Generac Welding System 005818 0 User Manual

Owner's Manual  
EcoGen 6kW Generator  
C
US  
L
ISTED  
Model 005818-0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Rules  
This symbol points out potential electrical shock hazard.  
INTRODUCTION  
Thank you for purchasing this compact, high performance, air-cooled,  
engine-driven generator. It is designed to supply electrical power to  
operate an inverter/battery charger as a component in an off-grid power  
solution.  
The operator is responsible for proper and safe use of the equipment. The  
manufacturer strongly recommends that the operator read this Owner's  
Manual and thoroughly understand all instructions before using this  
equipment. The manufacturer also strongly recommends instructing other  
users to properly start and operate the unit. This prepares them if they  
need to operate the equipment in an emergency.  
This unit is factory installed in an all-weather, metal enclosure and is  
intended exclusively for outdoor installation. This generator will operate  
using vapor withdrawn liquid propane (LP).  
NOTE:  
CONTENTS  
This generator is suitable for supplying typical residential loads such  
as Induction Motors (sump pumps, refrigerators, air conditioners,  
furnaces, etc.), Electronic Components (computer, monitor, TV, etc.),  
Lighting Loads and Microwaves.  
This manual contains important instructions that should be followed dur-  
ing installation and maintenance of the generator and batteries for the 6kW  
LP, V-twin GT-530 Engine.  
OPERATION AND MAINTENANCE  
READ THIS MANUAL THOROUGHLY  
It is the operator's responsibility to perform all safety checks, to make sure  
that all maintenance for safe operation is performed promptly, and to have  
the equipment checked periodically by a Dealer. Normal maintenance ser-  
vice and replacement of parts are the responsibility of the owner/operator  
and, as such, are not considered defects in materials or workmanship  
within the terms of the warranty. Individual operating habits and usage  
contribute to the need for maintenance service.  
If any portion of this manual is not understood, contact the nearest Dealer  
for starting, operating and servicing procedures.  
SAFETY RULES  
Throughout this publication, and on tags and decals affixed to the genera-  
tor, DANGER, WARNING, CAUTION and NOTE blocks are used to alert  
personnel to special instructions about a particular operation that may be  
hazardous if performed incorrectly or carelessly. Observe them carefully.  
Their definitions are as follows:  
Proper maintenance and care of the generator ensures a minimum number  
of problems and keep operating expenses at a minimum. See a Dealer for  
service aids and accessories.  
HOW TO OBTAIN SERVICE  
When the generator requires servicing or repairs, contact a Dealer for  
assistance. Service technicians are factory-trained and are capable of  
handling all service needs.  
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF  
NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.  
When contacting a Dealer about parts and service, always supply the  
complete model number and serial number of the unit as given on its data  
decal, which is located on the generator. See section "The Generator" for  
decal location.  
Indicates a hazardous situation or action which, if not  
avoided, could result in death or serious injury.  
Model No. _________________ Serial No.______________  
Indicates a hazardous situation or action which, if not  
avoided, could result in minor or moderate injury.  
Data Label Sample  
NOTE:  
Notes contain additional information important to a procedure  
and will be found within the regular text body of this manual.  
These safety warnings cannot eliminate the hazards that they  
indicate. Common sense and strict compliance with the special  
instructions while performing the action or service are essential to  
preventing accidents.  
Four commonly used safety symbols accompany the DANGER,  
WARNING and CAUTION blocks. The type of information each  
indicates is as follows:  
This symbol points out important safety information that,  
if not followed, could endanger personal safety and/or  
n
property of others.  
This symbol points out potential explosion hazard.  
This symbol points out potential fire hazard.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Rules  
IMPORTANT SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation  
be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this  
n
equipment.  
Study these SAFETY RULES carefully before installing, operating  
or servicing this equipment. Become familiar with this Owner’s  
Manual and with the unit. The generator can operate safely, effi-  
ciently and reliably only if it is properly installed, operated and  
maintained. Many accidents are caused by failing to follow simple  
and fundamental rules or precautions.  
• Install a battery operated carbon monoxide alarm indoors,  
according to manufacturer's instructions/recommendations.  
• Adequate, unobstructed flow of cooling and ventilating air is  
critical to correct generator operation. Do not alter the instal-  
lation or permit even partial blockage of ventilation provisions,  
as this can seriously affect safe operation of the generator. The  
generator MUST be installed and operated outdoors only.  
• Keep hands, feet, clothing, etc., away from drive belts, fans,  
and other moving or hot parts. Never remove any drive belt or  
fan guard while the unit is operating.  
The manufacturer cannot anticipate every possible circumstance  
that might involve a hazard. The warnings in this manual, and on  
tags and decals affixed to the unit are, therefore, not all-inclusive. If  
using a procedure, work method or operating technique the manu-  
facturer does not specifically recommend, ensure that it is safe for  
others. Also make sure the procedure, work method or operating  
technique utilized does not render the generator unsafe.  
• When working on this equipment, remain alert at all times.  
Never work on the equipment when physically or mentally  
fatigued.  
• Inspect the generator regularly, and contact the nearest Dealer  
for parts needing repair or replacement.  
• Before performing any maintenance on the generator, discon-  
nect its battery cables to prevent accidental start up. Disconnect  
the cable from the battery post indicated by a NEGATIVE, NEG  
or (–) first, then remove the POSITIVE, POS or (+) cable. When  
reconnecting the cables, connect the POSITIVE cable first, the  
NEGATIVE cable last.  
Despite the safe design of this generator,  
operating this equipment imprudently, neglect-  
n
ing its maintenance or being careless can  
cause possible injury or death. Permit only  
responsible and capable persons to install,  
operate and maintain this equipment.  
• Never use the generator or any of its parts as a step. Stepping  
on the unit can stress and break parts, and may result in dan-  
gerous operating conditions from leaking exhaust gases, fuel  
leakage, oil leakage, etc.  
Potentially lethal voltages are generated by  
these machines. Ensure all steps are taken to  
render the machine safe before attempting to  
work on the generator.  
Parts of the generator are rotating and/or  
hot during operation. Exercise care near run-  
EXHAUST HAZARDS  
n
ning generators.  
• Generator engine exhaust contains DEADLY carbon monox-  
ide, an odorless, colorless poisonous gas. Breathing carbon  
monoxide can cause: dizziness, throbbing temples, nausea,  
muscular twitching, headache, vomiting, weakness and sleepi-  
ness, inability to think clearly, fainting, unconsciousness or  
even death. If you experience any carbon monoxide poisoning  
symptoms, move into fresh air and immediately seek medical  
attention.  
Installation must always comply with appli-  
cable codes, standards, laws and regula-  
tions.  
n
n
A running generator gives off carbon mon-  
oxide, and odorless, colorless poison gas.  
Breathing in carbon monoxide can cause  
headaches, fatigue, diziness, nausea, vomit-  
ting, confusion, fainting, siezures or death.  
• Never operate the generator set with the vehicle inside any  
garage or other enclosed area.  
GENERAL HAZARDS  
ELECTRICAL HAZARDS  
• For safety reasons, the manufacturer recommends that this equip-  
ment be installed, serviced and repaired by a Service Dealer or  
other competent, qualified electrician or installation technician who  
is familiar with applicable codes, standards and regulations. The  
operator also must comply with all such codes, standards and  
regulations.  
• The engine exhaust fumes contain carbon monoxide, which  
can be DEADLY. This dangerous gas, if breathed in sufficient  
concentrations, can cause unconsciousness or even death.  
Do NOT alter or add to the exhaust system or do anything that  
might render the system unsafe or in noncompliance with appli-  
cable codes and standards.  
• All generators covered by this manual produce dangerous  
electrical voltages and can cause fatal electrical shock. Utility  
power delivers extremely high and dangerous voltages to the  
transfer switch as does the standby generator when it is in  
operation. Avoid contact with bare wires, terminals, connec-  
tions, etc., while the unit is running. Ensure all appropriate  
covers, guards and barriers are in place, secured and/or locked  
before operating the generator. If work must be done around  
an operating unit, stand on an insulated, dry surface to reduce  
shock hazard.  
• Do not handle any kind of electrical device while stand-  
ing in water, while barefoot, or while hands or feet are wet.  
DANGEROUS ELECTRICAL SHOCK MAY RESULT.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Rules  
• The National Electrical Code (NEC) requires the frame and external  
electrically conductive parts of the generator to be connected to  
an approved earth ground. Local electrical codes also may require  
proper grounding of the generator electrical system.  
STANDARDS INDEX  
In the absence of pertinent standards, codes, regulations and  
laws, the published information listed below may be used for  
installation guidance for this equipment.  
• After installing this home standby electrical system, the genera-  
tor may crank and start at any time without warning. When this  
occurs, load circuits are transferred to the STANDBY (genera-  
tor) power source. To prevent possible injury if such a start and  
transfer occur, always set the generator’s AUTO/OFF/MANUAL  
switch to its OFF position before working on equipment and  
remove the 7.5A fuse from the generator control panel.  
• In case of accident caused by electric shock, immediately shut  
down the source of electrical power. If this is not possible,  
attempt to free the victim from the live conductor. AVOID DIRECT  
CONTACT WITH THE VICTIM. Use a nonconducting implement,  
such as a dry rope or board, to free the victim from the live  
conductor. If the victim is unconscious, apply first aid and get  
immediate medical help.  
1. NFPA No. 37, STATIONARY COMBUSTION ENGINES AND  
GAS TURBINES, available from the National Fire Protection  
Association, 470 Atlantic Avenue, Boston, MA 02210.  
2. NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR  
HEALTH CARE FACILITIES, available same as Item 1.  
3. NFPA No. 54, NATIONAL FUEL GAS CODE, available same as  
Item 1.  
4. NFPA No. 58, AMERICAN NATIONAL STANDARD FOR  
STORAGE AND HANDLING OF LIQUEFIED PETROLEUM GAS,  
available same as Item 1.  
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELECTRIC  
CODE, available same as Item 1.  
6. Article X, NATIONAL BUILDING CODE, available from the  
American Insurance Association, 85 John Street, New York,  
N.Y. 10038.  
7. AGRICULTURAL WIRING HANDBOOK, available from the Food  
and Energy Council, 909 University Avenue, Columbia, MO  
65201.  
8. ASAE EP-3634, INSTALLATION AND MAINTENANCE OF  
FARM STANDBY ELECTRICAL SYSTEMS, available from the  
American Society of Agricultural Engineers, 2950 Niles Road,  
St. Joseph, MI 49085.  
