14 in. Water Column  
Generator Locked Rotor KVA Available @ Voltage Dip of 35%  
Single-phase or 208 3-phase........................................... 200 KVA  
480V, 3-phase .................................................................. 240 KVA  
ENGINE  
Make................................................................................... Generac  
Model......................................................................................V-type  
Cylinders and Arrangement.......................................................... 10  
Displacement.......................................................................6.8 Liter  
Bore...................................................................................... 3.55 in.  
Stroke ................................................................................... 4.17 in.  
Compression Ratio..................................................................9-to-1  
Air Intake System ...............................................Naturally Aspirated  
Valve Seats....................................................................... Hardened  
Lifter Type.......................................................................... Hydraulic  
Fuel Consumption - ft3/hr (Natural Gas/LPV)  
Exercise  
Cycle  
130/52  
25%  
Load  
50%  
Load  
75%  
Load  
991/400 1260/507  
100%  
Load  
371/149  
713/287  
* Engine is not field convertible between natural gas and propane. Jet size and ignition timing are  
factory set for the specific fuel.  
ELECTRICAL SYSTEM  
Battery Charge Alternator ............................................12V, 30 Amp  
Static Battery Charger....................................................12V, 2 Amp  
Recommended Battery................................................ 24F 525CCA  
System Voltage.....................................................................12 Volts  
Engine Parameters  
Rated Synchronous RPM..............................................60 Hz, 2300  
HP at rated kW................................................................60 Hz, 168  
Voltage Regulator  
Type................................................................................. Full Digital  
Sensing................................................................................ 3-phase  
Regulation ............................................................................. 1/4%  
Features ............................................Built into H-100 Control Panel  
V/F Adjustable, Adjustable  
Exhaust System  
Exhaust Flow at Rated Output 60 Hz.................................. 888 cfm  
Exhaust Temperature at Rated Output.................................. 960° F  
Combustion Air Requirements (Natural Gas)  
Flow at rated power, 60 Hz ................................................. 262 cfm  
Voltage and Gain  
Power Adjustment for Ambient Conditions  
Temperature Deration  
3% for every 10° C above °C..................................................... 25  
1.65% for every 10° above °F.................................................... 77  
Altitude Deration  
Governor  
Type.................................................................................. Electronic  
Frequency Regulation ...................................................Isochronous  
Steady State Regulation...................................................... 0.25%  
Adjustments:  
1% for every 100 m above m................................................... 183  
3% for every 1000 ft. above ft. ................................................. 600  
Speed............................................................................ Selectable  
Controller.............................................. H-panel  
. C v 1 1 / 0 5  
G e n S p e c 0 0 9  
6-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Specifications  
Figure 1 — Interconnections  
COLD WEATHER KIT  
For cold climates, optional cold weather kit (part num-  
ber 0F6148A) is recommended. The kit includes:  
• Battery Warmer  
• 4” Junction Box with hardware  
• 700 Cold Cranking Amp Battery  
• 6 qt. pack 5W-30 synthetic oil (engine)  
• 1 qt. 75W90 synthetic gear oil (gear drive)  
. C v 1 1 / 0 5  
G e n S p e c 0 0 9 R e  
6-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Specifications  
NOTE:  
5.4L & 6.8L IGNITION DESCRIPTION  
This single-fire Ignition is intended to operate with  
a 10-cylinder, 6.8L engine and an 8-cylinder, 5.4L  
engine.  
The ignition cover does not need to be removed to  
see the LED.  
The 6.8L engine uses a 40-1 crank sensor, a mag-  
pickup CAM sensor and individual coil-on-plug coils  
for each spark-plug.  
IGNITION SHUTDOWN ON LOSS OF CRANK  
OR CAM SIGNALS  
The ignition will stop firing the coils immediately fol-  
lowing the loss of the crank signal. The ignition will  
stop firing the coils after approx. 3 seconds following  
the loss of the cam signal.  
The 5.4L engine uses a 36-1 crank sensor, a mag-  
pick-up CAM sensor and individual coil-on-plug coils  
for each spark-plug.  
With a single-fire ignition, each high-voltage coil out-  
put is connected to one spark plug resulting in that  
spark plug being fired only during the compression  
cycle.  
DIAGNOSTIC BLINK PATTERNS (RED LED  
LOCATED ON THE IGNITION CONTROL  
BOARD)  
Engine Timing versus Engine Speed for the 6.8L  
engine is:  
During normal ignition operation the RED LED  
flashes at a 0.5 sec ON and a 0.5 sec OFF rate. This  
is considered one (1) blink.  
RPM  
1800 rpm  
3600 rpm  
NG/LP Engine Timing (BTDC)  
22 degrees  
LED Fault Code with Priority as shown:  
24 degrees  
1. No Crank Signal: LED blinks 2 times, is OFF for  
3.0 seconds and then repeats  
Engine Timing versus Engine Speed for the 5.4L  
engine is:  
2. No CAM Signal: LED blinks 3 times, is OFF for  
RPM  
1800 rpm  
3600 rpm  
NG/LP Engine Timing (BTDC)  
26 degrees  
3.0 seconds and then repeats  
Only one fault is displayed at a time. If multiple faults  
exist then the highest priority fault must be resolved  
prior to a lower priority fault being displayed. In the  
event that an ignition fault has occurred the ignition  
will wait 60 seconds before powering down.  
26 degrees  
IGNITION POWER-UP INPUT ("56 LINE  
INPUT")  
When battery voltage is applied to this input the igni-  
tion will power-up. For the ignition to power itself  
down, battery voltage must be removed from this  
input.  
NOTE:  
The ignition cover does not need to be removed to  
see the LED.  
IGNITION ENABLE ("14 LINE INPUT")  
This input must be connected to the +12V battery for  
the ignition to turn-on the coils. If this input is con-  
nected to battery ground the ignition will stop firing  
the coils and will power down within approximately  
2 seconds. In the event that an ignition fault has  
occurred, however, the ignition will wait 60 seconds  
before powering down. This allows time to view the  
diagnostic LED located on the ignition board.  
. C v 1 1 / 0 5  
G e n S p e c 0 0 9  
6-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
General Information  
GENERATOR AC LEAD CONNECTIONS  
ALTERNATOR POWER WINDING  
CONNECTIONS  
See “Voltage Codes”. This generator may be rated  
at any one of three voltages, either single-phase or  
three-phase. The electrical wires in the unit’s AC con-  
nection (lower) panel should be installed according to  
the number of leads and the voltage/phase required  
for the application. If there are any questions regard-  
ing lead connection, refer to the wiring diagrams at  
the back of this manual.  
3-PHASE ALTERNATORS  
The generator is designed to supply 3-phase electri-  
cal loads. Electric power is produced in the alterna-  
tor power windings. These windings were connected  
at the factory to the main circuit breaker with a “Y”  
configuration as shown in Figures 7.2 and 7.3.  
Voltage codes apply to the type of stator assembly  
installed on a particular generator.  
The rated voltage between circuit breaker terminals  
E1-E2, E1-E3 and E2-E3 is either 480V or 208V  
depending on the model.  
FOUR-LEAD, SINGLE-PHASE STATOR  
The rated voltage between each circuit breaker termi-  
nal and the neutral point 00 is either 277V or 120V  
depending on the model.  
Four-lead generators are built to supply electrical  
loads with voltage code "A" (240V, 1-phase, 60Hz).  
Electrical power is produced in the stator power  
windings. These windings were connected at the fac-  
tory to the main circuit breaker as shown in Figure  
7.1.  
Figure 7.2 — Stator Power Winding  
Connections - 3-phase, 277/480V (12 Lead)  
The rated voltage between each circuit breaker ter-  
minal is 240V. The rated voltage between each circuit  
breaker terminal and the neutral point 00 is 120V.  
E1  
S1  
Figure 7.1 — Four-lead, Single-phase Stator  
S4  
S7  
L - L  
S10  
S11  
S12  
S8  
S9  
S5  
S6  
S3  
E3  
S2  
E2  
L - N  
Figure 7.3 — Stator Power Winding  
Connections - 3-phase, 120/208V (12 Lead)  
E1  
S7  
S1  
L - L  
S10  
S12  
S4  
S5  
S9  
S2  
S6  
S11  
E3  
E2  
S3  
S8  
L - N  
. 0 v 0 8 / 0 5  
C A C o n n 0 0 2 R e  
7-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Installation  
PRIOR TO INITIAL START-UP  
INSTALLATION  
Refer to the separate “Installation Guide QT Product  
Line” supplied with the unit.  
Prior to initially starting the generator, it must  
be properly prepared for use. Any attempt to  
crank or start the engine before it has been  
properly serviced with the recommended types  
and quantities of engine fluids (oil, coolant, fuel,  
etc.) may result in an engine failure.  
PREPARATION BEFORE START-UP  
The instructions in this section assume that the  
standby generator has been properly installed, ser-  
viced, tested, adjusted and otherwise prepared for  
use by a competent, qualified installation contractor.  
Be sure to read the “Safety Rules”, as well as all other  
safety information in this manual, before attempting  
to operate this (and related) equipment.  
ENGINE COOLANT  
Have the engine cooling system properly filled with  
the recommended coolant mixture. Check the system  
for leaks and other problems. See “Specifications”  
and “Coolant” sections.  
Before starting the generator for the first time, the  
installer must complete the following procedures. For  
follow-up maintenance information and/or service  
intervals, please refer to the “Maintenance” section  
and the “Service Schedule”.  
BELT TENSION  
Check-the engine-fan belt tension and condition prior  
to placing the unit into service and at recommended  
intervals. Belt tension is correct when a force of  
approximately 22 pounds (10 kg), applied midway  
between pulleys, deflects the belt about 3/8- to 5/8-  
inch (10 to 16 mm).  
TRANSFER SWITCH  
If this generator is used to supply power to any elec-  
trical system normally powered by an electric utility,  
the National Electrical Code requires that a transfer  
switch be installed. The transfer switch prevents elec-  
trical backfeed between two different electrical sys-  
tems. (For additional information, see the applicable  
transfer switch manual for this unit.) The transfer  
switch, as well as the generator and other standby  
components, must be properly located and mounted  
in strict compliance with applicable codes, standards  
and regulations.  
ELECTRICAL SYSTEM  
Make sure the generator is properly connected to an  
approved earth ground.  
Make sure the generator battery is fully charged,  
properly installed and interconnected, and ready for  
use.  
FUEL SYSTEM  
Check to ensure that there are no loose electrical con-  
nections. Restrain any loose wires to keep them clear  
of any moving generator set components.  
Make sure the fuel supply system to the genera-  
tor (a) delivers the correct fuel at the correct pres-  
sure and (b) is properly purged and leak tested  
according to code. No fuel leakage is permitted. See  
“Specifications” for more information.  
INITIAL INSPECTION FOR QT GENSET  
STARTUP  
GENERATOR SET LUBRICATION  
Inspect for the following.  
Check the engine crankcase oil level before operating  
and add oil to the proper level – the dipstick “FULL”  
mark. Never operate the engine with the oil level  
below the dipstick ADD” mark. See “Specifications”  
and “Engine Oil Recommendations”.  
• Freight Damage.  
• Manuals present.  
• Fluid Levels (Oil, coolant, battery, Gear Drive).  
• Correct fuel piping.  
• Correct muffler installation for external applica-  
NOTE:  
tion.  
This engine is shipped from the manufacturer  
with “break-in” oil. This oil should be changed  
after 30 hours of operation.  
• Adequate air flow, clearances and ventilation per  
installation drawings and applicable codes.  
• Correct AC and DC wire size, connections and  
grounding. Control and communication wiring to/  
from the transfer switch must be run in a separate  
conduit from the AC power leads.  
• Battery charger connection to 120 VAC.  
• Communication wires connected between transfer  
switch and generator (HTS only).  
Check the oil level in the generator gearbox (if so  
equipped) prior to initial use and at the intervals  
indicated by the “Service Schedule.” The recom-  
mended oil is SAE 90 gear lubricant.  
Also, if the engine is equipped with a mechanical gov-  
ernor, make sure the governor is properly lubricated  
with clean engine oil.  
• Unit secured to pad.  
. C v 0 5 / 0 6  
I n s t a l l 0 0 1 R e  
8-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Installation  
• Check voltage at the generator terminals.  
START-UP CHECKLIST  
For 3-phase units, check phase rotation at the  
transfer switch terminals. The generator phase  
rotation must match the utility phase rotation.  
• Check for coolant, fuel, oil, and exhaust leaks.  
• Close the generators main line circuit breaker.  
Turn the generator set off.  
Before working on the generator, ensure the fol-  
lowing:  
• The AUTO/OFF/MANUAL switch is in the OFF  
position.  
