Generac Power Systems Switch 5464 User Manual

STANDBY GENERATOR ACCESSORIES  
21 Light Remote Annunciator  
Liquid-Cooled Generator Sets  
Model 5465  
Model 5466  
Model 5464  
DESCRIPTION  
The Remote Annunciator Panel provides remote monitoring and  
annunciation of up to 18 generator parameters using LED’s located on  
the annunciator keypad. It also provides two system level warnings which  
are System Ready and Communications OK.  
The specific faults can be selected using either the DIP switches located  
on the annunciator circuit board or through a computer via the RS232  
connection on the circuit board.All relays are energized on power up and  
open during a fault condition.  
The Relay panel has up to 8 selectable functions on form A relays,  
and multiple relay panels can be connected for all 18 generator  
parameters.  
Communication is via a RS485 serial data link and power is supplied by  
the generator battery (+12 VDC or +24 VDC)  
Note:These units are only compatible with the H-series generator  
controller (70-150 kW)  
ENVIRONMENTAL SPECIFICATIONS  
Operating Temperature.......................................................................................................................................................................... -25 º C to 60 º C  
Humidity............................................................................................................................................................................... 0 to 95% Non-Condensing  
Power Supply..........................................................................................................................................................................................+12 or +24 VDC  
Power Usage ............................................................................................................................................................................................ 6 Watts typical  
Power Supply.......................................................................................................................................................................................Generator Battery  
Communication Line..........................................................................................................................RS485 fully isolated twisted pair cable with shield  
Maximum Cable Length.................................................................................................................................................................................... 4000 feet  
Relay Output.............................................................................One NO contact (Engergized when annunciator is powered and no faults are present)  
Relay Contact Rating..............................................................................................................................................................................30 VDC, 1 amp  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Generac Power Systems Portable Generator QT04524 User Manual
Generac Power Systems Portable Generator QT018 User Manual
Generac Power Systems Portable Generator 0784 1 User Manual
Generac Power Systems Humidifier 5621 User Manual
Generac Portable Generator 005802 0 User Manual