• Never wear jewelry when working on this equipment. Jewelry  
can conduct electricity resulting in electric shock, or may get  
caught in moving components causing injury.  
FIRE HAZARDS  
• For fire safety, the generator must be installed and maintained  
properly. Installation must always comply with applicable  
codes, standards, laws and regulations. Adhere strictly  
to local, state and national electrical and building codes.  
Comply with regulations the Occupational Safety and Health  
Administration (OSHA) has established. Also, ensure that the  
generator is installed in accordance with the manufacturer’s  
instructions and recommendations. Following proper installa-  
tion, do nothing that might alter a safe installation and render  
the unit in noncompliance with the aforementioned codes,  
standards, laws and regulations.  
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS  
CODE, available same as Item 1.  
• Keep a fire extinguisher near the generator at all times.  
Extinguishers rated ABC” by the National Fire Protection  
Association are appropriate for use on the standby electric  
system. Keep the extinguisher properly charged and be familiar  
with its use. Consult the local fire department with any ques-  
tions pertaining to fire extinguishers.  
EXPLOSION HAZARDS  
CALIFORNIA PROPOSITION 65 WARNING  
Engine exhaust and some of its constituents are known  
to the State of California to cause cancer, birth defects  
and other reproductive harm.  
• Do not smoke around the generator. Wipe up any fuel or oil  
spills immediately. Ensure that no combustible materials are left  
in the generator compartment, or on or near the generator, as  
FIRE or EXPLOSION may result. Keep the area surrounding the  
generator clean and free from debris.  
CALIFORNIA PROPOSITION 65 WARNING  
This product contains or emits chemicals known to the  
State of California to cause cancer, birth defects and  
other reproductive harm.  
• Gaseous fluids such as natural gas and liquid propane (LP)  
gas are extremely EXPLOSIVE. Install the fuel supply system  
according to applicable fuel-gas codes. Before placing the  
home standby electric system into service, fuel system lines  
must be properly purged and leak tested according to applica-  
ble code. After installation, inspect the fuel system periodically  
for leaks. No leakage is permitted.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
1.3 EMISSION INFORMATION  
The Environmental Protection Agency requires that this generator  
comply with exhaust emission standards. This generator is certi-  
fied to meet the applicable EPA emission levels. Additional infor-  
mation regarding the requirements set by the EPA is as follows:  
Only qualified electricians or contractors  
should attempt such installations, which must  
n
comply strictly with applicable codes, stan-  
dards and regulations.  
The generator is certified for use as a stationary engine for standby  
power generation. Any other use may be a violation of federal and/  
or local laws. It is important to follow the maintenance specifica-  
tions in the "Maintenance" section to ensure that the engine com-  
plies with the applicable emission standards for the duration of the  
engine’s life. This engine is certified to operate on Liquid Propane  
fuel. The emission control system on the generator consists of the  
following:  
1.1 UNPACKING/INSPECTION  
After unpacking, carefully inspect the contents for damage.  
• This standby generator set is ready for installation with a factory  
supplied and pre-mounted base pad and has a weather protec-  
tive enclosure that is intended for outdoor installation only.  
• Fuel Metering System  
• Carburetor/mixer assembly  
• Fuel regulator  
• Air Induction System  
• Intake pipe/manifold  
• Air cleaner  
• Ignition System  
• Spark plug  
If this generator is used to power electrical load  
circuits normally powered by a utility power  
source, it is required by code to install a trans-  
fer switch. The transfer switch must effectively  
isolate the electrical system from the utility  
distribution system when the generator is oper-  
ating (NEC 700, 701 & 702). Failure to isolate an  
electrical system by such means will result in  
damage to the generator and also may result in  
injury or death to utility power workers due to  
backfeed of electrical energy.  
• Ignition module  
The Emissions Compliance Period referred to on the Emissions  
Compliance Label indicates the number of operating hours for  
which the engine has been shown to meet Federal emission  
requirements. See the table below to determine the compliance  
period for the generator. The displacement of the generator is listed  
on the Emissions Compliance Label.  
If any loss or damage is noted at time of delivery, have the  
person(s) making the delivery note all damage on the freight bill  
or affix their signature under the consignor's memo of loss or  
damage.  
If a loss or damage is noted after delivery, separate the damaged  
materials and contact the carrier for claim procedures.  
Displacement  
Category  
Compliance Period  
300 Hours  
125 Hours  
50 Hours  
A
B
C
A
B
C
A
B
C
“Concealed damage” is understood to mean damage to the con-  
tents of a package that is not in evidence at the time of delivery,  
but is discovered later.  
< 66 cc  
To properly open the roof, press down on the center top lip and  
turn the locks on both ends. If pressure is not applied from the top,  
the roof may appear stuck. Always verify that the side locks are  
unlocked before attempting to lift the roof.  
500 Hours  
250 Hours  
125 Hours  
1000 Hours  
500 Hours  
250 Hours  
66 cc -  
< 225 cc  
1.2 PROTECTION SYSTEMS  
Unlike an automobile engine, the generator may have to run for  
long periods of time with no operator present to monitor engine  
conditions. For that reason, the engine is equipped with the fol-  
lowing systems that protect it against potentially damaging condi-  
tions:  
225 cc  
1. Low Oil Pressure Sensor  
2. High Temperature Sensor  
3. Overcrank  
6. Low Battery  
7. Under-frequency  
8. Undervoltage  
9. Overvoltage  
4. Overspeed  
5. RPM Sensor  
10. Internal Failure  
There are readouts on the control panel to notify personnel that  
one of these failures has occurred. There is a Status message on  
the display that displays when all of the conditions described in the  
"Ready to Run" section are true.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
1.4 THE GENERATOR  
1.5 SPECIFICATIONS  
1.5.1  
GENERATOR  
Figure 1.1 – 6kW, V-twin, GT-530 Engine  
(door removed)  
Fuel Type ....................................................................................... LP vapor only  
Rated Voltage.........................................................................................120 VAC  
Rated Maximum Load Current (Amps) at 120 Volts (LP)* .............................50.0  
Main Circuit Breaker................................................................................ 50 Amp  
Phase ................................................................................................................1  
Number of Rotor Poles.......................................................................................2  
Rated AC Frequency....................................................................................60 Hz  
Battery Requirement........................ Group 26R, 12 Volts and 525 CCA Minimum  
Weight (unit only in lbs.) ................................................................................387  
Enclosure..................................................................................................... Steel  
Normal Operating Range: This unit is tested in accordance to UL 2200 standards  
with an operating temperature of 20 °F (-29 °C) to 122 °F. (50 °C). For areas  
where temperatures fall below 32 °F (0 °C), a cold weather kit is highly recom-  
mended. When operated above 104º F (40º C) there may be a decrease in engine  
power. (Please reference the engine specifications section).  
Air Filter  
External Oil Fill/Dipstick  
Control  
Panel  
Data  
Label  
Engine  
Oil Fill  
Circuit  
Breaker  
Engine Oil  
Dipstick  
Fuel Inlet  
(back)  
These generators are rated in accordance with UL2200, Safety Standard for  
Stationary Engine Generator Assemblies; and CSA-C22.2 No. 100-04 Standard  
for Motors and Generators.  
Fuel  
Regulator  
Exhaust  
Enclosure  
Oil Filter Battery  
Composite  
1.5.2  
ENGINE  
Compartment Base  
Type of Engine ......................................................................................... GT-530  
Number of Cylinders ..........................................................................................2  
Rated Horsepower @ 3,600 rpm*...................................................................18  
Displacement.............................................................................................530cc  
Cylinder Block.........................................................Aluminum w/Cast Iron Sleeve  
Valve Arrangement..................................................................... Overhead Valves  
Ignition System................................................................. Solid-state w/Magneto  
Recommended Spark Plug..................................................................... BPR6HS  
Spark Plug Gap................................................................. 0.76 mm (0.030 inch)  
Compression Ratio.......................................................................................9.5:1  
Starter .....................................................................................................12 VDC  
Oil Capacity Including Filter ..........................................................Approx. 1.7 Qts  
Recommended Oil Filter ............................................................. Part # 070185F  
Recommended Air Filter............................................................... Part # 0E9371  
Operating RPM............................................................................................2,600  
Figure 1.2 – Data Label Sample  
* Engine power is subject to and limited by such factors as fuel Btu content, ambi-  
ent temperature and altitude. Engine power decreases about 3.5 percent for each  
1,000 feet above sea level; and also will decrease about 1 percent for each 6 C  
(10 F) above 16 C (60 F) ambient temperature.  
1.6 READY TO RUN  
The "Ready to Run" on the display is ready when all of the following  
conditions are true:  
1. The AUTO/OFF/MANUAL switch is set to the AUTO position.  
2. The utility voltage being supplied to the unit is being sensed  
by the PCB. If the utility sense voltage is not connected to the  
unit or if it is below approximately 150-160 volts AC, then  
the system will display the message "No Utility Present". This  
indicates that if the AUTO/OFF/MANUAL switch is placed in  
the Auto position, the generator will start.  
3. No alarms are present, for example, low oil pressure, high  
temperature, etc.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
NOTE:  
1.7 FUEL REQUIREMENTS AND  
RECOMMENDATIONS  
This unit uses a LP vapor withdrawal system only. This type of  
system uses the vapors formed above the liquid fuel in the storage  
tank.  
A minimum of one approved manual shut-off valve must be  
installed in the gaseous fuel supply line. The valve must be eas-  
ily accessible. Local codes determine the proper location.  
1.9 LOCATION  
Recommended fuels should have a Btu content of at least 2,520  
Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu  
content of the fuel.  
The engine exhaust fumes contain carbon  
Required fuel pressure for liquid propane, 10 inches to 12 inches  
of water column (0.36 to 0.43 psi). The primary regulator for the  
propane supply is NOT INCLUDED with the generator.  
monoxide, which can be DEADLY. This dan-  
n
gerous gas, if breathed in sufficient con-  
centrations, can cause unconsciousness or  
even death. This generator must be installed  
properly, in strict compliance with applicable  
codes and standards. Following installation,  
do nothing that might render the system  
unsafe or in noncompliance with such codes  
and standards.  
NOTE:  
All pipe sizing, construction and layout must comply NFPA 58  
for liquid propane applications. Once the generator is installed,  
verify that the fuel pressure NEVER drops below 10 inches  
water column.  