• Connect the UTILITY supply to the transfer  
• The 120VAC supply to the battery charger is  
switch.  
switched OFF.  
• Set the AUTO/OFF/MANUAL switch to AUTO.  
• Disconnect utility power before the transfer  
switch.  
PREPARATION FOR START-UP  
Engine should start, transfer to load.  
Run at least 15 minutes on generator power.  
Make certain all 3-phase loads are functioning  
correctly (correct phase rotation).  
• Ensure that the 120VAC circuit breaker to the bat-  
tery charger is open.  
• Remove the fuse from the the control panel. For  
the H-100 and R-series: Open the front door of the  
control box and remove the 15 Amp ATO fuse in  
the lower left-hand corner of the control box.  
• Connect the battery cables to the battery. Attach  
negative battery cable last.  
• Reconnect Utility power  
Transfer switch will transfer back to Utility and  
engine will shut down within the given time  
parameters set up for the specific transfer switch  
and controller.  
• Close the 120VAC circuit breaker to the battery  
• Install all covers, access plates and door panels.  
• Put the Owners Manual in a safe and accessible  
place.  
charger.  
• Measure the voltage at the battery before and after  
the charger is turned on.  
• Make certain the AUTO/OFF/MANUAL switch is in  
Verify all AC electrical connections are tight at the  
circuit breaker and transfer switch.  
• Visually inspect entire area looking for loose paper,  
plastic wrappings, leaves, etc.  
the AUTO position.  
START-UP INSPECTION  
• Check all hoses clamps fittings for leaks or dam-  
When a start-up is performed by an Authorized  
Service Dealer, a standard three-part form titled  
“Start-up Inspection for Standby Power Systems”  
(part no. 067377), should be completed by the instal-  
lation technician or engineer. See page 1-3 for infor-  
mation on locating the nearest Authorized Service  
Dealer. The installer should complete the form and  
disseminate copies as follows:  
age.  
• Check all electrical plugs throughout the genera-  
tor. Ensure each plug is seated correctly and fully  
inserted into its receptacle.  
Verify the AUTO/OFF/MANUAL switch is in OFF  
position.  
• Open the valve to the engine fuel line.  
• Bleed the fuel system of air. (necessary for long fuel  
lines).  
• Open the generator main line circuit breaker.  
• Connect a manometer to the gas line and record  
the static pressure. It must be as listed in the  
Specifications.  
• White copy: Mail to Generac Warranty Department,  
P.O. Box 340, 211 Murphy Dr., Eagle, WI 53119-  
2062.  
• Pink Copy: For service file of installing dealer.  
Yellow Copy: For the customer’s records.  
• Insert the fuse into the control panel.  
• Move the AUTO/OFF/MANUAL switch to the MAN-  
UAL position. The engine should now crank and  
start.  
. C v 0 5 / 0 6  
I n s t a l l 0 0 1 R e  
8-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Operation  
GENERATOR CONTROL AND  
OPERATION  
Do not crank the engine continuously for longer  
than 30 seconds, or the heat may  
damage the starter motor.  
Refer to the appropriate control panel operator’s  
manual for this unit.  
• Let engine stabilize and warm up.  
OPERATING UNIT WITH MANUAL  
• Check all applicable instrument and gauge read-  
ings. When certain that all readings are correct,  
move the transfer switch manual handle to its  
STANDBY (GENERATOR) position, i.e., load cir-  
cuits supplied by the generator.  
TRANSFER SWITCH  
If the generator was installed in conjunction with a  
transfer switch capable of manual operation only, the  
following procedure applies. A manually operated  
transfer switch is one that will not provide automatic  
start-up and does not include an intelligence circuit.  
• Set the standby generator’s main line circuit break-  
er to its ON (or CLOSED) position.  
• Load circuits are now powered by the standby  
generator.  
ENGINE START-UP AND TRANSFER  
For additional information, refer to the applicable  
control panel manual for this unit, as well as any lit-  
erature pertaining to the specific transfer switch.  
RETRANSFER AND SHUTDOWN  
For additional information, refer to the applicable  
control panel manual for this unit, as well as any lit-  
erature pertaining to the specific transfer switch.  
DANGER  
To transfer the load back to the utility power source  
and shut down the generator, follow these direc-  
tions:  
The Maintenance Disconnect Switch and the  
AUTO/OFF/MANUAL switches (if so equipped)  
must be set properly, or the generator will crank  
and start as soon as the utility power to the  
transfer switch is turned off. Refer to applicable  
control panel and transfer switch manuals for  
more information.  
• Set the standby generator’s main line circuit break-  
er to its OFF (or OPEN) position.  
• Manually move the transfer switch handle to its  
UTILITY (NORMAL) position, i.e., load circuits  
connected to the utility.  
Turn ON the utility power supply to the transfer  
switch, using the means provided (such as the util-  
ity power source main line circuit breaker).  
• Let the generator run at no-load for a few minutes  
to stabilize internal temperatures.  
Do not proceed until certain that utility source  
voltage is available to the transfer switch and  
the transfer switch main contacts are set to  
UTILITY.  
Do not attempt manual operation until all power  
supplies to the transfer switch have been posi-  
• Shut down the generator.  
tively turned off, or extremely dangerous - pos-  
sibly lethal - electrical shock will result.  
OPERATING UNIT WITH AUTOMATIC  
Transfer switch enclosure doors should be kept  
TRANSFER SWITCH  
closed and locked. Only authorized personnel  
If the generator has been installed with an automatic  
transfer switch, such as an RTS, HTS, or GTS-type  
transfer switch, the engine may be started and  
stopped automatically or manually.  
should be allowed access to the transfer switch  
interior. Extremely high and dangerous voltages  
are present in the transfer switch.  
In order to transfer load from the utility source to the  
generator, follow these directions:  
NOTE:  
Refer to the applicable manual for your trans-  
fer switch and to “Transfer Switch Start Signal  
Connections”. In addition, please note the dangers  
under “Engine Start-up and Transfer.”  
Turn OFF or disconnect the utility power circuit  
to the transfer switch, using the means provided  
(such as the utility source main line circuit break-  
er).  
• Set the transfer handle to its UTILITY (NORMAL)  
position with load circuits connected to the utility  
power supply.  
• Set the standby generator’s main line circuit break-  
er to its OFF (or OPEN) position.  
• Start the generator.  
. 0 v 0 8 / 0 5  
O p e r 0 0 1 R e  
9-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Maintenance  
MAINTENANCE PERFORMED BY  
AUTHORIZED SERVICE FACILITIES  
The exhaust system parts from this product get  
extremely hot and remain hot after shutdown.  
High grass, weeds, brush, leaves, etc. must  
remain clear of the exhaust. Such materials may  
ignite and burn from the heat of the exhaust  
system.  
Before working on the generator, ensure the fol-  
lowing:  
• The AUTO/OFF/MANUAL switch is in the OFF  
position.  
• The 15A fuse has been removed from the con-  
CHECKING FLUID LEVELS  
trol box.  
• The 120VAC supply to the battery charger is  
switched OFF.  
CHECK ENGINE OIL  
Check engine crankcase oil level (Figure 10.1) at least  
every 20 hours of operation, or prior to use.  
EVERY THREE MONTHS  
• Remove oil dipstick and wipe dry with a clean, lint-  
free cloth.  
1. Check battery state of charge and condition.  
2. Inspect and test fuel system.  
3. Check transfer switch.  
4. Inspect exhaust system.  
5. Check engine ignition system.  
6. Check fan belts.  
• Install oil dipstick, then remove again.  
• Oil should be between FULL and ADD marks.  
• If oil level is below the dipstick ADD mark,  
remove oil fill cap. Add the recommended oil to  
bring oil level up to the FULL mark. DO NOT  
FILL ABOVE THE “FULLMARK. See “Engine Oil  
Recommendations” for recommended oils.  
ONCE EVERY SIX MONTHS  
1. Test Engine Safety Devices (low oil pressure, low  
coolant level, high coolant temperature).  
Figure 10.1 - Oil Dipstick and Oil Fill Cap  
Oil Fill  
ONCE ANNUALLY  
Oil  
Dipstick  
1. Test engine governor. Adjust or repair, if needed.  
2. Clean, inspect generator.  
3. Flush cooling system.  
FIRST 100 OPERATING HOURS  
1. Change engine oil and oil filter. (After initial  
change, service engine oil and filter at 150 operat-  
ing hours or 6 months, whichever comes first.)  
EVERY 500 OPERATING HOURS  
1. Service air cleaner.  
2. Check starter.  
3. Check engine DC alternator.  
Oil Filter  
COOLING SYSTEM  
Air intake and outlet openings in the generator com-  
partment must be open and unobstructed for contin-  
ued proper operation. This includes such obstruc-  
tions as high grass, weeds, brush, leaves and snow.  
BATTERY FLUID  
Check battery electrolyte fluid at least once weekly.  
Fluid should cover separators in all battery cells. If  
fluid level is low, add distilled water to cover tops of  
separators. DO NOT USE TAP WATER IN BATTERY.  
Without sufficient cooling and ventilating air flow, the  
engine/generator quickly overheats, which causes it  
to shut down.  
. 0 v 0 8 / 0 5  
M a i n t 0 0 4 R e  
10-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Maintenance  
ENGINE COOLANT  
CHECK FAN BELT  
Check coolant level in coolant recovery bottle. See the  
“Specifications” section.  
• Inspect fan belts every three months. Replace any  
damaged, deteriorated, worn or otherwise defec-  
tive belt.  
• Check fan belt tension. Thumb pressure, exerted  
midway between pulleys, should deflect about 3/8  
to 5/8 inch. Adjust belt tension as required.  
• Add recommended coolant mixture as necessary.  
• Periodically remove radiator pressure cap to make  
sure the coolant recovery system is functioning  
properly. Coolant should be at bottom of radiator  
filler neck. If coolant level is low, inspect gasket in  
radiator pressure cap. Replace cap, if necessary.  
To have pressure cap tested, contact an Authorized  
Service Dealer. Inspect cooling system and coolant  
recovery system for leaks.  
INSPECT ENGINE GOVERNOR  
Visually inspect electronic governor.  
DANGER  
Do not attempt to adjust the governor. Only  
qualified service facilities should adjust the gov-  
MAINTENANCE OWNER/  
OPERATOR CAN PERFORM  
ernor. Excessively high operating speeds are dan-  
gerous and increase the risk of personal injury.  
Low speeds impose a heavy load on the engine  
when adequate engine power is not available  
and may shorten engine life. Correct rated fre-  
quency and voltage are supplied only at the  
proper governed speed. Some connected electri-  
cal load devices may be damaged by incorrect  
frequency and/or voltage. Only qualified service  
technicians should adjust the governed speed.  
CHECK ENGINE OIL LEVEL  
Refer to the “Checking Fluid Levels” section.  
CHECK BATTERY  
• Check battery fluid level each week as outlined  
under “Check Fluid Levels”.  
• Check battery cables for condition, tightness, cor-  
rosion or damage. Clean, tighten or replace as  
necessary.  
CHANGING ENGINE OIL  
Refer to maintenance performed by authorized ser-  
vice facilities for engine oil and filter change frequen-  
cies.  
EXERCISE SYSTEM  
Start the generator engine at least once every seven  
days and let it run at least 20 minutes. See the  
“Weekly Exercise Cycle” section.  
Drain the oil while the engine is still warm from run-  
ning. This means warm up the engine, shut it down  
and drain immediately as follows:  
INSPECT COOLING SYSTEM  
1. Remove OIL DRAIN HOSE from its retaining  
clip.  
2. Loosen and remove OIL DRAIN HOSE CAP. Drain  
oil completely into suitable container.  
3. When all oil has drained, install and tighten OIL  
DRAIN HOSE CAP, and re-install into its retaining  
clip.  
• Inspect engine cooling system at least once each  
month.  
• Check hoses for damage, deterioration, leaks, etc.  
Correct any discrepancies found.  
• Check hose clamps for tightness.  
CHECK ENGINE COOLANT LEVEL  
4. Turn OIL FILTER (Figure 10.2) counterclockwise  
and remove. Dispose of old filter.  
See the “Checking Fluid Levels” section.  
5. Apply light coating of new engine oil to seal of new  
oil filter.-Install FILTER and tighten by hand only.  
DO NOT OVERTIGHTEN.  
PERFORM VISUAL INSPECTION  
Complete a thorough visual inspection of the entire  
engine-generator monthly. Look for obvious damage,  
loose, missing or corroded nuts, bolts and other fas-  
teners. Look for fuel, oil or coolant leaks.  