Prior to installation of the generator, the installer should consult  
local fuel suppliers or the fire marshal to check codes and regula-  
tions for proper installation. Local codes will mandate correct rout-  
ing of gaseous fuel line piping around gardens, shrubs and other  
landscaping to prevent any damage.  
Operate the generator outdoors ONLY.  
• Keep exhaust gases from entering a confined  
area through windows, doors, ventilation, crawl  
spaces or other openings (Figure 1.3).  
• It is highly recommended that carbon monox-  
ide detector(s) be installed indoors according  
to the manufacturer's instructions/recommen-  
dations.  
• The generator must me mounted safely per  
applicable codes and the manufacturer's speci-  
fications. Do NOT alter or add to the exhaust  
system, or do anything that might render the  
exhaust system unsafe or in noncompliance  
with applicable codes and standards.  
Special considerations should be given when installing the unit  
where local conditions include flooding, tornados, hurricanes,  
earthquakes and unstable ground for the flexibility and strength of  
piping and their connections.  
Use an approved pipe sealant or joint compound on all threaded  
fitting.  
All installed gaseous fuel piping must be purged and leak tested  
prior to initial start-up in accordance with local codes, standards  
and regulations.  
1.9.1  
GENERATOR  
Install the generator set, in its protective enclosure, outdoors,  
where adequate cooling and ventilating air is always available  
(Figure 1.3). Consider these factors:  
1.8 FUEL CONSUMPTION  
LP Vapor  
• The installation of the generator must comply strictly with  
NFPA 37, NFPA 58, and NFPA 70 standards.  
Unit  
1/2 Load  
Full Load  
6 kW  
0.82/30  
1.47/54  
• Install the unit where air inlet and outlet openings will not  
become obstructed by leaves, grass, snow, etc.. If prevailing  
winds will cause blowing or drifting, consider using a wind-  
break to protect the unit.  
** LP is in gallons per hour/cubic feet per hour.  
*** Values given are approximate.  
Verify that gas pipe and regulator is capable of providing enough  
fuel flow to include household appliances.  
• Install the generator on high ground where water levels will not  
rise and endanger it.  
• Allow sufficient room on all sides of the generator for mainte-  
nance and servicing. This unit must be installed in accordance  
with current applicable NFPA 37 and NFPA 70 standards; as  
well as any other federal, state and local codes for minimum  
distances from other structures. DO NOT install under wooden  
decks or structures unless there is at least four (4) feet of clear-  
ance above the generator, three (3) feet of clearance on sides  
and front, and 18 inches of clearance at back of unit.  
• Install the unit where rain gutter down spouts, roof run-off,  
landscape irrigation, water sprinklers or sump pump discharge  
does not flood the unit or spray the enclosure, including any air  
inlet or outlet openings.  
Gaseous fuels such as liquid propane (LP)  
gas are highly explosive. Even the slightest  
spark can ignite fuel and cause an explo-  
sion. No leakage of fuel is permitted. LP gas  
is heavier than air and tends to settle in low  
areas.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
• Install the unit where services will not be affected or obstructed,  
including concealed, underground or covered services such as  
electrical, fuel, phone, air conditioning or irrigation.  
• Where strong prevailing winds blow from one direction, face the  
generator air inlet openings to the prevailing winds.  
• Install the generator as close as possible to the fuel supply, to  
reduce the length of piping.  
• Install the generator as close as possible to the transfer switch.  
REMEMBER THAT LAWS OR CODES MAY REGULATE THE  
DISTANCE AND LOCATION.  
Annex A — Explanatory Material  
A4.1.4 (2) Means of demonstrating compliance are by means  
of full scale fire test or by calculation procedures.  
Because of the limited spaces that are frequently available for  
installation, it has become apparent that exception (2) would be  
beneficial for many residential and commercial installations. With  
that in mind, the manufacturer contracted with an independent  
testing laboratory to run full scale fire tests to assure that the  
enclosure would not ignite combustible materials outside the  
enclosure.  
• The genset must be installed on a level surface. The base frame  
The criteria was to determine the worst case fire scenario within  
the generator and to determine the ignitability of items outside the  
engine enclosure at various distances. The enclosure is construct-  
ed of non-combustible materials and the results and conclusions  
from the independent testing lab indicated that any fire within the  
generator enclosure would not pose any ignition risk to nearby  
combustibles or structures, with or without fire service personnel  
response.  
must be level within two (2) inches all around.  
• The generator is typically placed on pea gravel or crushed  
stone. Check local codes if a concrete slab is required. If a  
concrete base slab is required, all federal, state and local codes  
should be followed. Special attention should be given to the  
concrete base slab which should exceed the length and width  
of the generator by a minimum of six (6) inches (0.152 meters)  
on all sides.  
Based on this testing and the requirements of NFPA 37, Sec 4.1.4,  
the guidelines for installation of the generators listed above are  
changed to 18 inches (457mm) from the back side of the genera-  
tor to a stationary wall or building. For adequate maintenance and  
airflow clearance, the area above the generator should be at least  
4 feet with a minimum of 3 feet at the front and ends of the enclo-  
sure. This would include trees, shrubs and vegetation that could  
obstruct airflow. See the diagram on the reverse of this page and  
the installation drawing within the owner’s manual for details.  
Figure 1.3 – Generator Clearances  
Generator exhaust contains DEADLY carbon monoxide gas. This  
dangerous gas can cause unconsciousness or death. Do not place  
the unit near windows, doors, fresh air intakes (furnaces, etc.) or  
any openings in the building or structure, including windows and  
doors of an attached garage.  
If the AUTO/OFF/MANUAL switch is not set to  
its OFF position, the generator can crank and  
start as soon as the battery cables are con-  
nected. If the battery charger power supply  
is not turned off, sparking can occur at the  
battery posts and cause an explosion.  
1.9.2  
NEW INSTALLATION GUIDELINES FOR  
STATIONARY AIR-COOLED GENERATORS  
The National Fire Protection Association has a standard for the  
installation and use of stationary combustion engines. That  
standard is NFPA 37 and its requirements limit the spacing of an  
enclosed generator set from a structure or wall (Figure 1.4).  
NFPA 37, Section 4.1.4, Engines Located Outdoors. Engines, and  
their weatherproof housings if provided, that are installed outdoors  
shall be located at least 5 ft. from openings in walls and at least 5  
ft. from structures having combustible walls. A minimum separa-  
tion shall not be required where the following conditions exist:  
1. The adjacent wall of the structure has a fire resistance rating  
of at least 1 hour.  
2. The weatherproof enclosure is constructed of noncombus-  
tible materials and it has been demonstrated that a fire within  
the enclosure will not ignite combustible materials outside the  
enclosure.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
Figure 1.4 – Installation Guidelines  
No windows or openings in the wall permitted  
within 5 feet from any point of the generator.  
18 inches  
Existing Wall  
60 inches  
60 inches  
36 inches  
Minimum Distance  
Clearance from windows,  
doors, any openings in the  
wall, shrubs or vegetation  
over 12” in height  
36 inches  
Top of Generator  
Clearance from the ends and front of the  
generator should be 36 inches. This  
would include shrubs, trees and any  
kind of vegetation. Clearance at the top  
should be a minimum of 48 inches from  
any structure, overhang or projections  
from the wall. The generator should not  
be placed under a deck or other  
These guidelines are based upon fire  
testing of the generator enclosure and  
the manufacturer’s requirement for air  
flow for proper operation. Local codes  
may be different and more restrictive  
than what is described here.  
36 inches  
structure that is closed in and would limit  
or contain air flow.  
60” Minimum  
60” Recommended  
Minimum From Ends  
Generator  
18 inches  
Minimum  
This drawing supersedes installation instructions in all air-cooled installation and owner's manuals dated previous to May 26, 2007.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
1.10 BATTERY REQUIREMENTS  
1.12 THE BATTERY  
See the Specifications section for correct battery size and rating.  
Do not dispose of the battery in a fire. The  
battery is capable of exploding.  
1.11 BATTERY INSTALLATION  
Fill the battery with the proper electrolyte fluid if necessary and  
have the battery fully charged before installing it.  
A battery presents a risk of electrical shock  
and high short circuit current. The following  
precautions are to be observed when work-  
ing on batteries:  
Before installing and connecting the battery, complete the follow-  
ing steps:  
• Remove the 7.5A fuse from the generator con-  
trol panel.  
1. Set the generator's AUTO/OFF/MANUAL switch to OFF.  
2. Turn off utility power supply to the transfer switch.  
3. Remove the 7.5A fuse from the generator control panel.  
Battery cables were factory connected at the generator (Figure  
1.5). Connect cables to battery posts as follows:  
• Remove watches, rings or other metal objects.  
• Use tools with insulated handles.  
• Wear rubber gloves and boots.  
• Do not lay tools or metal parts on top of the  
battery.  
4. Connect the red battery cable (from starter contactor) to the  
battery post indicated by a positive, POS or (+).  
• Disconnect charging source prior to connecting  
or disconnecting battery terminals.  
5. Connect the black battery cable (from frame ground) to the  
battery post indicated by a negative, NEG or (—).  
6. Install battery post covers supplied with the generator.  
Do not open or mutilate the battery.  
Figure 1.5 – Battery Cable Connections  
Released electrolyte has been known to  
n
be harmful to the skin and eyes, and to be  
toxic.  
The electrolyte is a dilute sulfuric acid that  
is harmful to the skin and eyes. It is electri-  
n
cally conductive and corrosive.  
The following procedures are to be observed:  
• Wear full eye protection and protective clothing.  
• Where electrolyte contacts the skin, wash it off  
immediately with water.  
• Where electrolyte contacts the eyes, flush thor-  
oughly and immediately with water and seek  
medical attention.  
• Spilled electrolyte is to be washed down with  
an acid neutralizing agent. A common practice  
is to use a solution of 1 pound (500 grams)  
bicarbonate of soda to 1 gallon (4 liters) of  
water. The bicarbonate of soda solution is to  
be added until the evidence of reaction (foam-  
ing) has ceased. The resulting liquid is to be  
flushed with water and the area dried.  
NOTE:  
Dielectric grease should be used on battery posts to aid in the  
prevention of corrosion.  
Lead-acid batteries present a risk of fire  
because they generate hydrogen gas. The fol-  
NOTE:  
lowing procedures are to be followed:  
Damage will result if battery connections are made in reverse.  
• DO NOT SMOKE when near the battery.  
• DO NOT cause flame or spark in battery area.  
• Discharge static electricity from body before  
touching the battery by first touching a ground-  
ed metal surface.  
NOTE:  
In areas where temperatures regularly fall below 32° F (0° C) it  
is recommended that a pad type battery heater be installed to  
aid in cold climate starting.  
Be sure the AUTO/OFF/MANUAL switch is  
set to the OFF position before connecting  
n
the battery cables. If the switch is set to  
AUTO or MANUAL, the generator can crank  
and start as soon as the battery cables are  
connected.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Post Installation Start-up and Adjustments  
Be sure the utility power supply is turned off  
and the 7.5A fuse is removed from the gen-  
2.2 BEFORE INITIAL START-UP  
NOTE:  
erator control panel, or sparking may occur at  
These units have been run and tested at the factory prior to  
being shipped and do not require any type of break-in.  
the battery posts as the cables are attached  
and cause an explosion.  
Servicing of the battery is to be performed or supervised by per-  
sonnel knowledgeable of batteries and the required precautions.  
Keep unauthorized personnel away from batteries.  
NOTE:  
This unit comes filled with oil from the factory. Check the oil  
level and add the appropriate amount if necessary.  
See the Specifications section for the correct size and rating when  
replacing the battery. Have these procedures performed at the  
intervals specified in the “Service Schedule.” A negative ground  
system is used. Battery connections are shown on the wiring dia-  
grams. Make sure the battery is correctly connected and terminals  
are tight. Observe battery polarity when connecting the battery to  
the generator set.  
Before starting, complete the following:  
1. Set the generator’s main circuit breaker to its OFF (or OPEN)  
position.  
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF  
position.  
3. Turn OFF all breakers on the load center of the transfer box (T1  
and T2).  
1.13 BATTERY CHARGER  
4. Turn OFF all loads connected to the transfer switch terminals  
T1 and T2.  
NOTE:  
5. Check the engine crankcase and reservior oil level and, if nec-  
essary, fill to the dipstick FULL mark with the recommended  
oil. Do not fill above the FULL mark.  
6. Check the fuel supply. Gaseous fuel lines must have been  
properly purged and leak tested in accordance with applicable  
fuel-gas codes. All fuel shutoff valves in the fuel supply lines  
must be open.  
During initial start up only, the generator may exceed the normal  
number of start attempts and experience an “over crank” fault (See  
the "Overcrank" section). This is due to accumulated air in the fuel  
system during installation. Reset the control board and restart up  
to two more times, if necessary. If unit fails to start, contact the  
local dealer for assistance.  
The battery charger is integrated into the control module  
in all models and requires input to the generator between  
90-265VAC.  
It operates as a "Smart Charger" which ensures output is continu-  
ally optimized to promote maximum battery life and charging levels  
are at safe conditions. The user can monitor both battery voltage  
and current charge in both "Boost" and "Float" modes on the LCD  
display on the controller.  
NOTE:  
There is a warning on the LCD display when the battery needs  
service.  
2.1 ACTIVATE THE GENERATOR  
When battery power is applied to the generator during the installa-  
tion process, the controller will light up. However, the generator still  
needs to be activated before it will automatically run in the event  
of a power outage.  
Never operate the engine with the oil level  
below the Add” mark on the dipstick. Doing  
n
this could damage the engine.  
Activating the generator is a simple one time process that is guided  
by the controller screen prompts. Once the product is activated, the  
controller screen will not prompt you again, even if you disconnect  
the generator battery.  
2.3 ELECTRICAL CHECKS  
Complete electrical checks as follows:  
1. Set the generator's main circuit breaker to its OFF (or OPEN)  
After obtaining your activation code, please complete the following  
steps at the generator’s control panel in the Activation Chart.  
position.  
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF  
position.  
3. Turn on the battery charger power supply to the generator  
using the means provided (such as a utility main line circuit  
breaker).  
The generator is now electrically “hot.”  
Contact with “hot” parts will result in  
extremely hazardous and possibly fatal elec-  
trical shock. Proceed with caution.  
4. Check battery charger power source voltage across terminals  
T1 and the transfer switch neutral lug; then across terminal  
neutral. Nominal line-to-neutral voltage should be 120 volts  
AC.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Post Installation Start-up and Adjustments  
ACTIVATION CHART  
CHOOSE LANGUAGE  
TROUBLESHOOTING  
Display Reads:  
Use ARROW keys to scroll to desired lan-  
guage. Press ENTER to select.  
If the wrong language is chosen, it can be  
changed later using the “edit” menu.  
Language  
-
English  
+
Escape  
Enter  
Display Reads:  
Press ENTER to begin the activation pro-  
cess.  
If ESCAPE is pressed instead of ENTER,  
your generator will only run in manual mode  
(for test purposes) and NOT ACTIVATED will  
be displayed. You will need to reconnect the  
battery and begin with Step 1.  
Activate me (ENT) or  
ESC to run in manual  
Escape  
Enter  
Display Reads:  
If you do not have your activation code,  
1-888-9ACTIVATE (922-8482).  
To Activate go to  
If you already have your activation code,  
wait 3-5 seconds for the next display.  
Escape  
Enter  
ENTER ACTIVATION CODE (Passcode)  
TROUBLESHOOTING  
Display Reads:  
Use ARROW keys to scroll and find the first  
number of your Activation Code.  
Serial 123456789  
Passcode XXXXX +/-  
Press ENTER to select.  
Repeat this step until all digits have been  
entered.  
Escape  
Enter  
Use ESCAPE to correct previous digits.  
Display Reads:  
Activation is complete when all digits are  
entered above and your screen shows this  
display.  
What happens if “Wrong Passcode Try  
Again” appears?  
“SELECT HOUR (0-23)”  
“-  
Reenter the activation code. If a second  
attempt is unsuccessful, check the number  
against the code given on activategen.com.  
If it is correct and the generator will not  
accept it, contact 1-888-9ACTIVATE (922-  
8482).  
6
+”  
Follow the controller prompts to continue  
setting the time function. Refer to your  
Owner’s Manual with questions.  
Escape  
Enter  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
5. When certain that input voltage is compatible with battery  
charger ratings, turn OFF the power supply to the generator.  
6. On the generator panel, set the Auto/Off/ Manual switch to  
MANUAL. The engine should crank and start.  
7. Let the engine warm up for about five minutes to allow inter-  
nal temperatures to stabilize. Then, set the generator’s main  
circuit breaker to its ON (or closed) position.  
2.5 CHECKING AUTOMATIC  
OPERATION  
To check the system for proper automatic operation, proceed as  
follows:  
1. Set generator’s main circuit breaker to its OFF (or OPEN) posi-  
tion.  
2. Check that the AUTO/OFF/MANUAL switch is set to OFF.  
5. Turn ON the power supply to the battery charger, using the  
means provided (such as a line circuit breaker).  
6. Set the generator's main circuit breaker to its ON (or CLOSED)  
position.  
Proceed with caution! Generator power volt-  
age is now supplied to the inverter. Contact  
with live inverter parts will result in danger-  
ous and possibly fatal electrical shock.  
7. Set the AUTO/OFF/MANUAL switch to AUTO. The system is  
8. Connect the AC voltmeter test leads across terminal lugs E1  
and neutral. Voltage reading should be 125-120 volts AC.  
9. Set the generator’s main circuit breaker to its OFF (or OPEN)  
position. Let the engine run at no-load for a few minutes to  
stabilize internal engine generator temperatures.  
10. Set the generator's AUTO/OFF/MANUAL switch to OFF. The  
engine should shut down.  
now ready for automatic operation.  
8. Close or connect Remote 2-wire Start with a test switch  
installed at the inverter.  
With the AUTO/OFF/MANUAL switch at AUTO, the engine should  
crank and start when the remote start contact switch is closed.  
Let the system go through its entire automatic sequence of opera-  
tion.  
NOTE:  
With the generator running and loads powered by generator AC  
output, and the remote start contacts OPEN. The following should  
occur:  
It is important not to proceed until certain that generator AC  
voltage and frequency are correct and within the stated limits.  
• About one minute after remote start contacts OPEN (OFF) the  
engine should shut down.  
2.4 GENERATOR TESTS UNDER  
LOAD  
3.1 CONTROL PANEL INTERFACE  
To test the generator set with electrical loads applied, proceed as  
follows:  
3.1.1  
USING THE AUTO/OFF/MANUAL SWITCH  
(FIGURE 3.1)  
1. Set generator’s main circuit breaker to its OFF (or OPEN) posi-  
tion.  
2. Turn OFF all breakers on the load center of the inverter (if  
equipped).  
With the switch set to AUTO, the engine may  
crank and start at any time without warning.  
Such automatic starting occurs when utility  
power source voltage droops below a preset  
level or during the normal exercise cycle. To  
prevent possible injury that might be caused  
by such sudden starts, always set the switch  
to OFF and remove the fuses before work-  
ing on or around the generator or transfer  
switch. Then, place a “DO NOT OPERATE”  
tag on the generator panel and on the trans-  
fer switch.  
3. Set the generator's AUTO/OFF/MANUAL switch to MANUAL.  
The engine should crank and start immediately.  
4. Let the engine stabilize and warm up for a few minutes.  
5. Set the generator’s main circuit breaker to its ON (or CLOSED)  
position. The inverter is now powered by the standby genera-  
tor.  
6. Turn ON the load center of the inverter system.  
7. Connect an accurate AC voltmeter and a frequency meter  
across terminal lugs at the inverter.  
n
• Voltage should be greater than 120 volts and frequency  
should be 60 Hz.  
8. Let the generator run at full rated load for 20-30 minutes.  
Listen for unusual noises, vibration or other indications of  
abnormal operation. Check for oil leaks, evidence of overheat-  
ing, etc.  
1. AUTO” Position – Selecting this switch activates fully auto-  
matic system operation.  
2. “OFF” Position – This switch position shuts down the engine.  
This position also prevents automatic operation.  
3. “MANUAL Position – Set the switch to MANUAL to crank  
and start the engine. Transfer to standby power will not occur  
unless there is a utility failure.  
9. When testing under load is complete, turn OFF electrical  
loads.  
10. Set the generator's main circuit breaker to its OFF (or OPEN)  
position.  
11. Let the engine run at no-load for a few minutes.  
12. Set the AUTO/OFF/MANUAL switch to OFF. The engine should  
shut down.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Figure 3.1 – Generator Control Panel  
3.2 AUTOMATIC OPERATION  
To select automatic operation, do the following:  
1. Make sure the remote 2-wire contacts are set to their OPEN  
position.  
2. Be sure that normal battery charger power source voltage  
is available to terminal lugs T1 and Neutral (Refer to the  
Electrical Data section).  