6. Remove OIL FILL CAP. Add recommended oil (see  
SPECIFICATIONS). DO NOT FILL ABOVE THE  
DIPSTICK “FULLMARK. Crankcase oil capacity  
is 4.0 U.S. quarts (3.8 liters).  
INSPECT EXHAUST SYSTEM  
After refilling the crankcase with oil, always  
Inspect the exhaust system at least once every three  
months. Check all exhaust system pipes, mufflers,  
clamps, etc. for condition, tightness, leaks, security,  
damage.  
check oil level on dipstick. NEVER OPERATE  
ENGINE WITH OIL BELOW THE DIPSTICK “ADD”  
MARK.  
. 0 v 0 8 / 0 5  
M a i n t 0 0 4 R e  
10-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Maintenance  
7. Start engine and check for oil leaks.  
2. Remove the spark plugs and check the condition.  
Replace the spark plugs if worn or if reuse is  
questionable. See the “Service Schedule” section  
for recommended inspection.  
Figure 10.2 - Oil Filter  
Oil Fill  
3. Check the spark plug gap using a wire feeler  
gauge. Adjust the gap to 1.14 mm (0.045 inch)  
by carefully bending the ground electrode (Figure  
10.4).  
Oil  
Dipstick  
Figure 10.4 – Setting the Spark Plug Gap  
SET PLUG GAP AT 1.14 mm  
(0.045 inch)  
Oil Filter  
CHANGING THE ENGINE AIR CLEANER  
To replace the engine air cleaner, (part number  
0A4637), remove the air cleaner cover and replace  
the air filter making sure it is positioned properly  
before reattaching the cover.  
COOLANT CHANGE  
Every year, have an Authorized Service Facility  
drain, flush and refill the cooling system. See the  
“Specifications” section for cooling system recom-  
mendations.  
Figure 10.3 — Engine Air Filter  
Air Filter  
MISCELLANEOUS MAINTENANCE  
CLEANING THE GENERATOR  
Keep the generator as clean and as dry as possible.  
Dirt and moisture that accumulates on internal gen-  
erator windings have an adverse effect on insulation  
resistance.  
Periodically clean generator exterior surfaces. A soft  
brush may be used to loosen caked on dirt. Use a  
vacuum system or dry, low pressure air to remove  
any accumulations of dirt. The generator is housed  
inside an all-weather enclosure, clean the enclosure  
with a soft, damp cloth or sponge and water.  
Once each year, have the generator cleaned and  
inspected by an Authorized Service Dealer. That  
dealer will use dry, low pressure air to clean internal  
windings. Parts inside the control console should be  
cleaned and inspected at this time as well.  
See the “Service Schedule” section for air cleaner  
maintenance.  
SPARK PLUGS  
Finally, have the insulation resistance of stator and  
rotor windings checked. If insulation resistances are  
excessively low, the generator may require drying.  
Reset the spark plug gap or replace the spark plugs  
as necessary.  
1. Clean the area around the base of the spark plugs  
to keep dirt and debris out of the engine. Clean  
by scraping or washing using a wire brush and  
commercial solvent. Do not blast the spark plugs  
to clean.  
. 0 v 0 8 / 0 5  
M a i n t 0 0 4 R e  
10-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Maintenance  
BATTERY  
Battery electrolyte fluid is an extremely caus-  
All lead-acid storage batteries discharge when not in  
use. Refer to specific instructions and warnings that  
accompany the battery. If such information is not  
available, observe the following precautions when  
handling a battery:  
tic sulfuric acid solution that can cause severe  
burns. Do not permit fluid to contact eyes, skin,  
clothing, painted surfaces, etc. Wear protective  
goggles, protective clothing and gloves when  
handling a battery. If the fluid is spilled, flush  
the affected area immediately with clear water.  
• DO NOT use jumper cables and a booster battery  
to crank or start the generator engine.  
Do not use any jumper cables or booster battery  
to crank and start the generator engine. If the  
battery has completely discharged, remove it  
from the generator for recharging.  
• DO NOT recharge a weak battery while it is  
installed in the generator. Remove battery from  
generator and recharge in a well-ventilated area,  
away from fuel vapors, sparks, heat or flames.  
• Battery electrolyte fluid is an extremely caustic  
sulfuric solution that can cause severe burns. DO  
NOT permit fluid to contact eyes, skin, clothing,  
painted surfaces, wiring insulation, etc. If any bat-  
tery fluid is spilled, flush the affected area with  
clear water immediately.  
Be sure the AUTO/OFF/MANUAL switch is set to  
the OFF position before connecting the battery  
cables. If the switch is set to AUTO or MANUAL,  
the generator can crank and start as soon as the  
battery cables are connected.  
• Always wear safety glasses, rubber apron and  
Be sure the 120VAC power supply to the battery  
is turned OFF, or sparking may occur at the bat-  
tery posts as the cables are attached and cause  
an explosion.  
gloves when handling a battery.  
• Batteries give off explosive hydrogen gas while  
charging. The gas can form an explosive mixture  
around the battery for several hours after charging.  
Any spark, heat or flames can ignite the gas and  
cause an explosion which can shatter the battery,  
causing blindness or other serious injury.  
BATTERY REPLACEMENT  
When replacing batteries, use the same number and  
the type of battery that follows:  
BATTERY MAINTENANCE  
BCI Group No.  
CCA  
The battery should be inspected per the “Service  
Schedule” section. The following procedure should  
be followed for inspection:  
24F-6  
525 @ 0 deg. F  
NOTE:  
The BCI number should be located directly on the  
battery.  
1. Inspect the battery posts and cables for tightness  
and corrosion. Tighten and clean as necessary.  
2. Check the battery fluid level of unsealed batteries  
and, if necessary, fill with DISTILLED WATER  
ONLY. DO NOT USE TAP WATER IN BATTER-  
IES.  
3. Have the state of charge and condition checked.  
This should be done with an automotive-type bat-  
tery hydrometer.  
REPAIR PARTS  
The latter portion of this manual consists of exploded  
views, parts lists and electrical data pertaining to this  
generator set. The parts lists consist of (a) an item  
number, (b) a part number, (c) the quantity required,  
and (d) a description of the part. The item number  
corresponds to an identical number on the exploded  
view drawing.  
DANGER  
Storage batteries give off explosive hydrogen  
gas. This gas can form an explosive mixture  
around the battery for several hours after charg-  
ing. The slightest spark can ignite the gas and  
cause an explosion. Such an explosion can shat-  
ter the battery and cause blindness or other  
injury. Any area that houses a storage battery  
must be properly ventilated. Do not allow smok-  
ing, open flame, sparks or any spark producing  
tools or equipment near the battery.  
. 0 v 0 8 / 0 5  
M a i n t 0 0 4 R e  
10-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Service Schedule  
SERVICE SCHEDULE  
30 KW - 150 KW STANDBY GAS ENGINE DRIVEN GENERATOR SETS  
The following is a recommended maintenance schedule for standby gas engine driven generator sets from 30kW to  
150 kW in size. The established intervals in the schedule are the maximum recommended when the unit is used  
in an average service application. They will need to be decreased (performed more frequently) if the unit is used  
in a severe application. Use calendar time, from the previous maintenance interval to determine the next required  
maintenance interval.  
Service Maintenance Interval Information:  
The various service maintenance intervals are designated by interval numbers as follows:  
1 An early inspection of the generator set to insure it is ready to operate when required and to identify any poten-  
tial problem areas.  
This inspection may be performed by the end user providing the following safety steps are taken to prevent  
the engine from starting automatically without warning:  
To prevent injury, perform the following steps in the order indicated before starting any maintenance:  
• Disable the generator set from starting and/or connecting to the load by setting the control panel Auto/Off/  
Manual switch to the “OFF” position.  
• Remove the 15 amp control panel fuse.  
• Turn off the battery charger.  
• Remove the negative battery cable.  
The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition  
from burning out sensitive control panel components and circuits.  
Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal  
operation when required.  
2 A wear-in service inspection of the generator set to insure it is ready to operate and carry the load when  
required, and to identify any potential problem areas.  
Performed ONLY ONCE following the first three months or the first 30 hours of operation after purchase of  
the unit.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
3 An operational inspection of the generator set to insure it is ready to operate and carry the load when required,  
and to identify any potential problem areas.  
Performed semi-annually or following each 50 hours of operation of the unit.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
4 A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required,  
and to identify any potential problem areas.  
Performed annually or following each 100 hours of operation of the unit.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
5 A comprehensive inspection of the generator set to insure it is properly serviced and ready to operate and carry  
the load when required, and to identify any potential problem areas.  
Performed annually or following each 250 hours of operation of the unit.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
. A v 0 9 / 0 5  
v S S c h r d 0 0 1 R e  
11-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Service Schedule  
Maintenance Level 1  
Level 2  
Level 3  
Level 4  
Level5  
Tasks  
Recom-  
mended  
Task  
Required  
Task  
Required  
Task  
Task  
Required  
Task  
Comp. to be done Comp. to be done Comp.  
Required  
Comp. to be done Comp.  
Bi- (Date-  
Annually/ Initials) annually/ Initials)  
100 hrs. 250 hrs.  
to be done (Date- 3 months/ (Date-  
monthly/  
10 hrs.  
Semi-  
(Date- to be done (Date-  
Initials)  
Initials) Break-in Initials) annually/  
30 hrs. 50 hrs.  
1. Disable the unit  
from operating  
per the first page  
warning.  
2. Check the engine  
oil level. Adjust  
as necessary.  
3. Check the engine  
coolant level.  
Adjust as  
necessary.  
4. Check the engine  
coolant thermal  
protection level.  
Correct as  
necessary.  
5. Check the natural  
gas delivery  
system for leaks  
and correct  
pressure on gas  
engine driven  
units. Tighten  
connections as  
necessary.  
6. Check the air  
inlets and outlets  
for debris. Clean  
as necessary.  
7. Check the battery  
electrolyte level  
and specific  
gravity if  
accessible. Adjust  
as necessary.  
8. Check the battery  
posts, cables,  
and charger for  
loose  
connections,  
corrosion, and  
proper operation.  
Correct as  
necessary.  
9. Check the unit  
wiring for loose  
connections,  
corrosion, and  
damage. Correct  
as necessary.  
. A v 0 9 / 0 5  
v S S c h r d 0 0 1 R e  
11-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Service Schedule  
Maintenance Level 1  
Level 2  
Level 3  
Level 4  
Level5  
Tasks  
Recom-  
mended  
Task  
Required  
Task  
Required  
Task  
Task  
Required  
Task  
Comp. to be done Comp. to be done Comp.  
Required  
Comp. to be done Comp.  
Bi- (Date-  
Annually/ Initials) annually/ Initials)  
100 hrs. 250 hrs.  
to be done (Date- 3 months/ (Date-  
monthly/  
10 hrs.  
Semi-  
(Date- to be done (Date-  
Initials)  
Initials) Break-in Initials) annually/  
30 hrs. 50 hrs.  
10. Check the engine  
accessory drive  
belts and fan  
coupling device  
if equipped for  
correct tension,  
wear, weather  
cracking, and  
damage. Replace  
as necessary.  
11. Check the engine  
valve clearance.  
Adjust as  
necessary.  
12. Visually inspect  
the unit looking  
for leaks, wear or  
damage, loose  
connections or  
components, and  
corrosion. Correct  
as necessary.  
13. Test the engine  
and transfer  
switch safety  
devices. Correct  
and/or adjust as  
necessary.  
14. Initiate an  
automatic start  
and transfer of  
the unit to site  
load and exercise  
it for at least 1  
hour looking for  
leaks, loose  
connections or  
components, and  
abnormal  
operating  
conditions.  
Correct as  
necessary.  
15. Replace the  
engine  
accessory  
drive belts.  
16. Check gearbox  
oil level (if  
equipped).  
17. Change gearbox  
oil (if equipped).  
. A v 0 9 / 0 5  
v S S c h r d 0 0 1 R e  
11-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Service Schedule  
Maintenance Level 1  
Level 2  
Level 3  
Level 4  
Level5  
Tasks  
Recom-  
mended  
Task  
Required  
Task  
Required  
Task  
Task  
Required  
Task  
Comp. to be done Comp. to be done Comp.  
Required  
Comp. to be done Comp.  
Bi- (Date-  
Annually/ Initials) annually/ Initials)  
100 hrs. 250 hrs.  
to be done (Date- 3 months/ (Date-  
monthly/  
10 hrs.  
Semi-  
(Date- to be done (Date-  
Initials)  
Initials) Break-in Initials) annually/  
30 hrs. 50 hrs.  
18. Start and  
exercise the unit  
at full rated load  
(use a load bank  
if the site load is  
not enough) for  
at least 2 hours  
looking for leaks,  
loose  
connections or  
components, and  
abnormal  
operating  
conditions.  
Correct as  
necessary.  
19. Perform an  
engine oil  
analysis (send a  
sample to a lab  
for results).  
Change the  
engine oil and  
filters if the  
analysis results  
indicate this is  
required.  
20. Change the  
engine oil.  
21. Replace the  
engine oil filter(s).  
22. Replace engine  
spark plugs.  
Clean and re-gap  
or replace as  
necessary.  
23. Replace the  
engine air  
filter(s).  
24. Perform a 5  
minute no-load  
operational run  
of the unit  
looking for any  
post service  
problems.  
25. Return the unit  
to standby setup  
for operation  
when required.  
. A v 0 9 / 0 5  
v S S c h r d 0 0 1 R e  
11-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Troubleshooting  
TROUBLESHOOTING GUIDE  
PROBLEM  
Engine won’t crank.  
CAUSE  
1. 15 amp fuse blown.  
CORRECTION  
1. Replace fuse.  
2. Loose or corroded or defective  
battery cables.  
2. Tighten, clean or replace  
battery cables as necessary.  
3. Replace contactor.*  
3. Defective starter contactor.  
4. Defective starter motor.  
5. Dead or Defective Battery.  
6. 5 amp fuse blown.  
4. Replace starter motor.*  
5. Remove, change or replace battery.  
6. Replace fuse.*  
Engine cranks but won't start  
Engine starts hard, runs rough.  
Engine starts then shuts down.  
1. Out of fuel.  
1. Replenish fuel.  
2. Replace solenoid.*  
3. Reconnect wire.  
2. Fuel solenoid (FS) is defective  
3. Open Wire #14A from Engine Control  
circuit board.  
4. Spark plugs defective.  
5. Door on tank not closed.  
4. Clean, regap or replace plugs.  
5. Close door on tank.  
1. Flame arrestor (air cleaner) plugged or  
damaged.  
2. Plugged fuel line.  
1. Clean or replace as needed.  
2. Unclog fuel line.  
3. Defective spark plugs.  
4. Fuel pressure incorrect.  
3. Clean, regap or replace plugs.  
4. Confirm fuel pressure to regulator is as  
recommended in SPECIFICATIONS.  
1. Engine oil level is low.  
2. Engine is overheated.  
1. Check oil and add oil as needed.  
2. Check cooling system for leaks.  
3. Replace switch.*  
3. Defective Low Oil Pressure Switch  
4. Defective Coolant Temperature Switch  
5. Defective Control Module circuit board.  
6. Coolant Level is Low.  
4. Replace switch.*  
5. Replace board.*  
6. Repair leak - Add coolant.  
7. Replace Switch.*  
7. Defective Low Coolant Level Switch  
AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch  
1. Replace switch.*  
2. Reconnect/close wire.  
engine continues to run  
2. Open/disconnected wire #15A between  
AUTO/OFF/MANUAL switch and Control  
Module circuit board.  
3. Defective Control Module circuit board  
3. Replace board.*  
No AC output from generator.  
1. Check main line circuit breaker.  
2. Check circuit breaker & fuses.  
3. Transfer switch set to NORMAL position  
4. Generator internal failure.  
1. Reset to ON or CLOSED.  
2. Reset and replace, if necessary.  
3. Set to GENERATOR position.  
4. *  
5. Thermal circuit breaker open.  
5. Auto-reset - Wait 5 min. and  
attempt restart.  
*Contact the nearest Authorized Dealer for assistance.  
. 0 v 0 8 / 0 5 l s b h r t T 0 0 1 R e  
12-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
0F2885  
0F2883  
0F9637 (4)  
1
1
1
PANEL CB CONN BOX  
STAND RH CONTROL  
STAND RH CONTROL, TWO HOLE (FOR 5.4L 100KW &  
4.6L 80KW 1PHASE)  
STAND LH CONTROL C5 GRBX  
BUSHING SNAP SB-2.5-31  
BUSHING SNAP SB-2.5-31 (FOR 5.4L 100KW & 4.6L  
80KW 1PHASE)  
1.)  
A
B
UL CIRCUIT BREAKER (FD)  
0F2887  
065469  
0D5572  
0D5573  
0D5575  
0D5576  
0F0199  
065960  
022473  
022097  
022127  
0C2454  
029289  
0F1733  
1
1
-
-
-
COVER FD FRM CB  
DECAL DANGER HIGH VOLTAGE  
CB 0150A 3P 600V S FD6 LL  
CB 0175A 3P 600V S FD6 LL  
CB 0225A 3P 600V S FD6 LL  
CB 0250A 3P 600V S FD6 LL  
INSULATOR CB FD FRAME 30MIL  
SCREW SHC 1/4-20 X 4 G8.8 NZ  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
C
3
4
0F3685  
023484N  
023484N  
1
1
2
-
D
E
F
G
H
J
1
4
4
4
4
4
1
1
5
086961  
067617030A  
067617030B  
043180  
022264  
0C3990  
057701  
022155  
0C2428  
0F3618  
0A9457  
057073  
0D5466  
0A7822  
022237  
022241  
049226  
0C2266  
0C2454  
042568  
022473  
022097  
049813  
0D4698  
0F4464  
025433  
024469  
067210A  
0D6029  
051713  
081008  
077043J  
077043J  
1
-
-
4
4
4
INTERFACE 1PH 240V  
INTERFACE 3PHS 416/480V  
INTERFACE 3PHS 208/240V  
WASHER FLAT M4  
6
7
8
NUT HEX 1/4-20 STEEL  
WASHER LOCK #8-M4  
SCREW THF M6-1 X 16 N WA Z/JS  
TAPE ELEC 1/2 FOAM (AS REQ’D)  
DECAL CUSTOMER CONNECT INSIDE  
SCREW PHTT M4-0.7 X 10 ZYC  
BLOCK TERM 20A 8 X 6 X 1100V  
WASHER LOCK #6  
SCREW PHTT #6-32 X 1/2 ZYC  
DECAL CPL CUST CONN H CTRL  
DECAL NEUTRAL  
K
L
(1) 9  
10  
11  
12  
13  
REF.  
2
2
1
1
2
REF.  
REF.  
4
4
6
6
10  
4
12  
8
4
1
1
1
1
1
4
2
1
2.)  
A
B
UL CIRCUIT BREAKER (JD+LD)  
0F2721  
065469  
0D5577  
0D5578  
0D5579  
0D5581  
0D5585  
0F2353  
022770  
022473  
022097  
022127  
0C2454  
029289  
0F1733  
1
1
-
-
-
COVER CIR BRKR JD/LD  
DECAL DANGER HIGH VOLTAGE  
CB 0300A 3P 600V S JD6 LL  
CB 0350A 3P 600V S JD6 LL  
CB 0400A 3P 600V S JD6 LL  
CB 0600A 3P 600V S LD6  
14  
JUNCTION BLOCK 3/8-16  
C
(2) 15  
(2) 16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
(1) 26  
27  
28  
29  
30  
31  
32  
BUS BAR NEUTRAL BLOCK 390  
LUG SLDLSS 600/250-1/0 X 1/4-28  
WASHER LOCK 3/8  
NUT HEX 3/8-16 STEEL  
WASHER LOCK M5  
SCREW PHTT M5-0.8 X 16 ZYC  
SCREW THF M6-1 X 16 N WA Z/JS  
SCREW HHC M6-1.0 X 20 G8.8  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
NUT HEX M6 X 1.0 G8 YEL CHR  
BLOCK TERM 20A 6 X 3 X 1100V  
DECAL CUST CONN 120V UTILITY  
LUG SLDLSS #6-14 X 13/64 CU  
SCREW HHTT #10-32 X 3/8 CZ  
DECAL GROUND LUG  
-
-
CB 0450A 3P 600V S LD6 LL  
INSULATOR CIRCUIT BR. JD/LD  
SCREW RHM 1/4-20 X 3  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
D
E
F
G
H
J
2
4
4
4
4
7
1
1
NUT HEX 1/4-20 STEEL  
SCREW THF M6-1 X 16 N WA Z/JS  
TAPE ELEC 1/2 FOAM (AS REQ’D)  
DECAL CUSTOMER CONNECT INSIDE  
K
L
(1) ITEM INCLUDED WITH HARNESS.  
(2) ITEM INCLUDED WITH 0D5464B.  
(3) ITEM IS PART OF 9R.  
SCREW HHTT M6-1.0 X 16 ZYC  
WASHER FLAT M5  
GROMMET 1.25 X .25 X .75  
CONDUIT FLEX 2.0" ID  
CONDUIT FLEX 2.0" ID (FOR 5.4L 100KW & 4.6L 80KW  
33  
34  
3
4
(4) ROUTE ONE SET (11, 22, 33, 44) THROUGH ONE HOLE; AND  
ROUTE THE SECOND SET (11, 22, 33, 44) THROUGH THE OTHER  
HOLE.  
1 PHASE)  
35  
36  
(3) 37  
0F6156  
029289  
0F8656  
0F3113  
1
1
REF  
REF  
PLATE WIRE SNGL GALV  
TAPE ELEC 1/2 FOAM (AS REQ’D)  
ASSY PCB 4.6L IGNITION MODULE  
ASSY PCB HSB CTRL IGN MODULE (ALL OTHER  
APPLICATIONS EXCEPT 4.6L G3)  
SCREW HHC M6-1.0 X 16 G8.8  
SCREW PPHM #10/32 X 2  
WASHER FLAT #10 ZINC  
WASHER LOCK #10  
NUT HEX #10-32 STEEL  
38  
39  
40  
41  
42  
047411  
036943  
023897  
022152  
022158  
4
2
2
2
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.)  
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T
UL CIRCUIT BREAKER (225AF)  
COVER CB C5 225AF  
DECAL DANGER HIGH VOLTAGE  
CIRCUIT BREAKERS 200A FRAME  
COVER CB DISH 225AF  
RIVET POP .125 X .275 SS  
SCREW RHM #8-32 X 3-1/4  
WASHER FLAT #8 ZINC  
WASHER LOCK #8-M4  
NUT HEX #8-32 STEEL  
TAPE ELEC 1/2 FOAM  
DECAL CUSTOMER CONNECT INSIDE  
5.)  
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T
UL CIRCUIT BREAKER (800AF)  
COVER CB C5 800AF  
DECAL DANGER HIGH VOLTAGE  
CIRCUIT BREAKERS 800A FRAME  
INSULATOR CB 800AF  
SCREW RHM 1/4-20 X 3-1/2  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
0F4173  
065469  
0F4165$  
0F4186  
036261  
053640  
038150  
022264  
022471  
029289  
0F1733  
022129  
0F8432  
0C2454  
0F8451  
049897  
022145  
045771  
0F8843  
W/CB  
1
1
REF  
1
4
4
4
4
4
2
1
9
1
7
3
9
6
0F4176  
065469  
0F4167$  
0F8433  
024196  
022473  
022097  
022127  
0C2454  
029289  
060619  
022131  
022237  
045772  
0F8452  
097950  
0F1733  
W/CB  
1
1
REF  
2
4
4
4
4
7
2
3
9
6
6
3
3
1
NUT HEX 1/4-20 STEEL  
SCREW THF M6-1X16 N WA Z/JS  
TAPE ELEC 1/2 FOAM  
SCREW SHC M10-1.50 X 40 G12.9  
WASHER FLAT 3/8-M10 ZINC  
WASHER LOCK 3/8  
NUT HEX M10-1.5 G8 YEL CHR  
LUG SLDLSS 500-750 X 2 MCM AL/CU  
SCREW SHC M10-1.25 X 70 G8.8  
DECAL CUSTOMER CONNECT INSIDE  
TERM COVER VITZROTECH 400AF CB  
WASHER LOCK M8-5/16  
INSULATOR CB 225AF  
SCREW THF M6-1 X 16 N WA Z/JS  
LUG SLDLSS 300 MCM-6 AL/CU  
SCREW SHC M8-1.25 X 20 G8  
WASHER FLAT 5/16-M8 ZINC  
NUT HEX M8-1.25 G8 CLEAR ZINC  
BUS BAR 200A LUG ADAPTOR  
TERMINAL COVER CB  
U
V
(1) W  
3
3
2
(1) U  
2
6.)  
A
B
C
D
E
F
G
H
NEUTRAL BLOCK 390 / 200-400A  
BUS BAR NEUTRAL BLOCK 390  
SCREW HHC M8-1.25 X 45 G8.8 FT  
WASHER FLAT 5/16-M8 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 YEL CHR  
SCREW HHC 1/4-28 X 3/4 G5  
WASHER LOCK M6-1/4  
0D5466  
039287  
022145  
022129  
045771  
045335  
022097  
0A7822  
2
1
1
1
1
2
2
1
4.)  