MAIN FUSE  
7.5 AMP  
AUTO OFF MANUAL  
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO.  
4. Set the generator’s main circuit breaker to its ON (or CLOSED)  
position.  
With the preceding steps complete, the generator will start auto-  
matically when remote 2-wire start contacts are CLOSED (ON).  
After the unit starts, loads are transferred to the generator and  
charges the battery pack by the inverter system. Refer to the  
Sequence of Automatic Operation section.  
Escape  
Enter  
3.3 SEQUENCE OF AUTOMATIC  
OPERATION  
3.3.1  
REMOTE START ON  
Upon first power up of the generator, the display interface will  
begin an installation assistant. The assistant will prompt the user  
to set the minimum settings to operate. These settings are Current  
Date/Time. The maintenance intervals will be initialized when the  
exercise time is entered (Figure 3.1).  
• Initial Conditions: Generator in Auto, ready to run. When remote  
start contacts are CLOSED (ON), the engine will crank and  
start.  
• After remote start contacts OPEN (OFF), the engine will shut  
down after one (1) minute cool-down time.  
If the 12 volt battery is disconnected or the fuse removed, the  
Installation Assistant will operate upon power restoration. The  
only difference is the display will only prompt the customer for the  
current Time and Date.  
3.3.2  
CRANKING  
The system will control the cyclic cranking as follows: 16 second  
crank, seven (7) second rest, 16 second crank, seven (7) second  
rest followed by three (3) additional cycles of seven (7) second  
cranks followed by seven (7) second rests.  
NOTE:  
The current date/time will need to be reset every time the 12  
volt battery is disconnected and then reconnected, and/or when  
the fuse is removed.  
Choke Operation  
1. The 530cc engines have an electric choke on the stepper  
motor bracket that is automatically controlled by the electronic  
control board.  
Display Interface Menus  
The LCD display is organized as detailed below:  
Failure to Start  
This is defined as any of the following occurrences during crank-  
ing:  
• The “Home” page, this page is the default page which will be  
displayed if no keys are pressed for 30 seconds. This page  
normally shows the current Status message and the current  
date and time. The highest priority active Alarm and/or Warning  
will be automatically posted on this page as well as flashing  
the backlight when such an event is detected. In the case of  
multiple Alarms or Warnings, only the first message will be  
displayed. To clear an Alarm or Warning, see the Protection  
Systems section - Clear Alarm.  
1. Not reaching starter dropout within the specified crank cycle.  
Starter dropout is defined as four (4) cycles at 1,000 RPM.  
2. Reaching starter dropout, but then not reaching 2200 RPM  
within 15 seconds. In this case the control board will go into  
a rest cycle for seven (7) seconds, then continue the rest of  
the crank cycle.  
• The display backlight is normally off. If the user presses any key,  
the backlight will come on automatically and remain on for 30  
seconds after the last key was pressed.  
During a rest cycle the start and fuel outputs are de-energized and  
the magneto output is shorted to ground.  
• The “Main Menu” page will allow the user to navigate to all other  
pages or sub-menus by using the Left/Right and Enter keys.  
This page can be accessed at any time with several presses of  
the dedicated Escape key. Each press of the Escape key takes  
you back to the previous menu until the main menu is reached.  
This page displays the following options: HISTORY; STATUS;  
EDIT; AND DEBUG. (See the Appendix - "Menu System".)  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Figure 3.2 – Side Compartment  
Cranking Conditions  
The following notes apply during cranking cycle.  
1. Starter motor will not engage within five (5) seconds of the  
engine shutting down.  
2. The fuel output will not be energized with the starter.  
3. The starter and magneto outputs will be energized together.  
4. Once the starter is energized the control board will begin look-  
ing for engine rotation. If it does not see an RPM signal within  
three (3) seconds it will shut down and latch out on RPM  
sensor loss.  
5. Once the control board sees an RPM signal it will energize the  
fuel solenoid, drive the throttle open and continue the crank  
sequence.  
6. Starter motor will disengage when speed reaches starter  
dropout.  
7. If the generator does not reach 2200 RPM within 15 seconds,  
re-crank cycle will occur.  
8. If engine stops turning between starter dropout and 2200  
RPM, the board will go into a rest cycle for seven (7) seconds  
then re-crank (if additional crank cycles exist).  
Figure 3.3 – Open Side Compartment  
9. Once started, the generator will wait for a hold-off period  
before starting to monitor oil pressure and oil temperature  
(refer to the Alarm Messages section for hold-off times).  
10. During Manual start cranking, if the Mode switch is moved  
from the Manual position, the cranking stops immediately.  
11. During Auto mode cranking, if the remote start contacts OPEN  
(OFF), the cranking cycle does NOT abort but continues until  
complete. Once the engine starts, it will run for one (1) min-  
ute, then shut down.  
3.3.4  
REMOTE START OFF  
Initial Condition: Generator supplying power to customer load.  
Once the contacts open, the controller will run the engine through  
a one (1) minute cool down period and then shut down.  
3.5 PROTECTION SYSTEMS  
3.4 SIDE COMPARTMENT  
3.5.1  
ALARMS  
(FIGURES 3.2 & 3.3)  
Local codes may require this compartment to be locked. A hasp is  
provided so the owner can secure the compartment with their own  
padlock. Check local codes in the area.  
Highest Priority (Latching) Displayed on the control panel. They  
must be cleared before the alarm message goes away. The alarm  
log records each occurrence (see Appendix - "Menu System").  
Low Oil Pressure (Shutdown Alarm)  
3.4.1  
MAIN CIRCUIT BREAKER  
A five (5) second delay on start-up and seven (7) second delay  
once the engine is running.  
This is a 1-pole breaker rated according to the Specifications sec-  
tion.  
This switch (Figure 3.4) has normally closed contacts that are  
held open by engine oil pressure during operation. Should the oil  
pressure drop below the five (5) PSI range, switch contacts close  
and the engine shuts down. The unit should not be restarted until  
oil level is verified.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
High Engine Temperature (Shutdown Alarm – Auto Reset)  
Internal Fault (Shutdown Alarm)  
A 10 second delay on start-up and one (1) second delay before  
shutdown. Auto reset when the condition clears and restart the  
engine if a valid start signal is still present.  
This alarm cannot be cleared, call service dealer.  
Undervoltage (Shutdown Alarm)  
If the generator voltage falls below 85% of nominal for more than  
This switch’s contacts (Figure 3.4) close if the temperature should  
exceed approximately 140° C (284° F), initiating an engine shut-  
down. Once the oil temperature drops to a safe level the switch’s  
contacts open again.  
15 seconds, it shuts down.  
Overvoltage (Shutdown Alarm)  
If the generator voltage rises above 110% of rating for greater than  
three (3) seconds, an alarm will be issued and the unit will shut  
down.  
Over Crank (Shutdown Alarm)  
This occurs if the engine has not started within the specified crank  
cycle. (See "Cranking" section.)  
If the generator voltage rises above 130% of rating for greater than  
0.5 seconds, an alarm will be issued and the unit will shut down.  
Figure 3. 4 – Low Oil Pressure and  
High Temperature Switches  
Clear Alarm  
Clear the alarm by setting the AUTO/OFF/MANUAL switch to the  
OFF position. Press the ENTER key to unlatch any active fault and  
clear the corresponding alarm message.  
High Temp Switch  
3.5.2  
WARNINGS  
Second Priority (Non-latching) Displayed on the control panel  
and the external yellow LED (V-twins only). Warnings automati-  
cally clear when the monitored condition goes away. Warnings are  
recorded in the alarm log. Warnings cannot cause shutdowns.  
Low Battery  
Low Oil Switch  
The Control Board monitors battery voltage and displays a warn-  
ing if the battery voltage falls below 11.9 volts for one (1) minute.  
Warning is automatically cleared if the battery voltage rises above  
12.4 volts. Battery voltage is not monitored during the crank  
cycle.  
Oil Filter  
Over Speed (Shutdown Alarm)  
3000 RPM for three (3) seconds or 3300 RPM immediately. This  
feature protects the generator from damage by shutting it down  
if it happens to run faster than the preset limit. This protection  
also prevents the generator from supplying an output that could  
potentially damage appliances connected to the generator circuit.  
Contact the nearest Dealer if this failure occurs.  
3.5.3  
Third priority  
MAINTENANCE ALERTS  
Maintenance Message  
When a maintenance period expires, a warning message will  
be displayed. The alert can be reset by pressing the Enter key,  
which will cause the user to be prompted to confirm the action.  
Resetting will clear the alert and reset the maintenance counters  
for all conditions annunciated. The history log will record the alert.  
The maintenance counter will not accumulate without battery  
power. Once battery power is restored, the set time prompt will be  
displayed. The maintenance counters will be adjusted to the new  
time and date.  
RPM Sense Loss (Shutdown Alarm)  
During cranking, if the Control Board does not see a valid RPM  
signal within three (3) seconds, it will shut down and lock out on  
RPM sense loss. While engine is running, if RPM signal is lost for  
one (1) second the Control Board will shut the engine down, wait  
15 seconds, then re-crank the engine. If no RPM signal is detected  
within the first three (3) seconds of cranking, the Control Board  
will shut the engine down and latch out on RPM sensor loss. If the  
RPM signal is detected, the engine will start and run normally. If  
the RPM signal is subsequently lost again, the Control Board will  
try one more re-crank attempt before latching out and displaying  
the RPM sensor failure message.  
NOTE:  
Since most maintenance alerts will occur at the same time  
(most have 500 hour or two (2) year intervals), only one will  
appear on the display at any one time. Once the first alert is  
cleared, the next active alert will be displayed.  
Under-frequency (Shutdown Alarm)  
After starting, if the generator stays under frequency for more than  
30 seconds it will shut down. The under-frequency setting is 55  
Hz.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Figure 4.1 — Oil Dipstick and Fill  
4.1 FUSE  
The 7.5 amp fuse on the control panel protects the DC control  
circuit against overload (Figures 3.1 and 3.2). This fuse is wired  
in series with the battery output lead to the panel. If this fuse ele-  
ment has melted open, the engine will not be able to crank or start.  
Replace this fuse using only an identical 7.5 amp replacement  
fuse. Whenever the fuse is removed or replaced, the exercise timer  
needs to be reset.  
Oil Fill  
4.2 CHECKING THE ENGINE OIL  
LEVEL  
For oil capacities, see the Specifications section. For engine oil  
recommendations, see the Engine Oil Recommendations section.  