A
B
C
D
E
F
G
H
J
K
(2) L  
(2) M  
N
P
R
(1) S  
UL CIRCUIT BREAKER (400AF)  
COVER CB C5 400AF  
DECAL DANGER HIGH VOLTAGE  
CIRCUIT BREAKERS 400A FRAME  
DECAL CUSTOMER CONNECT INSIDE  
SCREW RHM 10-32 X 4  
WASHER FLAT #10 ZINC  
WASHER LOCK #10  
NUT HEX #10-32 STEEL  
SCREW THF M6-1 X 16 N WA Z/JS  
TAPE ELEC 1/2 FOAM  
SCREW SHC M10-1.5 X 25 G12.9  
WASHER LOCK M10  
BUS BAR CB ADAPTER 225-400 A  
LUG SLDLSS 600/250-1/0 X 1/4-28  
WASHER FLAT 3/8-M10 ZINC  
TERM COVER CB  
0F4175  
065469  
0F4166$  
0F1733  
042419  
023897  
022152  
022158  
0C2454  
029289  
052647  
046526  
W/CB  
1
1
REF  
1
4
4
4
4
7
LUG SLDLSS 600/250-1/0X1/4-28  
(1) HARDWARE FOR MTG. CB TERMINAL COVERS IS SUPPLIED  
WITH CIRCUIT BREAKERS.  
1
2/3  
2/3  
3
3
3
(2) 2/3 QTY. 2POLE & 3 POLE CB.  
0A7822  
022131  
W/CB  
2
T
U
V
(2) W  
023334  
022097  
022473  
W/CB  
6
6
6
2/3  
SCREW HHC 1/4-28 X 1/2 G5  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4-M6 ZINC  
SCREW SHC M10-1.5 X 25 G12.9  
WASHER LOCK M10  
(2) X  
W/CB  
2/3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
4
5
6
7
055173  
022129  
0E2747A  
0A3870  
0A3009  
0F5564D  
0F5563D  
0A3881D  
0A3881B  
0A3882B  
0A3883B  
052624  
0A5580  
0A1633  
0F7351  
0F7349  
0F7348  
0F7350  
068113  
022392  
043123  
051779  
052259  
051769  
068406  
072878  
087272  
068405C  
092950  
090063  
090152  
023365  
033143  
090064  
083485  
031980  
083401  
042561  
033212  
083549  
0A4089  
6
6
1
1
1
1
1
1
1
1
1
1
4
4
1
1
1
1
1
2
4
4
2
3
3
1
1
1
1
1
1
3
2
1
2
2
1
1
2
1
1
SCREW HHC M8-1.25 X 20 G10.9  
WASHER LOCK M8-5/16  
FAN SAE ALTERNATOR (G/B)  
KEY SQ 3/8 X 1-9/16 STEEL  
HUB DRIVE 390 SAE GB  
RTR 390 100KB3 GB SAE TECHUM  
RTR 390 130KB4 GB SAE TECHUM  
RTR 390 80GB BR BRLSS  
RTR 390 80GB 1P BRLSS  
RTR 390 100GB 1P BRLSS  
RTR 390 125GB 1P BRLSS  
BEARING BALL 6212 SEALED  
SCREW HHC M14-2.0 X 140 G8.8  
WASHER 390 SAE ALT.  
STR 390 130 GB4 CPL  
STR 390 80 AB3 CPL  
STR 390 100 AB3 CPL  
STR 390 130 AB4 CPL  
CARRIER REAR BRG 15"  
PIN DOWEL 1/2 X 1-1/4  
WASHER LOCK M14  
NUT HEX M14-2.0 G8 YEL CHR  
8 *  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
40  
WASHER FLAT M12  
WASHER LOCK M12  
SCREW HHC M12-1.75 X 60 G10.9  
KEY SQ 3/8 X 3-1/4 STEEL  
ASSY EXCITER 2.00" STK  
EXITER FIELD 2" LG SPD CONN  
COLLAR SLIP FIT 390 MM  
BRIDGE SUPPORT DIODE 15"  
ASSY BRIDGE RECTIFIER  
WASHER SHAKEPROOF INT #8  
SCREW HHM #8-32 X 7/8  
CAP END ROTOR 390MM  
PLATE NUT  
TIE WRAP UL 14.6 X .14 NATL  
BRACKET-STATOR WIRE  
CLAMP HOSE #36 1.88-2.7  
SCREW HHC 5/16-18 X 1-1/4 G5  
SLEEVE RUBBER  
ASSY SCROLL 390 SAE  
KIT PARTS  
0A2491  
0A2497  
0A2496  
056326  
022307  
022473  
045757  
047411  
0A2110  
I/N’S: 41 THRU 49  
SHROUD ALT SHEET METAL  
SCREEN SHROUD SAE  
BRKT TENSIONER SAE SCROLL  
TRIM VINYL BLACK 1/8 GP  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4-M6 ZINC  
SCREW HHC M6-1.0 X 25 G8.8  
SCREW HHC M6-1.0 X 16 G8.8  
SCREW SWAGE 1/4-20 X 1/2 ZYC  
41  
42  
43  
44  
45  
46  
47  
48  
49  
2
2
2
8.4 FT.  
6
6
2
4
12  
* ROTOR REPLACEMENT PART  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
0F2885  
0G0171  
0G0171A  
0G0172  
023484N  
0F4677  
067617030A  
067617030B  
043180  
022264  
0C3990  
057701  
022155  
0C2428  
0F3618  
0A9457  
057073  
0D5466  
0A7822  
022237  
022241  
049226  
0C2266  
0C2454  
042568  
022473  
022097  
049813  
0D4698  
0F4464  
025433  
024469  
067210A  
0D6029  
051713  
081008  
077043J  
0F6156  
1
1
1
1
1
1
-
-
PANEL CB CONN BOX  
STAND, RH CONTROL CPL C5  
STAND RH CONTROL CPL C5 2 HOLE  
STAND, LH CONTROL CPL C5  
BUSHING SNAP SB-2.5-31  
ASSY PCB INTERFACE 1PH 240V  
INTERFACE 3PHS 416/480V  
INTERFACE 3PHS 208/240V  
WASHER FLAT M4  
36  
37***  
38  
39  
40  
41  
42  
029289  
0F3113  
047411  
036943  
023897  
022152  
022158  
1
REF  
4
2
2
TAPE ELEC 1/2 FOAM (AS REQ’D)  
ASSY PCB HSB CTRL IGN MODULE  
SCREW HHC M6-1.0 X 16 G8.8  
SCREW PPHM #10/32 X 2  
WASHER FLAT #10 ZINC  
3
4
5
2
2
WASHER LOCK #10  
NUT HEX #10-32 STEEL  
6
7
8
4
4
4
WASHER LOCK #8-M4  
1.)  
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T****  
UL CIRCUIT BREAKER (800AF)  
1
1
REF  
2
4
4
4
4
1
2
3
9
6
6
3
3
SCREW PHTT M4-0.7 X 10 ZYC  
BLOCK TERM 20A 8 X 6 X 1100V  
WASHER LOCK #6  
SCREW PHTT #6-32 X 1/2 ZYC  
DECAL CPL CUST CONN H CTRL  
DECAL NEUTRAL  
JUNCTION BLOCK 3/8-16  
BUS BAR NEUTRAL BLOCK 390  
LUG SLDLSS 600/250-1/0 X 1/4-28  
WASHER LOCK 3/8  
0G0173  
065469  
0F4167$  
0F8433  
022477  
022473  
022097  
022127  
0F1733  
029289  
060619  
022131  
022237  
045772  
0F8452  
0D2576  
W/CB  
COVER, CB 803 C5  
9 *  
10  
11  
12  
13  
14  
15 **  
16 **  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26 *  
27  
28  
29  
30  
31  
32  
33  
34  
35  
REF.  
2
2
1
1
2
REF.  
REF.  
4
4
6
6
10  
4
12  
8
4
1
1
1
1
1
4
2
DECAL DANGER HIGH VOLTAGE  
CIRCUIT BREAKERS 800A FRAME  
INSUL CB 800AF  
SCREW RHM 1/4-20 X 1-1/2  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
NUT HEX 1/4-20 STEEL  
DECAL CUSTOMER CONNECT INSIDE  
TAPE ELEC 1/2 FOAM  
SCREW SHC M10-1.50 X 40 G12.9  
WASHER FLAT 3/8-M10 ZINC  
WASHER LOCK 3/8  
NUT HEX M10-1.5 G8 YEL CHR  
LUG SLDLSS 500-750X2 MCM AL/CU  
SCREW SHC M10-1.5 X 70 G10.9  
TERM. COVER VITZROTECH 400AF CB  
NUT HEX 3/8-16 STEEL  
WASHER LOCK M5  
SCREW PHTT M5-0.8 X 16 ZYC  
SCREW THF M6-1 X 16 N WA Z/JS  
SCREW HHC M6-1.0 X 20 G8.8  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
NUT HEX M6 X 1.0 G8 YEL CHR  
BLOCK TERM 20A 6 X 3 X 1100V  
DECAL CUST CONN 120V UTILITY  
LUG SLDLSS #6-14 X 13/64 CU  
SCREW HHTT #10-32 X 3/8 CZ  
DECAL GROUND LUG  
2
2.)  
A
B
C
D
E
F
G
H
NEUTRAL BLOCK 390 / 200-400A  
0D5466  
039287  
022145  
022129  
045771  
045335  
083896  
0A7822  
1
1
1
1
1
2
2
1
BUS BAR NEUTRAL BLOCK 390  
SCREW HHC M8-1.25 X 45 G8.8 FT  
WASHER FLAT 5/16-M8 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 YEL CHR  
SCREW HHC 1/4-28 X 3/4 G5  
WASHER LOCK 1/4-M6 SS  
SCREW HHTT M6-1.0 X 16 ZYC  
WASHER FLAT M5  
GROMMET 1.25 X .25 X .75  
CONDUIT FLEX 2.0" ID  
1
3
1
LUG SLDLSS 600/250-1/0 X 1/4-28  
PLATE WIRE SNGL GALV  
* ITEM INCLUDED WITH HARNESS  
** ITEM INCLUDED WITH 0D5464B  
*** ITEM IS PART OF 9R.  
**** HARDWARE FOR MTG. CB TERMINAL COVERS IS  
SUPPLIED WITH CIRCUIT BREAKERS.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
0F2687  
0F2611  
0F5254  
0F5253  
0F7077  
046526  
051756  
0C2454  
052250  
076749  
0F2573  
0F2610  
0F2572  
0F5689  
0F2862  
0F2560  
022131  
039414  
052625  
0F2561  
0C8165  
0D6795  
0C7043  
0E8909  
048031C  
0C8146  
082774  
0F2686  
0F5463  
0F8695  
0F4028  
0F4030  
0F4032  
0F4496  
042911  
0F2872  
022304  
022195  
022196  
049813  
049820  
022145  
022129  
035685  
045764  
065852  
0C7649  
055596  
069860E  
069811  
080713  
022473  
022097  
042568  
0F5050  
039253  
051769  
0C8145  
0E2507  
090283  
0C8566  
0F2776A  
052644  
1
1
1
1
1
12  
8
2
2
1
1
1
1
1
1
1
14  
1
3
1
5
1
12  
1
1
4
2
1
1
1
1
1
1
1
1
1
2
1
1
8
1
1
1
4
1
1
1
1
1
REF  
1
16  
16  
8
1
1
1
8
1
1
8
1
WELDMENT RADIATOR SUPPORT150  
RADIATOR 680 X 680 X 70 CPL  
V-BELT 31/64" X 62-3/8"  
V-BELT 31/64" X 61-3/8" (5.4L 100KW ONLY)  
V-BELT 1/2" X 63-3/8" (6.8L 100 130KW)  
WASHER LOCK M10  
SCREW HHC M10-1.5 X 20 G8.8  
SCREW THF M6-1 X 16 N WA Z/JS  
TAPE FOAM 1 X 1 (26.75” LG)  
TANK COOLANT RECOVERY  
PULLEY FAN V-GROOVE 9"  
FAN 26" LH ROTATION  
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
ARM TENSIONER  
SCREW SHC SHLDR LKG M8 X 16 LG  
SPRING TENSION CPL  
PULLEY V-BELT 4" FLANGED  
WASHER FLAT 3/8-M10 ZINC  
SCREW HHC M8-1.25 X 35 G8.8  
SCREW SHC M10-1.5 X 35 G12.9  
HUB FLEX PLATE  
NUT HEX LOCK 5/16-24 NY INS  
SCREW HHC M12-1.5 X 60 G8.8  
DISK FLEX  
COUPLING HUB FLEX (MACH)  
CLAMP HOSE BAND 1/4  
SCREW HHC 5/16-24 X 1.124  
KEY WOODRUFF 4 X 19D  
HOSE RADIATOR UPPER CPL  
HOSE LOWER RAD CPL C5 6.8L  
ASSY BRG/SHAFT CPL FANDRIVE  
PULLEY 6.5" DIA MACHINED (6.8L 100KW)  
PULLEY 6" DIA MACHINED (6.8L 130KW)  
PULLEY 5.5" DIA MACHINED (5.4L 80KW & 6.8L 150KW)  
PULLEY 4.5" DIA MACHINED (5.4L 100KW)  
SCREW HHC M10-1.5 X 30 G8.8  
SCREW HHC 1/2-13 X 2" G8  
WASHER FLAT 1/2 ZINC  
30  
31  
32  
33  
34  
35  
36  
39  
40  
42  
43  
44  
45  
46  
47  
48 *  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
WASHER LOCK 1/2  
NUT HEX 1/2-13 STEEL  
NUT HEX M6 X 1.0 G8 YEL CHR  
NUT HEX LOCK M8-1.25 NY INS  
WASHER FLAT 5/16-M8 ZINC  
WASHER LOCK M8-5/16  
CLAMP HOSE #28 1.32-2.25  
SCREW HHTT M4-0.7 X 8 BP  
SPRING CLIP HOLDER .37-.62  
CLAMP HOSE .38-.87  
BARBED STR 3/8 NPT X 3/8  
HOSE DRAIN ASSY 28"  
CAP HEX 1/4 NPT BRASS  
BRACKET COOLANT TANK  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
SCREW HHC M6-1.0 X 20 G8.8  
SHIELD RADIATOR C5  
SCREW HHC M8-1.25 X 20 G8.8  
WASHER LOCK M12  
WASHER FLEX (THIN)  
PROBE, COOLANT LEVEL 3/8 NPTF  
CAP RADIATOR 13 PSI  
SCREW HHFC M6-1.0 X 20 G8.8  
BRACKET, SIGNAL CONDITIONER  
SPACER .5 X 1.5 X .25 STL/ZINC  
1
* ITEM 48 IS INCLUDED WITH 47.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
0F3384  
065852  
052252  
052257  
052259  
055597  
052251A  
052860  
0F2895  
045764  
090502  
061383  
043107  
022473  
049813  
057192  
022131  
046526  
0536210360  
042909  
022261  
022129  
022145  
045771  
053557  
0F2591  
0F2910  
038750  
022097  
022447  
1
1
4
4
8
4
4
4
1
1
4
1
1
1
1
4
8
8
1
1
2
1
2
2
4
2
1
1
1
1
BASE CPL 100-130KW 6.8L GB  
SPRING CLIP HOLDER .37-.62  
DAMPENER VIBRATION  
SPACER .49 X .62 X 1.87 PWDR/ZINC  
WASHER FLAT M12  
SCREW HHC M12-1.75 X 85 G8.8  
DAMPENER VIBRATION 50 WHITE  
NUT LOCKING M12-1.75  
SUPPORT ENG 5.4L LH/RH 6.8L RH  
SCREW HHTT M4-0.7 X 8 BP  
SCREW SHC M10-1.5 X 60 G12.9  
LUG SOLDERLESS 3/0-#4 X 13/32 CU  
SCREW HHC M8-1.25 X 25 G8.8  
WASHER FLAT 1/4-M6 ZINC  
NUT HEX M6 X 1.0 G8 YEL CHR  
SCREW SHC M10-1.5 X 30 G12.9  
WASHER FLAT 3/8-M10 ZINC  
WASHER LOCK M10  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
WIRE ASSEM #4GA GRD  
SCREW HHC M8-1.25 X 30 G8.8  
WASHER SHAKEPROOF INT 3/8  
WASHER LOCK M8-5/16  
WASHER FLAT 5/16-M8 ZINC  
NUT HEX M8-1.25 G8 YEL CHR  
SCREW HHC M12-1.75 X 40 G8.8  
TOWER GB COMPROD C5  
SUPPORT ENGINE 6.8L LH SIDE  
SCREW HHC M6-1.0 X 30 G8.8  
WASHER LOCK M6-1/4  
WASHER SHAKEPROOF INT 1/4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
0F3408A  
0F3411A  
058665  
022131  
050331A  
050331  
038805Z  
038804U  
045771  
022129  
027482  
075763  
0C2454  
0F3409  
022097  
049813  
042568  
0G0783  
1
1
1
1
1
1
1
1
1
1
1
1
8
1
2
2
2
1
TRAY BATTERY 27F  
STRAP BATTERY RETAINMENT 27F  
BATTERY 12VDC 90-AH 27F  
WASHER FLAT 3/8-M10 ZINC  
BATTERY POST COVER RED +  
BATTERY POST COVER BLK -  
CABLE BATTERY BACLK #1 X 26.00  
CABLE BATTERY RED #1 X 28.00  
NUT HEX M8-1.25 G8 YEL CHR  
WASHER LOCK M8-5/16  
WASHER SHAKEPROOF EXT 5/16 STL  
BOOT BATTERY CABLE  
SCREW THF M6-1 X 16 N WA Z/JS  
SUPPORT BATTERY TRAY  
WASHER LOCK M6-1/4  
NUT HEX M6 X 1.0 G8 YEL CHR  
SCREW HHC M6-1.0 X 20 G8.8  
SUPPORT 27F BATTERY  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
9
0F2123  
0F2122  
095613  
051756  
046526  
049814  
051735  
0F2097  
072879  
097557B  
097785  
095970  
095968  
0E6866  
070263  
057019  
026847  
097784  
095969  
095967  
0E6865  
095966  
095976  
095971  
096777  
057019S  
096379  
048189  
095979  
021159  
097557A  
057163  
0F6518  
0F3201  
020443  
094666A  
099828  
099828A  
026925  
097557C  
038591  
025066  
031578  
052625  
049814  
0A1786  
027175  
045772  
052243  
057642  
0F6487  
0F6355  
0F6477  
0F6557  
1
1
1
2
44  
4
8
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
GEAR CASE ENG. MACHINED  
GEAR CASE ALT. MACHINED  
SEAL OIL  
SCREW HHC M10-1.5 X 20 G8.8  
WASHER LOCK M10  
SCREW HHC M10-1.5 X 25 G8.8  
SCREW HHC M10-1.5 X 70 G8.8  
GASKET 390 GEARBOX  
SPACER .69 X 2.75 X .37 ST/ZNC  
KEY 10 X 16 X 46  
GEAR OUTPUT 1.65:1  
GEAR OUT 390-50H 37T  
GEAR OUT 390-60H 35T  
GEAR OUTPUT 2:1 50HZ 390  
SCREW HHC M16-2.0 X 35 G10.9  
BALL BRG 65 X 120 X 23  
BREATHER  
GEAR INPUT 1.65: 1  
GEAR INPT 390-50 25T  
10  
11  
12  
13  
14  
15  
GEAR INPT 390-60 27T  
GEAR INPUT 2:1 50HZ 390  
SHAFT 390 INPUT GEAR  
COLLAR HARDENED  
SEAL OIL  
SNAP RING INT 120MM  
16  
17  
18  
19  
20  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
BEARING #6213 SEALED  
PLATE INTRNL BRG RET  
PIN DOWEL M8 X 24  
PLATE BEARING THRST  
SPACER STRESSPROOF  
KEY 10 X 16 X 40  
PLUG PIPE 3/8" MAGNETIC  
SCREW HHFC M10-1.5 X 25 G10.9  
COVER GEARBOX GUARD  
COUPLING INNER DRAWN  
COUPLING OUTER MACHN  
DAMPER GB CPLR VIBRA  
DAMPER GB CPLR VIBRA  
PLUG STD PIPE 3/8 STEEL SQ HD  
KEY 10 X 16 X 50  
4
1
1
1
8
8
2
1
1
1
6
NIPPLE PIPE 3/8 NPT X 3-1/2  
COUPLING FULL 3/8-18  
SCREW HHC 3/8-16 X 1-1/2 G8  
SCREW SHC M10-1.5 X 35 G12.9 (FORD ENGINES)  
SCREW HHC M10-1.5 X 25 G8.8  
RETAINING COMPOUND  
LUBE GREASE SAE #90 80W90 (NOT SHOWN)  
NUT HEX M10-1.5 G8 YEL CHR  
SCREW HHC M10-1.5 X 60 G8.8  
SCREW HHC M10-1.5 X 40 G10.9  
WASHER FLAT M10 SEALING COPPER  
GASKET SEAL PLATE 390 GB  
ENHANCER GEAR OIL (NOT SHOWN)  
THREADLOCK AND SEALANT  
REF.  
10  
2.5cc  
.200 GAL  
39  
40  
41  
44  
45  
46  
47  
48  
49  
50  
10  
10  
2
4
1
.050 GAL  
0.4cc  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMPONENTS INCLUDED IN 0F1826E  
1
2
3
4
5
6
7
8
0F1823  
0F1824  
0F2606  
036261  
0F5763  
0F1732  
0E9764  
0F1725C  
0F1958  
0F2256  
0E3161  
029673  
049226  
079224  
051713  
0F5886  
051716  
0C3990  
043280  
055014  
043184  
0F2557  
0F5884  
0C2265  
0F4333  
0F5883  
0F6305  
0F6305A  
0F6277  
1
1
1
6
1
1
1
1
1
1
1
1
8
4
8
3
5
3
3
10  
10  
1
1
4
1
1
2
1
1
ENCL H CONTROL PANEL  
COVER CONTROL PANEL  
HINGE CONTINUOUS H-PNL  
RIVET POP .125 X .275 SS  