When low battery levels necessitate running the generator for  
extended periods of time, the oil level should be checked weekly.  
Oil Dipstick  
To check the engine oil level, proceed as follows (Figures 4.1, 4.2  
and 4.3):  
1. If the generator is running, first turn OFF all associated loads  
running in the residence. Second, turn the generator's main  
circuit breaker to the OFF position.  
2. Move the AUTO/OFF/MANUAL switch to the OFF position.  
3. Remove the dipstick and wipe it dry with a clean cloth.  
4. Completely insert the dipstick; then, remove it again. The oil  
level should be at the dipstick “Full” mark. If necessary, add  
oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL”  
MARK.  
Oil Drain Hose  
5. Install the dipstick.  
6. Reset the AUTO/OFF/MANUAL switch to its original position.  
7. If the generator was running, first turn the generator's main  
circuit breaker back to the ON position. Second, turn ON  
needed loads in the residence.  
4.3 CHANGING THE ENGINE OIL  
* Repeat steps 3 through 5 for the oil reservoir.  
Hot oil may cause burns. Allow engine to  
cool before draining oil. Avoid prolonged  
n
or repeated skin exposure with used oil.  
Thoroughly wash exposed areas with soap.  
Never operate the engine with the oil level  
below the Add” mark on the dipstick. Doing  
n
4.3.1  
OIL CHANGE INTERVALS  
this could damage the engine.  
See the "Service Schedule" section.  
NOTE:  
When checking the oil level in the reservoir, it is normal that the  
oil is steadily consumed, especially for the first 500 hours. At  
the first service interval, the oil level in the reservoir will likely  
be near the bottom of the dipstick. It is important that the engine  
oil level remains within the limits of the dipstick.  
4.3.2  
ENGINE OIL RECOMMENDATIONS  
All oil should meet minimum American Petroleum Institute (API)  
Service Class SJ, SL or better. Use no special additives. Synthetic  
5W-30 is used under all conditions.  
Any attempt to crank or start the engine  
before it has been properly serviced with the  
recommended oil may result in an engine  
failure.  
n
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Figure 4.2 — Engine Air Cleaner  
4.3.3  
OIL & OIL FILTER CHANGE PROCEDURE  
To change the oil, proceed as follows:  
1. Start the engine by moving the AUTO/OFF/MANUAL switch to  
MANUAL and run until it is thoroughly warmed up. Then shut  
OFF the engine by moving the switch to the OFF position.  
2. Immediately after the engine shuts OFF, pull the oil drain hose  
(Figure 4.1) free of its retaining clip. Remove the cap from the  
hose and drain the oil into a suitable container.  
3. After the oil has drained, replace the cap onto the end of the  
oil drain hose. Retain the hose in the clip.  
Change the engine oil filter as follows:  
1. With the oil drained, remove the old oil filter by turning it  
counterclockwise.  
2. Apply a light coating of clean engine oil to the gasket of the  
new filter. See the Specifications section for recommended  
filter.  
3. Screw the new filter on by hand until its gasket lightly contacts  
the oil filter adapter. Then, tighten the filter an additional 3/4 to  
one turn (Figure 3.4).  
4. Refill with the proper recommended oil (see the Engine Oil  
Recommendations section). See the Specifications section  
for oil capacities.  
5. Start the engine, run for one (1) minute, and check for leaks.  
6. Shutdown and recheck oil level, add as needed. DO NOT  
OVER FILL.  
7. Reset the AUTO/OFF/MANUAL switch to the AUTO position.  
8. Dispose of used oil at a proper collection center.  
* Repeat steps 2 and 3 for the oil reservoir.  
4.5 SPARK PLUGS  
Reset the spark plugs gap or replace the spark plugs as necessary.  
See the Service Schedule section for maintenance requirements.  
1. Clean the area around the base of the spark plugs to keep dirt  
and debris out of the engine.  
2. Remove the spark plugs and check the condition. Replace  
the spark plugs if worn or if reuse is questionable. See the  
Service Schedule section for recommended inspection. Clean  
by scraping or washing using a wire brush and commercial  
solvent. Do not blast the spark plugs to clean.  
3. Check the spark plug gap using a wire feeler gauge. Adjust the  
gap to 0.76 mm (0.030 inch) by carefully bending the ground  
electrode (Figure 4.3).  
4.4 CHANGING THE ENGINE AIR  
CLEANER  
Figure 4.3 – Setting the Spark Plug Gap  
See "The Generator" section for the location of the air cleaner. Use  
the following procedures (Figure 4.2):  
1. Lift the roof and remove the door.  
2. Turn the two screws 1/4 turn counterclockwise to loosen.  
3. Remove the cover and air filter.  
4. Wipe away dust or debris from inside of the air box and  
around edges.  
5. Install the new air cleaner into the air box.  
6. Install the cover. Turn the two cover screws 1/4 turn clock-  
wise to tighten.  
See the Service Schedule section for air cleaner maintenance. See  
the Specifications section for air filter replacement part number.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
• DO NOT SMOKE when near the battery.  
4.6 BATTERY MAINTENANCE  
• DO NOT cause flame or spark in battery area.  
The battery should be inspected per the "Service Schedule" sec-  
tion. The following procedure should be followed for inspection:  
• Discharge static electricity from body before  
touching the battery by first touching a ground-  
ed metal surface.  
1. Inspect the battery posts and cables for tightness and corro-  
sion. Tighten and clean as necessary.  
Be sure the AUTO/OFF/MANUAL switch is  
2. Check the battery fluid level of unsealed batteries and, if nec-  
essary, fill with Distilled Water Only. Do not use tap water in  
batteries.  
set to the OFF position before connecting  
n
the battery cables. If the switch is set to  
AUTO or MANUAL, the generator can crank  
and start as soon as the battery cables are  
connected.  
3. Have the state of charge and condition checked. This should  
be done with an automotive-type battery hydrometer.  
Be sure the utility power supply is turned off  
and the 7.5A fuse is removed from the gener-  
ator control panel, or sparking may occur at  
the battery posts as the cables are attached  
and cause an explosion.  
Do not dispose of the battery in a fire. The  
battery is capable of exploding.  
ꢁ  
A battery presents a risk of electrical shock  
and high short circuit current. The following  
precautions are to be observed when work-  
ing on batteries:  
4.7 ADJUSTING GT-530 VALVE  
CLEARANCE  
After the first six (6) months of operation or 500 hours of  
operation, check the valve clearance in the engine, adjust if  
necessary.  
• Remove the 7.5A fuse from the generator con-  
trol panel.  
• Remove watches, rings or other metal objects.  
• Use tools with insulated handles.  
• Wear rubber gloves and boots.  
• Do not lay tools or metal parts on top of the  
battery.  
Important: If feeling uncomfortable about doing this procedure  
or the proper tools are not available, please contact the Dealer for  
service assistance. This is a very important step to ensure longest  
life for the engine.  
• Disconnect charging source prior to connecting  
or disconnecting battery terminals.  
To check valve clearance:  
Do not open or mutilate the battery.  
• The engine should be cool before checking. If valve clearance is  
0.002" - 0.004" (0.05 - 0.1mm), adjustment is not needed.  
• Remove spark plug wires and position wires away from plugs.  
• Remove spark plugs.  
Released electrolyte has been known to  
n
be harmful to the skin and eyes, and to be  
toxic.  
The electrolyte is a dilute sulfuric acid that  
• Make sure the piston is at Top Dead Center (TDC) of its com-  
pression stroke (both valves closed). To get the piston at TDC,  
remove the intake screen at the front of the engine to gain  
access to the flywheel nut. Use a large socket and socket  
wrench to rotate the nut and hence the engine in a clockwise  
direction. While watching the piston through the spark plug  
hole. The piston should move up and down. The piston is at  
TDC when it is at its highest point of travel.  
is harmful to the skin and eyes. It is electri-  
n
cally conductive and corrosive. The follow-  
ing procedures are to be observed:  
• Wear full eye protection and protective clothing.  
• Where electrolyte contacts the skin, wash it off  
immediately with water.  
• Where electrolyte contacts the eyes, flush thor-  
oughly and immediately with water and seek  
medical attention.  
To adjust valve clearance (if necessary), (Figure 4.4):  
• Make sure the engine is at 60° to 80° F.  
• Spilled electrolyte is to be washed down with  
an acid neutralizing agent. A common practice  
is to use a solution of 1 pound (500 grams)  
bicarbonate of soda to 1 gallon (4 liters) of  
water. The bicarbonate of soda solution is to  
be added until the evidence of reaction (foam-  
ing) has ceased. The resulting liquid is to be  
flushed with water and the area dried.  
• Make sure that the spark plug wire is removed from the spark  
plug and out of the way.  
• Remove the four screws attaching the valve cover.  
• Loosen the rocker jam nut. Use a 10mm allen wrench to turn  
the pivot ball stud while checking clearance between the rocker  
arm and the valve stem with a feeler gauge. Correct clearance  
is 0.002-0.004 inch (0.05-0.1 mm).  
NOTE:  
Lead-acid batteries present a risk of fire  
because they generate hydrogen gas. The  
following procedures are to be followed:  
Hold the rocker arm jam nut in place as the pivot ball stud is  
turned.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
When valve clearance is correct, hold the pivot ball stud in place  
with the allen wrench and tighten the rocker arm jam nut. Tighten  
the jam nut to 174 in/lbs. torque. After tightening the jam nut,  
recheck valve clearance to make sure it did not change.  
Figure 4.5 – Cooling Vent Locations  
• Install new valve cover gasket.  
• Re-attach the valve cover.  
AIR INTAKE  
AIR OUTLET  
NOTE:  
Start all four screws before tightening or it will not be possible  
to get all the screws in place. Make sure the valve cover gasket  
is in place.  
4.9 ATTENTION AFTER  
SUBMERSION  
• Install spark plugs.  
• Re-attach the spark plug wire to the spark plug.  
• Repeat the process for the other cylinder.  
If the generator has been submerged in water, it MUST NOT be  
started and operated. Following any submersion in water, have  
a Dealer thoroughly clean, dry and inspect the generator. If the  
structure (ex. home) has been flooded, it should be inspected by  
a certified electrician to ensure there won't be any electrical prob-  
lems during generator operation or when utility is returned.  
Figure 4.4 - Valve Clearance Adjustment  
Rocker  
Arm  
Pivot Ball  
Stud  
Jam Nut  
4.10 CORROSION PROTECTION  
Periodically wash and wax the enclosure using automotive type  
products. Frequent washing is recommended in salt water/coastal  
areas. Spray engine linkages with a light oil such as WD-40.  