ASSY PROGRAMMED PM H-100  
DECAL FUSES LOCATED INSIDE  
RAIL SNAPTRACK PCB HOLDER BULK (12” LG)  
ASSY PCB 2AMP 12V UL BATT CHGR  
PLATE HARNESS CLAMP  
ASSY PCB PWR AVR W/AMP HEADER  
ASSY PCB BOSCH GOV DRIVER  
DIO BRIDGE 25A 600V  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
WASHER LOCK M5  
SCREW PPHM M5-0.8 X 30 SS  
WASHER FLAT M5  
SCREW HHPM M5-0.8 X 12  
NUT HEX M5-0.8 G8 CLEAR ZINC  
SCREW PHTT M4-0.7 X 10 ZYC  
WASHER FLAT M4  
SCREW PPHM M4-0.7 X 8 BLK OX  
WASHER LOCK M4  
DECAL WARNING BATT CHRG 12/24V  
SCREW PHTT M3.5-0.6 X 10  
SCREW PHTT M4-0.7 X 12 ZYC  
CONN DUST CAP W/CHAIN DB9  
WASHER FLAT M3.5  
SEAL COVER 3.18 X 12.7 X 382  
SEAL COVER 3.18 X 12.7 X 283  
ASSY HARNESS H-PNL SW (NOT SHOWN)  
COMPONENTS INCLUDED IN WIRE HARNESS  
A
B
C
D
E
0F1263  
0F1262  
0F1264  
0E9049B  
055911  
1
4
1
1
1
ADPTR RH SIDE WICKMAN 178.6191  
HOLDER FUSE WICKMANN 178.6150  
ADPTR LH SIDE WICKMAN 178.6192  
ASSY PCB G-PANEL RELAY 12VDC  
BLOCK TERM 20A 12 X 6 X 1100V  
COMPONENTS NOT INCLUDED IN 0F1826E OR WIRE HARNESS  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
056739  
-
-
1
1
1
1
2
4
2
RELAY SOLENOID 12VDC PNL MNT  
DPE BREAKER SEE DRAWING 0F9280  
BOOST RESISTOR SEE DRAWING 0F9280  
COVER CONTROL PANEL SIDE  
SCREW HHC 1/4-20 X 3/4 G5  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
0F2627A  
022287  
022473  
022097  
043182  
051714  
052777  
0C2323  
0F5459  
0F5461  
022127  
0F5460  
0E7403C  
0E7403B  
0F6145  
091526  
0C2699  
051713  
049226  
3
WASHER LOCK M3  
3
3
NUT HEX M3-0.5 G8 YEL CHR  
WASHER FLAT M3  
2
1
1
SCREW PHTT #6-32 X 5/8 ZYC  
DECAL CPL CONTROL PANEL FUSES  
DECAL 5.4/6.8L TB3  
2
NUT HEX 1/4-20 STEEL  
1
1
2
A/R  
4
2
4
DECAL CPL 5.4/6.8L RELAY BOARD  
FUSE ATO TYPE 15 AMP (BLUE)  
FUSE ATO TYPE 10 AMP (RED)  
SEAL WEATHER .45" DIA  
SCREW PPHM M5-0.8 X 12 ZNC  
SCREW PHTT #6-32 X 3/8 ZYC  
WASHER FLAT M5  
4
WASHER LOCK M5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
0F2807C  
0F2807E  
0F9207  
0F2807B  
0F2807D  
0F9208  
0F4505  
0A6765  
0F4710  
0F7200  
080762  
0F2809  
0F2981A  
0F2962  
0C2454  
022097  
0F2830  
0F4462  
0C2454  
0F4367  
0F4368  
0F2773C  
0F2773D  
0D3159  
088775  
0F2808  
0F5447  
022473  
0F6214  
080762  
0F6803  
049813  
049721  
088510  
1
1
1
1
1
1
REF  
2
6
6
8
1
2
2
4
8
PIPE EXH MAN R/H 6.8L G/B CPL (6.8L C5)  
PIPE EXH MAN R/H 5.4L G/B & 2P (5.4L C5)  
PIPE EXH MANIFOLD 4.6L RH  
PIPE EXH MAN L/H 6.8L G/B CPL (6.8L C5)  
PIPE EXH MAN L/H 5.4L G/B & 2P (5.4L C5)  
PIPE EXH MANIFOLD 4.6L LH  
GLASS PACK 23.5" LG 2.5" IN/OUT  
RING GASKET 2.5 DIA  
WASHER LOCK M10 SS  
SCREW HHC M10-1.5 X 50 SS FTH  
BOLT U 3/8-16 X 2.62  
PIPE EXHAUST CROSSOVER  
MFLR 7" X 9" X 25" (2) 2.5" IN/2.5" OUT  
MUFFLER STRAP  
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
SCREW THF M6-1 X 16 N WA Z/JS  
WASHER LOCK M6-1/4  
2
MUFFLER BRACKET STIFFENER  
RAIN CAP ALUM FOR 2-1/2" PIPE  
SCREW THF M6-1 X 16 N WA Z/JS  
HEAT SHIELD EXHAUST STACK  
CAP HEAT SHIELD EXHAUST STACK  
EXHAUST BLANKET 900MM LONG (6.8L C5)  
EXHAUST BLANKET 850MM LONG (5.4L C5)  
FLANGE EXHAUST  
WASHER FLAT 3/8 SS  
EXHUAST OUTLET PIPE CPL  
BRKT MUFFLER  
WASHER FLAT 1/4-M6 ZINC  
PIPE ELBOW EXHAUST MUFFLER  
REF  
REF  
REF  
REF  
2
2
2
6
2
1
12  
2
REF  
4
4
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
BOLT U 3/8-16 X 2.62  
MUFFLER STRAP UPPER/LOWER  
NUT HEX M6 X 1.0 G8 YEL CHR  
SCREW HHC M6-1.0 X 35 G8.8 BLK  
NUT HEX M10-1.5 SS  
8
6
* PARTS INCLUDED IN 0F6322 KIT, GLASS PACK SHIP LOOSE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5 **  
6
7
0F3017  
039253  
022129  
022145  
0D5419  
0D7055  
0D3488G  
0D3488J  
0D3488  
0D3488K  
057795A  
0A6283  
0F3287  
0F5990  
0E9868A  
057796  
0F3216  
0F3216A  
0F3216C  
0F3216D  
055476  
0F4612  
0D6658  
029333A  
022097  
022473  
042568  
0D8027  
0D8025  
0D8026  
0D8030  
0F2846  
0D8029  
0D8028  
045771  
0D3454  
022131  
046526  
064416  
045772  
0F3217  
0F2776A  
0F6151  
0F4308  
0F3158  
057823  
0E0502  
0G0866  
0F4301  
0F4355  
0G0153  
057823  
1
3
4
4
REF  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
3
3
3
4
1
3
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
BRACKET,D.C. ALTERNATOR LOWER  
SCREW HHC M8-1.25 X 20 G8.8  
WASHER LOCK M8-5/16  
WASHER FLAT 5/16-M8 ZINC  
OIL FILTER, FORD V-10 ENGINE  
DIPSTICK TUBE, FORD 6.8L  
BELT SERPENTINE (65.0" LG) (1800 RPM)  
BELT SERPENTINE (65.3" LG) (2300 RPM)  
BELT SERPENTINE (67.16" LG) (3000 RPM)  
SERPENTINE BELT (68.3" LG) (3600 RPM)  
BARBED EL 90 3/4 PLASTIC  
HOSE PREFORMED BLOCK HEATER  
BRACKET DC ALTERNATOR UPPER  
HARN ENG 6.8L H-100 (NOT SHOWN)  
ALTERNATOR DC W/OUT PULLEY  
GROMMET  
PULLEY 80 OD DC ALTERNATOR (1800 RPM)  
PULLEY 102 OD DC ALTERNATOR (2300 RPM)  
PULLEY 132 OD DC ALTERNATOR (3000 RPM)  
PULLEY 160 OD DC ALTERNATOR (3600 RPM)  
BUSHING REDUCER 3/8 TO 1/8 GAL  
SENDER OIL PRESSURE 1/8" NPT  
DIPSTICK 6.8L FORD  
TIE WRAP UL 7.4" X .19" BLK (NOT SHOWN)  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4 ZINC  
SCREW HHC M6-1.0 X 20 G8.8  
BOLT WATER PUMP PULLEY  
BOLT GROOVED IDLER PULLEY  
BOLT BELT TENSIONER  
TENSIONER ENG. AUTOMATIC BELT  
PULLEY WATER PUMP FORD (1800RPM UNITS)  
PULLEY ENGINE WATER PUMP (2-POLE & GEAR BOX)  
PULLEY GROOVED ENGINE IDLER  
NUT HEX M8-1.25 G8 YEL CHR  
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18 *  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
ENGINE 6.8L FORD (V-10)  
WASHER FLAT 3/8-M10 ZINC  
WASHER LOCK M10  
SCREW HHC M10-1.5 X 45 G8.8 FT  
NUT HEX M10-1.5 G8 YEL CHR  
SPACER DC ALTERNATOR PULLEY  
BRACKET SIGNAL CONDITIONER  
CAP RUBBER  
BRACKET DC ALT STABILIZER  
OIL COOLER FORD (150KW 3600RPM)  
CLAMP HOSE #10 .56-1.06  
TEMPERATURE SENDER DELPHI  
HOSE OIL COOLER PREFORMED 3/4 (150KW 3600RPM)  
HOSE OIL COOLER (150KW 3600RPM)  
ADAPTOR 1/2" NPT - 3/8" NPT (150KW 3600RPM)  
BARBED EL 90 1/2 NPT X 3/4 HOSE (150KW 3600RPM)  
CLAMP HOSE #10 .56-1.06 (150KW 3600RPM)  
* NOTE: I/N 18 IS FOR HOLDING SENSOR TO I/N 35.  
**I/N 5 PART OF I/N 29.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
039253  
0D5418  
052625  
047411  
0D5623  
0D2608  
070006  
070008  
055934M  
047290  
046526  
057823  
057765  
049340  
0D5417  
049821  
022129  
070010  
0F2776A  
022097  
048191  
022473  
029333A  
0D9913  
055596  
069860E  
0D4255  
057772  
0D6686  
0F3131  
0D3805  
021113  
077996  
022131  
048031J  
052647  
0D2244M  
0D3808  
0F5114  
0F5454  
079121  
1
1
11  
1
SCREW HHC M8-1.25 X 20 G8.8  
STARTER MOTOR FORD V-10 ENGINE  
SCREW SHC M10-1.5 X 35 G12.9  
SCREW HHC M6-1.0 X 16 G8.8  
HEAT SHIELD EXHAUST  
SCREW HHC 5/16-18 X 1/2 SSTL  
WASHER LOCK M8 SSTL  
WASHER FLAT M8 SS  
CLAMP VINYL .75 X .343 Z  
2
10  
30  
10  
1
1
23  
1
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23 *  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
HOSE 3/8 ID SINGLE BRAID (15”)  
WASHER LOCK M10  
CLAMP HOSE #10 .56 - 1.06 (2300 & 3000RPM UNITS ONLY)  
ADAPTER M14-1.50 X 3/8 NPT  
BARBED EL 90 1/4 NPT X 3/8  
SCREW HHC M10-1.0 X 25 G10.9  
SCREW SHC M8-1.25 X 30 G12.9  
WASHER LOCK M8-5/16  
SCREW HHC M8-1.25 X 35 SS F-TH  
BRACKET SIGNAL CONDITIONER  
WASHER LOCK M6-1/4  
DOWEL PIN M10 X 24  
WASHER FLAT 1/4 ZINC  
TIE WRAP UL 7.4" X .19" BLK (NOT SHOWN)  
SCREW SHC M8-1.25 X 35 SS  
BARBED STR 3/8 NPT X 3/8  
HOSE DRAIN ASSY 28"  
GASKET EXHAUST MANIFOLD  
WASHER NYLON .565  
ASSEMBLY 6.8L G-BOX FLYWHEEL  
HOUSING FLYWHEEL 6.8L FORD MCH  
COVER FLYWHEEL MACH 6.8L V-10  
PLATE DAMPNER RETNR  
CAP HOSE (2300 & 3000RPM UNITS ONLY)  
WASHER FLAT 3/8-M10 ZINC  
HOSE CLAMP BAND 5/8"  
SCREW SHC M10-1.5 X 25 G12.9  
ASSY MAGPICKUP(3/8-24 MALE)  
EXH MANIFOLD MACH 6.8L V-10  
DECAL REFER TO OWNERS MANUAL  
PLATE MAG PICK-UP ADAPTOR  
SCREW SHC M10-1.50 X 100 G10.9  
1
1
REF.  
3
4
2
1
1
2
1
1
18  
1
1
2
1
1
1
1
1
1
7
1
9
1
2
1
1
2
* NOTE: I/N 23 IS FOR HOLDING SENSORS TO I/N 19.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
9
0D2513D  
0F5419  
0F4268  
0F4270A  
0F6977  
037561  
047411  
022097  
049811  
0F4269  
022473  
1
1
1
1
1
1
4
4
4
1
1
AIR CLNR BTM PLT W/CPLR 8.1L  
ELEMENT AIR FILTER  
TOP PLATE VENTURI  
HOLD DOWN AIR CLEANER PLATED  
PLATE AIR CLEAN TOP 5.4L/6.8L  
NUT WING 1/4-20 NYLK  
SCREW HHC M6-1.0 X 16 G8.8  
WASHER LOCK M6-1/4  
WASHER FLAT M6  
GASKET MIXER BODY  
WASHER FLAT 1/4-M6 ZINC  
10  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
049721  
065908  
0F6261G  
0F6261C  
0F6261D  
052617  
022304  
022129  
045773  
022195  
040173  
0C7649  
030131  
031015  
039130  
057822  
059057  
0A8064  
0D1509  
050279  
0F2756A  
0D2696B  
0E4390  
0E4392  
0F0960  
0F3885  
0F3694  
0F3691C  
0F3691D  
0F3691E  
026915  
059057  
035461  
081017  
046580  
039294  
022097  
047290  
052223  
0D2698  
059057  
064346  
0F4408  
0F6279  
4
1
1
1
1
2
2
4
2
2
2
2
1
1
1
9
2
2
1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
1
4
2
4
1
1
1
1
1
1
1
SCREW HHC M6-1.0 X 35 G8.8 BLK  
SUPPORT NAT GAS SOLENOID  
REGULATOR ASSM 5.4L 80KW NG  
REGULATOR ASSM 5.4L 100KW NG  
REGULATOR ASSM 6.8L 100KW NG  
SCREW HHC M12-1.75 X 20 G8.8  
WASHER FLAT 1/2 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M12-1.75 G8 YEL CHR  
WASHER LOCK 1/2  
CLAMP HOSE #5.5 .62-.62 (5.4L)  
CLAMP HOSE .38-.87 (6.8L 100KW)  
ELBOW 90D 1-1/4 NPT  
NIPPLE PIPE 1-1/4 NPT X 3  
NIPPLE CLOSE 1.25 NPT X 1.625  
CLAMP HOSE #8 .53-1.00  
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
HOSE 3/4 ID SAE-30R2 (42” LG)  
BSHG RDCR HEX 1-1/4-3/4  
DECAL INLET PRESSURE  
DECAL FUEL INLET NG  
MACHINING, INTAKE ADAPTOR 60MM (5.4L FORD)  
ADAPTOR THROTTLE BODY (BOSCH) (6.8L FORD GEARBOX)  
GASKET GOVERNOR ACTUATOR  
ACTUATOR BOSCH 60 GOVERNOR  
REDUCER 3.0" TO 2.75" TURBO  
MIXER 40/60MM ACTUATOR ASSY  
O-RING 2-7/8 X 3-1/16 X 3/32  
VENTURI THROTTLE 38MM (5.4L 80KW)  
VENTURI THROTTLE 40MM (5.4L FORD 2-POLE 100KW)  
VENTURI THROTTLE 42MM (6.8L FORD GEARBOX 100KW)  
NIPPLE CLOSE 3/4 X 1.375  
HOSE 3/4 ID SAE-30R2 (42” LG)  
BARBED STR 1/4 NPT X 3/8 (5.4L 80KW & 100KW NG)  
BARBED STR 1/4 NPT X 1/2 (6.8L 100KW NG)  
SCREW SHC M6-1.0 X 45 G12.9  
CLAMP HOSE #44 2.31-3.25  
WASHER LOCK M6-1/4  
HOSE 3/8 ID SINGLE BRAID (42” LG)  
HOSE 1/2 ID SAE-30R2 FUELOIL (42” LG) (6.8L 100KW)  
GASKET ADAPTER THROT BODY (6.8L FORD ONLY)  
HOSE 3/4 ID SAE-30R2 (42” LG)  
PIPE TEE 1-1/4 NPT  
Y CONNECTOR 500 SERIES BARBS  
HARNESS FUEL JUMPER DUAL REG  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
033212  
065908  
0F6261H  
0F6261J  
0F6261K  
0F6261L  
0F6261M  
052617  
022304  
022129  
045773  
064346  
0A8064  
030131  
031015  
088963  
026915  
057823  
059057  
0D2698  
0D1509  
050280  
0D2696B  
0F2756A  
0E4390  
0E4392  
0F0960  
0F3885  
0F3694  
0F3691B  
0F3691D  
0F3691E  
0F3691F  
0F3691J  
022195  
0F6279  
081017  
046580  
039294  
022097  
047290  
040173  
039130  
4
1
1
1
1
1
1
2
2
4
2
1
2
1
1
1
2
4
2
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
2
1
1
4
2
4
1
2
1
SCREW HHC 5/16-18 X 1-1/4 G5  
SUPPORT NAT GAS SOLENOID  
REGULATOR ASSM 5.4L 80KW LPV (5.4L 80KW)  
REGULATOR ASSM 5.4L 100KW LPV (5.4L 100KW)  
REGULATOR ASSM 6.8L 100KW LPG (6.8L 100KW)  
REGULATOR ASSM 6.8L 130KW LPV (6.8L 130KW)  
REGULATOR ASSM 6.8L 150KW LPV (6.8L 150KW)  
SCREW HHC M12-1.75 X 20 G8.8  
WASHER FLAT 1/2 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M12-1.75 G8 YEL CHR  
PIPE TEE 1-1/4 NPT  
BSHG RDCR HEX 1-1/4-3/4  
ELBOW 90D 1-1/4 NPT  
NIPPLE PIPE 1-1/4 NPT X 3  
NIPPLE PIPE 1.25 NPT X 5.5 BL IRN (6.8L 150KW ONLY)  
NIPPLE CLOSE 3/4 X 1.375  
CLAMP HOSE #10 .56-1.06  
HOSE 3/4 ID SAE-30R2 (45” LG)  
GASKET ADAPTER THROT BODY  
DECAL INLET PRESSURE  
DECAL FUEL INLET LPG (LP VAPOR APPLICATION)  
ADAPTOR THROTTLE BODY (BOSCH) (6.8L)  
MACHINING INTAKE ADAPTOR 60MM (5.4L)  
GASKET GOVERNOR ACTUATOR  
ACTUATOR BOSCH 60 GOVERNOR  
REDUCER 3.0" TO 2.75" TURBO  
MIXER 40/60MM ACTUATOR ASSY  
O-RING 2-7/8 X 3-1/16 X 3/32  
VENTURI THROTTLE 36MM (5.4L 80KW)  
VENTURI THROTTLE 40MM (5.4L 100KW)  
VENTURI THROTTLE 42MM (6.8L 100KW)  
VENTURI THROTTLE 44MM (6.8L 130KW)  
VENTURI THROTTLE 50MM (6.8L 150KW)  
WASHER LOCK 1/2  
HARNESS FUEL JUMPER DUAL REG  
BARBED STR 1/4 NPT X 1/2  
SCREW SHC M6-1.0 X 45 G12.9  
CLAMP HOSE #44 2.31-3.25  
WASHER LOCK M6-1/4  
HOSE 3/8 ID SINGLE BRAID (42” LG)  
CLAMP HOSE #5.5 .62-.62  
NIPPLE CLOSE 1.25 NPT X 1.625  
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(2) 1  
(2) 2  
(2) 3  
(2) 4  
(2) 5  
(2) 6  
(2) 7  
0F5873  
0F5868  
0F5872  
0F5871  
0F5869  
0F5870  
0F5867  
1
4
2
2
2
1
1
REAR WRAP C5  
DOOR C5  
CENTER SUPPORT C5  
DISCHARGE DUCT LH & RH SIDE C5  
FRONT CORNERS C5  
DISCHARGE CENTER DUCT C5  
ROOF C5 ALUM  
11  
0C2454  
0F2766  
78  
2
SCREW THF M6-1 X 16 N WA Z/JS  
SPLITTER  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
(1)44  
45  
46  
47  
48  
49  
0F3181  
0F3185  
0F3416  
0F3949  
0C2634A  
022473  
022097  
022127  
0F3072  
078115  
0F3949B  
0F3949A  
0F5048D  
0E5968  
4
2
2
2
1
5
1
1
20  
70  
3
4
4
1
4
2
1
8
2
1
4
1
2
1
2
4
14  
4
2
4
4
28  
2
1
SPLITTER SHORT  
STRINGER SPLITTER C3  
SUPPORT SPLITTER C5 130KW  
INSULATION CORNER POST  
ASSEMBLY COVER ACCESS  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
NUT HEX 1/4-20 STEEL  
INSULATION RETAINMENT HANGER  
WASHER SELF LOCKING DOME  
INSULATION SPLITTER  
INSULATION SHORT LOUVER  
VISE-ACTION LATCH SLOTTED CIR  
GASKET EXTRUDED TRIM (566” LG)  
TAB PULL  
INSULATION SPLITTER SML  
INSULATION ROOF TOP REAR  
RETAINER INSULATION (740)  
RIVET POP .1875 X .450 SS  
INSULATION ROOF TOP  
0F5049  
0F3949L  
0F3949E  
0F3890A  
087233  
0F3949C  
0F3949D  
0F3949G  
0F3949J  
0F3949K  
0F3949F  
0F3890B  
0F3890  
INSULATION DOOR  
INSULATION DISCHARGE DUCT  
INSULATION CENTER SUPPORT  
INSULATION DISCHARGE DUCT TOP  
INSULATION INNER DUCT SIDE  
RETAINER INSULATION (820)  
RETAINER INSULATION (450)  
SCREW HHC M6-1.0 X 20 G8.8  
ASSY WIRE 14 AWG 20.9" GRN/YEL  
WASHER SHAKEPROOF INT 1/4  
NUT HEX M6 X 1.0 G8 YEL CHR  
NUT HEX LOCK M6-1.0 SS NY INS  
ASSY WIRE 14 AWG 34.8" GRN/YEL  
SPLITTER C5  
042568  
0912970088  
022447  
049813  
077992  
0912970094  
0F2766A  
0F3949M  
0F8869D  
0E3257  
1
1
6
INSULATION SPLITTER SHRT MPS  
KEY VISE-ACTION LATCH SLOT CIR  
SCREW TH-FRM M6 W/CAP SHKPRF W  
(1) ALUMINUM ENCLOSURE NOTE: ALL ENCLOSURE PANELS THAT FASTEN TO  
THE BASE FRAME MUST BE SECURED USING ITEM 11 & 49 THREAD FORMING  
FASTENER AND ITEM 44 LOCK NUT. LOCK NUT IS TO BE INSTALLED AFTER THREAD  
FORMING FASTENER HAS PENETRATED THROUGH EXTRUSIONS IN ENCLOSURE PANELS.  
ALL ROOF PANELS ARE TO BE SECURED IN THE SAME MANNER.  
(2) I/N’S 1 THRU 7, REFER TO CHART BELOW FOR ENCLOSURE COLOR & MATERIAL TYPE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Warranty  
GENERAC POWER SYSTEMS STANDARD LIMITED WARRANTY FOR  
COMMERCIAL PRODUCT 50kW AND ABOVE  
For a period of two (2) years from the date of sale, or start-up by Authorized/Certified Generac Power Systems Dealer, or branch thereof, Generac  
Power Systems, Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or  
an Authorized/Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with  
the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized/  
Certified Generac Power Systems Dealer, or branch thereof. This warranty applies only to Generac Power Systems Generators used in "Standby"  
applications, as Generac Power Systems, Inc. has defined Standby, provided said generator has been properly installed and inspected on-site by  
appropriate personnel. Scheduled maintenance, as outlined by the generator owner's manual, is highly recommended. This should be performed by  
an Authorized/ Certified Generac Power Systems Dealer, or branch thereof. This will verify service has been performed on the unit throughout the war-  
ranty period.  
WARRANTY SCHEDULE  
YEAR ONE — Limited comprehensive coverage on mileage, labor, and parts listed.  
• - ALL COMPONENTS  
YEAR TWO — Limited comprehensive coverage on parts listed.  
• - ALL COMPONENTS  
*Start-up and/or On-line Registration, or Registration Card, along with Proof of Purchase, must be performed and/or sent in.  
Guidelines:  
• Any and all warranty repairs and/or concerns, must be performed and/or addressed by an Authorized/Certified Generac Power Systems Dealer, or  
branch thereof.  
• A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the genset. If a Non - Generac Power  
Systems, Inc. Transfer Switch is substituted for use and directly causes damage to the genset, no warranty coverage shall apply.  
• All warranty expense allowances are subject to the conditions defined in Generac Power Systems Warranty, Policies, and Procedures Flat Rate  
Manual.  
• Units that have been resold are not covered under the Generac Power Systems Warranty, as this Warranty is not transferable.  
• Unit enclosure is only covered against rust or corrosion the first year of the warranty provision.  
• Use of Non-Generac replacement part(s) will void the warranty in its entirety.  
• Engine coolant heaters (block-heaters), heater controls and circulating pumps are only covered during the first year of the warranty provision (If  
applicable).  
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:  
1. Any unit built/manufactured prior to March 1, 2005.  
2. Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up).  
3. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze.  
4. Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac Power Systems have defined Prime Power,  
Trailer Mounted or Rental Unit. Contact a Generac Power Systems Distributor for Prime Power, Trailer Mounted or Rental Unit definition and  
warranty.  
5. Units used for prime power in place of existing utility power where utility is present or in place of utility power where utility power service does not  
normally exist.  
6. Failures caused by any external cause or act of God such as, but not limited to, collision, fire, theft, freezing, vandalism, riot or wars, lightning,  
earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust.  
7. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing.  
8. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing.  
9. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the  
defective part(s).  
10. Failure due to misapplication, misrepresentation, or bi-fuel conversion.  
11. Telephone, facsimile, cell phone, satellite, internet, or any other communication expenses.  
12. Rental equipment used while warranty repairs are being performed (i.e. rental generators, cranes, etc.).  
13. Overtime, holiday, or emergency labor.  
14. Planes, ferries, railroad, busses, helicopters, snowmobiles, snow-cats, off-road vehicle or any other mode of transportation deemed abnormal.  
15. Any and all expenses incurred investigating performance complaints unless defective Generac materials and/or workmanship were the direct  
cause of the problem.  
16. Starting batteries, fuses, light bulbs, engine fluids, and overnight freight cost for replacement part(s).  
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC POWER SYSTEMS  
MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow  
limitations on how long an implied warranty lasts, so the above limitation may not apply to purchaser/owner.  
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT  
SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A  
DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.  
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to purchaser/  
owner. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence. This warranty gives purchaser/owner  
specific legal rights. Purchaser/owner also may have other rights that vary from state to state  
Generac Power Systems, Inc. • P.O. Box 8 • Waukesha, WI 53187  
Ph: (262) 544-4811 • Fax: (262) 544-4851  
Bulletin 0171370SVE / Printed in U.S.A. 7.05  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Generac Power Systems Switch 004678 2 User Manual
Generac Power Systems Portable Generator 004700 00 User Manual
Generac Power Systems Automobile Parts TXP User Manual
Generac Power Systems Automobile Parts 005055 1 User Manual
Generac Automobile Parts GTV 760 User Manual