Valve  
Stem  
4.11 OUT OF SERVICE PROCEDURE  
4.11.1 REMOVAL FROM SERVICE  
If the generator cannot be exercised every seven days, and will  
be out of service longer than 90 days, prepare the generator for  
storage as follows:  
1. Start the engine and let it warm up.  
2. Close the fuel shutoff valve in the fuel supply line and allow  
the unit to shut down.  
4.8 COOLING SYSTEM  
3. Once the unit has shut down, switch to the OFF position.  
4. Set the generator’s main circuit breaker to its OFF (or OPEN)  
position.  
5. Set the AUTO/OFF/MANUAL switch to OFF and turn off the util-  
ity power to the transfer switch. Remove the 7.5A fuse from  
the generator control panel. Disconnect the battery cables as  
outlined in “General Hazards”.  
6. While the engine is still warm from running, drain the oil  
completely. Refill the crankcase with oil. See ”Engine Oil  
Recommendations". Drain the oil reservoir and refill with rec-  
ommended oil to the proper level.  
Air inlet and outlet openings in the generator compartment must  
be open and unobstructed for continued proper operation. This  
includes such obstructions as high grass, weeds, brush, leaves  
and snow.  
Without sufficient cooling and ventilating air flow, the engine/  
generator quickly overheats, which causes it to quickly shut down  
(Figure 4.5).  
Make sure the doors and roof are in place during operation as  
running the generator with them removed can effect cooling air  
movement.  
7. Attach a tag to the engine indicating the viscosity and clas-  
sification of the oil in the crankcase.  
8. Remove the spark plugs and spray fogging agent into the  
spark plugs threaded openings. Reinstall and tighten the spark  
plugs.  
9. Remove the battery and store it in a cool, dry room on a  
wooden board. Never store the battery on any concrete or  
earthen floor.  
The exhaust from this product gets extremely  
hot and remains hot after shutdown. High  
grass, weeds, brush, leaves, etc. must  
remain clear of the exhaust. Such materi-  
als may ignite and burn from the heat of the  
exhaust system.  
10. Clean and wipe the entire generator.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
4.11.2 RETURN TO SERVICE  
4.11.3 ACCESSORIES  
To return the unit to service after storage, proceed as follows:  
There are performance enhancing accessories available for the  
air-cooled generators.  
1. Verify that utility power is turned off and that the AUTO/OFF/  
MANUAL switch is set to OFF.  
2. Check the tag on the engine for oil viscosity and classification.  
Verify that the correct recommended oil is used in the engine  
(see the Engine Oil Recommendations section). If necessary,  
drain and refill with the proper oil.  
• Cold Weather Kits are recommended in areas where tempera-  
tures regularly fall below 32° F (0° C).  
• Scheduled Maintenance Kits include all pieces necessary to  
perform maintenance on the generator along with oil recom-  
mendations.  
3. Check the state of the battery. Fill all cells of unsealed bat-  
teries to the proper level with distilled water. DO NOT USE  
TAP WATER IN THE BATTERY. Recharge the battery to 100  
percent state of charge, or, if defective, replace the battery.  
See “Specifications,” for type and size.  
• The Remote Monitor System is a wireless, indoor mounted,  
box that indicates generator run status and allows for exercise  
programing as well as provide maintenance reminders.  
• Touch-up Paint Kits are very important to maintain the look and  
integrity of the generator enclosure. These kits include touch-up  
paint and instructions if the need should arise.  
4. Clean and wipe the entire generator.  
5. Make sure the 7.5A fuse is removed from the generator con-  
trol panel. Reconnect the battery. Observe battery polarity.  
Damage may occur if the battery is connected incorrectly.  
6. Open the fuel shutoff valve.  
For more details on accessories, please contact a Dealer.  
7. Insert the 7.5A fuse into the generator control panel. Start the  
unit by moving the AUTO/OFF/MANUAL switch to MANUAL.  
Allow the unit to warm up thoroughly.  
8. Stop the unit by setting the AUTO/OFF/MANUAL switch to  
OFF.  
9. Turn on the utility power to the transfer switch.  
10. Set the AUTO/OFF/MANUAL switch to AUTO.  
11. The generator is now ready for service.  
NOTE:  
If the battery was dead or disconnected, the exercise timer, cur-  
rent date and time must be reset.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
4.12 SERVICE SCHEDULE  
ATTENTION: It is recommended that all service work  
be performed by the nearest Dealer.  
SYSTEM/COMPONENT  
X = Action  
PROCEDURE  
FREQUENCY  
W = Weekly  
M = Monthly  
Y = Yearly  
R = Replace as Necessary  
Inspect  
Change  
Clean  
* = Notify Dealer if Repair is  
Needed.  
FUEL  
Fuel lines and connections*  
X
X
M
W
LUBRICATION  
Oil level  
Oil  
X
X
2Y or 500 hours  
of operation.**  
Oil filter  
2Y or 500 hours  
of operation.**  
COOLING  
Enclosure louvers  
X
X
W
BATTERY  
Remove corrosion, ensure  
dryness  
X
X
X
X
M
M
Clean and tighten battery  
terminals  
Check charge state  
Electrolyte level  
X
X
R
R
EVERY 6 M  
EVERY 6 M  
ENGINE AND MOUNTING  
Air cleaner  
X
X
R
R
2Y or 500 hours  
2Y or 500 hours  
Spark plug(s)  
GENERAL CONDITION  
Vibration, Noise, Leakage, Temperature*  
X
M
COMPLETE TUNE-UP*  
ALTERNATOR  
TO BE COMPLETED BY A DEALER  
X
2Y or 500 hours  
Rotor Brushes  
2,500 hours  
* Contact the nearest dealer for assistance if necessary.  
** Change oil and filter every 500 hours or 2 years, whichever occurs first.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
5.1 TROUBLESHOOTING GUIDE  
Problem  
Cause  
Correction  
The engine will not crank.  
1. Fuse blown.  
1. Correct short circuit condition, replace 7.5A  
fuse in generator  
control panel.  
2. Loose, corroded or defective  
battery cables.  
2. Tighten, clean or replace  
as necessary.  
3. Defective starter motor.  
4. Dead Battery.  
3.  
*
4. Charge or replace battery.  
The engine cranks but  
will not start.  
1. Out of fuel.  
1. Replenish fuel/Turn on fuel valve.  
2. Defective fuel solenoid (FS).  
3. Open #14 wire from  
engine control board.  
2.  
3.  
*
*
4. Fouled spark plug(s).  
5. Valve lash out of adjustment.  
6. Choke not operating.  
4. Clean, re-gap or replace plug(s).  
5. Reset valve lash.  
6. Verify choke plate moves freely.  
The engine starts hard  
and runs rough.  
1. Air cleaner plugged  
or damaged.  
1. Check, replace air cleaner.  
2. Fouled spark plug(s).  
3. Fuel pressure incorrect.  
2. Clean, re-gap or replace plug(s).  
3. Confirm fuel pressure to regulator  
is 10-12” water column (0.36-0.43 psi) for  
LP.  
4. Choke remains closed.  
4. Verify choke solenoid moves freely.  
The AUTO/OFF/MANUAL  
switch is set to OFF, but  
the engine continues  
to run.  
1. Defective switch.  
1.  
2.  
*
*
2. AUTO/OFF/MANUAL switch  
wired incorrectly.  
3. Defective control board.  
3.  
*
There is no AC output  
from the generator.  
1. Main line circuit breaker is in  
the OFF (or OPEN) position.  
2. Generator internal failure.  
1. Reset circuit breaker  
to ON (or CLOSED).  
2.  
*
Unit consumes large  
amounts of oil.**  
1. Engine over filled with oil.  
1. Adjust oil to proper level.  
2. See "Engine Oil Recommendations".  
3. Check for oil leaks.  
2. Improper type or viscosity of oil.  
3. Damaged gasket, seal or hose.  
4. Engine breather defective.  
4.  
*
* Contact the nearest Dealer for assistance.  
** Most of the oil may be consumed in the oil reservoir between 500 hour service intervals. This is especially true during the first  
500 hours of use.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
6.1 MENU SYSTEM NAVIGATION  
To get to the MENU, use the "Esc" key from any page. It may need  
to be pressed many times before getting to the menu page. The  
currently selected menu is displayed as a flashing word. Navigate  
to the menu required by using the +/- keys. When the menu  
required is flashing, press the ENTER key. Depending on the menu  
selected, there may be a list of choices presented. Use the same  
navigation method to select the the desired screen (refer to the  
Menu System diagram).  
6.1.1  
CHANGING SETTINGS (EDIT MENU)  
To change a setting such as display contrast, go to the EDIT menu  
and use the +/- keys to navigate to the setting to change. Once  
this setting is displayed (e.g. Contrast), press the ENTER key to go  
into the edit mode. Use the +/- keys to change the setting, press  
the ENTER key to store the new setting.  
NOTE:  
If the ENTER key is not pressed to save the new setting, it will  
only be saved temporarily. The next time the battery is discon-  
nected, the setting will revert back to the old setting.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Drawing No. 0J1320-A  
Installation Diagram  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Diagram  
Drawing No. 0J1320-A  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Drawing No. 0J1320-A  
Installation Diagram  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Diagram  
Drawing No. 0J1319-B  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Drawing No. 0J1323-C  
Oil Make-up System  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
FOR GENERATORS 10KW AND BELOW  
FEDERAL EMISSION CONTROL WARRANTY STATEMENT  
YOUR WARRANTY RIGHTS AND OBLIGATIONS  
The United States Environmental Protection Agency (EPA) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission Control  
System warranty on your new 2008 and later equipment. New equipment that use small spark-ignited engines must be designed, built, and equipped to  
meet stringent anti-smog standards for the federal government. Generac will warrant the emission control system on your generator for the period of time  
listed below provided there has been no abuse, neglect, unapproved modification or improper maintenance of your equipment.  
Your emission control system may include parts such as the: carburetor, ignition system, fuel system, catalytic converter, and other associated emission-  
related components (if equipped).  
MANUFACTURER’S WARRANTY COVERAGE:  
This emission control system is warranted for two years. If, during such warranty period, any emission-related part on your equipment is found to be  
defective in materials or workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Dealer.  
OWNER'S WARRANTY RESPONSIBILITIES:  
As the generator owner, you are responsible for the completion of all required maintenance as listed in your factory supplied Owner's Manual. For  
warranty purposes, Generac recommends that you retain all receipts covering maintenance on your generator, but Generac cannot deny warranty solely  
due to the lack of receipts.  
As the generator owner, you should be aware that Generac may deny any and/or all warranty coverage or responsibility if your generator, or a part/  
component thereof, has failed due to abuse, neglect, improper maintenance or unapproved modifications, or the use of counterfeit and/or "grey market"  
parts not made, supplied or approved by Generac.  
You are responsible for contacting a Generac Authorized Warranty Dealer as soon as a problem occurs. The  
warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.  
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Dealer. To locate the Generac  
Authorized Warranty Service Dealer nearest you, call our toll free number:  
1-800-333-1322  
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System Warranty (ECS Warranty),  
which is provided to you by Generac pursuant to federal law. See also the "Generac Limited Warranties for Generac Power Systems, Inc.," which is  
enclosed herewith on a separate sheet, also provided to you by Generac. Note that this warranty shall not apply to any incidental, consequential or  
indirect damages caused by defects in materials or workmanship or any delay in repair or replacement of the defective part(s). This warranty is in place  
of all other warranties, expressed or implied. Specifically, Generac makes no other warranties as to the merchantability or fitness for a particular purpose.  
Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.  
The ECS Warranty applies only to the emission control system of your new equipment. If there is any conflict in terms between the ECS Warranty and  
the Generac Warranty, the Generac Warranty shall apply. Both the ECS Warranty and the Generac Warranty describe important rights and obligations with  
respect to your new engine.  
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty service, evidence must be  
presented showing the date of the sale to the original purchaser/owner.  
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the following address:  
ATTENTION WARRANTY DEPARTMENT  
GENERAC POWER SYSTEMS, INC.  
P.O. BOX 297 • WHITEWATER, WI 53190  
Part 1  
Part No. 0H1911 Rev. A 01/09  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
EMISSION CONTROL SYSTEM WARRANTY  
Emission Control System Warranty (ECS warranty) for equipment using small spark-ignited engines:  
(a) Applicability: This warranty shall apply to equipment that uses small off-road engines. The ECS Warranty period shall begin on the date the new  
equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.  
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or equipment and to each  
subsequent purchaser/owner that the ECS when installed was:  
(1) Designed, built and equipped so as to conform with all applicable regulations; and  
(2) Free from defects in materials and workmanship which cause the failure of a warranted part at any time during the ECS Warranty Period.  
(c) The warranty on emissions-related parts will be interpreted as follows:  
(1) Any warranted part that is not scheduled for replacement as required maintenance in the Owner's Manual shall be warranted for the ECS  
Warranty Period. If any such part fails during the ECS Warranty Period, it shall be repaired or replaced by Generac according to Subsection (4)  
below. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.  
(2) Any warranted part that is scheduled only for regular inspection as specified in the Owner's Manual shall be warranted for the ECS Warranty  
Period. A statement in the Owner’s Manual to the effect of "repair or replace as necessary" shall not reduce the ECS Warranty Period. Any such  
part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.  
(3) Any warranted part that is scheduled for replacement as required maintenance in the Owner's Manual shall be warranted for the period of time  
prior to first scheduled replacement point for that part. If the part fails prior to the first scheduled replacement, the part shall be repaired or  
replaced by Generac according to Subsection (4) below. Any such emissions-related part repaired or replaced under the ECS warranty shall be  
warranted for the remainder of the period prior to the first scheduled replacement point for that part.  
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no charge to the owner at a  
Generac Authorized Warranty Service Facility.  
(5) Notwithstanding the provisions of subsection (4) above, warranty services or repairs must be provided at Generac Authorized Service Facilities.  
(6) When the engine is inspected by a Generac Authorized Warranty Service Facility, the purchaser/owner shall not be held responsible for  
diagnostic costs if the repair is deemed warrantable.  
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient to meet the expected  
demand for such parts.  
(8) Any Generac authorized and approved emission-related replacement parts may be used in the performance of any ECS warranty maintenance or  
repairs and will be provided without charge to the purchaser/owner. Such use shall not reduce Generac ECS Warranty obligations.  
(9) Unapproved, add-on, modified, counterfeit and/or "grey market" parts may not be used to modify or repair a Generac engine. Such use voids  
this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim. Generac shall not be held liable hereunder for failures  
of any warranted parts of Generac equipment caused by the use of such an unapproved, add-on, modified, counterfeit and/or "grey market"  
part.  
EMISSION RELATED PARTS MAY INCLUDE THE FOLLOWING (IF EQUIPPED):  
1) FUEL METERING SYSTEM  
A. CARBURETOR AND INTERNAL PARTS  
B. PRESSURE REGULATOR  
2) AIR INDUCTION SYSTEM  
A. INTAKE MANIFOLD  
4) AIR INJECTION SYSTEM  
A. PULSE AIR VALVE  
5) EXHAUST SYSTEM  
A. CATALYST  
B. THERMAL REACTOR  
C. EXHAUST MANIFOLD  
B. AIR FILTER  
3) IGNITION SYSTEM  
A. SPARK PLUGS  
B. IGNITION COILS / MODULE  
Part 2  
Part No. 0H1911 Rev. A 01/09  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
GENERAC POWER SYSTEMS LIMITED WARRANTY FOR  
"ECO GEN AIR-COOLED AUTOMATIC STANDBY GENERATORS"  
For a period of three (3) years or 2000 hours, whichever comes first, from the date of original sale Generac Power Systems, Inc. (Generac) warrants that its standby  
generator will be free from defects in material and workmanship for the items and period set forth below. Generac will, at its option, repair or replace any part(s) which,  
upon examination, inspection and testing by Generac or an Authorized/Certified Generac Dealer, is found to be defective. Any equipment that the purchaser/owner claims to  
be defective must be examined by the nearest Authorized/Certified Generac Service Dealer. This warranty applies only to Generac emergency automatic standby generators  
used in "Standby" applications as Generac has defined Standby. This specific model of generator is intended to support alternative energy source systems that include an  
inverter, a battery bank, and an alternative energy source. Scheduled Maintenance, as outlined by the generator owner’s manual, is highly recommended. This Scheduled  
Maintenance should be performed by an Authorized/Certified Generac Dealer. This will verify service has been performed on the unit throughout the warranty period.  
WARRANTY SCHEDULE  
UNITED STATES AND CANADA  
YEARS ONE and TWO – A total of two (2) years or 2000 hours, whichever occurs first, limited comprehensive coverage on mileage, labor and parts listed.  
All COMPONENTS  
YEAR THREE – Total of three (3) years or 2000 hours, whichever occurs first, coverage on parts listed.  
ALL COMPONENTS  
INTERNATIONAL  
YEAR ONE – A total of one (1) year or 1000 hours, whichever occurs first, coverage on labor and parts listed.  
All COMPONENTS  
Extended Warranties are not available.  
GUIDELINES  
1. Warranty begins upon the successful registration of the unit.  
2. Proof of Purchase and Maintenance must be available.  
3. Warranty is transferable between ownership of original installation site.  
4. Warranty only applies to permanently wired and mounted units.  
5. Any and all warranty repairs and/or concerns, must be performed and/or addressed by an Authorized/Certified Generac Service Dealer, or branch thereof. Repairs or  
diagnostics performed by individuals other than Generac authorized dealers not authorized in writing by Generac will not be covered.  
6. Steel enclosures are warranted against rusting for the first year of ownership only.  
7. All warranty expense allowances are subject to the conditions defined in Generac's General Service Policy Manual.  
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:  
Any unit built/manufacturer prior to September 2010.  
Generac generators that utilize non-Generac replacement parts.  
Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up).  
Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac has defined Prime Power, Trailer Mounted or Rental Unit. Contact a  
Generac Distributor for Prime Power, Trailer Mounted or Rental Unit definition.  
Damage to generator system caused by improper installation or costs necessary to correct installation.  
Units used for prime power in place of existing utility power (where utility power is present) or in place of utility power where utility power service does not normally exist  
without a renewable energy system including an inverter, battery bank and alternative energy power source.  
Fuel connections other than conventional utility company supplied conventional LP vapor withdrawal systems.  
Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze.  
Steel enclosures that are rusting due to the improper installation, location in a harsh or saltwater environment or scratched where integrity of paint applied is compromised.  
Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all mechanical devices, the Generac engines  
need periodic part(s) service and replacement to perform as designed. This warranty will not cover repair when normal use has exhausted the life of a part(s) or engine.  
Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning, earthquake, windstorm,  
hail, volcanic eruption, water or flood, tornado or hurricane.  
Damage related to rodent and/or insect infestation.  
Products that are modified or altered in a manner not authorized by Generac in writing.  
Covered warranty labor rates are based on normal working hours. Overtime, holiday, or emergency labor costs for repairs outside of normal business hours will be the  
responsibility of the customer.  
Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the defective part(s).  
Failure due to misapplication.  
Telephone, cellular phone, facsimile, internet access or other communication expenses.  
Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty period.  
Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.  
Rental equipment used while warranty repairs are being performed and/or overnight freight costs for replacement part(s).  
Costs incurred for equipment used for removal and/or reinstallation of generator, (i.e.; cranes, hoists, lifts, etc.)  
Planes, ferries, railroad, buses, helicopters, snowmobiles, snow-cats, off-road vehicles or any other mode of transport deemed abnormal.  
Starting batteries, fuses, light bulbs and engine fluids.  
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES NO OTHER WARRANTIES AS TO THE  
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Any implied warranties which are allowed by law, shall be limited in duration to the terms of the  
express warranty provided herein. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. GENERAC'S  
ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR  
CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of  
incidental or consequential damages, so the above limitation may not apply to you. This warranty gives you specific legal rights. You also have other rights from state to state.  
GENERAC POWER SYSTEMS, INC. P.O. BOX 8 • Waukesha, WI 53187 • Ph: (888) GENERAC (436-3722) • Fax: (262) 544-4851  
To locate the nearest Authorized Dealer and to download schematics, exploded parts views  
and parts lists visit our website: www.generac.com  
Part No. 0J1629  
Revision A (10/01/10)  
Part No. 0J0984  
Revision A (10/14/10)  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Generac Power Systems Switch R 200A User Manual
Generac Power Systems Portable Generator GP7000 User Manual
Generac Power Systems Portable Generator 5747 0 User Manual
Generac Power Systems Automobile Parts 005055 1 User Manual
Generac Power Systems Automobile Parts 0D9727 User Manual